BPC DUPLEX 250 Easy, DUPLEX 400 Easy, DUPLEX 300 Easy Use, Maintenance And Installation Manual

DUPLEX 250, 300, 400 Easy
Version: 08
EN
Issue: 22. 04. 2014
Code: R_19_01_V08_EN_2014_04
Use, maintenance and installation manual
1. C o n t e n t
1. Content ................................................................................................................................................................2
2. Operating the equipment – CPA controller ..........................................................................................................3
2.1. Performance settings .............................................................................................................................3
2.2. Unit’s operating modes ..........................................................................................................................4
2.3. Description of controls ............................................................................................................................4
2.3.1 Basic menu ............................................................................................................................................4
2.3.2 “MODE“ menu (operating mode) ...........................................................................................................5
2.3.3 Menu „PROGRAM“ (weekly program) ...................................................................................................5
2.3.4 “PARTY“ and “HOLIDAY” menu (temporary operating modes) ..............................................................6
2.3.5 “REHEAT” menu (air reheat) ..................................................................................................................6
2.4. User system settings ..............................................................................................................................6
2.4.1 “FILTER“ menu .......................................................................................................................................6
2.4.2 “TIME” menu ..........................................................................................................................................7
2.4.3 “INPUT” menu ........................................................................................................................................7
2.4.4 “SWITCH” menu (binary input DI1) ........................................................................................................7
2.4.5 “SENSOR“ menu (analogue input IN1) .................................................................................................7
2.4.6 “LIMIT” menu..........................................................................................................................................8
2.4.7 “TEMPERATURE” menu ........................................................................................................................8
2.4.8 “DISPLAY” menu ....................................................................................................................................8
2.4.9 “LANGUAGE" menu ...............................................................................................................................8
2.4.10 Automatic ventilation modes ..................................................................................................................8
2.4.11 Constant pressure in a supply line .........................................................................................................9
2.4.12 Warning messages ................................................................................................................................9
2.4.13 Supply air reheat mode ..........................................................................................................................9
2.5. Operating the equipment – the CPB controller ......................................................................................9
2.6. Performance settings ...........................................................................................................................10
2.7. Description of controls ..........................................................................................................................10
2.8. Limiting ventilation capacity ..................................................................................................................10
3. Equipment maintenance by the user ................................................................................................................10
3.1. Basic instructions, filter replacement, maintenance and cleaning .......................................................10
3.2. G4 / F7 filter cloth replacement ............................................................................................................10
3.3. Cleaning the plastic heat recovery exchanger ..................................................................................... 11
3.4. Cleaning the CPA controller .................................................................................................................12
3.5. Other miscellaneous maintenance .......................................................................................................12
4. Faults, errors and troubleshooting ....................................................................................................................13
4.1. Description of fault messages and their causes ..................................................................................13
5. Equipment installation and commissioning .......................................................................................................14
6. Equipment installation and commissioning .......................................................................................................14
6.1. Package content ..................................................................................................................................14
6.2. Key dimensions of the equipment ........................................................................................................14
6.3. Overview of installation positions and versions ....................................................................................15
6.4. Mounting the unit, fixing points .............................................................................................................16
6.5. Fitting the unit, sloping, distances ........................................................................................................17
6.6. Fitting the condensate drain .................................................................................................................17
6.7. Connecting the condensate drain – under-ceiling installation ..............................................................17
6.8. Connecting the condensate drain – floor-standing and floor-standing flat installation .........................18
6.9. Condensate drain arrangement ...........................................................................................................19
6.10. Installation of additional SK cover ........................................................................................................20
6.11. Filter types ............................................................................................................................................20
6.12. Installing optional accessories .............................................................................................................20
7. Installing controllers, changing positions, electrical connections ......................................................................21
7.1. Installing the controller .........................................................................................................................21
7.2. Permanent disballancing of supply and exhaust fans ..........................................................................21
7.3. Changing the orientation of DUPLEX Easy units .................................................................................21
7.4. Wiring diagram .....................................................................................................................................23
7.5. Equipment’s manufacturing label .........................................................................................................24
8. Important notices ..............................................................................................................................................24
2. O p e r a t i n g t h e e q u i p m e n t – C PA c o n t r o l l e r
Display:
1. Time
2. Alerts (e.g. the need for filter replacement)
3. Date
4. Current room temperature
5. Air reheating indication (if the system includes a reheater)
6. Ventilation capacity setting in %
7. Selected operating mode
DUPLEX
EASY
Off 0 10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
250
OFF
Unit responds to
sensors and external
inputs
20
35
95
120
155
180
200
220
240
250
300
OFF
Unit responds to
sensors and external
inputs
20
40
110
160
200
230
250
275
305
315
400
OFF
Unit responds to
sensors and external
inputs
30
50
140
200
260
300
320
350
380
400
The equipment operated using a CPA controller with touch-screen display.
