Boulevard DVLL41FP92N-1, DVTL41FP90P-1, DVLL41FP92P-1, DVTL41FP90N-1 Installation Instructions And Owner's Manual

GAS-FIRED
Direct Vent Zero Clearance
Gas Fireplace Heater
INSTALLATION INSTRUCTIONS
AND
OWNER’S MANUAL
LUXURY DIRECT VENT
GAS FIREPLACE HEATER
MODEL SERIES
MULTI-FUNCTIONAL REMOTE SERIES
CONTEMPORARY
DVLL41FP92N-1 DVLL41FP92P-1
TRADITIONAL
DVTL41FP90N-1 DVTL41FP90P-1
— Do not store or use gasoline or other ammable
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
Immediately call your gas supplier from a
If you cannot reach your gas supplier, call the
— Installation and service must be performed by a
WARNING
HOT GLASS
CAUSEBURNS.
DO NOT T OUCH
UNTIL COOLED.
NEVER
WARNING: If the information in these instructions
are not followed exactly, a re or explosion may
result causing property damage, personal injury or loss of life.
vapors and liquids in the vicinity of this or any other appliance.
any phone in your building.
neighbor’s phone. Follow the gas supplier’s instructions.
re department.
qualied installer, service agency or the gas sup-
plier.
ALLOW CHILDREN
TO TOUCH GLASS.
WILL
GLASS
Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.
WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certied
kit is used.
Page 1
TABLE OF CONTENTS
SECTION PAGE
Important Safety Information .............................................................................................. 3
Safety Information for Users of LP Gas .............................................................................4
Requirements for Massachusetts ...................................................................................... 5
Introduction ........................................................................................................................ 6
Specications ..................................................................................................................... 7
Fireplace Dimensions ........................................................................................................ 7
Clearances ......................................................................................................................... 8
Locating Fireplace .............................................................................................................. 9
Gas Supply ...................................................................................................................... 10
Installation ................................................................................................................... 11-13
Venting ............................................................................................................................. 14
Venting Fireplace - Top ...............................................................................................14-17
Venting Fireplace ........................................................................................................18-19
Examples - Top Vent Run ...........................................................................................20-21
Termination Clearances ................................................................................................... 22
Vent Clearances ............................................................................................................... 23
Vent System Identication ................................................................................................ 24
Venting Framing and Finishing ...................................................................................25-26
Horizontal Termination ..................................................................................................... 27
Vertical Termination ..................................................................................................... 28-29
Finishing the Wall ........................................................................................................30-31
DVTL Log Placement ....................................................................................................... 32
DVLL Glass Media Installation ......................................................................................... 33
Lighting Instructions ......................................................................................................... 34
Operating Instructions ................................................................................................. 35-36
Maintenance Instructions ............................................................................................36-37
Accessories ...................................................................................................................... 39
Optional Porcelain Panels (DVTL Only) ........................................................................... 39
Optional Decorative Glass Panels (DVLL Only) ...............................................................40
Master Parts Distributor List ............................................................................................. 41
How To Order Repair Parts .............................................................................................. 41
DVLL Parts List ................................................................................................................42
DVLL Exploded View ....................................................................................................... 43
DVTL Parts List ................................................................................................................ 44
DVTL Exploded View ....................................................................................................... 45
Junction Box Wiring Installation Instructions .................................................................... 46
Accent Lamp Light Replacement - DVLL ......................................................................... 46
Quick Reference Guide ............................................................................................... 47-48
Warranty ...........................................................................................................................49
Appliance Service History ...........................................................................................50-51
29843-2-0612Page 2
IMPORTANT SAFETY INFORMATION
Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.
DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED
• If this appliance is installed directly on carpeting,
tile or other combustible material other than wood
ooring the appliance shall be installed on a metal
or wood panel extending the full width and depth of the appliance.
The base referred to above does not mean the
reproof base as used on wood stoves. The protection
is for rugs that are extremely thick and light colored tile.
• Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to avoid burns or clothing ignition.
• Young children should be carefully supervised when
they are in the same room as the appliance.
• Clothing or other ammable material should not be
placed on or near the appliance.
• Due to high temperatures the appliance should be located out of trafc and away from furniture and
draperies.
• The glass front or any part removed for servicing the
appliance must be replaced prior to operating the
appliance. Work should be done by a qualied service
person.
• Keep burner and control compartment clean.
• Vent cap is hot while replace is in operation.
• Installation and repair should be done by a qualied
service person. The appliance should be inspected
before use and at least annually by a qualied service
person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
• Adequate accessibility clearances for servicing and
proper operation.
• This appliance must not share or be connected to a ue serving a separate solid-fuel burning
appliance.
• Keep the area around your appliance clear of combustible materials, gasoline and other ammable
vapor and liquids.
• Under no circumstances should any solid fuels
(wood, coal, paper or cardboard etc.) be used in this appliance.
• The ow of combustion and ventilation air must not
be obstructed in any way.
• Do keep the appliance area clear and free from combustible material, gasoline and other ammable
vapors and liquids.
• Do examine venting system periodically and replace
damaged parts.
• Do make a periodic visual check of pilot and burners.
Clean and replace damaged parts.
• CAUTION: The glass used in your replace is ceramic
glass. If the glass is cracked or damaged in any way, it should be replaced only with a complete glass frame assembly from Empire. See parts list on Pages 42
to 45.
• Do not use this replace if any part has been under water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the control system and any gas control which has been under water.
• Do not put anything around the replace that will obstruct the ow of ventilation air.
• Clearance in accordance with local installation codes
and the requirements of the gas supplier.
29843-2-0612 Page 3
• Any safety screen or guard removed for servicing
an appliance must be replaced prior to operating the appliance.
SAFETY INFORMATION FOR USERS OF LP GAS
Propane (LP-Gas) is a ammable gas which can cause res
and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point
with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.
That’s your signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such as
basements. When you have reason to suspect a gas leak, keep
out of basements and other low areas. Stay out until reghters
declare them to be safe.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.
Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell the
odor of the chemical put into the gas. You must nd out if you
can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.
The odorant in LP-Gas is colorless, and it can fade under some circumstances. For example, if there is an underground
leak, the movement of the gas through soil can lter the odorant.
Odorants in LP-Gas also are subject to oxidation. This fading can
occur if there is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-Gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it to
nd out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas Dealer.
• If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualied, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too long before relling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause
odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any question
about the gas odor, call your LP-Gas dealer. A periodic sniff test of the LP-Gas is a good safety measure under any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under
no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air
through openings such as pilot light orices. If this occurs, some
new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your con­tainer is under vapor pressure by turning it off at the container
before it goes completely empty or having it relled before it is
completely empty.
29843-2-0612Page 4
REQUIREMENTS FOR MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination
is less than seven (7) feet above nished grade in the area of
the venting, including but not limited to decks and porches, the
following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gastter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the oor level where
the gas equipment is to be installed. In addition, the installing
plumber or gastter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner
to secure the services of qualied licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent
oor level.
b. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/ UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board;
and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems”, the following requirements
shall be satised by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instruction.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the installation.
29843-2-0612 Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after installation.
2. Installer must have owner ll out and mail warranty card supplied with the replace.
3. Installer should show owner how to start and operate the
replace.
This direct vent gas replace heater is designed to operate with
all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.
Warning: This unit is not for use with solid fuels.
Appliance Certication
This replace is design certied in accordance with American National Standard/CSA Standard ANSI Z21.88/CSA 2.33 and by
Underwriters Laboratories as a Direct Vent Gas Fireplace Heater and shall be installed according to these instructions. Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.
The replace, when installed, must be electrically grounded in
accordance with local codes or, in absence of local codes, with the
National Electric Code ANSI/NFPA 70 or Canadian Electric code, CSA C22.1, if an external electrical source is utilized.
These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be
performed only by a qualied agency. The term “qualied agency” means any individual, rm, corporation or company which either in
person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.
High Altitude
When installing this unit at an elevation above 2000 feet (in the United States) it may be necessary to decrease the input rating by
changing the existing burner orice to a smaller size. Generally,
input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper
orice size identication.
Canadian High Altitude
Altitude: 0-4500 feet (0-1370 m)
When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper
orice for location.
Preparation
This direct vent gas replace and its components are tested and
safe when installed in accordance with this Installation Manual.
Report to your dealer any parts damaged in shipment, specically
check glass condition. Do not install unit with damaged, incomplete, or substitute parts. Read all instructions before starting installation and follow these instructions carefully during installation to insure
maximum benet and safety. Failure to follow them will void your warranty and may present a re hazard.
The warranty will be voided by, and the warranter disclaims any
responsibility for the following actions:
• Installation of any damaged fireplace or vent system
component.
• Modication of the replace or direct vent system.
• Installation other than as instructed by Empire Comfort Systems,
Inc.
• Improper positioning of the logs, glass door or decorative media.
• Installation and/or use of any component part not manufactured
or approved by manufacturer.
State of Massachusetts: The installation must be made by a licensed plumber or gas tter in the Commonwealth of
Massachusetts.
The installation must conform with local codes or, in the absence of
local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54* Natural Gas and Propane Installation Code, or CSA B149.1 in Canada. *Available from the American National Standards Institute, Inc. 11 West 42nd St., New York, N.Y. 10036.
Warning: ANY CHANGE TO THIS FIREPLACE OR ITS CONTROLS CAN BE DANGEROUS. Improper installation or use of the replace can cause serious injury or death from re, burns, explosions, or carbon
monoxide poisoning.
Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change. Important
All correspondence should refer to complete Model Number, Serial Number and type of gas.
