Bradford White 6A, 12A, 20A, 30A, 40A User Manual

...
COMMERCIAL ELECTRIC ENERGY SAVER
WATER HEATER
ASME SERIES IMMERSION THERMOSTAT
WITH CONTACTORS
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
Models Covered
by This Manual:
6A, 12A, 20A, 30A, 40A, 50A, 80A, 120A
Manual 2
38-47202-00A REV 08/18
Save this manual for future reference
Table of Contents
Page Service Procedure
Introduction ………………………………………………………………………. 2 - - -
Tools……………………………………………………………………………… 2 - - -
General Information ……………………………………………………………… 3 - - -
Sequence of Operation …………………………………………………………… 10 - - -
Troubleshooting ………………………………………………………………….. 13 - - -
Heating Element Testing ……………..................................................................... 15 ACE-I
Line Voltage Testing………………...…………………………………………… 16 ACE-II
Fuse Testing…......................................................................................................... 17 ACE-III
High Limit (ECO) Testing……………………………………………………..…. 18 ACE-IV
Immersion Thermostat Operation Testing………................................................... 19 ACE-V
Contactor Operation Testing……………………………………………………… 20 ACE-VI
Immersion Thermostat Removal and Replacement…………….………………… 21 ACE-VII
High Limit (ECO) Removal and Replacement……………..…………………….. 22 ACE-VIII
Heating Element Removal and Replacement …………………………………….. 23 ACE-IX
Anode Inspection and Replacement ……………………………………………… 24 ACE-X
Generic Parts List ………………………………………………………………… 25 - - -
Glossary of Terms…………………………………………………………………. 26 - - -
Page 2
This service manual is designed to aid service and maintenance professionals on the function, proper diagnosis and repair of Bradford White Commercial Electric Water Heaters.
The text and illustrations in this manual provide step by step instructions to facilitate proper operation and troubleshooting procedures. Contact the Bradford White Technical Support Group immediately if diagnosis can not be made using the methods described in this service manual.
Introduction
ASME Series
Commercial Electric Water Heaters
Tools
- Multi Meter. - Phillips Head Screw Driver.
- 2-1/8" Deep Well Socket. - Common Screw driver.
- 1-1/16" Deep Well Socket. - Thermometer.
- ¼"
Nut Driver. -Drain Hose.
- Other Hand Tools: Pipe Wrench, Channel Locks, Pliers (common & needle nose), Wire cutters, Wire Strippers, Allen Wrench Set, Flash Light.
2
GENERAL INFORMATION
120A - 24 - 3 - 108B - BBG
Pressure Gage Option.
Control Circuit Option Code.
Any combination of the following optional controls:
- Heating Element Time Delay Sequencing.
- L
ow Water Power Interrupt.
- Pan
el Door Interlock
-High Pressure Power Interrupt
- L
ow Pressure Power Interrupt
- Al
arm Horn
Power Circuit Code.
-Voltage
-
k
W Rating
-
P
hase
-Amp Rating
Warranty
Tank
BRADF ORD WHITE CORPORATION 200 LAFAYETTE ST. MIDDLEVILLE MI 49333 Model No: 120A-24-3-108B-BBG Serial No: ZB25 64812 Cap. 120(gal.)/454.2(liters) Press: Test 300(psi), Working 150(psi)
Volts 240 Max Temp 180° Phase Single Amps 100 kW Each 6 Total kW 24 4 Elements Wattage Rating Based Upon 60 Hz
Page 3
Typical Rating Plate
Located On Front Of Water Heater
Model Number
Electrical Characteristics
Model Number Breakdown
kW Rating
In the Field, this inform ation is obtained from the heaters
rating plate
NOTE: Code “AA”
denotes no optional
controls used.
3
Page 4
GENERAL INFORMATION
General Controls Layout
P
ressure
G
age
(optional)
Control Circuit
T
ransformer
Thermostat
Control
Heating Element
Time Delay
Sequen cers
(optional)
Terminal strip
High Limit
(
ECO)
P
ower Circuit
F
use Blocks
T
erminal
Block
Control Circuit
Fuse Block
Contactors
High Limit
Immersion Bulb
T
hermostat
I
mmersion
Bulb
Heating Element
Alarm
Horn
(optional)
A
larm
Horn Relay
(optional)
Low Water
L
evel Control
(optional)
Low Pressure
L
imit Switch (optional)
H
igh Pressure
L
imit Switch (
optional)
Contactor
Terminal connections to the
fuse block and/or terminal block
Terminal connections to the
heating elements
Terminal connections of contactor operating coil.
Contactor operation is achieved by energizing a 120 volt operating coil located within the contactor in response to a call for heat from the immersion thermostat. Upon a call for heat, one or more contactors will energize all heating elements simultaneously. Optionally, time delay sequencers may be used to stage contactor activation thereby reducing the inrush of current to the water heater.
Standard Controls
4
GENERAL INFORMATION
Page 5
Immersion Style Thermostat Control
Immersion Thermostat Control
Standard Controls (continued)
D
irect
I
mmersion
b
ulb
T
he thermostat will complete control circuit voltage upon a call for heat. Likewise, the control will interrupt control circuit voltage when the water t
emperature is sufficient to satisfy the adjustable
temperature limit of control.
