Bradford-White 500-1825 User Manual

Page 1
Internet Version for Reference Only
Installation and Operation Instructions Document 2144
C O R P O R A T I O N
B WRADFORD HITE
®
Installation and Operation Instructions for
Copper Brute
Volume Water Heaters
Model B4 Sizes 500-1825
These instructions are to be stored in the pocket provided on the heater.
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualied in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in ue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency, or gas supplier.
H2317100-
Page 2
Internet Version for Reference Only
Page 2
B4 Volume Water Heater
Page 3
BRADFORD WHITE
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction.................................................... 3
1.2 Heater Identication.......................................3
1.3 Flow Requirements........................................3
1.4 Water Chemistry............................................ 4
SECTION 2. Installation
2.1 Heater Placement ......................................... 4
2.2 Installation of Indoor Heaters.........................4
2.2.1 Combustion Air Supply ..................................4
2.2.2 Venting........................................................... 6
2.3 Installation of Outdoor Heaters...................... 7
2.4 Gas Supply and Piping..................................7
2.5 Electrical Wiring............................................. 8
2.6 Water Piping of System.................................8
2.7 Water Expansion ........................................... 9
2.8 Pump Performance and Installation ..............9
2.9 Water Pressure............................................10
2.10 Tank Installation........................................... 10
2.11 Two-Temperature System............................ 11
SECTION 3. Operation
3.1 Controls - General ....................................... 14
3.1.1 Electronic Ignition Control............................14
3.1.2 Operating Control ........................................ 14
3.1.3 High Limit Controls ...................................... 14
3.1.4 Flow Switch .................................................14
3.1.5 Low Water Cut-Off (Optional) ......................14
3.2 Initial Start-Up.............................................. 14
3.3 To Start Up System......................................15
3.3.1 Start Up Heater............................................15
3.3.2 To Set Temperature and High Limit
Control....................................................15
3.4 To Turn Off Heater ....................................... 16
3.5 To Shut Down System ................................. 16
SECTION 4. Maintenance
.....................................................................16
SECTION 5. Troubleshooting and Analysis of Service Problems
.....................................................................17
Page 3
Internet Version for Reference Only
B4 Volume Water Heater
Page 3
SECTION 1. General Information
1.1 Introduction
This manual provides information for the installation and operation of Bradford White volume water heaters. It is strongly recommended that all application and installation procedures be reviewed completely before proceeding with the installation. Consult the Bradford White factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most problems are caused by improper installation.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the package slip. Inspect everything for possible damage upon delivery, and inform the carrier of any shortages or impairments. Any such claims should be led with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
WARNING
All volume water heaters must be installed in accordance with the procedures outlined in this manual. The warranty does not apply to heaters not installed or operated in accordance with these procedures. Consult local building and safety codes before proceeding with work. The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code; ANSI Z223.1, National Electrical Code ANSI/NFPA 70 and/or in Canada CSA B149.1 requirement. When required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any modication to the water heater, its gas controls, gas orices, wiring or draft diverter may void the warranty. If eld conditions require such modications, consult factory.
1.2 Heater Identication
Consult rating plate on the heater. The following
example simplies the heater identication.
1 2 3 4 5 6
B4 1670 I N 09 C
1. Basic heater model.
2. Input rate X 1000 BTU/hr.
3. Indoor (I) or Outdoor (E) installation.
4. Gas type: Natural (N) or Propane (P).
5. Ignition system: I.I.D. (09) or continuous pilot (16).
6. Firing rate: On/Off (C), 2-stage (K), 4-stage (L). Bradford White commercial water heaters are
available in two models: an indoor version and an outdoor version. Both are available from the factory (see Figure 1).
1.3 Flow Requirements
For proper operation, all low volume hot water
heaters must have continuous ow through the heat exchanger when ring. The system pump must be capable of developing sufcient pressure to overcome the resistance of the heater plus the entire circulating system at the designed ow rate.
12
(311)
A
Pump
Front
Gas
Conn.
Top
58
V
(1473)
10
(260)
B
17
(432)
295/
8
(752)
Out In
17
(197)
28
(718)
Side
C
Rear
29
(737)
Pump
30
19
Gas
(483)
Inlet
12
(305)
Figure 1. Heater Conguration.
A
Front
(781)
7
(197)
Out In
41
(1060)
Side
14
(356)
4
(102)
61
(1549)
Page 4
Internet Version for Reference Only
Page 4
B4 Volume Water Heater
Page 5
BRADFORD WHITE
1.4 Water Chemistry
Bradford White equipment is designed for use in a wide variety of water conditions. The water velocity maintained in the heat exchanger tubes is kept high enough to prevent scaling from hard water and low enough to avoid corrosion from soft water. Ninety-ve percent of the urban areas in the country have water that is compatible with this equipment, but in some areas a water supply will contain a large quantity of scaling chemicals or the water may be extremely soft and corrosive. In rare situations the water will contain both scaling chemicals and corrosive chemicals such as calcium or sodium chloride. These conditions may be the result of a nearby well or pumping station and the particular condition may not be characteristic of the entire city water system.
If an installer observes damage from these conditions to any water handling equipment in the area, a factory representative should be contacted immediately for assistance in minimizing maintenance costs. If erosion is present, the pump impeller can be replaced to reduce water velocity. If scaling conditions are bad, tube cleaning maintenance schedules can be established to prevent tube burn-out and cracking. Neglecting the problem could mean serious damage to the heater and water system.