29843-2-0612Page 6
SPECIFICATIONS
F
I
◄►
A
B
C
D
E
K
12” (305mm)
DVLL NAT DVLL LP DVTL NAT DVTL LP
Input Btu/hr Maximum 34,500 31,500 34,500 31,500
Btu/hr Minimum 18,000 20,500 17,000 16,700
KWH (Maximum) 10.1 9.2 10.1 9.2
(Minimum) 5.3 6.0 5.0 4.9
Orice #31, P209 #51, P210 3.10mm, P296 #51, P210
Min. Rate Screw #41 #52 #41 #52
Air Shutter Opening - Front 9/16 in. FULL OPEN 9/16 FULL OPEN
Height without standoff 24-1/4 in. (616 mm) 24-1/4 in. (616 mm) 24-1/4 in. (616 mm) 24-1/4 in. (616 mm)
Width 51-1/16 in. (129.7 cm) 51-1/16 in. (129.7cm) 51-1/16 in. (129.7cm) 51-1/16 in. (129.7cm)
Depth 15-13/16 in. (402 mm) 15-13/16 in. (402 mm) 15-13/16 in. (402 mm) 15-13/16 in. (402 mm)
Gas Inlet Shutoff Valve (Pipe)
NOTE: Air shutter settings are factory minimum settings. Some venting congurations may require minor air shutter adjustments for
optimum performance.
1/2 NPT 1/2 NPT 1/2 NPT 1/2 NPT
J
FIREPLACE DIMENSIONS
DIMENSIONS
in inches (metric)
A
B
C
D
E
F
G
H
I
J
K
DVLL(DVTL)
51-1/16
(129.7cm)
44-1/2
(113.0cm)
16-1/2
(419mm )
36-5/8
(930mm)
24-5/8
(625mm)
15-13/16
(402mm)
6-9/16
(167mm)
9-1/4
(235mm)
23-7/8
(606mm)
1-9/16
(40mm)
1-1/4
(32mm)
G
▼ ▲
H
A
TOP VIEW
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
29843-2-0612 Page 7
Figure 1
CLEARANCES
IN THIS AREA
HEADER RECOMMENDATION: USE DOUBLE HEADER OR PLACE HEADER VERTICALLY
SEE MANTEL CHART FOR MAXIMUM MANTEL DEPTH AND HEIGHT
57-7/16”
(145.0cm)
STANDOFF 12” (305mm) HEIGHT ABOUT TOP OF FIREPLACE
NON-COMBUSTIBLE FINISHED WALL FIRST 13-1/2” (343mm)
1-1/4” (32mm)
Clearance to Combustibles - Shown in inches (metric)
Back 1-1/4 (32mm) Side 3-1/8 (79mm) Floor 0 (0mm) Top Stand-off 12 (305mm) Top Framing Edge 12 (305mm) Minimum Height Floor To Ceiling 45-3/4 (116.2cm)
Mantel Chart
20”
(508)
19”(482)
18”(457)
20 ½” (521)
21 1/2” (546)
19 ½” (495)
18 ½” (469)
17 ½” (444)
16 ½” (419)
15 ½” (394)
17”(431)
16”(406)
14 ½” (368)
15”(381)
14”(356)
13 ½” (343)
13”(330)
(305)
12”
IMPORTANT NOTE: NO COMBUSTIBLES MAYBE PLACED IN THE AREA BETWEEN THE TOPOF THE FIREPLACE AND THE MANTEL
Figure 4
Ceiling Height and Side Wall Clearances
Minimum ceiling height is 46" (116.8cm)
Clearance from side of replace to adjacent sidewall is 2" (51mm).
Note: Some decorative fronts require more than 2" clearance due
to front size.
Combustible Material
No greeting cards, stockings or ornamentation of any type should be placed on or attached to the replace. The ow of heat can
ignite combustibles.
3-1/8” (79mm)
Figure 2
1-1/4” (3mm)
ONLY NON-COMBUSTIBLE MATERIALS
ALLOWED OVER THE FIREPLACE FACE
ON EACH SIDE
Figure 3
3-1/8” (79mm)
21-1/2”
()546mm
MINIMUM
Figure 5
2”
()51mm
29843-2-0612Page 8
LOCATING FIREPLACE
Note: Island and Room Divider installation is possible as long as the horizontal portion of the vent system does not exceed 20 feet (609.6cm) with a minimum vertical run of 8 feet (243.8cm). See details in Venting Section. See Figure 6.
CABINET
INSTALLATION
CORNER INSTALLATION
ANGLED CORNER INSTALLATION
ISLAND INSTALLATION
Figure 6
FLUSH WALL
INSTALLATION
ROOM DIVIDER INSTALLATION
29843-2-0612 Page 9
GAS SUPPLY
The gas pipeline can be brought in through the left side of the
appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10ft
0-3m
11-40ft 4-12m
41-100ft
13-30m
101-150ft
31-46m
1/2 in.
12.7mm
1/2 in.
12.7mm
1/2 in.
12.7mm
3/4 in.
19mm
3/8 in.
9.5mm
1/2 in.
12.7mm
1/2 in.
12.7mm
1/2 in.
12.7mm
1/2 in.
12.7mm
5/8 in.
15.9mm
3/4 in.
19mm
7/8 in.
22.2mm
3/8 in.
9.5mm
1/2 in.
12.7mm
1/2 in.
12.7mm
3/4 in.
1.9 mm
Note: Never use plastic pipe. Check to conrm whether your local
codes allow copper tubing or galvanized. Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings.
— ANS Z21.45 Assembled Flexible Appliance Connectors of Other
Than All-Metal Construction The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a
exible appliance connector cannot exceed three feet in length.
FLEXIBLE GAS LINE CONNECTION
GAS SUPPLY
TEE HANDLE
FLARE SHUT OFF VALVE
FLEX TUBING
FLARE FITTING
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE: The gas controls are equipped with a captured screw type
pressure test point, therefore it is not necessary to provide a 1/8 in.
test point up stream of the control.
When using copper or ex connector use only approved ttings.
The appliance and its individual shut off valve must be disconnected from supply piping system during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to
or less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess
of 1/2 psig (14 in. w.c.) (3.5 kPa) on the replace gas valve, it will
result in a hazardous condition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold
pressure of approximately 3.5 in. w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 5.0 in. w.c. (1.245kPa) for the purpose of input adjustment to a maximum of
14.0 in. w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0 in. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8 in. w.c. (2.68kPa) for the purpose of input adjustment to a maximum of
14.0 in. w.c. (3.484kPa).
Figure 7
Gas Supply Pressure (inches w.c.)
Minimum Normal Maximum
Natural Gas 5.0 7.0 14.0
LP (Propane) 10.8 11.0 14.0
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas 3.5
LP (Propane) 10.0
2-7/16” (61mm)
Figure 8
29843-2-0612Page 10
VENT PIPE
INSTALLATION
Vent Pipe Clearance Note: Maintain one inch (1 in.) of clearance around vertical vent
pipe. See Figure 9. For horizontal vent, maintain a minimum 1 in. clearance to the bottom and sides of the vent, and 3 in. clearance to combustibles above the vent pipe. See Figure 10.
3” (76mm)
TOP OF VENT PIPE
4”
DIAMETER
FLUE
6-5/8”
DIAMETER
INTAKE VENT
1” (25mm) MINIMUM CLEARANCE AROUND VENT PIPE
Figure 9
Attention: Horizontal venting through a wall requires a wall
thimble on the interior side of the wall above the pipe.
2” (50.8mm)
1” (25.4mm)
Figure 10
29843-2-0612 Page 11
INSTALLATION
Framing and Finishing
NOTE: You must use the standoffs that are supplied with the
replace. The standoffs are shipped in a at-state on top of the replace.
1. Locate the two (2) steel standoffs and two (2) header shields
attached to the back of the replace.
2. Remove the two (2) screws that secure the standoffs and header
shields in place; save the screws.
3. The right and left standoffs have a perforation located in the
middle. Bend them at the perforation to a little more than 90°.
4. Bend the short tabs on each end the opposite direction. Secure
the standoffs to the replace top with three (3) screws each
from the hardware bag. There are pilot holes located in the
top of the replace for each stand-off.
5. Verify that the front of the standoffs are 1/2 in. (13mm) back
from the face of the replace. Verify that the stand-off is
12 in. (305mm) tall.
6. Locate the bottom header shield; it is the shorter one. Using
four (4) screws, attach it between the standoffs.
7. Locate the top header shield; it is the longer one. Using four
(4) screws, attach it between the standoffs. See Figure 12.
8. Remove the non-combustible board that is shipped between
the replace and pallet.
9. Frame in replace with a header across the top.
IMPORTANT: Allow for nished face when setting the depth
of the frame.
10. Attach the replace to the frame. See Figure 12.
11. Install the non-combustible board across the top and sides
of the replace. The board sits on the 1/2 in. surface on top
of the replace and in front of the standoffs. See Figure 11.
Flush Mount Mantel Installation
The fireplace must extend 3/4 in. (19mm) beyond finished wall surface when using a ush mount mantel. Refer to Figure 12 to locate nailing anges on replace sides. Mark and drill four (4) 1/8 in. holes into replace side to mount each nailing flange. Use eight (8) 1/2 in. hex-head screws supplied in hardware package to attach nailing anges to replace sides.
STAND-OFF
HEADER SHIELD
BOTTOM
HEADER SHIELD
STAND-OFF
TOP
IMPORTANT: IN ORDER TO USE SOME OPTIONAL FRONTS
YOU MUST RAISE THE FIREPLACE ON A HEARTH SO THE
BOTTOM OF THE FIREPLACE IS A MINIMUM DISTANCE
ABOVE THE TOP OF THE HEARTH EXTENSION FINISHING
MATERIAL. CHECK DECORATIVE FRONT DIMENSIONS
PRIOR TO SETTING THE HEIGHT OF THE FIREPLACE
HEARTH EXTENSION.
NON-COMBUSTIBLE
BOARD
NAIL OR OTHER SUITABLE FASTENER
Figure 12
Figure 11
29843-2-0612Page 12
INSTALLATION
Framing
Fireplace framing can be built before or after the replace is set
in place. Framing should be positioned to accommodate wall
covering and replace facing material. The replace framing
should be constructed of 2 x 4 lumber or heavier. The framing
headers may rest on the replace standoffs. Refer to Figure 13 for minimum framing dimensions. CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS, AND WALL COVERING DETAILS BEFORE FRAMING CONSTRUCTION BEGINS.