The high limit (ECO) control will interrupt control circuit voltage causing the heater to shut down when the high temperature limit of the control is reached (196°F±4°F). Once the cause for over heated water has been determined, The control must be manually reset to restore normal operation.
Immersion Style High Limit (ECO) Control for Contactor Models
Direct
Immersion
bulb
Manual Reset
Buttons
5
Page 6
GENERAL INFORMATION
Optional Controls
High and Low Water Pressure Controls-
These controls interrupt the electrical current to the contactor coil when the pressure settings are exceeded. The operation and setting of these controls are described in the manual provided by the control manufacturer. This manual is included with the water heater Installation and Operating Instruction manual provided with the water heater.
The pressure settings for these controls are adjustable. These controls are specified for use when the installation has unique pressure requirements that must be safeguarded. Therefore, before adjusting the pressure values, it is recommended that you consult the person responsible for the facility that the water heater is servicing.
The electrical connections are referenced in the Control Circuit Wiring Diagram and in the pressure control manual provided by the control manufacturer. Refer to these instructions when servicing the controls.
2-1/8 Hex Screw-in Flange
T
erminal Block
Screw
T
erminal Block
Z
inc Plated Copper or
I
ncoloy Sheath
E
lement Rating Ink Stamped
on face of Te rminal Block.
Direct Immersion “Screw-in” Type Heating Element
Standard Controls (continued)
Certain control components are available as “Optional“. When these optional components are installed with the water heater, the control circuit wiring diagram accordingly will include these components. The optional equipment available from the manufacturer includes the following:
-High Water Pressure Switch -Heating Element Time Delay Sequencers
-Low Water Pressure Switch -Electrical Door Lock
-Low Water Level Switch -Alarm Horn
6
GENERAL INFORMATION
Optional Controls (continued)
T
his control will interrupt the electrical current to the contactor coil when a low water level condition is sensed inside the water heater tank. When the low water level condition is corrected the control will automatically sense the new situation a
nd electrical current will again energize the contactor coil. Normal water heater operation will be resumed.
T
o remove the low water level control from the tank you must first loosen the control by un-threading it from the tank fitting and then rotating the control until the arrow printed on the side of the hex fitting is pointing downward. This will enable the float orientation to align itself with the opening in the tank-fitting.
Low Water Level Control-
When installed, refer to the direction of the arrow on the hex and insure that it is pointing upwards. If it is not pointing upward, the control switch will not activate when the tank is refilled with water. Refer to illustration below for clarification.
Heating Element Time Delay Sequencers-
Heating element sequencers are available in order to stage the activation of the heating elements thereby, reducing the inrush of electrical current to the water heater. The sequencers will control one or more contactor coils depending upon the water heater voltage, phase, and KW.
One contactor will be energized immediately when there is heating demand, the second contactor, controlled with a sequencer, will be activated approximately 20 seconds later, and the third contactor will be activated in another 20 seconds thereby, staging the three contactors over the 40 second time period. The staging occurs in a similar manner for applications having more than three contactors.
Refer to the Control Circuit Wiring Diagram for the specific application being serviced.
Note: On the occasion of servicing the water heater where frequent restarts in a short time interval are encountered (i.e. on, off, on, etc.), the timing sequences will not begin until the sequencers have experienced a time interval to reset.
Page 7
7
GENERAL INFORMATION
Optional Controls (continued)
Electrical Door lock-
An electrical door lock is offered in order to secure the access to the water heater control cabinet. This device will lock the control cabinet door when the 120VAC control circuit voltage is applied to it.
Note: Once the door is opened, the water heater can be re-energized, if necessary, for service diagnosis.
Alarm Horn-
The Alarm Horn is an option specified when the installation desires an audible signal to immediately sound an alert when the water heater operation is interrupted for certain faults. Referring to the control circuit wiring diagram, the alarm will activate when any one of the following events occur:
The Hi-Limit control has been tripped
The High Water Pressure Control senses excessive pressure
The Low Water Pressure Control senses insufficient pressure
The Low Water Level Control senses an insufficient quantity of water
The alarm will sound only for the options specified (i.e. if a low water level control is not specified then the alarm will not recognize a low water level condition).
Horn Relay
Horn Relay
Internal Wiring
Page 8
Combination Temperature and Pressure Gage-
A non-electrical device to visually reference water temperature and internal tank pressure.