Scaling can be recognized as a layer deposited on the inner walls of the tube which reduces the inner diameter of the tube. Scale can be any color or texture; smooth or rough, granular or amorphous. Signs of erosion are generally pitting, cavitation, ridges and “islands” on the inner walls of the tubes. Since this condition results from extremely soft water sources, or as a result of a water softening program, the internal copper surfaces will be extremely shiny. Other chemicals, such as chlorine or chlorides in the water, will cause dark surfaces of erosion.
In areas where the water supply is extremely corrosive, it is advisable to order the heater with cupro-nickel tubes in the exchanger.
Damage From Scaling, Corrosion, or Erosion is Not Covered by the Warranty.
SECTION 2. Installation
2.1 Heater Placement
The heater must be placed to provide specic clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces. These clearances also apply to non-combustible materials because the heater requires air circulation for proper operation.
Heater should be mounted on a level surface. An integral combustible ooring base is provided as standard equipment on outdoor models. Indoor
models can be installed on a combustible oor with a special base assembly which is available from the factory, or with a base that complies with local code requirements. See rating plate for part number of the base assembly.
Do not install a heater on carpeting.
Under the National Fuel Gas Code, ANSI Z223.1, it is permissible to place the heater on oors other than non-combustible when the installation complies with the American Insurance Code. Figures 2, 3, 4 and 5 show common installation on combustible ooring.
2.2. Installation of Indoor Heaters
1. Locate the water heater to provide adequate
clearance for inspection and service on all sides
(see Table 1). We recommend minimums of 24"
from front (for proper access to and service of
controls) and 18" at water connection end. For
alcove installation (see Figure 6).
2. Install the heater on a waterproof oor with an
adequate oor drain and a 6" minimum curb on
all four sides to protect the building if heater
repairs are required. The manufacturer will
not be held liable for any water damage in
connection with this heater.
2.2.1 Combustion Air Supply
1. Copper Brute water heaters must have provisions
for combustion and ventilation air in accordance
with section 5.3, Air for Combustion and
Ventilation, of the National Fuel Gas Code,
ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of
CSA B149.1, Installation Codes, or applicable
provisions of the local building codes.
A Copper Brute heater may receive combustion
air from the space in which it is installed, or
it can be ducted directly to the unit from the
outside. Ventilation air must be provided in either
case.
2. In the United States, the most common
requirements specify that the space shall
communicate with the outdoors in accordance
with method 1 or 2, which follow. Where ducts
are used, they shall be of the same cross-sectional
area as the free area of the openings to which
they connect.
Method 1: Two permanent openings, one commencing within 12 inches (30 cm) of the top and one commencing within 12 inches (30 cm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical
Page 5
Internet Version for Reference Only
B4 Volume Water Heater
Concrete Slab Must Extend Out A
Base For Combustible Floors
Concrete Slab - 4
" Minimum
Minimum Of
12" On All Sides
Roof - W
ood & Steel Construction
Unit
(End
View)
Base
Rail
Base For Combustible Floors
Raised Mounting
Platform (W
ood)
Mounting Platform Must Extend Out
A
Minimum Of 12" On All Sides
Unit
(End
View)
Base
Rail
20 GA
Galvanized
Sheet Metal
Cap
Flashing
Roof
Roof
Base Must Extend Out Min. 12" On All Sides Of Heater Frame
Met
al Plate 20 Ga. Min. Under Entire Heater
Concrete Blocks Or
Tile
Min.
7" High With 3" Min.
Air Openings
Blocks must provide solid base and be braced so they cannot slip out of place. Air openings in blocks must be arranged to provide unobstructed opening through entire width or length of base.
Unit
(Front
View)
20 GA
Galvanized
Sheet Met
al
Cap
Flashing
Roof
Roofing
4X4
Stringer
Base
Rail
Base
for Combustible Floors
Clearance Indoor Outdoor From (inches) (inches)
Top 30 Unobstructed Water Conn. Side 12 24 Opposite Side 6 24 Front Alcove Unobstructed Rear 8 24 Vent Pipe* 6 — Hot Water Pipes Per Code Per Code
*1" when using type B Vent (refer to Manufacturer's Instructions
Table 1. Minimum Heater Clearances
From Combustible Surfaces.
Page 5
Figure 4. Typical Heater Installation with Base for Com­bustible Floors, Example C.
Figure 2. Typical Heater Installation with Base for Com­bustible Floors, Example A.
Figure 3. Typical Heater Installation with Base for Com­bustible Floors, Example B.
Figure 5. Installation on Concrete Blocks or Tile.
Water
Heater
CLOSET INSTALLATION
(UNACCEPTABLE)
A closet is any 4 sided enclosure which is less than 16* times the total volume of all the gas red appliances within the enclosure.
Water
Heater
When the ceiling height exceeds 8 feet, you are only allowed to consider 8
*
feet when calculating the total volume of the enclosure.
ROOM INSTALLATION
(ACCEPTABLE)
A room is any enclosure which is at least 16* times greater than the total volume of all the gas red appliances within the enclosure.
ALCOVE INSTALLATION
(ACCEPTABLE)
An alcove suitable for the installa­tion of a water heater is a restricted section of a room not separated from the room by a door or partition and which meets the minimum clearances for the specic model water heater listed below.
Figure 6. Alcove Installation.
Page 6
Internet Version for Reference Only
Page 6
B4 Volume Water Heater
Page 7
BRADFORD WHITE
ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (5.5 square cm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (11 square cm/ kW) of total input rating of all equipment in the enclosure. Table 2 shows data for this sizing method, for each Copper Brute model.
Method 2: One permanent opening, commencing within 12 inches (30 cm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 Btu/hr (7 square cm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the conned space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CSA B149.1.