A
C
B
Flush Wall Installation
HEADER: A DOUBLE HEADER OR PLACING THE HEADER VERTICALLY IS RECOMMENDED
STANDOFF 12” (305mm) HEIGHT ABOVE TOPOF THE FIREPLACE
FIRST 13-1/2” (343mm) NON-COMBUSTIBLE FINISHED WALL
TOP OF THE FIREPLACE
Figure 14
Combustible Surround Installation
DVLL/DVTL
A 36-7/8 in. (937mm)
B 54-1/2 in. (138.4cm)
C 17-1/16 in. (433mm)
Figure 13
Framing dimension "A" includes a 12 in. (304 mm)
clearance for standoffs on rebox. After installing rebox into framing, the nished wall surface must cover the 12 in. (304mm) opening above the rebox. Board provided with replace.
ATTENTION: If a base or mantel is not used and the appliance is installed directly on carpeting, tile or other combustible material other
than wood ooring, it shall be installed on a metal or wood panel
extending the full width and depth of the appliance. The vertical dimension in Figure 13 must be adjusted when a metal or wood panel is placed beneath the appliance.
CAUTION: If the joints between the nished wall and the replace
surround (top and sides) are sealed, a 300°F minimum sealant material must be used. These joints are not required to be sealed. Only non-combustible material (using 300°F minimum adhesive if
needed), can be applied as facing to the replace surround.
2 X 4
HEADERS
STANDOFFS
FINISHED WALL
13-1/2” (343mm) NON-COMBUSTIBLE MATERIAL SUPPLIED WITH FIREPLACE
NON-COMBUSTIBLE MATERIAL
COMBUSTIBLE MANTLE
Figure 15
Finishing
Finish the walls with the material of your choice. Figure 4 on page 8 shows the minimum vertical and corresponding maximum horizontal dimensions of mantels or other combustible projections above the
top front edge of the replace. Only non-combustible materials may be used to cover the metal replace face.
29843-2-0612 Page 13
CAP
VENTING FIREPLACE
Attention: Cold climate installation recommendation: When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.
Vent Runs
In planning the installation for the replace, it is necessary to install
certain components before the appliance is completely positioned and installed. These include the direct vent system, gas piping for the appliance and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1. A at, hard combustible surface.
2. A raised wooden platform.
3. Four (4) corner supports. (Example: Four (4) concrete masonry
blocks.) These supports must be positioned so they contact all four (4) perimeter edges on the bottom of the unit and under the center leg supports. Two more supports spaced evenly for front and back may be required pending local code.
Vertical, 90° Elbow With Horizontal Termination
3” (76mm) MINIMUM CLEARANCE TO COMBUSTIBLES
90°
ELBOW
Vertical, 90° Elbow To
Horizontal Out The Wall
C
B
A
PIPE LENGTH
VENT
WALL FIRESTOP
61-5/8”
(156.52cm)
VENT CAP/ THIMBLE
WALL FIRESTOP
Figure 16
IMPORTANT: MINIMUM HEIGHT OFF THE TOP REQUIREMENTS
DVLL & DVLT - MUST USE a 2 ft. (610 mm) vertical vent pipe as
the rst section BEFORE installing the elbow.
A B C
6 in.
9 in.
12 in.
11-3/4 in. to 12-3/4 in.
(298mm to 323mm)
14-1/4 in. to 15-3/4 in.
(362mm to 400mm)
17-1/4 in. to 18-3/4 in.
(438mm to 476mm)
4-3/4 in. to 6-1/4 in.
(121mm to 159mm)
7-3/4 in. to 9-1/4 in.
(197mm to 235mm)
10-3/4 in. to 12-1/4 in.
(273mm to 311mm)
Figure 17
29843-2-0612Page 14
20’
(6.1M)
8’
(243.8cm)
TO TOP OF UNIT
VENTING FIREPLACE
Corner Installation Vertical, 90° Elbow
To Horizontal Out The Wall
B
D
A
◄►
*
C
E
VENT CAP THIMBLE
WALL FIRESTOP
Maximum Horizontal Run For A Minimum Vertical Rise
20” (50.8 cm)
MAXIMUM
24” (609.6mm)
MINIMUM VENT
PIPE LENGTH
*NOTE: YOU MUST USE A2’ (609.6mm) VERTICAL
VENT PIPE AS YOUR FIRST SECTION BEFORE INSTALLING THE ELBOW.
DVLL/DVTL
A
B
C
D
E
Note: Corner installation may require more vertical vent pipe
than just the minimum required depending on wall thickness and horizontal dimension.
62-1/4 in.
(158.1 cm)
44-1/16 in.
(111.9 cm)
24-5/8 in.
(62.6 cm)
88-1/16 in.
(223.7 cm)
24 in.
(60.9 mm)
Figure 18
Figure 19
Minimum Vertical Rise For Maximum Horizontal Run
29843-2-0612 Page 15
Figure 20
VENTING FIREPLACE
To Use the Vent Graph
1. Determine the height of the center of the horizontal vent pipe.
Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the
bottom of the graph.
3. Select the indicated dimension, and position the unit in accordance
with same.
EXAMPLE A:
If the vertical dimension from the top of the unit is 35 ft. (10.67 m), the
horizontal run to the outer wall ange must not exceed 5 ft (1.52 m).
EXAMPLE B:
If the vertical dimension from the top of the unit is 5 ft. (1.52 m), the
horizontal run to the outer wall ange must not exceed 11 ft. (3.35 m).
Special Note: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system. Reduce 3 ft. (91.4 cm) for every 90° elbow.
Example: According to the chart the maximum horizontal vent length is 20 ft. (6.10 m) and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17 ft. (5.18 m).
The maximum number of 45 degree elbows permitted per side wall installation is two. These elbows can be installed in either the vertical or horizontal run.
NOTE: The rst elbow does not get counted.
Vertical Venting
When venting long straight vertical sections, use of the vertical vent
bafes may be required for optimal ame performance.
To install vertical vent bafes, align the two holes on the vertical vent bafe with the two holes in the ue bafe. Secure the vertical vent bafe with the screws provided. Repeat for both sides of the ue bafe.
Acceptable vertical and horizontal vent run. (40 ft. (12.19 m) maximum vertical and 20 ft. (6.10 m) maximum horizontal)
Unacceptable vertical and horizontal vent run.
Figure 21
Figure 22
29843-2-0612Page 16
FIRESTOP AT CEILING LEVEL
3” (76 mm) MINIMUM
18” (457 mm) MINIMUM
12”
(305 mm)
ABOVE GRADE
48”
(121.9cm)
VENTING FIREPLACE
Below Grade Installation
When it is not possible to meet the required vent terminal clearances of 12 in. (305mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7 in. (178mm) below grade level. The 7 in. (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.
Typical Basement Installation
Example Of Possible Venting System Using One 90° Elbow
8 ft. (2.44 m) is listed as minimum vertical vent run with 20 ft. (6.10 m) of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to exterior of wall.
Figure 23
SEE GRAPH (Figure 21) FOR PERMISSIBLE
"H" AND "V" DIMENSIONS
Figure 24
29843-2-0612 Page 17
FIRESTOP AT CEILING LEVEL
VENTING FIREPLACE
Example Of Possible Venting System Using Two (2) 90° Elbows
Examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure
25 is 37 ft. (11.28 m).
SEE GRAPH (Figure 21) FOR PERMISSIBLE
"H" AND "V" DIMENSION
NOTE: H1 AND H2 MUST BE ADDED TOGETHER TO USE GRAPH THEN SUBTRACT 3' (91.4 cm) FOR THE SECOND 90° ELBOW
Figure 25
29843-2-0612Page 18
12”
(305mm)
VENTING FIREPLACE
10”
(254mm)
C
B
H
V
CENTER
OF ELBOW
C
B
A
CENTER OF FRAMING
(MINIMUM VENT)
Figure 26
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACE
Positioning the Fireplace
FIREPLACE SERIES
DVLL/DVTL
HARD ELBOW DIMENSIONS
A B C
55-5/8 in.
(141.3 cm)
5 in.
(127 mm)
7 in.
(178 mm)
VENT CAP
9” (229mm)
MINIMUM TO SIDE WALL
Figure 27
Determine the exact position of the appliance so the direct vent termination will be centered (if possible) between two (2) studs. This will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the nal position.
Cutting the Hole
After the replace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole must be 12 in. (305mm) high x 10 in. (254mm) wide with its center line determined by the amount of vertical rise and horizontal run of the termination. See Figure 26. When locating the hole it must be noted that the bottom of the cap must be 12 in. (305mm) above the ground level, and top of the cap must be no less than 18 in. (457mm) below a combustible projection, and no closer than 9 in. (229mm) to any wall running parallel to vent termination. See Figure 27.
29843-2-0612 Page 19
24
H2
H1
V1
EXAMPLES - TOP VENT RUN
24” MINIMUM CLEARANCE TO COMBUSTIBLES
H1
H2
V1
If total horizontal needs to be 8' (2.44 m), then the minimum required vertical is 5' (1.52 m).
H=8' (+90°) = 11' (equivalent horizontal)
H=2.44 m (+90°) = 2.44 m (equivalent horizontal)
From the graph the required vertical is 5' (1.52 m).
Figure 28
If total horizontal needs to be 10' (3.05 m), then the minimum required vertical is 7' (2.13 m).
H=10' (90° + 90°) = 16' (equivalent horizontal)
H= 3.05 m (90° + 90°) = 4.88 m (equivalent horizontal)
From the graph the required vertical is 7' (2.13 m).
Figure 29
29843-2-0612Page 20
EXAMPLES - TOP VENT RUN
H2
H1
V1
If total vertical is to be 9' (2.74 m), then the maximum allowed horizontal run can be 20' (6.10 m).
H=20'
H=6.10 m
From the graph the allowed vertical is 20' (6.10 m).
Figure 30
29843-2-0612 Page 21
TERMINATION CLEARANCES
Termination clearance for buildings with combustible and noncombustible exteriors.
