Bosch Security Systems DCNWDU, DCNWAP User Manual

DCN Wireless | Installation and User Instructions | System Design and Planning en | 30
8 Device set-up
8.1 General
Caution
Do not put objects on top of devices. Objects can fall through the airflow holes. A blockage of the airflow holes can cause a risk of fire.
Caution
Do not put the devices near or above a radiator, heat grill or in direct sunlight.
Caution
Do not cause vibration of the devices.
Make sure that the area is clean.
Make sure that the air is sufficiently cool.
Make sure that there is sufficient lighting.
8.4 Ventilation
Keep a good airflow. Airflow holes are in the front, right and left sides of all 19-inch devices (for example, the central control unit and the audio expander).
Put the devices on a hard and level surface.
Put the central control unit at minimum distance of
0.10 m from walls to let sufficient air flow.
8.5 Cleaning
Caution
Do not use alcohol, ammonia or petroleum solvents or abrasive cleaners to clean the devices.
1 Disconnect the mains power supply from the
devices, if you want to clean the devices.
2 Use a soft cloth that is not fully moist with a weak
soap and water solution.
3 Let the device fully dry before you operate the
device again.
8.6 Storage
8.2 Cables
8.3 Temperature
When devices are in a 19-inch rack, make sure there is rack space between the devices to let sufficient air flow. Forced airflow may be necessary to keep the temperature of the devices below the maximum temperature (refer to section 9.2). This extends the lifetime of the devices.
Note
If the central control unit is stopped or disconnected from the mains power supply for more than 100 days, the values of all system parameter are erased. This includes all the values of the parameters of the interpreter desks and the wireless access point. This does not include the subscription list.
1 Disconnect the mains power supply from the
devices, if you do not use the devices for a long time.
2 Keep the devices in a clean and dry area with a
sufficient airflow.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 31
8.7 Acoustic feedback
Acoustic feedback (‘howling’) occurs when the sound of the loudspeakers or headphones in the system is sent to the system again by activated microphones.
table 8.1: Acoustic feedback
Source Quick solution Structural solution
The acoustic feedback is caused by the loudspeakers of the contribution devices.
Decrease the volume level of the system. For example, with the knob on the front of the central control unit (refer to section 10.6.3).
Do as follows: 1 Install a feedback suppressor
between audio input 2 and audio output 2 of the central control unit.
2 Set the audio routing mode of
the system to Insertion (refer to section 12.6).
The acoustic feedback is caused by an external public address system that is connected to the DCN Wireless digital congress network.
The acoustic feedback is caused by the headphones that are connected to the contribution devices.
Decrease the volume level of the public address system or the DCN Wireless digital congress network.
Tell the chairmen and the delegates to decrease the volume level of their headphones with their contribution devices.
Install a feedback suppressor between audio output 1 and the input of the external public address system.
Install and configure the headphones level reduction of the contribution devices. (Refer to the section about the contribution devices.)
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 32
9 Technical data
9.1 System electrical and electro-acoustic characteristics
9.1.1 General
table 9.1: Electro-acoustic characteristics
Nominal input level:
85 dB SPL
Overload input level:
110 d B S P L
Automatic gain reduction (not for PA-floor output):
24 dB (interpretation channels)
12 dB (delegate loudspeaker channel)
Automatic gain reduction with:
3 dB (2 microphones on)
6 dB (4 or more microphones on)
Loudspeaker gain control:
24 x 1 dB and off (mute)
9.1.2 Transmission links
From delegate microphone to interpreter headphones
From delegate microphone to delegate headphones
From interpreter microphone to delegate headphones
From interpreter microphone to interpreter headphones
From auxiliary input to delegate headphones
From auxiliary input to interpreter headphones
From delegate microphone to auxiliary output
From interpreter microphone to auxiliary output
table 9.2: Transmission links
Frequency response:
125 Hz to 20 kHz (General)
125 Hz to 3.5 kHz (Intercom links)
Harmonic distortion:
< 0.5%
Harmonic distortion @ overload:
< 1%
Crosstalk attenuation @ 4 kHz:
> 80 dB
Dynamic range:
> 90 dB
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 33
9.1.3 Combined devices from input to output
Delegate microphone with transmission link to interpreter headphones
Delegate microphone with transmission link to delegate headphones
Delegate microphone with transmission link to auxiliary output
Interpreter microphone with transmission link to interpreter headphones
Interpreter microphone with transmission link to delegate headphones
Interpreter microphone with transmission link to auxiliary output
table 9.3: Combined devices from input to output
Typical frequency response:
125 Hz to 20 kHz
Front-to-random sensitivity index:
> 4.6 dB
Rated equivalent sound pressure level due to inherent noise:
< 25 dB(A)
Total harmonic distortion @ overload:
< 1%
Crosstalk attenuation:
> 80 dB
9.2 Environmental conditions
table 9.4: Environmental conditions
Working conditions:
Fixed, stationary, transportable
Temperature range:
-20 to +70 °C (transport)
+5 to +45 °C (operation)
For EPS and contribution devices with an LCD, the maximum temperature is +40 °C.