Heater Each Opening* Model (Square Inches)
500 125 600 150 715 179 850 213 1010 253 1200 300 1430 358 1670 418 1825 457
*Net Free Area in Square Inches
Area indicated is for one of two openings; one at oor level and one at the ceiling, so the total net free area could be double the gures indicated. For special conditions refer to the latest edition of ANSI Z223.1. or CSA B149.1
Consult factory if not communicating directly through the walls with the outdoors.
Note: Check with louver manufacturers for net free area of louvers. Correct for screen resistance to the net free area if a screen is installed. Check all local codes applicable to combustion air.
IMPORTANT: In beauty shops, barber shops, cleaning establishments and self-service laundries with dry cleaning equipment, it is important that the water heater be installed in a location where combustion and ventilation air is received from a source outside the building. Please refer to the most recent edition of the National Fuel Gas Code, ANSI Z223.1, or in Canada, CSA requirements.
3. (a) In the United States: Exhaust Fans or
Vents: Any equipment which exhausts air from
the heater room can deplete the combustion air
supply or reverse the natural draft action of the
venting system. This could cause ue products
to accumulate in the heater room. Additional air
must be supplied to compensate for such exhaust.
The information in Table 2 is not applicable in
installations where exhaust fans or blowers of
any type are used. Such installations must be
designed by qualied engineers.
(b) In Canada: Follow Canadian standard, CSA
B149.1 or local codes.
4. If a blower or fan is used to supply air to the
heater room, the installer should make sure it
does not create drafts which could cause nuisance
shutdowns of the pilot. If a blower is necessary to
provide adequate combustion air to the heater, a
suitable switch or equivalent must be wired into
the heater control circuit to prevent the heater
from ring unless the blower is operating.
5. The heater must be completely isolated and
protected from any source of corrosive chemical
fumes such as trichlorethylene, perchlorethylene,
chlorine, etc.
2.2.2 Venting
1. Bradford White heaters have built-in draft
diverters for natural draft operation and must not
be connected to any portion of a mechanical draft
system under positive pressure. The ue outlet
must be connected to a clear, unobstructed vent
of adequate capacity ending above the highest
point of the building with an approved vent cap.
The venting system should be installed according
to the latest edition of ANSI Z223.1 and/or, in
Canada, CSA B149.1 requirement and any local
codes having jurisdiction.
IMPORTANT NOTE: Do not use sheet metal
screws at the snap lock joints of Type B gas
vents.
2. Do not weld or fasten the vent pipe to the heater
draft hood. The weight of the stack must not rest
on the heater. The draft hood and heater top must
be easily removable for normal heater service
and inspection.
Table 2. Minimum Recommended
Air Supply to heater.
Page 7
Internet Version for Reference Only
B4 Volume Water Heater
Window
Or Grill
Indoor
Room
WRONG
3. Avoid using long horizontal runs of the vent pipe, and too many 90° elbows, reductions or restrictions. Horizontal runs should have at least a 1/4" rise per foot in the direction of ow. A vent connector should be supported for the design and weight of the material used to maintain clearances and prevent physical damage and separation of joints.
4. Avoid ending heater vents near air conditioning or air supply fans. The fans can pick up exhaust ue products from the heater and return them inside the building, creating a possible health hazard. A minimum of 4 feet horizontal distance must be maintained from electrical meters, gas meters, and relief equipment.
5. Always use double-wall or insulated vent pipe (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising ue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling ue products into the heater room.
6. Avoid oversize vent piping or extremely long runs of the pipe which may cause excessive cooling and condensation. Rule of Thumb: The total length of the vent, including the connector and any offset, should not exceed 15 feet for every inch of vent diameter. Longer total lengths shown in venting tables are based on maximum capacity, not condensation factors.
7. When the installation of a draft fan is necessary in connecting a venting system to a the heater, the installation should be engineered by competent personnel following good engineering practices. The draft fan supplier should be consulted for correct size. The installation should be in accordance with the latest edition of ANSI Z223.1 and/or, in Canada, CSA B149.1 requirement and any local codes having jurisdiction. When a draft fan is installed, a suitable draft switch must be wired into the heater control circuit at terminal designated “Field Interlock” to prevent ring of the heater unless a positive draft has been established.
Page 7
Figure 7. Incorrect Outdoor Installation.
etc. which connect in any way with an inhabited area of a building. This includes other structures such as garages or utility rooms (see Figure 7).
4. Although these models are CSA designed certied for outdoor installations, such installations are not recommended in areas where the danger of freezing exists unless proper precautions are taken for freeze protection.
2.4 Gas Supply and Piping
Review the following instructions before
proceeding with the installation.
1. Verify that the heater is tted for the proper type of gas by checking the rating plate. Bradford White heaters are normally equipped to operate below a 2000 foot altitude. Heaters equipped to operate at higher altitudes have appropriate stickers or tags attached.
2.3 Installation of Outdoor Heaters
1. Locate the heater to provide the minimum clearances as listed in Table 1, “Placement of Heater”.
2. Do not place the heater in an enclosure or wall recess. Avoid locations where wind deection off structures might cause down draft. When such wind conditions are possible, place the heater at least three (3) feet from the structures.
3. Never install the heater under any kind of roof overhang. Do not place the heater below or adjacent to any doors, windows, louvers, grills,
Note: These gures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pres­sure with a manometer, and local code requirements for varia­tions. For LPG, reduce pipe diameter one size, but maintain a 1" minimum diameter. A normal number of Tees and elbows have been taken into allowance.