Vertical Sidewall Installations Important! Minimum clearance between vent pipes and combustible materials is three (3 in.) (76mm) on top, and (1 in.) (25mm) on bottom
and sides.
Important! When vent termination exits through foundation less than 20 in. (508 mm) below siding outcrop, the vent pipe must extend
outward so that the horizontal vent terminal is located ush to, or beyond the outcrop siding.
Information on Various Venting Routes and Components
Important: It is always best to locate the replace in such a way that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its balance between the combustion air intake and the ue gas exhaust, certain limitations as to vent congurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.
The horizontal vent run refers to the total length of vent pipe from the ue collar of the replace to the face of the outer wall.
The maximum horizontal vent run is 20 ft. (457 cm) when the vertical vent rise is 8 ft. (244 cm). See Figure 21.
Venting terminals shall not be recessed into wall or siding.
Figure 31
29843-2-0612Page 22
VENT CLEARANCES
VENT TERMINAL AIR SUPPLYINLET
Figure 32
AREA WHERETERMINALISNOT PERMITTED
A = *Clearance above grade, veranda, porch, deck or balcony
[*12 inches (30cm) minimum]
B = clearance to window or door that may be opened [*12 inches
(30cm) minimum for appliances < 100,000 Btuh (30kW)
C = clearance to permanently closed window [minimum 12 inches
(30cm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soft located above the terminal
within a horizontal distance of 24 inches (60cm) from the center of the terminal [18 Inches (46cm) minimum
E = clearance to unventilated soft [12 inches 30cm) minimum]
F = clearance to outside corner [See Page 22]
G = clearance to inside corner [See Page 22]
H = *not to be installed above a meter/regulator assembly
within 3 feet (90cm) horizontally from the center-line of the regulator
I = clearance to service regulator vent outlet [*6 feet (1.8m)
minimum]
J = clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance [*12 inches
(30cm) minimum for appliances ≤ 100,000 Btuh (30 kW)
36 inches (90cm) minimum for appliances > 100,000 Btuh
(30kW)]
K = clearance to a mechanical air supply inlet [* 6 feet (1.8m)
minimum]
L = †clearance above paved sidewalk or a paved driveway located
on public property [*7 feet (2.1m) minimum]
M = clearance under veranda, porch, deck, or balcony [*12 inches
(30cm) minimum ¥]
† a vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings*
¥ only permitted if veranda, porch, deck, or balcony, is fully
open on a minimum of 2 sides beneath the oor*
* as specied in CGA B149 Installations Codes or ANSI Z223.1.
Note: Local Codes or Regulations may require different
clearances.
29843-2-0612 Page 23
VENT SYSTEM IDENTIFICATION
Installing Vent Components
Begin the vent system installation by installing the rst Duravent component to the starting collar, 24 inch (60.10 cm) minimum straight
pipe on the top of the appliance, then the remaining pipe length and the horizontal or vertical termination kit.
NOTE: All outer connection joints must be sealed with aluminum tape, screws or silicone sealant rated above 300°F/149°C. The
inner ue joints do not require any sealant.
Duravent vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four (4) equally spaced indented sections. When the internal beads of each starting outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.
Continue adding components per the pre-planned vent system conguration. Be certain that each succeeding vent component is securely tted and locked into the preceding component in the vent system.
Special Venting Components (Duravent)
See Empire Comfort Systems Retail Price List for 4 x 6-5/8 inch Duravent part numbers and pricing.
WALL THIMBLE
90° ELBOW OR 45° ELBOW
VERTICAL TERMINATION
(MAXIMUM OF
THREE 90° ELBOWS)
90° ELBOW
CEILING FIRESTOP
WALL STRAP
PIPE LENGTH
HORIZONTAL TERMINATION
(MAXIMUM OF TWO 90° ELBOWS)
STORM COLLAR
ROOF FLASHING
Figure 33
29843-2-0612Page 24
EXISTING CEILING JOISTS
VENTING FRAMING AND FINISHING
Installing Support Brackets
A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch
clearance to combustibles above ue pipe and elbows and 1 inch clearance on both sides and bottom of the ue pipe to combustibles
on all horizontal pipe sections and elbows.
Vertical runs of this vent systems must be supported every 4 feet
above the appliance ue outlet by wall brackets attached to the
vent pipe and secured with nails or screws to structural framing members.
PIPE STRAP
STUD WALL
A
B
48”
(121.9cm)
► ◄
1” MIN.
(25.4mm)
FLUE
OUTLET
1-1/4” MIN.
(32.7mm)
Figure 34
Installing Firestops
Firestops are required for safety whenever the vent system passes
through an interior wall, an exterior wall, or a ceiling. These restops act as a rebreak heat shield and as a means to insure that minimum
clearances are maintained to the vent system.
Horizontal runs in the vent system which pass through either interior
or exterior walls, require the use of wall restops on both sides of
the wall through which the vent passes.
Cut an appropriate sized hole in wall. See Figure 35. Position
restop on interior side of wall for hole.
Attention: Wall restop hole is off-set towards bottom of wall
opening. Secure with nails or screws. Continue the vent run through
the restop. See Figure 35.
Attention: Horizontal venting through a wall requires a wall
thimble on the interior side of the wall above the pipe.
WALL FIRESTOP HOLE IS OFF-SET
TOWARDS BOTTOM OF WALL OPENING
Vent Size A B
6-5/8 in.
(168.3 mm)
12-3/8 in
(314.3 mm).
12-3/8 in.
(314.3 mm)
Figure 35
Vertical runs of this system which pass through ceilings require the
use of ONE (1) ceiling restop at the hole in each ceiling through
which the vent passes.
Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check
the oor above for any obstructions such as wiring or plumbing
runs. Reposition the appliance and vent system, if necessary, to
accommodate ceiling joists and/or obstructions.
Cut an appropriate sized hole through the ceiling, using the center point previously marked. See Figure 36. Frame the hole with framing lumber the same size as the ceiling joists. See Figure 36.
NEW FRAMING
CEILING BELOW
A
B
Vent Size A B
6-5/8 in.
(168.3 mm)
10-1/2 in.
(266.7 mm)
10-1/2 in.
(266.7 mm)
Figure 36
29843-2-0612 Page 25
VENTING FRAMING AND FINISHING
NAILS, 4 REQUIRED
If the area above the ceiling is NOT an attic, position and secure the ceiling restop on the ceiling side of the previously cut and
framed hole. See Figure 37. If the area above the ceiling is an attic,
position and secure the restop on top of the previously framed
hole. See Figure 38.
NOTE: Remove insulation from the framed area in the attic before
installing the restop and/or vent pipes.
A
B
NAILS, 4 REQUIRED
CEILING FIRESTOP
CEILING FIRESTOP
B
Vent Size A B
6-5/8"
(168.3 mm)
10-1/2"
(266.7 mm)
10-1/2"
(266.7 mm)
Figure 38
A
Vent Size A B
6-5/8"
(168.3 mm)
10-1/2"
(266.7 mm)
10-1/2"
(266.7 mm)
Figure 37
29843-2-0612Page 26
HORIZONTAL TERMINATION
NOTE: Termination cap should pass through the wall restop from
the exterior of the building. Adjust the termination cap to
its nal exterior position on the building.
Warning: Termination cap must be positioned so that arrow is
pointing up.
Attach the termination cap with the four wood screws provided. Before attachment of the termination, run a bead of silicone sealant rated above 250°F on its outside edge too, so as to make a seal to the exterior wall.
NOTE: Wood screws can and should be replaced with appropriate
fasteners for use on stucco, brick, concrete or other types of siding.
CAUTION: If exterior walls are nished with vinyl siding, (or materials
that could become discolored or warp) it is necessary to install a vinyl siding standoff.
The vinyl siding standoff will be installed between the vent termination and the exterior wall. See Figure 39. This horizontal vent termination
bolts onto the at portion of the vinyl siding standoff, so an air space
will exist between the wall and the termination cap.
CUT VINYL SIDING AWAY TO FIT STANDOFF
NUT
(4 REQUIRED)
BOLT(4 REQUIRED)
VENT TERMINATION
WOOD SCREWS (4 REQUIRED)
Figure 39
29843-2-0612 Page 27
VERTICAL TERMINATION
Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this center point. Make the outline of the roof hole around this center point.
NOTE: Size of the roof hole dimensions depend on the pitch of
the roof. There must be a 1 inch clearance (25mm) to the vertical pipe sections. This clearance is to all combustible material.
Cover the opening of the vent pipe and cut and frame the roof hole. Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to frame must withstand high winds. The storm collar is placed over this joint to make a water-tight
seal. Non-hardening sealant should be used to completely seal this ashing installation.
Determining Minimum Vent Height Above the Roof.
WARNING: Major U.S. building codes specify minimum chimney and/or vent height above the roof top. These minimum heights
are necessary in the interest of safety. These specications are summarized in Figure 40.
LOWEST
VENT CAP
GAS VENT
ROOF PITCH H (Min.)
Flat to 6/12 12 in. (305 mm)
6/12 to 7/12 15 in. (381 mm)
Over 7/12 to 8/12 18 in. (457 mm)
Over 8/12 to 16/12 24 in. (610 mm)
Over 16/12 to 21/12 36 in. (914 mm)
Figure 40
Note that for steep roof pitches, the vent height must be increased.
In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.
DISCHARGE
OPENING
H
H (MIN.) = MINIMUM HEIGHT
FROM ROOF TO LOWEST
12
ROOF PITCH IS X/12
DISCHARGE OPENING
X
24” MIN.
(609.6mm)
12” MIN.
(304.8mm)
(609.6mm)
24” MIN.
Figure 41
When terminating the vent cap near an exterior wall or overhang,
maintain minimum clearances as shown in Figure 41.
General Maintenance
Conduct an inspection of the venting system semi-annually.
Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks and, in extreme cases, holes. These components should immediately be replaced.
2. Remove the cap and shine a ashlight down the vent. Remove
any bird nests or other foreign material.