Relative humidity:
< 95%
9.3 Safety
According Low Voltage Directive 73/23/EEC amended by Directive 93/68 EEC.
For European countries: according EN60065. Marking: CE
For international countries: IEC 60065 according CB-Scheme.
For North America:
USA: ANSI/UL 60065
Canada: CAN/CSA no. 60065
Marking c-CSA-us.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 34
9.4 Electro-magnetic compatibility
table 9.5: Electromagnetic compatibility
EMC compatibility:
According ECM Directive 89/336/EEC amended by Directive 93/68/ECC European approvals: CE marking EMC environment: for commercial or professional use
EMC emission:
According harmonized standard EN 55103-1 (E3) (prof. audio/video equipment) According FCC rules (FCC part 15) complying to limits for class A digital devices
EMC immunity:
According harmonized standard EN 55103-2 (E3) (prof. audio/video equipment)
9.5 Wireless devices
table 9.6: Wireless devices
Frequency
2400 - 2483.5 MHz
Max. transmitting power:
100 mW e.i.r.p.
Bandwidth:
22 MHz
Leading listed and certified country approvals:
Europe CE
Standard Telecom
EMC
Safety
USA Standard Telecom, EMC
Safety
Canada Standard Telecom, EMC
Safety
Japan Standard Telecom, EMC Ordinance regulating
EN 300 328 EN 301 489-1 EN 301 489-17 EN 60950-1 FCC part 15.247 ANSI / UL 60950-1 RSS 210 CSA 22.2 no. 60950-1
radio equipment: Item 19 Article 2
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 35
9.6 Miscellaneous
table 9.7: Miscellaneous
Basic standard ESD:
According EN 61000-4-2. Contact discharge: 4 kV and air discharge: 8 kV
Basic standard mains harmonics and voltage fluctuations, flicker:
According EN 61000-3-2 and EN 61000-3-3
Basic standard RF electromagnetic fields:
According EN 61000-4-3 RF conducted: 150 kHz - 80 MHz: 3 Vrms RF radiated 80 - 1000 MHz: 3 V/m Cellular telephone (GSM) dummy test: at 20 cm speech distance Criteria: not effecting normal operation.
Magnetic immunity:
Rack mounting: 50 Hz - 10 kHz: 4 - 0.4 A/m No rack mounting: 50 Hz - 10 kHz: 3 - 0.03 A/m
Basic standard low energy electrical fast transients, bursts:
According EN 61000-4-4 Mains: fast transients: 1 kV; signal and control data lines: 0.5 kV
Basic standard high energy surges:
According EN 61000-4-5 Mains: surges: 1 kV CM and 0.5 kV DM.
Basic standard voltage dips, short interruptions, variations:
According EN 61000-4-11 Mains: voltage dips 100% for 1 period, 60% for 5 periods, > 95% for 5 seconds.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planning en | 36
Intentionally left blank.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 37
Section 2 - Central Devices
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 38
10 DCN-WCCU Wireless
Central Control Unit
10.1 Introduction
The DCN-WCCU Wireless Central Control Unit controls the system. The central control unit can operate with or without a control PC.
Note
The DCN-WCCU-UL is the CSA/UL approved version of the DCN-WCCU.
10.2 Controls, connectors and indicators
10.2.1 Front view
The front of the central control unit (refer to figure 10.1) contains: 1 On/off switch - Starts and stops the central control
unit.
2 Display - Shows the configuration menu (refer to
10.6).
3 Knob - Operates the configuration menu (refer to
10.6). You can also change the volume level of the system with the knob.
4 Headphones socket - Connects headphones to
the central control unit (refer to 10.5.4).
Caution
Riskofelectricshock.
Donot open.
Avis
Riskofelectricshock.