Table 3. Gas Piping Sizes.
Page 8
Internet Version for Reference Only
B4 Volume Water Heater
Page 9
Gas Supply Inlet
Te
e
Fitting
3" Min.
Nipple
Cap
To Equipment Inlet
Page 8
Figure 8. T-Fitting Sediment Trap Installation.
BRADFORD WHITE
8. Before operating the heater, the complete gas supply system and all connections must be tested for leaks using a soap solution. Do not use raw ame.
Caution
Since some leak test solutions (including soap and water) may cause corrosion or stress cracking, the piping must be rinsed with water after testing, unless it has been determined that the leak test solution is noncorrosive.
2. Use the gures in Table 3 to provide adequate gas piping from the gas meter to the heater.
3. A trap (drip leg) must be provided ahead of the gas controls (see Figure 8 ). A manual gas shutoff valve must also be provided for service convenience and safety. Check the local codes.
4. The heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. The heater must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
5. Provide gas supply pressure to the heater as follows:
Natural Gas LPG
Min. (inches water column)
Max. (inches water column)
9 14
Per Rating Plate
Note: The heater and all other gas appliances
sharing the heater gas supply line must be ring at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersized gas meter and/or obstructed gas supply line.
6. The correct burner manifold gas pressure is stamped on the rating plate. The regulator is preset at the factory and normally requires no further adjustment.
7. The gas manifold and control assembly was tested and conform to the safe lighting and other performance criteria specied in the latest editions of ANSI Z21.13, Low Pressure Boiler Standard.
2.5 Electrical Wiring
WARNING
The heater must be electrically grounded in accordance with the most recent edition of the National Electrical Code, ANSI/NPA 70. In Canada, all electrical wiring to the heater should be in accordance with the Canadian Electrical Code, CSA C22.1 Part 1. Do not rely on the gas or water piping to ground the metal parts of the heater. Oftentimes, plastic pipe or dielectric unions isolate the heater electrically. Service and maintenance personnel who work on or around the heater may be standing on wet oors and could be electrocuted by an underground heater.
1. Check heater wiring and pump for correct voltage, frequency and phase. If the pump circuit is other than 115V, check to see that the heater is provided with an appropriate transformer.
2. Wire the heater and pump exactly as shown in the wiring diagram supplied with the heater.
3. The pump and heater must be electrically interlocked so the heater cannot come on unless the pump is running.
4. All eld installed electrical safety devices and all eld installed devices (draft switches, relays, timers, outdoor temperature reset devices, etc.) can be connected to the heater wiring at points shown in the wiring diagram designated “Field Interlock”.
2.6 Water Piping of System
1. Be sure to provide valves at the inlet and outlet of the heater so it can be readily isolated for service. A buttery or similar type of valve is recommended.
2. The pressure relief valve installed in the tapped opening provided in the outlet header (see
Page 9
Internet Version for Reference Only
B4 Volume Water Heater
Pressure Relief Valve
Hot
Water
Hot
Water
Storage
Tank
Floor
Automatic
Tempering
Valve
Cold
Water
Tempered Water
24"
Figure 9. Pressure Relief Valve Location.
Figure 9), must be piped, but not fastened, to a drain or oor sink. The drain pipe must be the same size as the valve outlet and must pitch downward from the valve.
Special attention must be given to relief valve
settings in installations where the heater is located on the ground oor of a tall building. The static pressure of the system is elevated and could cause the relief valve to leak. Where no special
setting of the relief valve is ordered, the factory will furnish a 125 psi setting. Never reduce the
relief valve openings.
3. Pressure relief valve lever must be tripped at least once a year to insure that waterways are clean. When manually operating lever, water will discharge through drain line. Precautions must be taken to avoid contact with hot water and water damage.
4. The weight of all water and gas piping should be supported by suitable hangers or oor stands.
5. Check piping diagrams with local applicable plumbing, heating and building safety codes.
6. All two-temperature systems using temperature valves must have forced recirculation in the low temperature building loop.
7. A check valve installed at the hot water inlet to the tempering valve will prevent cold water from being drawn in reverse through the tempering valve into the hot water.
8. When installing a tempering valve, place at bottom of antithermosyphon loop at least 24" high to prevent excessive hot water from entering mixed water supply. Bring the cold water supply up from the oor to the valve (see Figure 10).
Page 9
Figure 10. Tempering Valve Installation.
2.7 Water Expansion
When cold water is heated the water expands. If no water is being used during the heat-up period the expanded water will normally back up into the city mains.
A water pressure reducing valve installed in the incoming cold water line may act as a check valve and prevent the expanded water from moving backward. This will cause pressure to rise in the heater, which will be relieved by the pressure relief valve.
If the relief valve pops frequently a mineral deposit may build up on the valve seat, causing it to leak.
Th e following suggestions may sol ve the problem:
1. Install a properly sized expansion tank.
2. Replace the installed water pressure reducing valve
with a suitable valve having a back ow port. These
valves have a back ow port which allows water
to ow backwards when the pressure in the system
exceeds the pressure in the mains.
3. Install an auxiliary small relief valve set at 25 psi
less than the main relief valve. The valve must
be piped to a drain and may require occasional
cleaning. It will bleed off the expanded water
and protect the main pressure relief valve from
becoming fouled.