3. Check for evidence of excessive condensate, such as water droplets forming in the inner liner and subsequently dripping out at joints. Condensate can cause corrosion of caps, pipe and
ttings. It may be caused by having excessive lateral runs, too
many elbows and exterior portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe sections or ttings have been
disturbed and, consequently, loosened. Also, check mechanical
supports, such as wall straps or plumbers’ tape for rigidity.
Venting terminal shall not be recessed into a wall or siding.
A removable panel or other means must be provided in the enclosure
for visual inspection of the ue connection.
NOTE: This also pertains to vertical vent systems installed on the
outside of the building.
Slide the vertical vent cap over the ends of the vent pipe and secure.
See Figure 41.
29843-2-0612Page 28
VERTICAL TERMINATION
Installing the Vent System in a Chase
A chase is a vertical box-like structure built to enclose the gas
appliance and/or its vent system. Vertical vent runs on the outside of
a building may be, but are not required to be installed inside a chase.
CAUTION: Treatment of restop spacers and construction of
the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, your local building codes must be checked to determine the requirements for these steps.
NOTE: When installing this vent system in a chase, it is always good
building practice to insulate the chase as you would the outside walls of your home. This is especially important for cold climate installations. Upon completion of building your chase framing, install the vent system by following the instructions in this manual. Remember to build the chase large enough so that minimum clearance of combustible materials (including insulation) to the vent system are maintained.
Reassembly and Resealing Vent Pipe System
Attach vent pipe to inlet and outlet vent adaptor on replace, replace
horizontal and vertical pipe lengths, elbows and horizontal or vertical termination kit.
All vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four (4) equally spaced indented sections. When the internal beads of each starting outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.
Continue replacing components per the vent system conguration. Be certain that each succeeding vent component is securely tted
and locked into the preceding component in the vent system.
Vertical Through the Roof Applications
Your Gas Fireplace has been approved for:
a) Vertical installations up to 40 ft. (12.19 m) in height. b) Two sets of 45 degree elbow offsets within these vertical
installations. From 0 to a maximum of 8 ft. a vent pipe can be used between elbows. See Figure 43.
c) Wall straps must be used to support offset pipe every 4 ft.
(1.22 m).
This application will require that you rst determine the roof pitch
and use the appropriate venting components.
45°
45°
40’
(12.19M)
MAXIMUM
8’
(2.44M)
MAXIMUM
8’
(2.44M)
MAXIMUM
Figure 42
FEMALE LOCKING LUG
MALE LOCKING LUG
TYPICAL ROOF
SUPPORT
TYPICAL JOIST
SUPPORT
Figure 43
29843-2-0612 Page 29
FINISHING THE WALL
5/8” (15.8mm)MINIMUM
FROM BOTTOM OF UNIT
TO TOP OF HEARTH
EXTENSION MATERIAL
55-1/2” x 13-1/2”
NON-COMBUSTIBLE BOARD
1/8” (3mm) MINIMUM FROM SIDE OF UNIT
TO COMBUSTIBLE MATERIAL
24-1/4”
(616mm)
51”
(129.5cm)
5/8” (15.8mm) MINIMUM
FROM BOTTOM OF UNIT
TO TOP OF HEARTH
EXTENSION MATERIAL
26”
(660mm)
53-3/4”
(136.5cm)
1” (25.4mm) MINIMUM
FROM FINISHING MATERIAL
TO TOP OF UNIT
3/4” (19mm) MINIMUM
FROM FINISHING MATERIAL
TO BOTTOM OF UNIT
Finishing The Wall For DF414BL DF41W Series & DF41EHPBL Decorative Front
A minimum of 5/8 in. (15.8mm) is required from the bottom of the replace to the top of the hearth extension material. A minimum of 1/8 in. (3mm) is required from the side of the unit
to combustible material.
Finishing The Wall for DF414BL, DF41W Series, & DF41EHPBL Decorative Front With Finishing Materials Greater Than 1 in. (25.4mm) Thick
For nishing materials over 1 in. (25.4mm) thick, center the unit side
to side in a 26 in. x 53-34 in. (660mm x 136.5cm) opening. The front
will t inside the nishing material.
Stop Finishing Materials 1 in. (25mm from the top of the unit. This
will allow 3/8 in. (10mm) of space for lifting the front to unhook and
remove it.
Stop Finishing Materials 3/4 in. (19mm) from the bottom of the unit.
Figure 46
Figure 44
Finishing The Wall For DF41W Series, DF41EHPBL, DF414BL Decorative Front With Finishing Materials Less Than 1 in. (25.4mm) Thick - Figure 45
Stop nishing materials at the top and bottom of the unit.
Finishing materials up to 1 in. (25.4mm) thick may come up to
the sides of the unit. The Optional Front will overlap the nishing
materials.
Figure 45
29843-2-0612Page 30
FINISHING THE WALL
55-1/2” x 13-1/2”
(141cm x 343mm)
NON-COMBUSTIBLE BOARD
HOOD
STONE STOPS
SIDE
STONE STOPS
SIDE
STONE STOPS
NON COMBUSTIBLE
BOARD
2” x 24” (5cm x 61cm)
NON COMBUSTIBLE BOARD 2” x 24” (5cm x 61cm)
NON COMBUSTIBLE BOARD
NON COMBUSTIBLE
BOARD
Finishing The Wall for DF412BL Decorative Front With Inside Fit
The inside t front allows for nishing over the face of the replace and right up to the removable front.
1. After installing the replace, install the front kit.
2. Locate the side stone stops, loosen the four front screws a few turns - do not remove them.
3. Slip the side stone stop under the four screws and tighten. Repeat for the other side.
4. Locate the steel hood stone stop. Loosen the 7 screws under the top edge of the replace - do not remove. Slip the hood stone
stop under the 7 screws and tighten while holding back tightly to the top face of the replace.
5. Secure front face of the hood stone stop to upper replace face with three screws.
6. Hang the front on the four rectangle cut-outs on the face of the replace.
7. Finish around the replace, you must use only non-combustible material to cover the steel face and non-comb board on the re-
place. All non-combustible nishing materials must stop at the side and hood stone stops. Finishing material must not go past the stone stops of the front will not t. Stop the nishing material at the bottom of the valve opening so the valve and fans are clear for
service.
Figure 47
STOP THE FINISHING MATERIAL ON TOPOF THE HOOD STONE STOPS
STOP THE FINISHING MATERIAL ON TOPOF THE SIDE STONE STOPS
29843-2-0612 Page 31
Figure 48
STOP THE FINISHING MATERIAL FLUSH
WITH THE BOTTOM OF THE VALVE OPENING
DVTL LOG PLACEMENT
RIGHT REAR LOG
RIGHT
BRANCH
CENTER
BRANCH
RIGHT TWIG
CENTER TWIG
LEFT TWIG
LEFT
BRANCH
LEFT REAR LOG
Before you begin: If you are installing logs into the DVTL36 Model then this replace is supplied with a set of 8 ceramic ber logs. Do
not handle these logs with your bare hands. Always wear gloves to
prevent skin irritation from ceramic bers. After handling logs, wash your hands gently with soap and water to remove any traces of ber.
The positioning of logs is critical to safe and clean operation of
this replace. Sooting and other problems may result if the logs are not properly and rmly positioned in the replace. Please refer
to Figures 49 through 51 and corresponding WARNING, when completing the following log placement steps. Place dime-sized pieces of ember across the burner surface. A single layer, is sufficient; do not over-apply.
1. Place Right Rear Log onto Rear Logshelf. The cut-out on the
log ts around the pilot shield.
2. Place Left Rear Log onto the Rear Logshelf.
3. Place the Left Branch on the peg on the Left Rear Log. Angle the branch so that it rests on the grate assembly covering the screw head on the far left side.
4. Place the Right Branch on the peg on the Right Rear Log. Angle the branch so that it rests on the grate assembly covering the screw head on the far right side.
5. Place the Center Branch so that it rests on the Right Rear Log and Left Rear Log. The lower portion of the Middle Branch will rest on top of the screw head in the middle of the grate assembly.
6. Place the Left Twig on the left pin on the grate, cover the screw
head on the at portion of the grate assembly with the left twig.
7. Place the Center Twig on the middle pin on the grate, cover the
screw head on the at portion of the grate assembly with the
center twig.
8. Place the Right Twig on the right pin on the grate, cover the
screw head on the at portion of the gate assembly with the
right twig.
PLACE GLOWING EMBERS (ROCK WOOL) IN SHADED AREA ONLY. DO NOT COVER PORTS.
Figure 49
Figure 50
Figure 51
29843-2-0612Page 32
DVLL GLASS MEDIA INSTALLATION
Installation of the glass media is critical to safe and clean op-
eration of the replace.
WARNING
Failure to position the parts in accordance with the dia­grams and instructions below or failure to use only parts
specically approved for use with this heater may result in
property damage or personal injury.
DECORATIVE GLASS ACCESSORY PLACEMENT
This Linear Contemporary replace is approved for use with smooth glass media measuring as small as 1/4 inch and up to 1/2
inch in diameter. Empire Comfort Systems offers a selection of
glass media for this replace. Additional colors may be available
from your Empire dealer. Use properly sized smooth glass media
approved for gas replaces. Follow the diagrams in this manual for
placement of media and clearance to burner ports.
CAUTION
Use of gloves and eye protection is required while applying the decorative glass.
1. Remove the front and the glass frame assembly.
2. Place the long thin glass piece (glass media retainer) into the groove in front of the media tray in the firebox opening. This will keep the glass beads from falling out.
3. Place dime-sized pieces of ember across the burner surface. A single layer, is sufficient; do not over-apply.
4. Carefully open the 7.5 lbs. bag of glass beads. Distribute the glass beads evenly across the media tray, taking care not to let the glass beads fall down by the burner or the pilot. If they do, make sure they don't block the burner or pilot. There are
1/2" walls around the burner, pilot and back air slots to keep
the beads out.
5. Replace the glass frame assembly and decorative front.
MEDIA TRAY
GLASS MEDIA RETAINER
GLASS MUST NOT BE PLACED ON TOP OF OR NEXT TO BURNER. GLASS TO BE PLACED ONLY TO THE OUTSIDE OF THE FLANGED OPENING.