Description of functions:
Controls are divided into user and servicing sections (accessible by service technicians only). Ventilation capacity can be set in a range of 0-100 %. Options to switch on the air reheater, air preheater and shut-off damper servo drive. Control in manual mode or via separate weekly programs for ventilation capacity and air reheating. Additional operating mode “Party” (a temporary increase in capacity) and “Holiday” (temporary ventilation switch-off). An option to control ventilation automatically by external sensors (air quality, CO2, relative humidity etc.).  An option to start increased ventilation using external switches, e.g. in the bathroom or toilet. An option to limit maximum and minimum ventilation capacity. Displays the current room temperature and operating mode. Alerts to the need for air filter replacement.
Description of controls:
Short press – general controls and parameter settings Long press (3 s) of the ventilation capacity symbol – quick operation on / off Long press (5 s) at the top of the display – entering the service menu
2.1. Performance settings
When a CPA controller is used for controlling and programming, the capacity is shown (displayed) in per cents of the maximum. The table shows approximate air flow rates (m3/h); they may vary depending on the duct network.
Displayed
mode
Description
Suitable application
(data may vary depending on national regulaitons)
“Manual mode“ – a general ventilation mode, with ventilation provided by the unit according to current settings.
Continuous ventilation during occupancy, with the capacity set at outside temperatures as follows:
Above approx. -5°C to approx. 25 m3/h/person, i.e. for
4 persons 100 m3/h, with 70 m3/h set at night.
Below approx. -5°C to approx. 20 m3/h/person, i.e. for
4 persons 80 m3/h, with 50 m3/h set at night.
“Weekly program“ – a general ventilation mode, with a required rate of ventilation provided by the unit according to schedule parameters.
“Automatic mode“ – the capacity of ventilation is set by an active external input, i.e. the user's request from the bathroom / toilet / kitchen or according to an air quality, CO2, humidity etc., if installed.
The unit switches over to these modes automatically if current ventilation demand exceeds the capacity set in manual mode or a weekly program.
“Ventilation run-down time“ – a temporary ventilation mode which stops automatically after the pre-set time has elapsed.
The unit switches over to this mode automatically after a request from the bathroom / toilet / kitchen has expired (if a run-down time is set).
The “Party“ mode is temporary and stops according to the pre-set time.
A temporary mode for less frequent use of the building, such as a party attended by a large number of people (a request for higher ventilation capacity).
The “Holiday“ mode is temporary and stops according to the pre-set date and time; after that a weekly program is activated automatically.
A temporary mode for less frequent use of the building, such as a holiday (a unit deactivation request).
2.2. Unit’s operating modes
The HVAC unit works according to settings made by the controller, external inputs from the bathroom, toilet or kitchen and air quality sensors in following modes:
2.3. Description of controls
The operating modes of the unit can be changed by selecting functions and parameters in respective menus using the touch -screen display.
The requested option (changing the function or parameter) in each menu must be confirmed by pressing the "OK" symbol or a symbol of "arrows" to move to the next menu. If you press the symbol "Esc" option is ignored and the system automatically returns to basic (Information) menu.
Note in idle (display) state is the touch screen CPA glazed over, at the first touch automatically activates the backlight display, next touch can change particular functions (see description below).
2.3.1 Basic menu
Operating mode selection Ventilation capacity selection or operation start / end Switching on air reheating (if a reheater is installed in the system)
If operation is ended by setting ventilation capacity to “OFF”, the unit does not respond to an external request, i.e. switches in the bathroom / toilet / kitchen and the air quality sensor are ignored).
If power is set to "0 %", then the fans are stopped and the unit is not ventilating. In contrast to the "OFF" state, in this "0 %" mode is still active automatic start according to external switches.
Note – if none of buttons in submenus is pushed for a long period of time, then the CPA driver automatically switches to the main menu
2.3.2 “MODE“ menu (operating mode)
Selecting a weekly program / manual mode / Party mode / Holiday mode
If more than one parameter is shown in the menu, you can switch between these by a short press; a parameter can be set by pressing “+” and “- “ repeatedly (setting can be faster if you press and hold the symbol).
2.3.3 Menu „PROGRAM“ (weekly program)
Setting a weekly program (time schedule) for ventilation capacity Setting a weekly program for starting air reheat
Changes made in a weekly program for a selected period of Mon-Sun / Mon-Fri / Sat-Sun are effected in all selected days together, while changes made for a period of Mon / Tue / Wed / Thu / Fri / Sat / Sun are effected only for the specific selected day.
Warning:
If one or more days of the week have been set individually, parameters for these individual days will be rewritten according to the new settings when a period of Mon-Sun / Mon-Fri / Sat-Sun is subsequently selected in adjustment mode (the pencil symbol).