2.8 Pump Performance and Installation
1. The factory provided pumps on all Copper Brute
heaters are sized to provide proper circulation
through the heater and heater-to-tank circulation
loop (see Figures 11 and 12). If the heater-to-tank
circulating loop does not contain more than 6
elbows or 30 feet of pipe, use pipe ttings in the
loop no smaller than the following:
Model Pipe Size
500 through 850 2" 1010 through 1825 2-1/2"
Page 10
Internet Version for Reference Only
Page 10
B4 Volume Water Heater
Page 11
BRADFORD WHITE
If the heater-to-tank circulating loop contains
more than 6 elbows or 30 feet of pipe, use pipe or ttings in the loop no smaller than the following:
Model Pipe Size
500 through 850 2-1/2" 1010 through 1825 3"
Pump performance requirements are provided in
Table 4 for reference purposes.
To assure free circulation, do not use globe
valves, side outlet tee connections or other restrictive ttings in heater-to-tank loop.
2. Copper Brute heaters are not suitable for heating swimming pools or any other application where temperature of the water owing through the heater remains below the dew point (110°F).
In applications requiring the rapid use of
measured volumes of water, the recovery of the heater between the time intervals of use must equal the volume used.
2.9 Water Pressure
It is very important that water pressure in the
system be maintained above 30 psi. If the system pressure should drop below this, the vapor pressure of water in the suction side of the pump can cause hammer and cavitation in the pump and damage the heater through lack of water circulation.
2.10 Tank Installation
1. Be sure the oor is waterproof and structurally capable of supporting the tank when it is lled with water.
2. The tank should be placed so that manholes, inspection covers, nameplates and drain valves are accessible.
3. Be sure the tank is suitable for the water in the system. Some water is corrosive and requires a protected tank with a special lining.
4. If the tank is glass-lined, it should be equipped with a suitable magnesium anode. It is good practice to replace the anode when it is approximately 50% used. The factory warranty on a glass-lined tank will be void if a satisfactory anode is not in place at the time of a failure or if it is consumed by cathodic action.
5. Make sure the tank connections in the heater­tank circulating loop are the proper size as listed in Section 2.8. If tappings are smaller than the recommended pipe size, a larger pump may be required. Consult the factory if in doubt.
Flow Head* Temp. Rise Water Rate Loss Across Model Category (GPM) (ft.) Heater, (°F)
Soft 45 5.0 17 500 Normal 68 9.9 11 Hard 90 15.7 8
Soft 45 5.1 20 600 Normal 68 10.0 14 Hard 90 15.9 10
Soft 45 5.3 24 715 Normal 68 11.0 16 Hard 90 17.8 12
Soft 45 5.4 30 850 Normal 68 11.1 20 Hard 90 18.1 15
Soft 45 3.9 35 1010 Normal 68 7.5 23 Hard 90 11.7 18
Soft** 68 7.8 27 1200 Normal 68 7.8 27 Hard 90 12.2 21
Soft** 68 8.1 32 1430 Normal 68 8.1 32 Hard 90 12.6 24
Soft** 68 8.3 37 1670 Normal 68 8.3 37 Hard 90 13.0 28
Soft** 90 13.5 30 1825 Normal** 90 13.5 30 Hard 90 13.5 30
Water Category Grain Hardness per Gal. Soft 1 through 7.5 Normal 7.6 through 17 Hard Over 17
* Pressure drop includes loss through 30 feet of pipe and normal ttings when heater is installed with storage tank. Pipe and ttings are assumed to be 2" on Models (500-850) and 2 1/2" on Models (1010-1825)
** To prevent erosion, these models must be ordered with cupro-nickel heat exchanger tubes.
Table 4. Pump Performance Requirements.
6. Install a pipe in the tank drain tting that goes to a oor sink, and install a drain valve. If a oor sink is not available, install a hose bib.
7. Hot water tanks in an existing installation are likely to have a deposit of silt on the bottom. Therefore, it is important to extend the pump suction pipe in the tank to a position near the top. Pipe the return from the heater to the bottom of the tank.
8. Incorrect installation can cause rapid failure of water tanks due to electrolysis. Tanks must be installed with dielectric connections to electrically isolate the tank from stray current. Note that the use of brass or bronze connectors does not replace the need for dielectric connections.
Page 11
Internet Version for Reference Only
B4 Volume Water Heater
5
1
2
3
4
CWMU
SUPPL
Y
RECIRC
5
1
2
3
4
RECIRC.
CWMU
SUPPL
Y
Page 11
2.11 Two-Temperature System
See Figures 13 and 14 for piping schematics. This system is designed to maintain the tempered water circulating loop at the desired temperature during idle periods as well as when there is a
demand for hot water. It is recommended for general purpose water supply including shower and bathing applications. Water at 180°F is available directly from the tank.
With
Vertical
Tank
With
Horizontal
Tank
Figure 11. Hot Water Supply System
Page 12
Internet Version for Reference Only
Page 12
B4 Volume Water Heater
Page 13
5
3
2
1
2
4
CWMU
SUPPL
Y
CIRC. RETURN
D
B
K
J
C
C
H
C
H
J
180°F Water
To
Bldg.
Conventional
Tank
140°F Water
To Bldg.
To
Drain
To Drain
Cold
Water
To
Drain
Pump
140°F
Water
Return From
Bldg.
180°F
Water
Return From
Bldg.
Cold
Water
Pump
BRADFORD WHITE
Figure 12. Hot Water Supply System with Dual Tanks, Building Loop Return and Circulating Pump.
Legend B - Check Valve C - Check Valve D - Tempering Valve H - Throttling Valves in Building Loop Returns J - Circulating Pump for Return Loop K - Service Valves to Isolate Heater and Pump
for Service
Figure 13. Two-Temperature Hot Water Supply System with Vertical Tank.
Page 13
Internet Version for Reference Only
B4 Volume Water Heater
Cold
Water
180°
Water
To
Bldg.