8
GENERAL INFORMATION
Watts
Volts x 1.732
Watts = Amps x Volts
Volts
Watts
2
Commonly Used Formulas
240V 1Ph
Ungrounded
Ungrounded
Grounding
BLACK
R
ED
G
REEN
240
120
Common Service Wire Configurations
Page 9
120
(balanced 3 phase)
Amps =
Watts
Volts
(
Single phase)
Amps =
O
hms =
120
ABCNeutral
RED BLACK RED
120
120
208
208 208
208 3Ph
120
ABCNeutral
RED BLACK RED
120
120
240
240 240
240 3Ph
277
ABCNeutral
RED BLACK RED
277
277
480
480 480
480 3Ph/277 1Ph
Full Load Current Amps
208 Volt
1 Ph 3 Ph
6
kW
9
12
13.5
15
18
24
27
30
36
45
54
28.8 16.6
43.2
25.0
57.6 33.3
64.9
37.5
72.1 41.6
86.5
50.0
115.4
66.7
129.8
75.0
144.2 83.3
173.0 100.0
216.3 125.0
259.6 150.0
240 Volt 277 Volt 380 Volt 415 Volt 480 Volt
25.0 14.4
37.2 21.6
50.0 28.9
56.2 32.5
62.5 36.1
75.0 43.4
100.0 57.8
112.5
65.0
125.0 72.2
150.0 86.7
187.5 108.3
225.0 130.0
12.5 7.2
18.7 10.8
25.0 14.4
28.1 16.2
31.2 18.0
37.5 21.6
50.0 28.9
56.2 32.5
62.5 36.1
75.0 43.3
93.7 54.1
112.5 65.0
1 Ph
21.6
32.4
43.3
48.7
54.1
64.9
86.6
97.4
108.3
129.9
162.4
194.9
3 Ph
8.3
12.5
16.7
18.8
20.9
25.0
33.4
37.5
41.7
50.1
62.6
75.1
3 Ph
9.1
13.6
18.2
20.5
22.7
27.3
36.4
41.0
45.6
54.7
68.4
82.0
1 Ph 3 Ph 1 Ph 3 Ph
3 14.4 - 12.5 - 6.3 -10.8 --
81 389.4 224.8 337.5 194.8 168.7 97.4292.4 112.6123.1
600 Volt
3 Ph
5.7
8.66
11.5
13.0
14.4
17.3
23.1
26.0
28.8
34.6
43.3
52.0
-
78.0
9
SEQUENCE OF OPERATION
This water heater has two distinct electrical systems. One system, referred to as the “Control Circuit”, controls the w
ater heater operation, while the other system referred to as the “Power Circuit”, connects the electrical power to the heating elements, The electrical contactors interconnect these two systems. In order to clearly illustrate the electrical circuits, two wiring diagrams are provided. These diagrams are labeled as the “Control Circuit Wiring Diagram” and the “
Power Circuit Wiring Diagram” and they are attached to the surface of the panels inside the water heater control
cabinet.
The control circuit operates with 120VAC electrical service. This voltage is provide by the multi-tap transformer which has the primary coil connected to the field wiring that is serving the water heater. The Transformer, Thermostat, Hi-Limit c
ontrol, and the Contactor Coil are always included in the Control Circuit.
Control Circuit Description-
Certain other control components are available as “Optional“. When these optional components are installed with the w
ater heater, the control circuit wiring diagram accordingly will include these components. The optional equipment available from the manufacturer includes the following:
High Water Pressure Switch
Low Water Pressure Switch
Low Water Level Switch
Alarm Horn
Heating Element Sequencers
Electrical Door Lock
Control Circuit Wire Diagram
4
When the thermostat calls for heat, contacts close inside the thermostat completing the circuit and energizing the contactor coil.
The energized contactor coil causes the contactor to close energizing the heating elements.
5
When the temperature setting of the thermostat is reached, the contacts in the thermostat open. This interrupts current flow through the control circuit de­energizing the contactor coil.
6
The de-energized contactor coil causes the contactor to open, interrupting current flow through the Heating elements.
7
Page 10
NOTE: To help understand the concept of the operating sequence, the control circuit shown is without any optional controls. See page
11 For control circuit showing all available optional controls
Control Circuit Sequence of Operation-
Line voltage from
power circuit
1
Line voltage is applied to control circuit fuse block.
2
Line voltage continues to transformer with one leg of voltage connecting to the common terminal and the other leg connecting to the appropriate line voltage multi-tap terminal. Transformer output (always 120 volts) continues to high limit (ECO) control.
3
Hi limit (ECO) control is closed so one leg of 120 volts continues to one side of the contactor coil. The other leg is connected to the thermostat.
Appropriate line
voltage multi-tap
terminal
10
SEQUENCE OF OPERATION
Page 11
C
ertain other control components are available as “Optional“. These controls are specified when the installation has unique requirements that must be safeguarded. When these optional components are installed the control circuit wiring diagram accordingly will include these components. The optional equipment available from the manufacturer includes the following:
High Water Pressure Switch
Low Water Pressure Switch
Low Water Level Switch
Alarm Horn
Heating Element Sequencers
Electrical Door Lock
-Heating Element Sequencers are wired in series with contactor coils staging contactor activation at intervals of approximately 20 seconds.
Control Circuit Sequence (Continued)-
-Hi and Low Pressure Switch and Low Water Level Switch when specified are always wired in series ahead of the Hi-limit control.
Control Circuit Sequence of Operation with Optional Controls-
Control Circuit Wire Diagram
Showing Optional Controls
L
ine voltage from
power circuit
Same as explained on page 10 with the following exceptions:
-Alarm Horn is wired in series ahead of the thermostat. It monitors only the Hi and Low pressure switch, Low water level Switch and the hi-limit (ECO). If either of these switches open, power to the horn relay is interrupted causing the relay to close sounding the alarm horn.
-Electrical Door Lock is wired in parallel to secure the access to the water heater control cabinet. This device will lock the control cabinet door when the 120VAC control circuit voltage is applied. Once the door is opened, the water heater can be re-energized, if necessary, for service diagnosis.
A
ppropriate line
v
oltage multi-tap
terminal
11
SEQUENCE OF OPERATION
The Power Circuit Wiring Diagram illustrates the electrical connections from the incoming power supply through the contactors to the heating elements. The power circuits are available with internal circuit fusing and without internal circuit fusing.
