Bourns 1251-120S-N2, 1252, 1251-240S-N2, 1251-240S-N1, 1251-208Y-N2 Installation Instructions Manual

...
1251 & 1252 Series
Hardwired AC Hybrid H-SPD
INSTALLATION INSTRUCTIONS
ATTENTION!
• Applicable electrical installation rules must be followed.
• The unit must be used only as a surge protector and according to the conditions described in this document.
Technical Data
Specication
Single Phase
Split Phase
Wye
Type 1 2 Max. Discharge
Current by Mode (Imax)
Nom. Discharge Current by Mode (In)
MCOV L-N (Vac)
MCOV L-L (Vac)
NOTES: Model 1252 Series contains a lter. N1: For the side nipple. N2: For the nipple in the back.
1251­120S-
N1
N/A 280 280 N/A 280 280 N/A 280 280 N/A 280 280
1251­240S-
N1
1251­208Y-
N1
1251­120S-
N2
1251­240S-
• The device must be selected in relation to a dedicated AC network (see Technical Data).
• If LED lights are OFF, the surge protector must be replaced.
Model
N2
1251­208Y-
N2
50 kA
20 kA
140
1252­120S-
N1
1252­240S-
N1
1252­208Y-
N1
1252­120S-
N2
1252­240S-
N2
1252­208Y-
N2
Asia-Pacic: Tel: +886-2 2562-4117 • Email: asiacus@bourns.com EMEA: Tel: +36 88 520 390 • Email: eurocus@bourns.com The Americas: Tel: +1-951 781-5500 • Email: americus@bourns.com
www.bourns.com
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
Specifications are subject to change without notice.
Installation
2.44
: ALL LED ON = system fully protected
1251 & 1252 Series
Hardwired AC Hybrid H-SPD
INSTALLATION INSTRUCTIONS
Figure 1
N L1 L2 L3
GND
Main switchboard or sub-panel
F1
1. Disconnect breaker supplying all power to the equipment prior to SPD installation.
2. See Figure 1.
3. Conrm Model 125x Series device is rated for your system by comparing voltage measurements to the Line Voltage on the product label.
4. Install in accordance with the applicable electric code in your area.
5. Conrm that the electrical terminals used to attach this device are identied for these conductors.
6. Twist conductors 1/2 turn or more for every 12 inches of length.
Fusing installation not required but recommended for Type 1 SPD installation according to UL 1449. Mandatory for Type 2.
7. Keep conductor length as short as possible with no sharp bends.
8. Do not loop or coil wires.
9. Ensure a high quality ground is in place.
Panel wall
Diagnostic Operation
LED ON = Normal operation. LED OFF (one or more) = Fault, check phase voltage and
connections. If okay, replace unit. AUDIBLE ALARM ON = Fault, check phase voltage and
Introduce accessory on SPD output for tightness
13 mm (0.5 in.) knockout (trade size) Actual hole size 22 mm (.875 in.)
Nut
connections. If okay, replace unit.
Wiring Dimensions (inches)
Version N2
Version N1
Green/Yellow wire
N
L1 L2 L3
Black wires
White wire
GND
Black wires
Green/Yellow wire
White wire
Maintenance
: ALL LED ON = system fully protected
07/16
Specifications are subject to change without notice. The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time. Users should verify actual device performance in their specific applications.
4
3.46
0.78
0.79
0.83
: 1, 2 or 3 LED OFF = system unprotected
0.81
and replace
with 125x-xxx-Nx