Conventional
Tank
To
Drain
24" Min.
To Drain
Pump
140°
Water
To
Bldg.
140°
Water
Return
From Bldg.
180°
Water
Return
From Bldg.
H
H
C
C
B
D
K
K
E
J
Cold
Water
180°
Water
To
Bldg.
Conventional
Tank
To Drain
140°
Water
To
Bldg.
To
Drain
Pump
180°Water
Return
From Bldg.
140°Water
Return
From Bldg.
B
D
E
K
J
I
H
H
C
C
Page 13
With
Horizontal
Tank
Legend B - Check Valve in Hot Water Supply
to Tempering Valve
C - Check Valve in Return Line from
Building Loop
D - Tempering Valve E - Venturi (Suction) Tee H - Throttling Valves in Building Loop
Returns
I - Circulating Pump for 180° Building
Loop
J - Circulating Pump for 140° Building
Loop
K - Service Valves to Isolate Heater
and Pump for Service
With
Vertical
Tank
Legend B - Check Valve in Hot Water Supply
to Tempering Valve
C - Check Valve in Return Line from
Building Loop
D - Tempering Valve E - Venturi (Suction) Tee H - Throttling Valves in Building Loop
Returns
I - Circulating Pump for 180° Building
Loop
J - Circulating Pump for 140° Building
Loop
K - Service Valves to Isolate Heater
and Pump for Service
Figure 14. Two-Temperature Hot Water Supply System.
Page 14
Internet Version for Reference Only
Page 14
B4 Volume Water Heater
Page 15
Rating Plate
Ignition Control
Pressure Relief Valve
Flow Switch
In
Out
Transformer
Terminal Strip
Operating Control (Aquast
at)
Hi-Limit
Operating Gas Valve
Manual Pilot Valve
Manual Main
Gas
Valve
Safety Gas Valve
BRADFORD WHITE
SECTION 3. Operation
3.1 Controls - General
See Figure 15 for control locations.
3.1.1 Electronic Ignition Controls:
a. Intermittent Ignition:
Pilots are automatically lit when the
operating aquastat calls for heat (System #9).
The unit performs its own safety check and
opens the main valves only after the pilot is proven to be lit. Whenever the pilot ame is interrupted, the main gas valve closes within 0.8 seconds.
b. Electronically Supervised Standing Pilot
System (System #16):
When pilot ame fails, the ignition control
module responds in less than 0.8 seconds and provides 100% safety shutdown.
3.1.2 Operating Controls:
Electrically Operating Controls:
Copper Brute units are equipped with operating
temperature. The temperature sensing bulb is located in the heater inlet.
3.1.3 High Limit Controls:
The manual reset high limit switches are
provided as standard equipment on all heaters. Automatic reset switches are optionally provided. The temperature sensing bulb of the switch is always located in the heater outlet. Burners will automatically shut down whenever overheating of water occurs.
3.1.4 Flow Switch: Standard on all models, the switch is mounted
directly in the header outlet. The ow switch shuts down all burners in case of low water condition or pump failure.
3.1.5 Low Water Cut Off: (Optional)
The low water cut off automatically shuts off the
heater whenever the water level drops below the probe. The probe is located at the heater inlet.
3.2 Initial Start-Up
Before placing the heater in operation, be certain that the heater is lled with water and all air is purged from the system. Once the heater is connected to the gas supply, the automatic safety shutoff devices must be checked.
1. Before beginning the tests, make sure the main
manual gas valve, and any other heater ring
valves are in the “OFF” position.
Figure 15. Control Components.
Page 15
Internet Version for Reference Only
B4 Volume Water Heater
Pilot Valve
ON POSITION
ON
ON
OFF
OFF
ON
ON
OFF POSITION
Main Gas Valve
Main Gas
Valve
Pilot
Valve
OFF
ON
ON
2. Make sure the heater’s power switch is in the “ON” position. After placing the manual pilot gas valve in the open position and resetting all safety devices, (high limit, pressure switch, low­water cutoff, etc.) pilot(s) can be lit following the procedure located on the heater rating plate.
3. Once the pilot(s) is lit and has been established for ve minutes, the ame failure response time should be checked as follows:
System 9 - (Intermittent ignition): With this
system pilots are automatically lit when the operating controls call for heat. If the pilot ame fails for any reason, the main valve is shut off within one second and the pilot spark ignition is initiated until the pilot ame has been reestablished. On propane systems, unit locks out for safety. This sequence should be checked by turning off the manual pilot gas valve, and, at the same time, monitoring the audible sparking at the pilot burner and signal interruption to the main valve.
Caution
Propane gas is heavier than air and sinks to the ground. Exercise extreme care in lighting the heater when so equipped.
Page 15
Figure 16. Gas Manual Valves.
System 16 - (Electronically supervised standing
pilot system): Extinguish the pilot ame by placing the manual pilot valve in the closed position, and at the same time, begin recording the time it takes for the output signal from the electronic ignition control to be interrupted. The signal interruption can be detected either with a test light or a voltmeter. The response time should never exceed one second.
4. With the pilots lit, initial activation of the main burners can be achieved by slowly opening the main manual valve. The result should be a smooth lighting of the main burners.
Hi-Limit Checkout:
After running the heater for a long enough
period, bring the water temperature within the range of the hi-limit and slowly back off the high limit setting until the heater shuts off. The main burners should reignite when the hi-limit is reset and turned back up to its original setting. The heater should now run until it shuts off automatically on operating aquastat.