Donot open.
Network
12
Trunk
12
8 9
figure 10.1: Front and rear views
23 41
5
RS232 Port 1
RS232
Fault
AudioIn 1 AudioOut 1 AudioIn 2 AudioOut 2
Port 2
OK Fail
6 7
Mains
230
115:100-120V 50-60Hz T2.5A250V 230:220-240V 50-60Hz
T2AH 250V
10 13 1411 12 11 12
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 39
10.2.2 Rear view
The rear of the central control unit (refer to figure 10.1) contains: 5 RS232 ports - Connects a PC, remote controllers or
video cameras to the central control unit (refer to
10.5.8).
6 Power inlet - Connects the central control unit to
the mains power supply with a power cable (refer to
10.5.1).
7 Ground screw - Connects the central control unit
to ground.
8 Optical network sockets - Connects the central
control unit to the optical network (refer to 10.5.3).
9 DCN sockets - Connect the central control unit to
the DCN (refer to 10.5.2).
10 Fault contact - Connects the central control unit to
devices to sense the condition of the central control unit (refer to 10.5.7).
11 Audio inputs - Connect the central control unit to
external analog audio sources (refer to 10.5.5).
12 Audio outputs - Connect the central control unit
to external analog audio devices (refer to 10.5.6).
13 Voltage selector - Selects the voltage on which the
central control unit must operate (refer to 10.5.1).
14 Fuse holder - Prevents damage to the internal
power supply unit of the central control unit (refer to
10.5.1).
10.3 Internal settings
10.3 .1 Ove rvie w
Warning
Before you open the central control unit, discon­nect it from the mains power supply. Electrical discharges from the mains power supply can kill you.
Caution
Before you open the central control unit, take measures to prevent electro-static discharges.
The PCBs of the central control unit (refer to figure
10.2) contain:
15 Software LEDs - Show the condition of the
software of the central control unit. When the software runs correctly, the yellow and green LEDs flash.
16 S600 switches - Reserved (refer to 10.3.2). 17 X605 jumper block - Enables or disables the
watchdog (refer to 10.3.5).
18 Reset switch - Starts the central control unit again. 19 Optical network processor indicator - Comes
on when the optical network processor operates correctly.
20 S500 switches - Configure the RS232 ports of the
central control unit (refer to 10.3.3).
21 X600 jumper block - Connects and disconnects
the internal back-up battery of the central control unit (refer to 10.3.4).
22 X104 jumper block - Connects and disconnects
the mechanical ground and the electrical ground
(refer to 10.3.6).
23 Fuse - Prevents damage to the electronic
components in the central control unit.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 40
X155
S601
T1K4K1R1
J1 F1
L1N1
M1
P1
R2
K2T2
J2 F2
L2M2
N2
P2
T3 R3
K3
J3 F3
L3
N3 M3
P3
T4
R4
J4 F4
L4
P4
N4 M4
T5
R5
P5
N5 M5
L5
J6H7F6
R6R9T6K5K6
M6P6
N6 L6
R7
T7 K7
M7P7
N7 L7
J8
T8 K8
R8
L8
P8 M8
N8
J9 G9
L9
T9 K9
P9 M9
N9
T10
K10
J10
M10
L10P10R10
N10
K11
T11
J11
R11 M11
L11P11
N11
T12
K12
J12
N12R12
L12P12
M12
T13
K13
J13
M13
R13
L13P13
N13
T14
K14
J14
P14 N14
M14
R14
L14
T15
K15
P15R15 N15 L15
M15
T16
K16
N16P16R16
L16
X600
15
B601 B602 B604
X103
X605
17 1618
S600
ON
57
2
31 864
X14
G600
X1001
E1
B1
D1
A1
H1
G1
E2
B2
A2C3D2
H2
G2
E3
D3C1A3
B3
G3
H3
E4
C4C2B4 A4
D4
G4
H4
H5G7F5
E5
C5 A5D8B5
G5J5
E6
G6
H6
B6D6
C6 A6
E7
F7
B7D7
C7 A7
E8
C8 A8
F8H8
B8
G8
E9
F9H9
C9
B9D5A9
D9
A10C10
B10
D10
E10
F10
G10
H10
D11
A11
C11
B11
E11
F11
H11
G11
D12
A12
C12
B12
E12
F12
H12
G12
B13
A13
C13
D13
E13
G13
F13
H13
B14 A14
D14
C14
E14
G14
H14
F14
D15 A15
B15C15
E15
F15
H15J15 G15
S800
B16C16D16
A16
E16
F16
H16 G16J16
X1000
ON
2
31864
S1000
57
S500
B1000
F100
19
20
figure 10.2: Internal settings
Bosch Security Systems | 2007-02 | 9922 141 70691 en
21
X104
2322
DCN Wireless | Installation and User Instructions | Central Devices en | 41
10.3.2 S600 switches
table 10.1: S600 switches (* = default)
Switch Position Description
S600-1 ON*
OFF
S600-2 ON
OFF*
S600-3 ON
OFF*
S600-4 ON
OFF*
S600-5 ON
OFF*
S600-6 ON
OFF*
S600-7 ON
OFF*
S600-8 ON
OFF*
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Enables the download of new firmware. Normal operation.