2.3.4 “PARTY“ and“HOLIDAY” menu (temporary operating modes)
Setting the required ventilation capacity of the “Party” mode in a range of 20 – 100 % Setting the duration of the “Party” mode in a range between 10 minutes and 5 hours Setting the time and date of ending the “Holiday” mode
After the “Party” mode has finished, the unit automatically returns to the operating mode selected before that; when the “Holiday” mode has finished, the unit automatically switches over to operating mode which is current according to a weekly program.
Note – The “Party” and “Holiday” modes can be stopped early by selecting another operating mode.
2.3.5 “REHEAT” menu (air reheat)
Starting air reheat in manual mode
This menu is accessible only provided that an electric or hot-water air reheater is installed (selection in the service menu).
Information on air reheater operation is indicated in the basic menu by symbols and .
Note – Air reheating with an electric heater is only possible with a minimum ventilation capacity of 30 % due to a sufficient air flow rate for cooling the heating elements.
2.4. User system settings
Using directional arrows you can move between individual user menus:
MODE / VENTILATION / REHEAT / FILTER / TIME / SETTINGS
By pressing “OK” in the “SETTINGS” menu other parameter menus become accessible:
INPUT / SWITCH / SENSOR / SENSOR / LIMIT / TEMPERATURE / DISPLAY / FIRMWARE / LANGUAGE / LANGUAGE / LANGUAGE
WARNING – The wrong parameter settings can have a negative influence on the proper operation of the equipment!
2.4.1 “FILTER“ menu
Indication of the number of days left until the air filter must be replaced Setting the regular filter replacement interval in a range of 3 0 – 150 days (by 10 day periods) Filter replacement confirmation (a new countdown automatically starts after confirmation)
The regular filter replacement interval should be set according to the dust and pollen load of the outdoor environment.
2.4.2 “TIME” menu
Date and time setting Selecting between 12 and 24 hour time format
Note – Automatic switching between summer and winter times (DST) is not supported.
2.4.3 “INPUT” menu
An option to allow / disallow the increased ventilation capacity function.
- Binary input DI1 for connecting external voltage-free switches in bathrooms, toilets or kitchens.
An option to allow / disallow the function of automatic ventilation control according to the concentration of the quantity being
measured.
- Analogue input IN1 for connecting an external sensor (sensor “S“) with a 0-10V signal output which can monitor air quality, CO
concentration, relative humidity etc.
2
2.4.4 “SWITCH” menu (binary input DI1)
Setting ventilation capacity in a range of 10 – 100 % with input DI1 closed Setting a function’s start delay time in a range of 0 – 300 s (in 10 second steps) Setting a function’s run-down time in a range of 0 – 300 s (in 10 second steps)
If a button is used the start delay time must be set to “0 s” in order for the short press of t he button to be accepted, and the run-down time must be set to a non-zero value.
2.4.5 “SENSOR“ menu (analogue input IN1)
Setting the ventilation curve in relation to the level of the 0-10V signal from an external sensor This function allows suitably adjusting the unit’s response (ventilation capacity) to a gradual increase in the concentration of the
quantity being measured, e.g. for economical or noise reasons.
The “inverse” setting of ventilation capacity response to the 0-10V control signal is also supported, i.e. the reverse direction of curve A-B).
This function allows connecting also a sensor with a different output voltage range, e.g. 0-5V or 2-10V.
2.4.6 “LIMIT” menu
Setting maximum and minimum permitted ventilation capacity limits An option to allow / disallow the operation OFF function (ventilation capacity = OFF)
Attention – Settings in the “LIMIT” menu subsequently affect (limit) all operating modes and parameter settings in other user menus.
If the “Min:“ parameter is set to a non-zero value, the unit can be switched off only by a long press (3 s) of the ventilation symbol in the basic menu or manually selecting ventilation capacity OFF (if permitted).
2.4.7 “TEMPERATURE” menu
Setting the calibration of the internal air temperature in a range of +/- 3°C (in 0.5 °C steps)
2.4.8 “DISPLAY” menu
Setting the display brightness and contrast (recommended values are 70 % and 50 %)
2.4.9 “LANGUAGE" menu
Setting the menu language
Note – If the controller has been disconnected from power supply for more than 48 hours, the language is automatically set to English when switched on again.
2.4.10 Automatic ventilation modes
If there is a discrepancy between the operating mode displayed and the one set manually by the user or a weekly program, then the current operation of the equipment (ventilation capacity) is affected by external request via a contact or analogue input (sensor).
- A request from a switch in A request from an air quality the bathroom / toilet / kitchen / CO2 / relative humidity sensor
2.4.11 Constant pressure in a supply line
If the unit is operated under constant pressure in the supply line (set in the service menu), then in the "FANS" and "PROGRAM" options are available: OFF / 0% / /
The symbols "sun" and "moon" are the two possible levels of pressure required, is standard operating (daily) pressure value, symbolizes the lower pressure value specified for night setback (e.g. due to noise).