3.3 To Start Up System:
3.3.1 Start Up Heater
Be certain system pump is running, then proceed
as follows:
1. Turn off main electrical switch.
2. Turn off all manual gas valves and wait ve
3. Set operating control to lowest setting.
minutes (see Figure 16).
4. Slowly turn manual gas valve to “ON”.
5. Reset all safety valve switches (manual reset high limit and low water cut off).
6. Open manual pilot valve. Turn on main electrical switch.
7. Set temperature controller to desired temperature. Pilot will light automatically to ignite main burners whenever the aquastat calls for heat.
For standing pilot system, press on pilot relay
knob, see Figure 17, light pilot and keep relay knob depressed for one minute then release. Once the pilot is lit, the power is supplied through the aquastat to the main gas valve.
3.3.2 To set the temperature and high-
limit controls:
When using a tank aquastat: Set the tank aquastat to the desired tank
temperature. Set the heater temperature control 20°F higher than tank aquastat. Set the manual reset high limit 50°F higher than tank aquastat. Example: If desired temperature is 140°F, set the tank aquastat at 140°F, set the heater temperature control at 160°F, and set the manual reset high limit at 190°F. If the heater is equipped with a pump time delay, the three-position switch on the side of the heater can be put into the “Auto Pump” position, so that the pump will only run when the tank aquastat calls for heat. Then, when the call for heat is satised, the heater will turn off, but the pump will run for the set amount of delay time (adjustable between 0.1 and 10 minutes).
Page 16
Internet Version for Reference Only
B4 Volume Water Heater
Page 17
Pilot Reset
Page 16
Figure 17. Pilot Safety Relay.
When a tank aquastat is not used:
The pump on the heater must run continuously, so the heater's temperature control will sense the tank's water temperature. Set the heater temperature control to the desired tank temperature. Set the manual reset high limit 50°F higher than the heater temperature control. Example: If desired temperature is 140°F, set the heater temperature control at 140°F, and set the manual reset high limit at 190°F.
BRADFORD WHITE
3.4 To Turn Off Heater:
1. Turn off main electric switch.
2. Close all manual gas valves.
3.5 To Shut Down System:
To shut down heater, turn off all manual gas valves and electrical disconnect switches. Whenever danger of freezing exists, shut off water supply and remove drain plug in the bottom of front header cover. Drain every part of system subject to freezing temperature.
SECTION 4. Maintenance
1. Lubricate the water circulating pump (see
instructions found on the pump).
2. If a strainer is employed in a pressure reducing
valve or in piping, clean it every six (6) months.
3. At start-up and every six (6) months thereafter,
the pilot and main burner ame should be
observed for proper performance (see Figure 18).
See attached lighting and shut-down instructions
for proper pilot ame pattern). If ame has the
appearance of “sooting” tips, check for debris
near orices. Call serviceman.
4. Inspect the venting system for obstruction,
leakage and corrosion at least once each year.
Figure 18. Main Burner Flame Pattern.
5. Keep heater area clear and free from combustible material, gasoline and other ammable vapors and liquids (see Table 1 for minimum clearances).
6. Be certain all combustion air and ventilation openings are unobstructed.
7. Check for fouling on the external surfaces of the heat exchanger every six months. (NOTE: After installation and rst start-up, check the heat exchanger for fouling after the following periods of operation: 24 hours, 7 days, 30 days, 90 days, and once every six months thereafter).
Fouling on the external surfaces of the heat
exchanger is caused by incomplete combustion and is a sign of combustion air and/or venting problems. As soon as any fouling is observed, the cause of the fouling should be corrected (see Section 5, Troubleshooting Guide). The heat exchanger can be checked by locating a mirror under the burners with a ashlight. An alternate method is to remove the venting and top panel as necessary to inspect from above. Also check the vent system for defects at this time.
a. If cleaning is required, shut off all electrical
and gas supply to the heater.
b. To expose the heat exchanger:
Indoor Models:
Remove ue pipe, top of unit, rear upper jacket,
ue collector rear panel and heat exchanger bafes.
Outdoor Models:
Remove vent top assembly, rear upper jacket,
ue collector rear panel and heat exchanger bafes.
c. Remove all burners:
It is usually more convenient to remove
the burner tray assembly. Disconnect sensor wire, ignition cable (or thermocouple generator) and pilot gas line. Disconnect manifold inlet union(s). Remove the four (4) retaining screws. Grasp burner/pilot assembly rmly at the front. Push it back, disengaging it from the gas orice. Lower the front of the burner (to avoid damaging pilot shield) then remove the burner tray.
Page 17
Internet Version for Reference Only
B4 Volume Water Heater
Caution
Black carbon or green soot on a dirty heat exchanger can, under certain conditions, be ignited by a random spark or open ame. To prevent this unlikely occurrence, dampen the soot deposits with wet brush or ne water spray before servicing or cleaning the heat exchanger.
With a wire brush, remove soot and loose scale
from heat exchanger. Clean fallen debris from bottom of heater. Make sure burner ports are clear and pilot assembly is free of debris.
d. Reassemble in reverse order: Be sure the
heat exchanger bafes are replaced.
8. The gas and electric controls installed on heaters are engineered for both dependable operation and long life, but the safety of this equipment completely depends on their proper functioning. It is strongly recommended that the basic items be checked by a competent serviceman every year and replaced when necessary. The basic controls are:
a. Water temperature controls. b. Pilot safety system. c. Automatic electric gas valve(s). d. Flow sensing safety device.
9. Low water cutoffs should be inspected every six (6) months, including ushing of oat types.
NOTE: Warranty does not cover any damage
caused by lack of required maintenance or improper operating practices.