10.3.3 RS232 configuration
Use the S500 switches to configure the RS232 ports of the central control unit (refer to table 10.2 and table
10.3).
table 10.2: RS232 protocol (* = default)
Protocol Port 1 Port 2
S500-1 S500-2 S500-5 S500-6 Open interface Off Off Off Off Terminal Off On Off On Full On* Off* On Off Camera control On On On* On*
table 10.3: RS232 baudrate (* = default)
Baudrate Port 1 Port 2
S500-3 S500-4 S500-7 S500-8
9.6k Off Off Off Off
19.2k Off On Off* On*
57.6k On Off On Off
115.2k On* On* On On
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 42
10.3.4 Internal back-up battery
Use the X600 jumper block to connect and disconnect the internal back-up battery of the central control unit (refer to table 10.4).
Note
When your central control unit is new, you must energize the central control unit to charge the internal back-up battery. The internal back-up battery is fully charged after 24 hours.
table 10.4: X600 jumper block (* = default)
Jumper shunt Description
1 and 2 * Connects the internal back-up
battery. When you stop the central control unit, the memory of the central control unit is not erased.
2 and 3 Disconnects the internal
back-up battery. When you stop the central control unit, the memory of the central control unit is immediately erased. The memory of the central control unit contains:
The license code
The settings of the interpreter desks.
Note
You only have a license code when you use the system in combination with:
The PC Control Software
A remote controller
Note
The subscription list is not erased when the internal back-up battery is empty. The subscription list is stored in another location.
10.3.5 Watchdog
Use the X605 jumper to enable or disable the watchdog of the central control unit (refer to table 10.5).
table 10.5: X605 jumper block (* = default)
Jumper shunt Description
Present The watchdog is disabled. The
central control unit does not start again after an error.
Not present* Enables the watchdog. The
central control unit starts again after an error.
Note
When you disable the watchdog, the system can operate incorrectly.
10.3.6 Ground
Use the X104 jumper block to connect and disconnect the system ground and the ground of the central control unit (refer to table 10.6). For example, you can connect the system ground and the ground of the central control unit to prevent hum.
table 10.6: X104 jumper block (* = default)
Jumper shunt Description
1 and 2 Connects the system ground
and the ground of the central control unit.
2 and 3 * Disconnects the system ground
and the ground of the central control unit.
Note
When you connect the system ground to the ground of more than one device in the system, you can create ground loops. Ground loops can cause hum.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 43
10.4 Installation
Install the central control unit in a 19-inch rack system or on a flat surface. Four feet and two brackets are supplied with the central control unit (refer to figure
10.3).
figure 10.3: Installation
table 10.7: Physical characteristics
Dimensions (h x w x d), flat surface:
92 x 440 x 400 mm (without brackets, with feet)
Dimensions (h x w x d), 19-inch rack system:
88 x 483 x 400 mm (with brackets, without feet)
Weight:
6.7 kg (without brackets, without feet)
Note
When you install the central control unit in a 19-inch rack system, the central control unit extends 36 mm in front of the brackets.
10.5 External connections
10.5 .1 Power su pp ly
To connect the central control unit to a mains power supply do as follows:
Note
The DCN-WCCU is configured for a voltage of 220 - 240 V(AC). The DCN-WCCU-UL is configured for a voltage of 100 - 120 V(AC).