This special mode in cooperation with the duct pressure sensor is able to provide automatic control of ventilation capacity by varying the number of ventilated rooms in the building (e.g. central ventilation of residential house)
Note If a problem occurs during operation, the measurement of pressure in the supply line (e.g. due to pressure sensor failure), it is possible to cancel CS("constant sensor") in the user menu "Inputs" and to deactivate ventilation on constant pressure.
Now you can control the fans performance standard way in manual mode or by setting a weekly program (see description in chapter
2.3.1 and 2.3.2).
2.4.12 Warning messages
The controller may display some warning messages during operation which alert to the need for replacing an air filter or flat battery; if the equipment has a defect, a warning message is shown recommending contacting the service department.
Replacing the controller's battery:
Before replacing the battery disconnect the equipment from power supply! Then use a tool such as a flat screwdriver to apply pressure onto "lock" on the bottom of the controller and remove the front panel
with display. Now it is possible to replace the CR1632 battery and put the two parts of the controller back together. After turning it on it is necessary to set the correct time and date.
2.4.13 Supply air reheat mode
Only external EPO-PTC series duct electric air heaters, fitted with their own thermostat to set air temperature downstream the heater, can be connected to the equipment.
Up to two such heaters may be connected simultaneously can be connected in the following configuration: As a fresh air pre-heater (before the unit's inlet)
- The heater works fully automatically without being switching by the user, solely based on the temperature setting; this funct ion
(air preheating) only works when the unit is running.
As a reheater of air supplied into the building (it is located at the unit's outlet, downstream heat recovery)
- The heater is started by the user with the controller in manual mode or according to weekly program settings. The reheating
function is only active when the unit is running.
Heaters must be fitted and connected according to the wiring diagram and only by a person with a relevant licence.
Before the heater is put into operation, the temperature required downstream the heater must be set on the thermostat:
For a pre-heater: from 0 °C to +4 °C For a reheater: between 10 and 35 °C
2.5. Operating the equipment – the CPB controller
As standard, the equipment is operated using a simple CPB controller.
Description of functions:
Ventilation capacity setting in a range of 0-100 %. An option to start the air reheater. An option to start the shut-off damper servo drive. An automatic ventilation control option according to an external sensor (air quality, CO2, relative humidity etc.).
An option to increase ventilation capacity using external switches, e.g. in the bathroom or toilet.
Description of controls:
1. Ventilation capacity setting
2. Operation indication
3. Starting air reheating (if a reheater is installed)
An option to limit maximum and minimum ventilation capacity. Equipment operation indication.
2.6. Performance settings
Identical to those the table in chapter 2.1. The HVAC unit operates according to settings by the controller, the closing of e xternal inputs from the bathroom, toilet or kitchen, or an air quality sensor.
2.7. Description of controls
Selecting ventilation capacity or starting / stopping operation
- Rotate the controller to set the required ventilation capacity in a range of 10–100 %.
- Ventilation is stopped by turning the controller anti-clockwise until it reaches the symbol "0" at the end position; however the
equipment still responds to external commands – see the chapter 3.3.
Starting air reheat
- The setting applies only provided that an external air heater with its own thermostat is fitted.
- Start air reheat by pressing the button in the right hand bottom corner of the controller next to the thermometer symbol (stop by
pressing again)
Note:
- Air is reheated only when the unit is running.
- The thermostat temperature is set by the technician in charge of installing the equipment in a range between 15 and 35 °C
2.8. Limiting ventilation capacity
Removing the rotary controller provides access to other control features, the turning of which sets the minimum and maximum ventilation capacity levels (a full range of 0-100 % is set by the manufacturer).
Description:
1. Setting of min. ventilation capacity
2. Setting of max. ventilation capacity
3. E q u i p m e n t m a i n t e n a n c e b y t h e u s e r
3.1. Basic instructions, filter replacement, maintenance and cleaning
Maintenance involves visually checking the equipment, regularly replacing filters and cleaning the heat recovery exchanger. During maintenance observe the rules of personal hygiene and use protective equipment (a face mask, packaging for
contaminated filters).
Before starting maintenance of the unit, always disconnect the equipment from power supply by unplugging the plug
from the power socket.
During maintenance observe safety instructions contained in the manual (“Important notice”), follow the fundamental rules of
safe work and use suitable means of accessing HVAC equipment (ladders, stepladders).
3.2. G4 / F7 filter cloth replacement
You should replace the filter cloth only provided that you do not suffer from allergic reactions to dust particles. Do not co nduct
replacement when people with such a level of sensitivity are present.
Replace the filter cloth from the filter frame in a well-ventilated area or out of doors. Before removing the frame with cloth, we recommend that you should have an air-tight bag (a plastic carrier bag etc.) ready to
carry the frame to a suitable area to conduct replacement and subsequently use it to dispose of the contaminated cloth, e.g. with common waste.