10. Both modulating and stage valve are adjusted at the factory for minimum permissible rates and should not be readjusted.
Page 17
c. Tube cleaning kit consisting of reamer,
stainless steel brush, speed handle and handle extensions.
d. Heater thermometer (with 1/2" NPT well)
100-240°F.
2. In addition, the heater should be equipped with a system pressure gauge with proper ranges for heater operation.
I. HEATER WILL NOT FIRE.
Possible Cause What To Do
A. Electric power is off A. Check to see that main power switch is “ON.” Use testing device to trace power to heater junction box.
B. Operating or safety control B. Turn off power. Use continuity has opened circuit to electric across terminals of each gas valve. operating and safety control switch up to the electric gas valve. Replace effective control.
C.Pilot ame is out. C.Relight pilot per instruction.
D.Manual reset device has D. Follow instructions for start­ tripped. up. Reset Pilot safety and all manual reset safety switches and reset manual safety gas valve.
E. No gas pressure to burners. E.Trace gas line to service shutoff cock. If service cock is open, trace gas line to meter. If no pressure is present at meter, call for public utility service. If gas is present in heater inlet, check pressures in following sequence: (1) downstream from pressure regulator. (2) downstream from electric gas valve. Replace or adjust as necessary.
SECTION 5. Troubleshooting and Analysis of Service Problems
1. For proper service and problem diagnosis of the heater and heater system, the following tools are required:
a. Gas pressure test kit with range from zero
to 14 W.C. Either a slack tub manometer or an accurate gas pressure gauge is acceptable with proper adapters which will connect to the available ttings in the line and on the
gas valve. b. Multi-meter with the following ranges: 0 to 500 volts A.C. 0 to 1000 ohms continuity.
F. Electric gas valve operator is F. Disconnect wiring harness at burned out or shortened. gas valve terminals. Check continuity to actuator coil. If open circuit or short is
Page 18
Internet Version for Reference Only
Page 18
B4 Volume Water Heater
Page 19
BRADFORD WHITE
II. HEATER IS POUNDING, KNOCKING OR EMIT­TING STEAM FROM RELIEF VALVES.
Possible Cause What To Do
A. Low or no water ow. A. This condition is usually
caused by lack of adequate
water ow through heater. Check the following:
1. Is the heater wired into the pump circuit so that the heater cannot re unless the pump is running?
2. Check to see that all valves in system are open to be sure that water can circulate through the heater and the system.
3. If the system has automatic water valves (2-way or 3-way) that can cut off the water ow through the heater check to see that they are equipped with end-switches which shut the heater down when the water ow through the heater is reduced by 70% from full ow.
4. Examine pump for clogged impeller.
B. Low or no system pressure. B. Clean strainer in pressure
reducing valve. Look for closed
valve water line or a leak in the system.
C.Clogged “Y” strainer. C. Remove strainer element and clean screen.
D.Debris from system piping D. Remove header covers. is blocking tubes. Examine all tubes and waterways. Use new gaskets when reassembling. Clean out tubes.
E. Scale has formed in tubes. E. This is always caused by the inow of raw water into the system. Clean tubes with tube cleaning kit. Determine hardness. Check water ow, replace pump for modied ow if necessary.
III. WATER DRIPPING IN FIREBOX.
Possible Cause What To Do
Tube in heat exchanger has A tube failure is almost always overheated and ruptured. caused by (a) scale formation in the tube or (b) inadequate water ow through the heater.
IV. PRESSURE RELIEF VALVES LEAKING INTER­MITTENTLY OR STEADILY.
Possible Cause What To Do
A.Static pressure in system A. Calculate height of water in exceeds setting of relief valve. system above heater. Install
new valve with psi setting 25%
above required static system working pressure. Do not exceed 160 psi.
B. Expansion tank is water- B. Drain expansion tank, then logged (if installed). reopen it to the system. Look
for leaks in expansion tank
or ttings. Calculate required volume of expansion tank in relation to system to determine if tank is adequate.
V. SOOT IN FLUEWAYS OR IN TUBES, OR NOX­IOUS FUMES INDICATIVE OF BAD COMBUSTION.
Possible Cause What To Do
A. Combustion air supply to A. Check air supply opening. heater room is inadequate. Look for debris in screen or
louvre which covers combus-
tion air opening, or for material blocking the opening.
B. Stack or vent is blocked or B. Look for blocked stack and restrictive. excessive number of elbows in
stack or excessive length of
horizontal runs.
C.Severe down draft is causing C.Check for (1) proper vent cap spillage of ue products into on stack; (2) adequate height room. of stack above roof;
(3) equipment exhausting air
from inside of building; and (4) proper installation of draft diverter.
D.Gas pressure to burners is D.Check gas pressure with excessive. nanometer, and adjust with heater ring at full rate.
E. Heater not tted for the fuel E. See nameplate for correct fuel. supplied.
F. Heater installed at high F. Installations at altitudes in altitude without proper excess of 2000 ft. above sea derating. level are subject to jurisdiction of the local inspection authorities.
Page 19
Internet Version for Reference Only
B4 Volume Water Heater
Page 19
This page intentionally left blank.
Page 20
Internet Version for Reference Only
Page 20
C O R P O R A T I O N
B W
RADFORD HITE
®
BRADFORD WHITE
®
Ambler, PA 19002 Tech. Service (800) 334-3393 Service Parts (800) 538-2020 Warranty Service (800) 531-2111
H2317100-
www.Bradford White.com
Litho in U.S.A. © Bradford White 0602 Document 2144
Loading...