1 Set the voltage selector on the rear of the central
control unit to the correct position (refer to table
10.8).
table 10.8: Voltage selector
Power supply voltage Voltage selector
90 to 132 V(AC) 115 198 to 264 V(AC) 230
2 Make sure that the fuse holder in the rear of the
central control unit contains the correct fuse (refer to table 10.9).
table 10.9: Fuses
Voltage selector Fuse
115 T2.5A 250 V (UL 248) 230 T2AH 250 V (IEC 60127)
3 Connect a locally approved power cable to the
central control unit (refer to figure 10.4).
Bosch Security Systems | 2007-02 | 9922 141 70691 en
figure 10.4: Power supply
DCN Wireless | Installation and User Instructions | Central Devices en | 44
LED
4 Connect the power cable to a power supply.
Warning
Make sure that the mains power supply is grounded. Electrical discharges from the mains power supply can kill you.
10.5 .2 D CN
Connect the trunk of the DCN to the DCN sockets of the central control unit (refer to figure 10.5).
LED
figure 10.5: DCN
Each DCN socket has a red LED that comes on if there is an overload (refer to figure 10.5 and 3.5.4).
table 10.10: DCN connection
Number of connections:
2x DCN socket
Location:
Rear side
Power supply:
max. 65 W (refer to figure 2.1)
10.5.3 Optical network
Connect the trunk of the optical network to the optical network sockets of the central control unit with optical network cables (refer to figure 10.6).
figure 10.6: Optical network
Each optical network socket has a red LED that comes on if there is an overload (refer to figure 10.6 and 3.5.4).
table 10.11: Optical network connections
Number of connections:
2x proprietary sockets
Location:
Rear side
Nodes:
2
Power supply:
max. 65 W (refer to figure 3.1)
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 45
Audio In
2
3
4
1
5
10.5.4 Headphones
You can connect headphones to the headphones socket of the central control unit. The headphones must have a
3.5 mm plug (refer to figure 10.7).
2 3 1
figure 10.7: 3.5 mm headphones plug, connection
table 10.12: 3.5 mm headphones plug, connection
Number Signal
1Left 2 Common 3Right
Note
You can also connect mono headphones to the headphones socket.
10.5.5 Audio inputs
You can connect an external analog audio source to the audio inputs of the central control unit. The central control unit has two audio inputs. Each audio input has (refer to figure 10.8):
1 XLR socket for balanced signals. The electric
1 double cinch socket for unbalanced signals.
circuits behind the XLR sockets contain transformers.
Note
The audio inputs change stereo signals in mono signals.
You can select the signal that is available on the headphones socket with the configuration menu (refer to 10.6.5).
figure 10.8: Audio input, connection
table 10.13: Audio input, connection
Pin Type Signal Description
1 XLR Xternal Shield/ground 2 Live Positive 3 Return Negative 4 Cinch Live Signal in 5 Return Shield/ground
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 46
Audio Out
1
3
4
2
5
You can select the procedure that is used to send audio signals through the central control unit with the audio routing modes (refer to 10.6.8).
Note
You can only connect line level sources to the audio inputs of the central control unit. It is not possible to connect microphone sources.
table 10.14: Audio input details, line level signals
Number of connections:
1x XLR socket for each audio input
1x double cinch socket for each audio input
Location:
Rear side
Cable:
Shielded cable
Maximum level:
Refer to appendix A
Nominal level:
Refer to appendix A
Frequency response:
-3 dB @ 30 Hz and 20 kHz
Impedance:
XLR: 22 k
•Cinch: 12 k
Signal-to-noise ratio:
> 85 dBA @ max. level
CMRR:
> 60 dB @ 100 Hz > 50 dB @ 1 kHz
Crosstalk attenuation:
> 85 dB @ max. level
Distortion:
< 0.1% @ 100 Hz @ -3 dB of the max. input
10.5.6 Audio outputs
You can connect an audio recording device or a public address system to the audio outputs of the central control unit. The central control unit has two audio outputs. Each audio output has (refer to figure 10.9):
1 XLR plug for balanced signals. The electric circuits behind the XLR plugs contain transformers.
1 double cinch socket for unbalanced signals.