Replacement is carried out depending on the dust load of the ambient environment between every 500 and 2,000 operation
hours (usually approx. 2 - 3 months). The recommended inspection interval is indicated on the controller's display.
10
When replacing filters, do not remove the unit’s door – use the special cover for filter replacing.
Release the filter plugs in the
housing unit using the product in
the package – pull straight on
Do not pull on a slant!
Remove the cover on the
unit’s enclosure
-start from the bigger recess
Take out the frame with filter cloth
Slide a new filter cloth onto the frame
- the fibre is to be slid onto the
Properly fitted cloth – the blue /
red side faces the unit’s ports
and the white one the heat
recovery exchanger
Fitting filter covers
-proceed from one side to another
Press the cover into the unit’s enclosure so
that it is flush with the lid’s edge along the
entire perimeter
Sliding the filter frame out of the unit and replacing the cloth
3.3. Cleaning the plastic heat recovery exchanger
The recommended interval of heat recovery exchanger cleaning is about 2 years, depending on the nature of the operating
environment.
If necessary, wash the heat recovery exchanger block with warm water with a detergent several times; the water temperature
should be up to 60 °C, ideally such that you could keep your hands in it comfortably (e.g. BODE Kohrsolin FF ).
Do not expose the heat recovery exchanger to ultraviolet light and sunlight, store it in a dark place if necessary.
ATTENTION: Never use cleaning agents that might contain organic solvent to clean the heat recovery exchanger as they could cause its irreversible damage!
11
.
T2
T1
4 x
Remove the cover and unscrew the locking screws from the unit's lid – 4 in the corners
Open the unit’s door carefully and gradually from one side. Start from the wiring entry side, in ceiling units disconnect the condensate drain.
Unlock the butterfly nut on one side of the exchanger
Slide out the heat recovery exchanger block
Side A
Removing the heat recovery exchanger
Disconnect the unit from power supply, disconnect the condensate drain in ceiling units, open the unit and unlock the heat re covery exchanger on both sides.
Note down the position of the heat exchanger (the number depends on the equipment type) for seal fitting. The sticker with le tter A must be by the edge of the fan enclosure.
Follow the procedure in reverse to slide the heat recovery exchanger back in. Before sliding exchangers in, we recommend lubricating only the seal with silicon oil for easy sliding and increasing the flexibility and life span of the seal.
3.4. Cleaning the CPA controller
The CPA controller requires the same maintenance as the lighting switch – cleaning is only possible using a dry cloth, no water may enter the inside of the controller. Liquids which might damage its surface must not be used for its cleaning (e.g. organic
solvents).
3.5. Other miscellaneous maintenance
Before any intervention with the unit it must be disconnected from power supply!
During filter cloth or cassette replacement and every time you are opening the unit check the following:
The condensate drain in the unit's door or bottom for cleanliness. Any blockage of the condensate drain might cause serious trouble. The water level in the condensate drain, especially in summer and autumn. If the level is not high enough, air from the sewer
might be drawn in; flood the condensate drain.
If any parts of the equipment are covered in dust, clean them with a slightly damp cloth.
12
Fault
Description
Possible cause
Troubleshooting
The equipment cannot be started
The equipment
remains idle even after the required performance level was selected
Power supply is not connected
Connect the equipment to power
supply (switch on upstream safety circuit breakers)
Not found
Disconnect from power
supply and contact a service technician
The equipment is not supplying enough air
The equipment is
providing a significantly lower volume of air
Blocked filter
Disconnect the equipment
from power supply
Replace the filter cloth or
cassette
If the equipment has been in
operation for more than approx. 4 years, clean the heat recovery exchanger/s
A mechanical obstacle at fresh
air suction or supply air outlets
Check whether the suction
openings of fresh air or supply air outlets are not mechanically covered
Remove any obstacles Visually and by listening check
whether the dampers open properly
Not found
Disconnect from power
supply and contact a service technician
The equipment is not heating or is heating insufficiently
When the heater
has been started, supply air continues to be cold
The electric heater is not
connected to power supply
Connect the equipment to power
supply (switch on upstream safety circuit breakers) – can only be done by an authorized person
Response of the electric
heater’s heat protection
Wait to see if the fault does not
sort itself out after approx. 1 hour
Low maximum capacity of the
heater
Does not constitute a fault
(insufficient capacity designed)
Not found
Disconnect from power
supply and contact a service technician
Water is dripping from the equipment
Water droplets
form between the door and body of the equipment during operation
The condensate drain siphon is
insufficiently flooded
Disconnect the equipment
from power supply and flood
the condensate drain siphon
The condensate drain is blocked
with dirt
Disconnect the equipment
from power supply and clean
the condensate drain including the siphon
The seal groove is damaged
(the fault can be accompanied by a whistling sound caused by air flowing through the gap)
Disconnect the equipment
from power supply and replace
the seal
Water droplets
form at the condensate drain connection point
The condensate drain seal or
line is damaged
Disconnect the equipment
from power supply and re-seal
the condensate drain
Not found
Disconnect from power
supply and contact a service technician
4. F a u l t s , e r r o r s a n d t r o u b l e s h o o t i n g
4.1. Description of fault messages and their causes
13
5. E q u i p m e n t i n s t a l l a t i o n a n d c o m m i s s i o n i n g
During transport and storage the prescribed position indicated by the sticker on the box must be observed!