As it would be impractical to show all wired configurations in this service manual, a reference wiring diagram is illustrated below to aid in the understanding of the power circuit operating sequence. Service providers must refer to the water heaters power circuit wiring diagram attached to the inside panel of the control cabinet for the specific connections of the water heater being serviced.
The power circuit components and supporting information that appear on the wiring diagram include the following:
Field wiring connection via terminal block or other connection point
Fuse block with amperage ratings displayed (when provided)
Contactors with amperage ratings displayed
Electrical elements with voltage and wattage ratings displayed
Water heaters total amperage draw is displayed
Power Circuit Description-
Line voltage is applied across terminals of fuse block or a terminal block. Line voltage continues down and connects to terminals L1, L2 & L3 of one or more contactors.
A)
C
ontactor is open (no call for heat), so there is no
v
oltage across terminal T1, T2 & T3
o
f contactor.
B)
The
contactor is controlled by the control circuit
a
s explained on pages 10 & 11.
1
2
The control circuit senses a call for heat and energizes the operating coil within the contactor.
The energized contactor coil causes the contactor to close energizing the elements from terminals T1, T2 & T3 of the contactor.
3
When the temperature setting of the thermostat is reached, the contacts in the thermostat open. This interrupts current flow through the control circuit de­energizing the contactor coil.
4
The de-energized contactor coil causes the contactor to open, interrupting current flow through the elements.
5
Power Circuit Sequence-
Line voltage from
service panel
Line voltage to control circuit
Page 12
12
TROUBLESHOOTING
Most common cause for improper electric water heater operation can be linked to heating element failure.
W
hen troubleshooting an electric water heater with the incidence of “No Hot Water” or “Insufficient Amount of Hot
Water” It is always a good idea to check the heating elements first following the procedure on page 15.
C
ommon Heating Element Failures Are:
1
. Dry Firing. Elements may be partially submerged in water or most likely, completely exposed with no water
in the tank at all. In open air, an energized element (Dry Fired) will become completely inoperable within seconds. In some cases sediment or lime build up around an element can eventually cause an air pocket, resulting in a dry fired element. When element replacement is required, be sure tank is full of water prior to energizing the water heater.
2. Grounded Element. In most cases, an element with a short circuit to ground will cause the circuit breaker in the service panel to open or shut off. In some cases there may not be enough current draw for the circuit breaker to open. This will allow the heating element to be in continuous operation resulting in over heated water, limited only by the hi-limit (ECO) located in the control circuit. Repeated actuation of the hi-limit usually is the result of a grounded heating element.
3. Sediment build up. Slow hot water recovery can usually be traced back to sediment or lime build up around heating element. Sediment build up can also over time cause a dry fired element.
If an heating element is found to be inoperative, it must be replaced. Follow service procedure ACE-IX on page 23.
The illustration below shows a common “Screw-In” type heating element identifying certain features commonly referred to throughout this manual.
Typical Direct Immersion “Screw-In”
Type Heating Element
Page 13
2-1/8 Hex Screw-in Flange
Terminal Block Screw
Terminal Block
Zinc Plated Copper or Incoloy Sheath
Element Rating Ink Stamp ed on face of Te rminal Block.
13
SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION
No Hot Water
1. No power to h eater. 2
. Blown water heater fuses.
3. Loose wire connections. 4
. Inoperative heating element(s).
5. Inoperative thermosta t.
6. Open ECO.
7. Inoperative contactor(s).
1. Inoperative heatin g element(s).
2. Thermostat set to low.
3. Inoperative thermosta t.
4. Inoperative contactor(s).
5. Loose wire connection.
6. High demand period.
7. Undersized heater.
8. Very cold inlet water to heater.
9. Plumbing connections reversed.
Not Enough Hot
Water
Slow Hot Water
Recovery
1. Sediment or lime build up on element(s).
2. Loose wire connections.
3. Inoperative contactor(s).
4. Derated heating element installed.
Over Heated
Water
1. Grounded heating element(s).
2. Thermostat set to high.
3. Inoperative thermosta t.
4. Inoperative ECO.
1
. Check circuit breakers at service panel.
2. Check water heater fuses. 3
. Check all wire connectio ns.
4. Check heating element(s).
5. Check thermosta t operation.
6. Reset (check) ECO.
7. Check contactor operation.
1. Check heating element(s).
2. Increase thermostat setting.
3. Check the rmosta t.
4. Check contactor operation.
5. Check all wire connectio n.
6. Reduce demand.
7. Replace with large r heater.
8. Temper water to hea ter.
9. Correct plumbing connections.
1. Clean or re place hea ting elements.
2. Check all wire connectio ns.
3. Check contactor operation.
4. Verify element voltage and wattage rating.
1. Check heating element(s).
2. Adjust thermostat to desired setting.
3. Check the rmosta t.
4. Check ECO.
SERVICE
PROCEDURE
2. ACE-III, Page 17
4. ACE-I, Page 15. 5
. ACE-V, Page 19.