Note
The two cinch sockets contain the same mono signal.
figure 10.9: Audio output, connection
table 10.15: Audio output, connection
Pin Type Signal Description
1 XLR Xternal Shield/ground 2 Live Positive 3 Return Negative 4 Cinch Live Signal out 5 Return Shield/Ground
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 47
OK Fail
You can select the procedure that is used to send audio signals through the central control unit with the available audio routing modes (refer to 10.6.8).
table 10.16: Audio output details
Number of connections:
1x XLR plug for each audio output
1x double cinch socket for each audio output
Location:
Rear side
Cable:
Shielded cable
Maximum level:
Refer to appendix A
Nominal level (audio output 1):
Refer to appendix A
Nominal level (audio output 2):
Refer to appendix A
Frequency response:
-3 dB @ 30 Hz and 20 kHz
Impedance:
< 100
Signal-to-noise ratio:
> 89 dBA @ max. level
Crosstalk attenuation:
> 85 dB @ max. level
Distortion:
< 0.1% @ 100 Hz @ - 3 dB of the max. input
10.5.7 Fault contact
Use the fault contact to send the condition of the central control unit to external devices. If the central control unit operates correctly, the OK pins are internally connected. The central control unit internally connects the Fail pins when:
The central control unit is stopped.
The internal power supply unit operates incorrectly.
The central control unit does a reset.
figure 10.10: Fault contact
table 10.17: Fault contact
Number of connections:
4-pole plug
Location:
Rear side
Signal:
Potential-free change-over relay
Voltage:
Max. 24 V(DC), 15 V(AC)
Current:
Max. 500 mA
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 48
10.5.8 RS232 ports
You can connect a PC, remote controllers or video cameras to the RS232 ports of the central control unit (refer to the DCN Next Generation Installation and User Instructions). The central control unit has 2 RS232 ports (refer to figure 10.11). You can set the protocol and the baudrate of the RS232 ports with the S500 switches (refer to 10.3.3).
15
9 6
figure 10.11: RS232 port, connection
table 10.18: RS232 port, connection
Pin Definition Description
1 DCD Data Carrier Select 2 RxD Receive Data 3TxDTransmit Data 4 DTR Data Terminal Ready 5 SG Signal Ground 6 DSR Data Set Ready 7 RTS Request To Send 8 CTS Clear To Send 9RI Ring Indicator
table 10.19: RS232 ports
Number of connections:
2x 9-pole SUB-D socket
Location:
Rear side
Maximum cable length:
9600 baud: 15 m, >9600 baud: 3 m
Signal levels:
EIA RS232-C interface specifications
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 49
10.6 Configuration menu
10.6 .1 Ove rvie w
Use the configuration menu of the central control unit to configure the central control unit and the system (refer to figure 10.12).
Main
Fault status
1
2Monitoring
3Enquiry
2A
Source/ Volume
3A CCU
3Aa
3B WAP
3Ba
Serial Number
3Ab
HW Version
3Ac
FPGA Version
3Ad
Serial Number
3Bb
HW Version
3Bc
FPGA Version
3Bd
SW Version 3Ae
FW Version
SW Version
4H
Floor Distr.
4I
Intercom
4Ia
Assign Operator 4Ib
Menu item
Menu item with sub-menu
4L
4K
De-init
Wireless
4J
4Ja
Auto mic off 4Jb
Assign Chairman
4M
Defaults
Unit Name
System ID 4Jc
Repetition 4Jd
WAP
4F
4E
Routing I/O2
4D
Level
Mic. Mode
4C
Loudspkr
4B
4Ba
4A
Setup
Back
figure 10.12: Configuration menu
Bosch Security Systems | 2007-02 | 9922 141 70691 en
4
<
Wireless Mode
Bass
4Bb
Treble
4G
Mic. Priority
Att. Tones
DCN Wireless | Installation and User Instructions | Central Devices en | 50
10.6.2 Navigation and operation
10.6.2.1 Menu items
The configuration menu consists of menu items. Refer to figure 10.13 for the parts of a menu item.
Main menu
number
figure 10.13: Menu item parts
10.6.2.2 Number and characters
Identify menu items by the main menu number sub-menu character. The number identifies the main menu to which the menu item is connected. The characters identify the sub-menus to which the menu item is connected.
10.6.2.3 Menu title
Each menu item has a title. The title gives a short description of the function of the menu item.
10.6.2.4 Parameters and values
Most menu items have one or more parameters. To make adjustments, change the values of the parameters.
10.6.2.5 VU meter
Some menu items have a VU meter. The VU meter shows the volume levels of signals. The VU meter has seven rows.
Sub-menu
character
Value VU meter
Menu item
title
Parameter
10.6.2.6 To open the main menu
To open the main menu, push the knob in the Main menu item. The main menu number and the menu item title flash.
10.6.2.7 To go through the main menu
Turn the knob clockwise in the main menu to go to the next menu item in the main menu.