The equipment may only be stored in dry, clean places with ambient temperatures between 0 °C and 50° C. Up to 7 units
may be stored horizontally. The equipment must be placed on a flat, hard surface to avoid damaging it or its pa ckaging.
During storage the equipment must be kept in its original, intact packaging including all spacing, tightening and
indicating elements.
The transport packaging may not be removed until the unit has been delivered at the site of final installation. All parts
which are to come into contact with flowing air must be checked for cleanliness and cleaned if necessary before installation.
If the equipment is to be handled using a forklift or palette truck, it must be placed on a transport EUR pallet. During transport the equipment must be protected against any falls, mechanical d amage, water leaks and any other
adverse effects that could damage the equipment or its packaging.
DUPLEX 250
Easy
DUPLEX 300
Easy
DUPLEX
400 Easy
Dimensions
W
mm
850
850
850
H
mm
660
820
820
D
mm
280
280
280
Ports
e1
mm
160
160
160
e2
mm
160
160
160
i1
mm
160
160
160
i2
mm
160
160
160
Weight
kg
20
21
21
Condensate drains
mm
2 x ø 14 (prepared for 3 more)
Fixing
mm
4 x Ø8
4 x Ø8
4 x Ø8
6. E q u i p m e n t i n s t a l l a t i o n a n d c o m m i s s i o n i n g
6.1. Package content
The basic package of DUPLEX Easy units contains the following accessories:
The operation, maintenance and installation manual An abridged control manual A CPA controller connected, with a 230 V power supply plug (with a connecting cable length of 3 lm). Plastic components for connecting the condensate drain line An extra condensate drain installation kit for floor-standing and floor-standing flat positions (a bushing, seals, nuts) A mounting kit for fixing the unit (a high nut, 2 washers, a hexagonal screw, a plastic cover)
6.2. Key dimensions of the equipment
14
6.3. Overview of installation positions and versions
Installati
on
position
View
Configuration of ports and condensate drain positions
Under-
ceiling
PODSTROPNÍ
PODLAHOVÁ
PARAPETNÍ
K
K
K
K K
K
K
K
K K
Floor-
standing
PODSTROPNÍ
PODLAHOVÁ
PARAPETNÍ
K
K
K
K K
K
K
K
K K
Floor-
standing
flat
PODSTROPNÍ
PODLAHOVÁ
PARAPETNÍ
K
K
K
K
K
DUPLEX 250, 300, 400 Easy units can only be installed in the positions indicated. Installation in a different position is not permitted. A positional configuration change can only be done as indicated in par. 7.
LEGEND:
e1 – Fresh air supply from the outside e2 – Supply of air after heat recovery to the interior i1 – Exhaust air extraction from the interior i2 – Exhaust air discharge into the atmosphere K – Condensate drain
15
Open the unit’s door carefully and gradually from one side. Start from the wiring entry side.
Remove the fan-protecting scrolls.
Anchoring points
DUPLEX 250 Easy
DUPLEX 300 Easy, DUPLEX 400 Easy
618
4xO9
280
805
4xO9
805
775
280
618
4xO9
280
805
Anchoring detailed view
3
2 1
4 5 6
7
délka závitové tyče 230 + délka kotvení
6.4. Mounting the unit, fixing points
Before installing the unit remove the safety elements inside it!
The unit is fixed to the building structure by the elements supplied and a threaded rod and an anchor. The threaded rod and the is not included.
16
Recommended distances
min. 250
min. 75
min. 350min. 350
A condensate drain outlet from the door in
section i2, with condensate drain accessories
Connecting the condensate
drain with a 90°elbow and
connecting the line
Inserting the line and securing it with a
clip (the clip and the line is provided by
the plumbing installation company)
Connecting a straight condensate drain with
a sleeve to connect the line
Inserting the line and securing it
with a clip (the clip and the line
is provided by the plumbing
installation company)
6.5. Fitting the unit, sloping, distances
If the unit is installed to ventilate a general use indoor environment, its interior design (only for floor-standing and under-ceiling installation) ensures the transport of condensate to the required point without the need for additionally sloping the unit. For floor­standing flat position it is necessary to keep the unit slope towards the condensate outlet.