6. ACE-IV, Page 18
7. ACE-VI, Page 20
1. ACE-I, Page 15.
3. ACE-V, Page 19.
4. ACE-VI, Page 20 .
1. ACE-IX, Page 23 .
3. ACE-VI, Page 20 .
4. See page 6.
1. ACE-I, Page 15.
3. ACE-V, Page 19.
4. ACE-IV, Page 18.
Page 14
Noisy (singing or
hissing) Elements
1. Lime formation on elements.
2. High or low line voltage.
1. Clean or re place hea ting elements.
2. Verify line voltage to heater.
1. ACE-IX, Page 23 .
2. ACE-II, Page 16 .
TROUBLESHOOTING
WARNING High voltage exposure. Use caution when making voltage checks to avoid hazard to
life or property.
Noisy Contactor
1. Low line voltage.
2. Debris between contactor plates.
3. Incorrect or defective operating coil.
4. Loose wire connections.
1. Verify line voltage to heater
2. Replace contactor.
3. Replace contactor.
4. Check wire connections.
1. ACE-II, Page 16
Quick Step Plan to Hot Water
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Check all wire connections to insure they are snug and corrosion free.
3. Reset high limit (ECO) (page 18).
4. Check for inoperative heating element (page 15).
5
. Check line voltage (pg 16), and internal fuses (page 17).
6. Refer to table below if items 1 through 5 above do not correct problem.
14
SERVICE PROCEDURE ACE-I
Heating Element Testing
1
. STOP, DANGER! Turn power “OFF” to water heater.
2
. Open control panel access door.
3. Disconnect wires from heating element.
4
. Set multi-meter to “ohms” setting.
5. Touch probes of multi-meter to screw terminals of heating element (see illustration 1).
6
. Reading should be 12.8 ohms (±6%) for a 240 volt, 4500 watt element, see table below for other elements.
A reading outside the range using the formula above (±6%), indicates a bad element and the element must be replaced.
Test for Open or Burned Out Element.
DANGER
High voltage exposure. To avoid hazard to
Life or property, be sure power is turned
OFF to water heater while performing this
procedure.
Test For Grounded Heating Element (damaged heating element with short circuit to ground).
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control panel access door.
3. Disconnect wires from heating element.
4. Set multi-meter to “ohms” setting.
5. Touch one probe of multi-meter to either screw terminal of heating element and the other on the element flange (see illustration 2). There should be no reading on the ohm meter. Any reading indicates a grounded element and the element must be replaced. Repeat this step for the other screw terminal.
Ohms = Volts
2
Watts
E
lement Screw Terminals
Element
Screw Te rminal
Element Flange
Illustration 1
Illustration 2
Page 15
NOTE
Disconnect
element
Wires
NOTE
Disconnect
element
Wires
Ohms of electrical Resistance
For commonly Used Elements
Voltage Rating of Element Element Wattage 208 240 480 600
2000 21.6 28.8 115.2 180 3000 14.4 19.2 76.8 120 4000 10.8 14.4 57.6 90 4500 9.6 12.8 51.2 80 5000 8.7 11.5 46.1 72 6000 7.2 9.6 38.4 60 9000 4.8 6.4 25.6 40
15
SERVICE PROCEDURE ACE-II
Line Voltage Testing
L
ine Voltage Testing
Illustration 3
Page 16
1
. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control panel door.
3. Determine connection point for line voltage from service panel, terminal block or
fuse block
4. Set multi-meter to volts AC. Be sure to scale meter for appropriate voltage.
5. Use caution and turn power “ON” to water heater.
6. Use caution and check voltage across top terminals where service voltage connects to water heater. (see illustration 3).
A) Rated voltage IS present, power to
the water heater is okay.
B) Rated voltage NOT present, Check
service panel.
Line voltage (single phase or three phase) will connect to a terminal block or directly to a fuse block l
ocated inside control panel.
Determine heaters voltage and phase by referring to the rating plate located on the front of the heater. Apply the a
ppropriate phase procedure below to determine if proper line voltage is present.
Single Phase Line Voltage Testing
Line voltage from
service panel
connected to Terminal bloc k
of heater
Line voltage from
service panel
connected to Fu se block
of heater
OR
Check voltage across
top terminals.
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control panel door.
3. Determine connection point for line voltage from service panel, terminal block or
fuse block
4. Set multi-meter to volts AC. Be sure to scale meter for appropriate voltage.
5. Use caution and turn power “ON” to water heater.
6. Use caution and check voltage across top terminals where service voltage connects to water heater. (see illustration 4).
A) Rated voltage IS present, power to
the water heater is okay.
B) Rated voltage NOT present, Check
service panel.
Three Phase Line Voltage Testing
Line voltage from
service panel
connected to Terminal block
of heater
Line voltage from
service panel
connected to Fu se block
of heater
OR
Check voltage across
top terminals.
Illustration 4
DANGER
High voltage exposure. To avoid hazard to
life or property use extreme caution when
making voltage checks .
16
SERVICE PROCEDURE ACE-III
Fuse Testing
F
use Testing
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control panel door to allow access to fuse block.
3. Locate fuse block and remove fuses.
4. Set multi-meter to the “Ohms” setting.
5. Check continuity across fuse (see illustration 5).
A) Continuity IS present, fuse is okay.
B) Continuity NOT present, Replace with new fuse
Illustration 5
Page 17
DANGER
High voltage exposure. To avoid hazard to Life
or property, be sure power is turned OFF to
water heater while performing this procedure.