29843-2-0612 Page 33
BURNER
Figure 52
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition
device which automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE LIGHTING smell all around the ap-
pliance area for gas. Be sure to smell next to
the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
• do not use any phone in your building.
• Immediately call your gas supplier from
a neighbor's phone. Follow the gas sup­plier's instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.
• If you cannot reach your gas supplier, call the re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools. If the knob will not push in or turn by hand,
don't try to repair it; call a qualied service
technician. Force or attempted repair may
result in a re or explosion.
D. Do not use this appliance if any part has
been under water. Immediately call a quali­ed service technician to inspect the appli­ance and to replace any part of the control system and any gas control which has been under water.
4. Remove outer liner.
5. Turn gas control knob clockwise to "OFF."
6. Wait ten (10) minutes to clear out any gas. Then smell
for gas, including near the oor. If you smell gas,
STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting. (if applicable.)
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove front panels.
7. Turn gas control knob counterclockwise to "ON".
8. Close louver front assembly.
9. Turn on all electric power to the appliance.
10. Set thermostat to desired setting.
11. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO APPLIANCE" and call your service technician or gas supplier.
4. Turn gas control knob clockwise not force.
5. Replace front panels.
to "OFF". Do
29843-2-0612Page 34
OPERATING INSTRUCTIONS
RF VALVE OPERATION (AF-4044 Electronic Gas Valve system only)
NOTE: THE FIREPLACE WILL ONLY OPERATE WITH THE HAND HELD REMOTE TRANSMITTER. THE TRANSMITTER CONTROLS ALL FUNCTIONS OF THE FIREPLACE.
Please refer to the separate instructions for detailed operation and programming of the Multi-function Remote Control. The AF-4044 Electronic Gas Control Valve features a Remote
controlled High/Low Variable - 6 Volt DC Motor Drive. This gas
control uses a spark to pilot burner assembly. For use with Pro­pane or natural gas (pre-set at the factory).
This gas control system includes the items identied in Figure 53.
Index No. Description
1 Battery Back-up
2 AF Valve, RF
3 AF Control Module
4 AF Extension Module
5 AC Adapter
6
Not Shown Remote Control
Pilot Assembly - Nat
Pilot Assembly - LP
SPECIAL FEATURES ON THE CONTROL MODULE
The Control Module has two special pilot mode features built into the system.
CONTINUOUS PILOT FEATURE: This allows the user to change from a spark to pilot system to a standing pilot system.
1. There is a switch located on the right side of the Control
Module (#4) that reads CONTINUOUS PILOT ON/OFF. This
switch will allow the user to select the pilot mode of opera­tion.
2. When the continuous pilot switch is in the OFF position and
the appliance turned ON, the pilot will spark and light, then the
main burner will light as well. When the appliance is turned OFF, the pilot and main burner will shut OFF.
3. When the continuous pilot switch is in the ON position and the appliance is turned ON, the pilot will spark and light. Then when the appliance is turned OFF the pilot will remain ON,
but the main burner will shut OFF. Note: The Continuous pilot mode setting is generally recom­mended on Direct Vent appliances during cold climate sea-
sons to help keep the rebox warm.
1
4
3
29843-2-0612 Page 35
6
2
5
Figure 53
OPERATING INSTRUCTIONS
REMOTE CONTROL FEATURE: The Control Module has a built
in remote control receiver which allows the user to program the hand held remote transmitter.
1. There is a switch located on the right side of the Control Mod-
ule that reads REMOTE/OFF.
2. When the remote/off switch is in the OFF position the appli-
ance will operate from an appliance mounted rocker switch or
optional wall switch connected to the two (2) BROWN wires
on the Control Module.
3. When the remote/off switch is in the REMOTE position the
appliance will operate from the Remote Control transmitter.
The Control Module must be programmed to the Remote Control.
1. To program, located the learn button on the left side of the
Control Module Note: Press and release the learn button.
There will be a beep sound from the Control Module, then press any key on the remote transmitter. Once the internal receiver accepts the transmitter code there will be a series of
conrming beeps.
2. The remote system is ready for use. Please refer to the sepa­rate Multi-function Remote Control Instruction manual for pro­gramming and detailed operational information.
REMOTE CONTROL OPERATION
1. The MODE button toggles between ON, THERMO and OFF.
2. The FLAME MAIN button will control the level of the burner
with level 7 being the largest ame and 1 being the smallest ame.
3. The LIGHTS button will control the level of intensity of the media light on the DVLL with level 6 being the brightest and level 0 being off.
4. The FAN button will control the level of the fan speed after the
rst 12 minutes of operation with level 6 being the highest and
0 being off.
POWER SUPPLY SYSTEM
The Gas Control system is powered by a standard 110 volt AC through a 6.0 volt DC adaptor. The AC adaptor is connected to the
Control Module with two 1/4 in. (6.35 mm) female terminals.
This control system also includes a Battery Back-up pack that al­lows the Gas Control system only to operate in the event of a power outage.
NOTE: The Accent Light and/or Blower features will not operate
during a power outage. NOTE: All Batteries should be replaced at least once each year, preferably at the beginning of the heating season.
CAUTION: Fire or explosion hazard. Can cause property damage, sever injury or death. Do not attempt to take apart the gas control or to clean it. Improper assembly and cleaning can cause unreliable operation.
This control system also includes a Battery Back-up pack that al­lows the Gas Control system only to operate in the event of a power outage.
NOTE: The Accent Light and/or Blower features will not operate
during a power outage. NOTE: All Batteries should be replaced at least once each year, preferably at the beginning of the heating season.
CAUTION: Fire or explosion hazard. Can cause property damage, sever injury or death. Do not attempt to take apart the gas control or to clean it. Improper assembly and cleaning can cause unreliable operation.
MAINTENANCE INSTRUCTIONS
MAINTENANCE
Maintenance frequency must be determined individually for each
application. Some considerations are:
Exposure to water, dirt, chemicals and heat can damage the
gas control and shut down the control system.
Cycling frequency. Appliances that may cycle 20,000 times
annually should be checked monthly.
Intermittent use. Appliances that are used seasonally should
be checked before shutdown and again before the next use.
Dusty, wet or corrosive environment. Because these environ­ments can cause the gas control to deteriorate more rapidly, the system should be checked more often.
Any control should be replaced if it does not perform properly
on checkout or service. In addition, replace any module if it is wet or looks like it has been wet.
SERVICE
Do not disassemble the gas control; it contains non-replaceable components. Attempted disassembly or repair can damage the control. Exactly follow the warnings and the lighting instructions.
1. Before lighting, smell around the appliance area for gas. If the appliance uses LP (bottled) gas, be sure to smell next to
the oor because LP gas is heavier than air. If you smell gas,
immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank. Do not try to light any appli­ance. Do not touch any electrical switch or use the phone. Leave the building and call your gas supplier. If your gas sup-
plier cannot be reached, call the re department.
2. The gas control must be replaced if it has been ooded with water. Call a qualied service technician.
3. The gas control is a safety device. It must be replaced in case of any physical damage such as bent terminals, missing parts, stripped threads, or evidence of exposure to excessive heat.
Follow the operating instructions provided by the manufacturer of your heating appliance.
29843-2-0612Page 36
MOTOR
COMM.GLIGHTS
AUX
FAN
MAIN
PILOT
Learn
MOTOR COMM.
POWER
IPI
Continuous
Pilot
Off/On
Remote/Off
S I
ADJ.
(GND)
BLACK
ORANGE
GREEN
WHITE
BROWN
PILOT
(OPTIONAL)
ON/OFF
SWITCH
GAS CONTROL
VALVE
120V
EXTENSION
MODULE
ELECTRONIC
CONTROL MODULE
JUNCTION BOX
BATTERY
BACK-UP
ORANGE
WHITE
DVLL ONLY
MAINTENANCE INSTRUCTIONS
TROUBLESHOOTING
IMPORTANT: All service and trouble-shooting procedures should be performed by an experienced qualied service technician. If the pilot will not stay lit:
1. Conrm that the sensor wire (white) and the ignitor wire (or-
ange) are properly connected to the Control Module “S” and “I” terminals.
2. Conrm that the Spark to Pilot burner is properly grounded to
the Gas Control Valve and the Control Module.
3. Check the power source from the 6-volt power adaptor or the Battery Back-up pack connection and condition of batteries.
4. Check the position of the CONTINUOUS PILOT switch on the Control Module. If main burner does not come ON when the manual switch and remote control is turned ON: a. Conrm that the pilot sparks and lights.
b. Check the two (2) pin plastic connectors that plug into the
face of the Gas Control valve.
c. Conrm that the Gas Control valve is properly grounded
to the Control Module.
WIRING DIAGRAM
OPTIONAL GAS CONVERSION KITS
Please contact your dealer or distributor for the proper Conversion kit for these replace models. Conversion kits will include com­plete instructions, minimum rate screw, plus the pilot and main
burner orice for the gas type required. The AF-4044 Electronic
Gas Control Valve is convertible to use either natural or propane gas by simply turning a small Rotary knob located at the front of the gas valve. This rotary knob is located under a small rubber (or aluminum) cap and should only be adjusted when converting gas type.
CAUTION: The gas type has been pre-set at the factory and must not be changed unless a complete conversion is made which in­cludes changing of the gas pilot injector, air shutter settings and
main burner orice.
Note: For "RF" Fireplace models with Premium Multi-Function
Remote Control, Refer to the separate instructions for operation of the remote control system.
29843-2-0612 Page 37
Figure 54
MAINTENANCE AND SERVICE
Please Note It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
It is not unusual for your gas replace to give off some odor the rst time it is burned. This is due to the curing of the paint and any
undetected oil from the manufacturing process.
Please ensure that your room is well ventilated - open all windows.
It is recommended that you burn your replace for at least six (6) hours the rst time you use it.
IMPORTANT: Turn off gas before servicing appliance. It is
recommended that a qualied service person perform these check-
ups at the beginning of each heating season.