If the unit is used to ventilate areas with long-term high humidity loads of over 60 %, we recommend additionally sloping the unit with a gradient of 2 % so that the lowest point is always at the condensate outlet.
To achieve acceptable acoustic values it is necessary to install air distribution with guaranteed acoustic attenuation. The minimum distance of the nearest outlet from the ventilation unit in the supply line (behind supply fan) is 2-3 m. The line
before the first diffuser must be done with noise attenuation - fixed or flexible distribution silencer with sound dampening insulation.
6.6. Fitting the condensate drain
The unit must have a condensate drain fitted in exhaust air outlet section i2 – see paragraph 6.3.
Condensate drains not in use must remain sealed. The condensate drain line must be connected so that it does not get damaged during handling the unit. In under-ceiling
installation the condensate drain must be disconnected before opening the door of the unit. For the position condensate drain in various configurations of ports see paragraph 6.3. – must be observed.
6.7. Connecting the condensate drain – under-ceiling installation
17
6.8. Connecting the condensate drain – floor-standing and floor-standing flat installation
The point designed to fit the condensate drain with accessories
Push out the middle part of the hole using just your finger – the hole below the outlines of the smaller hole
Remove the plug
Insert the bushing, with the flange on the inside of the unit
Put on a washer from the other side and tighten with a nut – tightening to be done only by hand
A condensate drain from the bottom of
the unit – use the shorter tube first
Direct / elbow condensate drain connection
for inserting the line
Insert the line and secure it with
a clip (the clip is provided by the
plumbing installation company)
When the unit is to be installed in a floor-standing or floor-standing flat position, a condensate drain must be first prepared using the bushing provided and silicon. All this must be done before putting the unit into operation; the equipment must be disconnected from power supply.
To install the condensate drain use only the points provided on the units in the form of visible recesses. Holes for the fitting kit are provided and needn’t be cut out - just push out the plug being pushed out.
Fitting the bushing into the unit’s enclosure
Fitting
Fitting the line on the sleeve
18
6.9. Condensate drain arrangement
Siphon arrangement on a flexible hose
Detailed view of securing the siphon with a plastic clip
DUPLEX EASY – under-
ceiling
DUPLEX EASY – floor-
standing
DUPLEX EASY – floor-
standing flat
The condensate drain must be fitted with a siphon and connected to the sewer system. The siphon must be permanently flooded. After the unit has been out of operation, it is necessary to check the siphon for flooding and free passage before re-commissioning the unit.
19
DUPLEX 250 Easy
DUPLEX 300/400 Easy
Bottom section instal before mounting the unit According to filter covers place an upper and lower part Push toward each other (the cover and the unit) Tighten four screws for attaching the lid and upper part
of the unit SK cover
Spare filter cloths –
packaging, optional
accessory
Filter frame with filter cloth
6.10. Installation of additional SK cover
Cover SK (Silent kit) is used for a further reduction of sound pressure to the area by about 6 db. This is a separate part that is not included HVAC unit itself.
Material: painted galvanized 0.75 mm plate in silver color RAL 9006, kit is supplied with bolts for attaching the cover to the body of the unit.
The cover consists of two pieces top and bottom. Attached to the unit via a secured lid using anchor bolts.
Dimensions:
Installation:
6.11. Filter types
The basic version of the equipment is supplied with a Class G4 filter cloth in a stainless frame, with a Class F7 cloth available as an optional extra.
6.12. Installing optional accessories
The following external pre-heaters or reheaters can be connected to the unit:
An EPO-PTC external air pre-heater on the supply fresh air route to the unit. An EPO-PTC external air reheater on the exhaust air route to the building.
A manual for fitting, connecting and wiring these external appliances is supplied along with them. For necessary settings see paragraph 2.3.
Other than the above types of electric heaters are not permitted for use with DUPLEX EASY units!!!
20
7. I n s t a l l i n g c o n t r o l l e r s , c h a n g i n g p o s i t i o n s , e l e c t r i c a l
CPA
Installation on the wall
7.2. Permanent disballancing of supply and exhaust fans
The unit it must be disconnected from power supply before any intervention with!
Use the MX terminal block mounted on terminals inside the unit (under the hood, blue accessory on terminals Me and Mi) to disballance performance of Mi exhaust and Me supply fans.
The disballance can be a maximum of 30 %. Turn adjustment screw is reduced performance of the fan – extreme position = 30% reduction from the original nominal power.
Disconnect the device from the power supply! Remove the lid of the device Remove the junction box cover Rotate to enable the appropriate adjusting screw
for fan or Mi or Me
Position of sensors T1 a T2 – default factory position
New positions of sensors T1 a T2 after changing
c o n n e c t i o n s
7.1. Installing the controller
A CPA touch-screen controlled providing full control and programming is connected as standard. It is supplied for installation on the wall and can be fitted into a recessed installation box.