17
SERVICE PROCEDURE ACE-IV
High Limit Control Testing
H
igh Limit Control (ECO) Operation
1. Determine if Hi-Limit has actuated. This can be done by simply depressing the reset buttons. If you hear and/or feel a small click, the switch has actuated.
2. Use caution and turn power on to water heater and observe heating cycle following the Hi-Limit Heating Cycle flow chart.
S
witch Contacts:
Normally closed. Open on rise @ 196°F ±4°F Manual Reset.
Page 18
DANGER
High voltage exposure. To avoid
hazard to Life or property, be sure
power is turned OFF to water heater
while performing this procedure.
N
I
s water temp
o
ver 196°F
N
O
bserve heating cycle.
D
oes switch open?
S
witch OK
I
s water temp
o
ver 196°F
Replace switch
N
Y
Y
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Water temperature must be below 196°F ±4°F
3. Remove Hi-Limit switch from control panel. It is not necessary to remove immersion bulb from tank at this time. See general controls layout on page 4 for location.
4. Disconnect wire leads to Hi-Limit Control.
5. Depress reset buttons to insure switch contacts are closed.
6. Set multi-meter to Ohms setting, Check continuity Thru circuit A & B as shown in the illustrations below.
- Continuity IS present, Switch is okay.
- Continuity NOT present, Replace switch.
High Limit Control Continuity Testing
High Limit Heating Cycle Flow Chart
NOTE
Disconnect
Wire Leads to Control
Circuit “A” Continuity Testing Circuit “B” Continuity Testing
Y
18
SERVICE PROCEDURE ACE-V
Immersion Thermostat Testing
I
mmersion Thermostat Operation Testing
Thermostat Control Continuity Testing.
1. This procedure assumes line voltage, ECO and contactor(s) are in working order.
2. STOP, DANGER! Turn power “OFF” to water heater.
3. Open control panel door.
4. Locate thermostat control (see general controls layout on page 4) and remove wire leads to control screw terminals.
5. Water temperature in tank must be within operating range of thermostat for this test. If above or below, it will be necessary to drain tank and remove thermostat immersion bulb from tank to warm or cool the bulb to be within operating range of thermostat.
6. Set multi-meter to the “Ohms” setting.
7. Rotate thermostat dial to highest setting.
8. Check across screw terminals of control (see illustration 7).
A) Continuity IS present, okay,
Go to step 9.
B) Continuity NOT present,
replace thermostat.
9. Rotate thermostat dial to lowest setting.
10. Check across screw terminals of control (see illustration 7).
A) Continuity NOT present, thermostat is okay,
B) Continuity IS present, replace thermostat.
P
roviding the water temperature in tank is within the operating range of the thermostat, checking thermostat operation can be as simple as rotating the thermostat dial and listening to the contactor(s) to see if they respond to a call for heat.
Use caution and turn Power “ON” and rotate the thermostat dial to call for heat. With water temperature below the thermostat setting, the contactor(s) close. With the contacts closed, use caution and check for rated voltage across lower terminals of contactor(s) (see illustration 10), If rated voltage is present, the thermostat is calling for heat.
Rotate thermostat dial to the minimum setting. With water temperature above the thermostat setting the contactor(s) will open. With the contacts open, voltage should not be present at lower terminals of contactor(s).
Follow the procedure below If preliminary testing above does not verify thermostat operation.
T
hermostat Specification:
Calibration: 184°F/176°F Max Differential: 6°F Operating Range 80 to 180°F
Page 19
DANGER
High voltage exposure. To avoid hazard to
life or property use extreme caution when
making voltage checks .
T1 T2 T3
L1 L2 L3
C
heck voltage across
l
ower term inals of contactor(s)
NOTE: Disconnect
Wire Leads to Control
Screw Terminals
Thermostat
Dial
Thermostat Immersion Bulb
Illustration 6
Illustration 7
19
SERVICE PROCEDURE ACE-VI
Contactor Testing
Contactor Operation Testing
Noisy or chattering contactor operation in most cases is due to voltage variations being supplied to the water heater. E
xtended periods of voltage variations will cause damage to the operating coil of the contactor causing noisy operation. Determine that service voltage to the unit meets the electrical requirements per the rating plate located on the front of the water heater, see page 16
In addition, debris between the contact plates will cause noisy operation.
Noisy Contactor
This procedure assumes control circuit is operating correctly.
Providing the water temperature in tank is within the operating range of the thermostat, checking contactor operation can be as simple as rotating the thermostat dial and listening to the contactor(s) to see if they respond to a call for heat.
1. Turn Power “ON” and rotate thermostat dial to the maximum setting, with water temperature in tank below the
thermostat setting, the contactor(s) will close. With the contacts closed, check for 120 volts across operating coil terminals (see illustration 8).
A) 120 volts IS present, okay, go to step 2.
B) 120 volts NOT present, verify control circuit
operation.
2. Check for rated voltage across lower terminals of
contactor(s) (see illustration 9).
A) Rated voltage IS present, okay,
go to step 3.
B) Rated voltage NOT present, replace
contactor.
3. Rotate thermostat dial to the minimum setting.
With water temperature in tank above thermostat setting, the contactor(s) will open. With the contacts open, voltage should not be present at lower terminals of contactor(s).
4. Check for 120 volts across operating coil
terminals (see illustration 8).
