Bradford White ES-3000-1-S-10, ES-3500-1-S-10, ES-4100-2-S-10 User Manual

Electric Tankless Water Heaters
The KwickShot® Electric Tankless Water Heaters Models Feature:
n On Demand Hot Water—No delay. n Reduced Energy Waste—Flow switch activates heater only
on demand (no stand-by heat loss). 99% efficient.
temperature rise.
n Prevention Of Bacteria Growth. n Easy Installation—Mounts on wall – no sweat connections. n Ni Chrome Heating Element—A unique, patented flow
path ensures optimum heat transfer and extended element life.
n Durable Design—Reduces calcification and sedimentation. n Space Saving Installation—Compact size. n High Temperature Limit Switch (ECO)—Protects against
element burn out, with reset button.
n Warranty—Heaters are designed for durability and
guaranteed against failure due to leaks of Heater Body/ Element Assembly for a period of 10 years. Field serviceable element with replaceable cartridge element (1 year warranty).
n Single Phase and Three Phase models—Single Phase
models 240 volt and below are cUL certified.
For more information on warranty, please visit www.bradfordwhite.com
LISTED WHERE
APPLICABLE
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 5,682,666; 7,634,976; 5,660,165; 5,954,492; 6,056,542; 6,935,280; 5,372,185; 5,485,879; 5,574,822; 7,971,560; 7,992,526; 6,684,821; 6,442,178; 7,334,419; 7,866,168; 7,270,087; 7,007,748; 5,596,952; 6,142,216; 7,699,026; 5,341,770; 7,337,517; 7,665,211; 7,665,210; 7,063,132; 7,063,133; 7,559,293; 7,900,589; 5,943,984; 8,082,888; 5,988,117; 7,621,238; 7,650,859; 5,761,379; 7,409,925; 5,277,171; 8,146,772; 7,458,341; 2,262,174. OTHER U.S. AND FOREIGN PATENT APPLICATIONS PENDING. CURRENT CANADIAN PATENTS: 2,314,845; 2,504,824; 2,108,186; 2,143,031; 2,409,271; 2,548,958; 2,112,515; 2,476,685; 2,239,007; 2,092,105; 2,107,012. KwickShot
For products installed in USA, Canada and Puerto Rico. Some states do not allow limitations on warranties. See complete copy of the warranty included with the heater.
®
is a registered trademark of Bradford White® Corporation.
217-B-0716-A
Electric Tankless Water Heaters
Single Point (Single Phase)
Model
NumberkWRating
ES-3000-1-S-10 3.0 120 25.0 41 10 AWG ES-3500-1-S-10 3.5 120 29.0 48 10 AWG ES-3500-4-S-10 3.5 240 14.6 48 14 AWG ES-4100-2-S-10 4.1 208 19.7 56 12 AWG ES-4100-5-S-10 4.1 277 14.8 56 14 AWG ES-5500-4-S-10 5.5 240 22.9 75 10 AWG
Voltage AMPS
Refer to Voltage Identification Code Chart on page 5.
Temperature
Rise °F
0.5 GPM
Recommended
Wire Size
Specifications: Dimensions: 103⁄4" x 51⁄4" x 27⁄8"
Weight: 3 lbs.
Materials:
Cover: ABS UL rated 94Vo. Glass reinforced Fortron Heater Body and Ni Chrome Element
Color: White Element: Replaceable cartridge insert Pipe-Fittings: 3/8" compression at top
of unit. Operating Pressure: Min 25 PSI, Max 150 PSI.
Intregal 0.5 GPM flow control and faucet aerator provided.
Note: Designed to comply with 0.5GPM hand washing code target outlet temperature 105°F - 110°F. Please consult local codes for electrical requirements. Additional voltages and wattages are available. For more information please consult factory.
Applications: Single Phase Only. Shopping Malls, Schools, Stadiums, Public Hand Washing.
OUTLET
FLOW
REGULATOR
3
"
8
3
"
8
INTLET
REMOVABLE
FILTER
1
"
2
2
®
1
"
2
1
ELECTRICAL
SUPPLY
1
"
5
4
10
3
"
4
3
"
4
3
"
4
9
7
"
8
2
Thermostatic (Single Phase)
Model
NumberkWRating
EFT-7500-4-S-10 7.5 240 32.0 68 51 34 25 8 AWG EFT-9500-4-S-10 9.5 240 40.0 86 65 43 32 8 AWG
Voltage AMPS
Temperature Rise °F
0.5
0.75
GPM
GPM
1.0
GPM
1.5
GPM
2.0
GPM
Recommended
Wire Size
Please specify your application when you place your order. Example: EFT-9500-4-S-10-S (Dishwasher 180°F)
SPEC OPTIONS: S - Sanitation Setting 180°F FS - Factory Set Temperature
(Ambient to 180°F) ML - Multiple Lavs (5.5 to 10kW) Factory Set Temp 105°F. .5 GPM Turn On
Specifications: Dimensions: 103⁄4" x 51⁄4" x 27⁄8"
Weight: 3 lbs.
Materials:
Cover: ABS UL rated 94Vo. Glass reinforced Fortron® Heater Body and Ni Chrome Element Color: White Standard temperature range 100°F-140°F. Maintains accurate temperature control +/- 1°F
Element: Replaceable cartridge insert Pipe-Fittings: 1/2" compression at bottom
of unit. Operating Pressure: Min 25 PSI, Max 150 PSI.
Turn on 0.5 GPM (up to 6.5kW) Turn on 0.7 GPM (7.5 kW and up) Max Flow 2.0 GPM
Note: Designed to comply with 0.5GPM hand washing code target outlet temperature 105°F - 110°F. Please consult local codes for electrical requirements. Additional voltages and wattages are available. For more information please consult factory.
Refer to Voltage Identification Code Chart on page 5.
Applications: Single Phase Only. Dishwashers, Boosters (to 180°F). Schools, Hospitals, Nursing Homes, Laboratories. Emergency Eye Wash Fountains. Single and Multiple Hand wash Stations.
7
"
2
1
"
5
4
OUTLET INTLET
1
"
1
2
10
9
3
"
4
8
3
"
4
3
"
4
2
Loading...