The controller should be mounted on the wall at a height of 1.3 – 1.5 metres at an easily accessible, well-lit and dry place, not close to heaters and heat radiating surfaces.
Included is a low-current shielded connecting cable (SYKFY 5x2x0,5) 3 metres long. When the controller is required to be further away from the ventilation unit, the cable must be replaced / extended (up to 25 metres).The controller must be installed by a specialized installation company’s technician.
Warning: Before installing or removing the controller disconnect the unit from power supply. Handling the controller with power left on might lead to electrocuting or damage the controller.
7.3. Changing the orientation of DUPLEX Easy units
The unit it must be disconnected from power supply before any intervention with!
The unit’s orientation is changed simply by changing the production default position of the two temperature sensors and re­connecting the cables.
T1 – Fresh air intake sensor ( at the filter – red terminals) T 2 – Exhaust air discharge sensor ( at the M2 fan – blue terminals)
21
Unscrew the screw from the control module cover Remove the cover from the control module
Change the position of cables M1 and M2. Factory connections: M1 terminal Me, M2 terminal Mi
Connections after orientation change: M1 terminal Mi, M2 terminal Me
Slide out the air filters Unscrew sensor T1 from its original position Pull it out of the terminals (red)
Put the sensor in its new position
Screw it into the guide
Insert it into the terminals (either polarity)
Unscrew sensor T2 from its original position Pull it out of the terminals (blue) Unscrew the screw from the fan
Put the sensor in its new position
Screw sensor T2 on
Insert it into the terminals (either polarity)
Screw the screw into fan M2
M1
M2
M2
M2
M1
M1
22
23
7.4. Wiring diagram
7.5. Equipment’s manufacturing label
(1)
Model, nominal capacity
(2)
Manufacturing number
(3)
Year of production
(4)
Weight
(5)
Nominal capacity of fans
(6)
Fan type
(7)
Fan power supply
(8)
Filter class
(9)
Filter cloth dimensions
(10)
Heat recovery exchanger type
(11)
Control system type
The manufacturer is not liable for damage caused by improper installation which fails to observe the
installation manual and common practice in installing HVAC units and control systems.
8. I m p o r t a n t n o t i c e s
DUPLEX series heat recovery units are designed for comfort ventilation in areas with normal environmental conditions and
relative humidity up to 60 %. If the equipment were to be used for other purposes such as to dry out new buildings or not to be run properly in compliance with instructions contained in the operation and maintenance manual, the manufacturer would not be liable for any resulting damage.
Only adult persons who have read and are sufficiently familiar with the operation, use and maintenance manual may operate the
equipment.
The user is not allowed to tamper with or modify any part of the equipment, particularly its electrical wiring!! Only professional service technicians with relevant qualifications may perform equipment repairs. Unprofessional repairs are
very risky and may result in a loss of warranty.
Before opening the door of the equipment for cleaning, filter cloth replacement or general maintenance, make sure that it is
disconnected from power supply and prevent its reconnection by another person.
To prevent injury caused by a fan impeller, ductwork of at least 2 metres in length must always be connected on the fan
discharge side. The ductwork must be fastened to the equipment in such a way that it cannot be removed without tools.
The equipment can only be installed in areas with temperatures up to 10 °C and relative humidity 60 % at 20 °C. If the equipment has been out of operation for a long period, extra care must be taken during its re -commissioning. The equipment designed for normal environmental conditions may be operated within the temperature range of ventilation air
between -25 °C and +45 °C and relative air humidity up to 70 %, in an environment where there is no risk of fire or explosion of flammable gases and fumes, not containing organic solvents or aggressive substances that might damage the mechanical parts of the equipment. If there is a danger of such gases and fumes temporarily entering the duct system (e.g. floor bonding, painting), the equipment must be switched off sufficiently beforehand.
Only persons with relevant electrical engineering qualifications may make electrical connections, commissioning and setting o f
the equipment.
The units must be protected with a 1 x 10A char. C circuit breaker. If additional protection against a dangerous touch of live and neutral parts using a current protector is used, a special current
protector designed for circuits with frequency convertors and switched-mode power supplies is necessary. It is a protector sensitive to alternate, pulse and residual currents and resistant to current surges 5kA.
Before installing and commissioning the equipment, thoroughly read the installation, use and maintenance manual! The equipment and all accessories must be installed and used in compliance with the design, the technical conditions of the
manufacturer and applicable legislative regulations and technical standards.
The equipment must not be installed and operated in an aggressive environment which could damage its external and internal
components.
Before putting the equipment into permanent operation, an initial inspection report for the equipment’s power supply must be
provided.
In the event of a defect the equipment must be immediately disconnected from power supply! During the installation and handling of the equipment observe all rules of safe work, including safe work in heights and work with
suspended loads, and use suitable protective equipment.
During installation make sure the equipment’s enclosure does not get damaged or deformed.
24