• Clean Burner and Control Compartment
Keep the control compartment, logs, and burner areas surrounding
the logs clean by vacuuming or brushing at least twice a year.
Cleaning Procedure
1. Turn off pilot light at control module.
2. Remove glass front. (See Glass Removal)
3. Vacuum burner compartment.
4. Reinstall glass front.
5. Ignite pilot. (See Lighting Instructions)
6. Operate the pilot burner. If it appears abnormal call a service person.
• Check Vent System
The appliance and venting system should be inspected before
initial use and at least annually by a qualied service person.
Inspect the external vent cap on a regular basis to make sure
that no debris is interfering with the air ow.
Glass Cleaning
It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass
surface. Also initial paint curing may deposit a slight lm on the glass.
It is therefore recommended that the glass be cleaned two or three times with a non-abrasive ammonia free household cleaner and
warm water (we recommend gas replace glass cleaner, contact a
local dealer for this product). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.
General Glass Information
Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass
should be done by a licensed or qualied service person.
Only glass approved for use by the manufacturer in replace may
be used for replacement. The glass replacement should be done
by a licensed or qualied service person.
WARNING:
1. The use of substitute glass will void all product warranties.
2. Care must be taken to avoid breakage of the glass.
3. Under no circumstances should this appliance be operated without the glass front or with a broken glass front. Replacement of the glass (with gasket) as supplied by the manufacturer should be
done by a qualied service person.
4. Do not abuse the glass by striking or hitting the glass.
WARNING: Do not use abrasive cleaners on glass. Do not attempt to clean glass when glass is hot.
Glass Removal and Replacement
1. Remove the front .
2. Unlatch the 4 spring clips going around the glass frame assembly. Use the included tool to make it easier.
3. Grasp the glass frame on the top and the bottom. Pull the glass
straight out to disengage the glass from the replace.
4. To replace, reverse the above steps. See Figure 55.
GLASS
CLIPS
GLASS
CLIPS
Figure 55
Reassembly and Resealing Gas Accumulation Relief System Glass Frame Assembly and Combustion Chamber
Whenever the glass frame assembly is pivoted open by a delayed ignition in the main burner, the glass frame assembly gaskets and
combustion chamber must be examined by a qualied service person
for damage. All damaged gaskets on the glass frame assembly and
combustion chamber must be replaced by a qualied service person.
If damage occurs to the combustion chamber, it must be replaced
by a qualied service person. Contact Empire Comfort Systems,
Inc. for replacement parts.
29843-2-0612Page 38
ACCESSORIES
The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond
what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois 62220-2623.
DECORATIVE ACCESSORIES
DF412BL 2" (50.8 mm) Decorative Front DF414BL 4" (101.6 mm) Decorative Front DVFS41SBL Fireplace Screen DG41C Decorative Glass Panels (DVLL Only)
DVP41LKR Liner, Black Reective (DVTL Only) FBB9 Blower Kit
OPTIONAL PORCELAIN PANELS (DVTL ONLY)
NOTE: Install liner before positioning the logs in place.
Figure 56
PLACING THE OPTIONAL PORCELAIN PANELS INTO THE DVTL41 FIREPLACE:
1. Locate the left and right side porcelain pieces.
2. Place them into the rebox, tight against the side walls and pushed back tight against the back wall.
3. Place the back porcelain piece into the back of the replace. The bend with the two screw holes is on the top.
4. Align the two screw holes on the angled bend. With the two pilot holes in the angled exhaust bafe on the roof of the replace. Drive a screw through each hole to hold the back in place. The back locks the sides in place.
5. Locate the two holes in each side porcelain piece. These will line up with two holes in the front face of the rebox. Place a screw through each hole and fasten. See Figure 56.
29843-2-0612 Page 39
OPTIONAL DECORATIVE GLASS PANELS (DVLL ONLY)
NOTE: INSTALL GLASS PANELS BEFORE INSTALLING THE GLASS MEDIA BEADS. PLACING THE OPTIONAL DECORATIVE GLASS PANELS INTO THE DVLL41 FIREPLACE:
1. Remove front glass and door. Be sure there are no glass media beads on the media tray.
2. Carefully unpack the glass pieces. Wear gloves to prevent
any accidental cuts and to prevent ngerprints on the glass.
3. Slide the large narrow glass pieces down through the small tabs and into the slots in the media tray base in back outside areas.
4. Slide the large glass panels down through the small tabs and into the slots in the media tray base in the back center area.
5. Slide three small glass pieces down through the small tabs and into the slots in the media tray base in front.
6. Install the glass media beads around the media tray to hide the small tabs that hold the glass (see DVLL Glass Medial Installation Section). The glass edges will be illuminated from the light below the media tray.
LARGE GLASS PANELS
LARGE GLASS PANELS
SMALL GLASS PANELS
Figure 57
29843-2-0612Page 40
MASTER PARTS DISTRIBUTOR LIST
To Order Parts Under Warranty, please contact your local Empire dealer. See the dealer locator at www.empirecomfort. com. To provide warranty service, your dealer will need your name and address, purchase date and serial number, and the nature of the problem with the unit. To Order Parts After the Warranty Period, please contact your dealer or one of the Master Parts Distributors listed below. This list changes from time to time. For the current list, please click on the Master Parts button at www.empirecomfort.com.
Please note: Master Parts Distributors are independent businesses that stock the most commonly ordered Original
Equipment repair parts for Heaters, Grills, and Fireplaces manufactured by Empire Comfort Systems Inc.
Dey Distributing
1401 Willow Lake Boulevard
Vadnais Heights, MN 55101
Phone: 651-490-9191 Toll Free: 800-397-1339 Website: www.deydistributing.com Parts: Heater, Hearth and Grills
East Coast Energy Products
10 East Route 36
West Long Branch, NJ 07764
Phone: 732-870-8809 Toll Free: 800-755-8809 Fax: 732-870-8811 Website: www.eastcoastenergy.com Parts: Heater, Hearth and Grills
Victor Division of F. W. Webb Company
200 Locust Street Hartford, CT 06114
Phone: 860-722-2433 Toll Free: 800-243-9360 Fax: 860-293-0479 Toll Free Fax: 800-274-2004 Websites: www.fwwebb.com & www.victormfg.com Parts: Heater, Hearth and Grills
HOW TO ORDER REPAIR PARTS
Parts Not Under Warranty
Parts can be ordered through your Service Person, Dealer, or a Master Parts Distributor. See this page for the Master Parts Distribu­tors list. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the
service person/dealer.
Warranty Parts
Warranty parts will need a proof of purchase and can be ordered by your Service Person or Dealer. Proof of purchase is required for warranty parts.
All parts listed in the Parts List have a Part Number. When ordering parts, rst obtain the Model Number and Serial Number from the name plate on your equipment. Then determine the Part Number (not the Index Number) and the Description of each part from the fol-
lowing illustration and part list. Be sure to give all this information . . .
Appliance Model Number Part Description
Appliance Serial Number Part Number
Type of Gas (Propane or Natural)
Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.
Shipments contingent upon strikes, res and all causes beyond our control.
29843-2-0612 Page 41
DVLL PARTS LIST
Index
No.
1 28452 Standoff Support
2 28454 Standoff Support
3 28453 Upper Standoff (Qty. 2)
4 28482 Porcelain Firebox Liner - Left
5 28481 Porcelain Firebox Liner - Back
6 28483 Porcelain Firebox Liner - Right
7 28465 Support Bracket (Qty. 2)
8 28428 Vertical Vent Bafe (Qty. 2)
9 28497 Pilot Shield
10 R3492 Three-prong receptacle (Qty. 2)
11 R3490 Junction Box
12 28466 Junction Box Heat Shield
13 28414 Burner Base Assembly
14 28413 Burner Assembly
15 28445 Media Tray
16 28412 Glass Frame Assembly
17 28441 Valve Cover
18 R11260 Glass Media Retainer
19 28450 Nailing Tab (Qty. 4)
21 28451 Rear Standoff (Qty. 4)
22 R10923 Non-combustible Board
23 R10499 5-PIN Wire Harness
24 R10417 Control Module
25 R10920 Valve
26 R10419 7.5V AC Adaptor
27 R10418 Battery Back-up
28 R10416 120V Extension Module
29 R10497 Extension Harness
30 R10498 8-PIN Wire Harness
N/S 28431 Flue Bafe
N/S P209 Orice, Nat
N/S P210 Orice, LP
N/S R10928 Bulb, Halogen
N/S R10924 Lens
N/S R10925 Glass Media
N/S R10423 Pilot, Nat
N/S R10424 Pilot, LP
N/S R11393 Minimum Rate Screw, Nat
N/S R10428 Minimum Rate Screw, LP
N/S R11006 Remote Control
N/S 16458 Bottom Standoff (Qty. 3)
N/S 28499 Extension Module Plate
N/S 30674 Heat Shield - Left
N/S 30675 Heat Shield - Right
Part
Number
Description
N/S = Not Shown
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
29843-2-0612Page 42
DVLL EXPLODED VIEW
22
20
26
21
25
27
19
24
28
23
30
29
3
1
3
2
15
14
19
8
7
4
9
16
11
5
19
13
7
12
10
18
6
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
29843-2-0612 Page 43
17
DVTL PARTS LIST
Index
No.
1 28452 Top Standoff Support
2 28454 Top Standoff Support
3 28453 Top Standoff (Qty. 2)
5 28498 Pilot Shield
6 R3492 Three-prong receptacle (Qty. 2)
7 R3490 Junction Box
8 28499 Extension Module Mount Plate
9 28466 Junction Box Heat Shield
10 28414 Burner Base Assembly
11 28444 Support Brackets (Qty. 2)
12 28445 Media Tray
13 28443 Wind Bafe
14 28413 Burner Assembly
15 28415 Grate Assembly
16 28412 Glass Frame Assembly
17 28441 Valve Cover
18 28450 Nailing Tab (Qty. 4)
19 28428 Vertical Vent Bafe (Qty. 2)
20 28451 Rear Standoff (Qty. 4)
21 R10923 Non-combustible Board
22 R10499 5-PIN Wire Harness
23 R10417 Control Module
24 R10920 Valve
25 R10419 7.5V AC Adaptor
26 R10418 Battery Back-up
27 R10416 120V Extension Module
28 R10497 Extension Harness
29 R10498 8-PIN Wire Harness
30 29750 Log, Left Rear
31 29751 Log, Right Rear
32 29752 Log, Left Branch
33 29753 Log, Center Branch
34 29754 Log, Right Branch
35 29755 Log, Left Twig
36 29756 Log, Center Twig
37 29757 Log, Right Twig
Part
Number
Description
Index
No.