A) 120 volts IS present, verify control circuit operation.
B) 120 volts NOT present, okay go to step 5.
5. Check for rated voltage across lower terminals
of contactor(s) (see illustration 9).
A) Rated voltage IS present, replace contactor.
B) Rated voltage NOT present, contactor is okay.
Page 20
DANGER High voltage exposure. To avoid hazard to life or property, use extreme caution when
making voltage checks .
Illustration 8
Contactor operation is achieved by energizing an operating coil located within the contactor. The contactor coil is considered part of the control circuit operating at 120 volts as described on page 10.
Contactor Operating Coil
T1 T2 T3
L1 L2 L3
Check voltage across
lower terminals of contactor(s)
Illustration 9
20
I
mmersion Thermostat Removal
1
. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control box door.
3. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain. Open
a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow heater to drain to a point below the Immersion bulb location (see illustration 10 for location ).
4
. Close drain spigot and remove hose.
5. Locate thermostat control inside lower control box
mounted to the right inside surface of the control box. (see illustration 10).
6. Follow copper capillary tube from thermostat control to
the immersion bulb location and remove immersion bulb from tank, 11/16" wrench.
7. Remove (pull) thermostat dial from stem of
thermostat control.
8. Remove the two control mounting screws and remove
thermostat control from control panel.
9. Disconnect wire leads to the thermostat control.
NOTE: It may be necessary to identify wires for proper reconnection to new thermostat.
Immersion Thermostat Replacement
10. Refer to control circuit wire diagram and properly
reconnect wire leads to new thermostat control and install new control inside control box using screws from step 8.
11. Replace control dial to stem of thermostat.
12. Loosen ferrule nut of immersion bulb.
(see illustration 11)
SERVICE PROCEDURE ACE-VII
Thermostat Removal and Replacement
Immersion
bulb
Ferrule
nut
Copper
capillary
tube
Tank
nut
13. Position tank nut at end of immersion bulb as shown in illustration 11. Insert immersion bulb into tank and tighten
tank nut.
14. Gently pull copper capillary tube to insure the immersion bulb is in a horizontal position as shown in illustration 11
and tighten ferrule nut.
15. Resume water supply, fill tank and check for leaks.
16. Be sure tank is full or water and resume power supply to water heater. Verify proper thermostat operation.
Page 21
DANGER
High voltage exposure. To avoid hazard to
Life or property, be sure power is turned
OFF to water heater while performing this
procedure.
Illustration 10
Illustration 11
Thermostat
Control
Thermostat
Immersion
Bulb
Copper
capillary
21
SERVICE PROCEDURE ACE-VIII
High Limit (ECO) Control Removal
and Replacement
Page 22
High Limit Control (ECO) Removal
1
. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control box door.
3. Turn off cold water supply to heater. Connect hose to drain
spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow heater to drain to a point below the Immersion bulb location
(see illustration 12).
4. Close drain spigot and remove hose.
5. Locate hi-limit control inside lower control box mounted
to the right inside surface of control box (see illustration 12).
6. Follow copper capillary tube from control to the
immersion bulb location and remove immersion bulb from tank, 11/16" wrench.
7. Remove the two control mounting screws
located outside the control box.
8. Disconnect wire leads to the control.
NOTE: It may be necessary to identify wires for proper reconnection to new control.
High Limit Control (ECO) Replacement
9. Refer to control circuit wiring diagram located on the
inside of the control box and properly reconnect wire leads to new control and install new control inside control box using screws from step 7.
10. Loosen ferrule nut of immersion bulb.
(see illustration 13)
Immersion
bulb
Ferrule
nut
Copper
capillary
tube
Tank
nut
11. Position tank nut at end of immersion bulb as shown in illustration 13. Insert immersion bulb into tank and tighten
tank nut.
12. Gently pull copper capillary tube to insure the immersion bulb is in a horizontal position as shown in illustration 13
and tighten ferrule nut.
13. Resume water supply, fill tank and check for leaks.
14. Be sure tank is full of water and resume power supply to water heater. Verify proper high limit operation.
DANGER
High voltage exposure. To avoid hazard to
Life or property, be sure power is turned
OFF to water heater while performing this
procedure.
Illustration 12
Illustration 13
ECO
control
Copper
c
apillary
ECO
immersion
bulb
22
SERVICE PROCEDURE ACE-IX
Heating Element Removal
and Replacement
Heating Element Removal
1. STOP, DANGER! Turn power “OFF” to water heater.
2
. Open control box door.
3. Turn off cold water supply to heater. Connect hose to drain
spigot of water heater and route to an open drain. Open a nearby hot water faucet to vent heater for draining. Open
drain spigot of water heater and allow heater to drain to a point below the heating element(s).
4. Close drain spigot and remove hose.
5. Disconnect wires from heating element terminals.
6. Remove heating element from tank using 2-1/8"
deep well socket or appropriate wrench. Unscrew element counter-clockwise to remove from tank.
7. Be sure to remove old element gasket from the tank. It is not recommended to be re-used.
Heating Element Replacement
1. Check new heating element terminal block for proper electrical rating. NOTE: Some heating elements have dual
ratings, be sure to check all surfaces of the heating element terminal block (see illustration 14).
2. Apply new gasket to the new heating element. Be sure gasket is seated flat against heating element flange without
rolls or gaps (see illustration 14).