N/S 28431 Flue Bafe
N/S P296 Orice, Nat
N/S P210 Orice, LP
N/S 29749 Log Set
N/S R10423 Pilot, Nat
N/S R10424 Pilot, LP
N/S R11393 Minimum Rate Screw, Nat
N/S R10428 Minimum Rate Screw, LP
N/S R11006 Remote Control
N/S 16458 Bottom Standoff (Qty. 3)
N/S 30674 Heat Shield - Left
N/S 30675 Heat Shield - Right
N/S - Not Shown
Part
Number
Description
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
29843-2-0612Page 44
DVTL EXPLODED VIEW
1
2
3
3
5
6
7
8
10
20
4
18
18
21
15
14
13
12
9
18
11
11
16
17
35
36
37
31
30
32
33
34
19
29
22
23
24
25
26
27
28
Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.
29843-2-0612 Page 45
JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS
WING NUTS
CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION, MAKE SURE THAT MAIN POWER SUP­PLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).
A factory installed junction box is located on the lower right side of
the replace. Wiring must be fed to the junction box and attached
to the receptacle that is provided. Leave approximately 6" of wire in the junction box for connection. Attach black wire to one side of the receptacle and white wire to opposite side of receptacle. The ground wire should be attached to the green (ground) screw.
Install the receptacle into the junction box. Attach cover plate.
POWER SUPPLY
JUNCTION BOX CONNECTIONS
110 VOLT
JUNCTION BOX
BLACK
ACCENT LAMP LIGHT REPLACEMENT - DVLL
Your Luxury Direct Vent Gas Fireplace (DVLL ONLY) comes equipped with our "Accent Lamp." The light has been pre-wired and is controlled from the remote.
If in the event the lamp or lens needs to be replaced, follow the
instructions below:
1. Unplug the remote from the junction box or disconnect all
power to the replace.
2. Remove the decorative front access panel.
3. Remove the valve cover to access the area underneath the
rebox.
4. Remove the wing nuts on each side of the light socket. Lower the socket straight down.
5. Wearing gloves, pull the light bulb out of the socket. Replace the light bulb with a new one of the exact type, making sure the white gasket is in place around the bulb.
IMPORTANT: Do not handle the lamp (bulb) with bare
ngers, protect with clean dry cloth.
6. Raise the socket and bulb straight up onto the bolts and tighten
the wing nuts. DO NOT OVER-TIGHTEN.
NOTE: The lamp will pull straight out of the socket. Replace with 35 Watt/120 Volt Halogen bulb.
When re-installing, ensure integrity of gasket seal.
Light bulb specs if purchased at a hardware store:
· 120V, 35W
· Halogen, GY6.35
· Base, T3 Shape
Replacement Parts Number:
· Bulb R10928
· Red colored light lter R10924
Figure 58
GROUNDWHITE
UNIT SHOWN FROM THE BOTTOM WITH THE BASE REMOVED FOR CLARITY.
Figure 59
29843-2-0612Page 46
21-1/2”
()546mm
MINIMUM
2”
()51mm
EMPIRE
EMPIRE
Comfort Systems
20”
(508)
19”(482)
18”(457)
20 ½” (521)
17”(431)
19 ½” (495)
16”(406)
18 ½” (469)
15”(381)
17 ½” (444)
14”(356)
16 ½” (419)
13”(330)
15 ½” (394)
14 ½” (368)
21 1/2” (546)
13 ½”
(343)
Empire Comfort Systems
918 Freeburg Avenue Belleville, Illinois 62220-2623
GAS-FIRED
CLEARANCES TO COMBUSTIBLES
12”
(305)
IMPORTANT NOTE: NO COMBUSTIBLES MAYBE PLACED IN THE AREA BETWEEN THE TOPOF THE FIREPLACE AND THE MANTEL
Web Site www.empirecomfort.com
Direct Vent Zero Clearance
Gas Fireplace Heater
INTERMITTENT PILOT:
MODERN - DVLLFP92(N,P)-1
TRADITIONAL - DVTL41FP90(N,P)-1
IN THIS AREA
HEADER RECOMMENDATION: USE DOUBLE HEADER OR PLACE HEADER VERTICALLY
SEE MANTEL
CHART FOR MAXIMUM MANTEL DEPTH AND HEIGHT
STANDOFF 12” (305mm) HEIGHT ABOUT TOP OF FIREPLACE
57-7/16”
(145.0cm)
Note: Some fronts may require more
clearance
29843-2-0612 Page 47
NON-COMBUSTIBLE FINISHED WALL FIRST 13-1/2” (343mm)
Clearance to Combustibles Back 1-1/2 in. (38 mm) Side 1-1/2 in. (38 mm) Floor 0 in. (0 mm) Top Stand-off 12 in. (305 mm) Top Framing Edge 12 in. (305 mm) Minimum Height
Floor To Ceiling
1-1/4” (32mm)
96 in. (243.9 cm)
Empire Comfort Systems
F
I
◄►
C
D
E
K
12” (305mm)
EMPIRE
EMPIRE
Comfort Systems
918 Freeburg Avenue Belleville, Illinois 62220-2623
GAS-FIRED
Web Site www.empirecomfort.com
Direct Vent Zero Clearance
Gas Fireplace Heater
INTERMITTENT PILOT:
MODERN - DVLLFP92(N,P)-1
TRADITIONAL - DVTL41FP90(N,P)-1
J
TOP VIEW
FRONT VIEW
FIREBOX DIMENSIONS
G
▼ ▲
H
A
LEFT SIDE VIEW
RIGHT SIDE VIEW
DIMENSIONS
in inches (metric)
DVLL(DVTL)
A
B
C
D
E
F
G
H
I
J
K
51-1/16
(129.7cm)
44-1/2
(113.0cm)
16-1/2
(419mm )
36-5/8
(930mm)
24-5/8
(625mm)
15-13/16
(402mm)
6-9/16
(167mm)
9-1/4
(235mm)
23-7/8
(606mm)
1-9/16
(40mm)
1-1/4
(32mm)
FRAMING DIMENSIONS
A 36-7/8 in. (937mm)
A
C
B
B 54-1/2 in. (138.4cm)
C 17-1/16 in. (433mm)
DVLL/DVTL
29843-2-0612Page 48
WARRANTY
Empire Comfort Systems Inc. warranties this hearth product to be free from defects at the time of purchase and for the
periods specied below. Hearth products must be installed by a qualied technician and must be maintained and oper­ated safely, in accordance with the instructions in the owner’s manual. Empire will not warranty any Château, Boulevard, or Mantis replace that is not installed by the selling dealer or that dealer’s direct contract agents. This warranty applies
to the original purchaser only and is not transferable.
All warranty repairs must be accomplished by a qualied gas appliance technician.
Limited Lifetime Parts Warranty – Combustion Chamber, Heat Exchanger, and Factory-Installed Glass
If the combustion chamber, heat exchanger (see parts list) or factory-installed glass fails because of defective
workmanship or material, Empire will repair or replace at Empire’s option.
Limited Three-Year Parts Warranty – All Other Components (Except Remote Controls, Thermostats, Accessories and Replacement Parts)
Should any part fail because of defective workmanship or material within three years from the date of purchase,
Empire will repair or replace at Empire’s option..
Limited One-Year Parts Warranty – Remote Controls, Thermostats, Accessories, and Parts
Should any remote control, thermostat, accessory, or other part fail because of defective workmanship within one
year from the date of purchase, Empire will repair or replace at Empire’s option.
Duties Of The Owner
The appliance must be installed by a qualied installer and operated in accordance with the instructions furnished
with the appliance. A bill of sale, cancelled check, or payment record should be kept to verify purchase date and establish warranty period. Ready access to the appliance for service.
What Is Not Covered
Damages that might result from the use, misuse, or improper installation of this appliance. Travel, diagnostic costs and freight charges on warranted parts to and from the factory. Claims that do not involve defective workmanship or materials. Unauthorized service or parts replacements. Removal and reinstallation cost. Inoperable due to improper or lack of maintenance.
How To Get Service
To make a claim under this warranty, please have your receipt available and contact your installing dealer. Pro­vide the dealer with the model number, serial number, type of gas, and purchase verication. The installing dealer is re­sponsible for providing service and will contact the factory to initiate any warranted parts replacements. Empire will make replacement parts available at the factory. Shipping expenses are not covered.
If, after contacting your Empire dealer, service received has not been satisfactory, contact: Consumer Relations
Department, Empire Comfort Systems Inc., PO Box 529, Belleville, Illinois 62222, or send an e-mail to info@empirecom­fort.com with “Consumer Relations” in the subject line.
Your Rights Under State Law
This warranty gives you specic legal rights, and you may also have other rights, which vary from state to state.
29843-2-0612 Page 49
APPLIANCE SERVICE HISTORY
Date Dealer Name Service Technician Name Service Performed/Notes
29843-2-0612Page 50
APPLIANCE SERVICE HISTORY
Date Dealer Name Service Technician Name Service Performed/Notes
29843-2-0612 Page 51
Empire Comfort Systems Inc. 918 Freeburg Ave. Belleville, IL 62220
EMPIRE
EMPIRE
Comfort Systems
If you have a general question about our products, please e-mail us at info@empirecomfort.com. If you have a service or repair question, please contact your dealer.
www.empirecomfort.com
29843-2-0612Page 52
Loading...