3. Clean any debris from tank fitting where heating element is to be installed. Lubricate heating element threads as
needed with thread lubricant.
4. Thread new heating element clockwise into tank fitting. Tighten heating element using 2-1/8" deep well socket or
appropriate wrench. Do not over tighten, over tightening may damage gasket.
5. Reconnect wires to heating element, be sure connections are snug and corrosion free. Do not over tighten, doing so
may damage terminal block.
6. Resume water supply to heater, be sure tank is full of water and check for leaks.
7. To resume operation, BE SURE TANK IS FULL OF WATER and restore power to water heater. Verify proper heater
operation.
WARNING
Heater components and stored water may be
HOT when performing the following steps in
this procedure. Take necessary precaution to
prevent personal injury.
Page 23
DANGER
High voltage exposure. To avoid hazard to
Life or property, be sure power is turned OFF
to water heater while performing this
procedure.
2-1/8" Hex Screw-in Flange
Terminal Block Screw
Terminal Block
Zinc Plated Copp er or Incoloy Sheath
Element Rating Ink Stamp ed on face of Te rminal Block.
Element Ga sket Seate d Flat Again st Element Flange Without Rolls or Gaps
Illustration 14
23
Page 24
WARNING
Heater components and stored water may be HOT when performing the following steps in
this procedure. Take necessary precaution to prevent personal injury.
SERVICE PROCEDURE ACE-X
Anode Inspection and Replacement
Anode Inspection and Replacement
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.
Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow
heater to drain to a point below the anode locations at the top of the tank.
3. Close drain spigot and remove hose.
4. Remove the plastic anode access plugs at the anode locations.
5. Remove anode from the water heater (1-1/16" socket).
6. Visually Inspect anode. Anode should show signs of depletion, this is normal.
If depletion is ½ of the original anode diameter (original diameter approximately ¾”), replacement is recommended. If any of the steel core of the anode is exposed, replacement is recommended.
7. Upon completion of inspection or subsequent replacement, reinstall anode into heater. resume water supply, refill
heater with water and check for leaks.
8. To resume operation, BE SURE HEATER IS FULL OF WATER and turn power “ON” to water heater.
DANGER
High voltage exposure. To avoid hazard to Life
or property, be sure power is turned OFF to
water heater while performing this procedure.
Anode Ro d Location
for all models
Second anode location For models having two
anodes (5 0A,80A,120A).
24
Page 25
Generic Parts List
25
Generic Parts List
Item Description
1 T&P Relief Valve. 2 Nipple Plastisert. 3 Hot Water Outlet Nipple. 4 Magnesium Anode. 5
Nipple Galvanized.
6
Pipe Tee Galvanized. 7 Combination T&P Gage (optional). 8 High Pressure Switch (optional). 9 Low Pressure Switch (optional). 10 Screw. 11 Immersion Thermostat. 12 Thermostat Dial. 13 Hex Nut. 14 Lock Washer. 15 Screw. 16 High Limit Spacer. 17 High Limit Switch. 18 Cleanout Access Cover. 19 Cleanout Cover Screw. 20 Cleanout Cover. 21 Cleanout Gasket. 22 Brass Drain Valve. 23 Finish Flange. 24 Extender. 25 Alarm Horn Relay (optional). 26 Alarm Horn (optional). 27 Heating Element Gasket. 28 Heating Element. 29 Heating Element Plug. 30 Low Water Switch (optional).
Item Description
31 Low Water Switch (optional). 3
2 Electrical Door Lock (optional). 33 Control Box Door. 34 Control Box. 3
5 Knockout Plate. 36 Louver Plate. 37 Contactor 2 Pole. 38 Contactor 3 Pole. 39 Contactor 4 Pole. 40 Screw. 41 Terminal Block “A”. 42 Terminal Block End “A”. 43 Terminal Block 2 Pole. 44 Terminal Block 3 Pole. 45 Screw. 46 Fuse Block 2 Pole Class G. 47 Fuse Block 3 Pole Class G. 48 Fuse Block 2 Pole Class T. 49 Fuse Block 3 Pole Class T. 51 Terminal Strip 2 post. 52 Fuse Class G. 53 Fuse Class T. 54 Ground Lug Large. 55 Ground Lug Small. 56 Screw. 57 Control Circuit Transformer. 58 Control Circuit Transformer (600 Volt). 59 Time Delay Sequencer.
Page 26
Glossary of Terms
Term Definition Unit of measure Voltage - Electrical potential Volts Current- Rate of voltage flow Amperes (amp) Resistance- Ability of a device to dissipate Ohms
power irreversibly Energy- Ability to do work kW/hr, Joule Power- Energy per unit of time Watts, kW, VA
One kilowatt (1kW) = 1,000 Watts. = 3,412 BTU BTUH = British thermal units per hour DC = Direct Current PSI = Pounds per square inch AC = Alternating Current GPM = Gallons per minute Hz = Hertz GPH = Gallons per hour
ECO = Energy cut off °F = Degrees Fahrenheit NPT = National pipe thread °C = Degree Centigrade ASME = American Society of Mechanical Engineers
26
NOTES
Page 34
27
Email
parts@bradfordwhite.com
techserv@bradfordwhite.com
www.bradfordwhite.com
Loading...