Turn the knob counterclockwise in the main menu to go to the previous menu item in the main menu.
10.6.2.8 To open a sub-menu
When the display shows a menu item that has three dots (...), the menu item gives access to a sub-menu. To open the sub-menu, push the knob in a menu item that has three dots. (The last sub-menu character and the menu item title flash.)
Note
To open the Setup sub-menu, you must push and hold the knob for more than 3 seconds.
10.6.2.9 To select menu items in a sub-menu
Turn the knob clockwise in a sub-menu to go to the next menu item in the sub-menu.
Turn the knob counterclockwise in a sub-menu to go to the previous menu item in the sub-menu.
10.6.2.10 To open a menu item
1 Turn the knob to select the applicable menu item. 2 When the display shows the correct menu item, push
the knob to open the menu item. The display shows a cursor.
table 10.20: VU meter
VU meter Description
One row on No signal Seven rows on Maximum signal Triangle Clipped signal Minus Muted by control input
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 51
10.6.2.11 To select a parameter
1 Open the correct menu item (refer to 10.6.2.10). 2 Turn the knob to move the cursor to the parameter
that is shown.
3 On the parameter, push the knob. The parameter
flashes. 4 Turn the knob to go to the applicable parameter. 5 When the display shows the applicable parameter,
push the knob to select the parameter. The display
shows a cursor.
10.6.2.12 To change the value of a parameter
1 Select the applicable parameter (refer to 10.6.2.11). 2 Turn the knob to move the cursor to the value. 3 Push the knob. The value flashes. 4 Turn the knob to go to the value. 5 When the display shows the correct value, push the
knob to select the value. The display shows a cursor.
10.6.2.13 To close a menu item
1 Turn the cursor to the last character that identifies
the menu item. 2 Push the knob to close the menu item. The last
character and the menu item title flash.
10.6.2.16 Example
For an example, do as follows to change the level of audio input 2 of the central control unit:
Note
Make sure that when you do this example, you start from the Main menu item.
1 Push the knob to open the main menu.
2 Turn the knob to go to 4 Setup ...
3 Push-and-hold the knob for 3 seconds to open the
sub-menu.
10.6.2.14 To close a sub-menu
1 Turn the cursor to go to the second last character
that identifies the menu item. 2 Push the knob to close the sub-menu. The last
character and the menu item title flash.
10.6.2.15 To close the main menu
1 From the main menu, turn the primary knob
clockwise to go to the < Back menu item. 2From the < Back menu item, push the knob to go to
the Main menu item.
4 Turn the knob to go to 4D Level.
5 Push the knob to open the menu item.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 52
6 Turn the knob to move the cursor to the parameter
that is shown.
7 On the parameter, push the knob.
8 Turn the knob to go to Output 2.
9 Push the knob to select Output 2.
12 Turn the knob to change the value.
Note
In this example, the knob is turned counterclockwise to decrease the value from 0 dB to -18 dB. Turn the knob clockwise to increase the value.
13 Push the knob to select the value.
14 Turn the knob to go to the main menu number.
10 Turn the knob to move the cursor to the value that is
shown.
Note
In this example, the value is 0 dB. It is possible that your display shows a different value.
11 On the value, push the knob.
15 Push the knob to go back to the main menu.
16 Turn the knob clockwise to go to the < Back menu
item.
17 Push the button to go to the Main menu item.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 53
10.6 .3 M ai n
When you start the central control unit, the display first shows Starting. The display then shows the Main menu item:
The Main menu item contains:
An indicator that shows the volume level of the
loudspeakers of the contribution devices. Turn the
knob to change the volume level (refer to 12.6).
The name of the central control unit. The default
name is CCU. You can change the name with the
4L Unit Name menu item (refer to 10.6.8).
The microphone mode and the maximum number
of activated microphones. You can change the
microphone mode and the maximum number of
activated microphones with the 4C Mic. Mode menu
item (refer to 10.6.8).
Note
When a PC is connected to the central control unit, the Main menu item also shows PC.
10.6.4 Fault status
Use the 1 Fault Status menu item to see the condition messages of the central control unit. If there is more than one message, the display shows the most important message (refer to table 10.21).
table 10.21: Messages (low to high importance)
Messages Description
No Fault The central control unit
operates correctly.
Low Battery The battery pack of a
wireless device is empty within 1 hour.
Bad Signal A wireless device has a
bad signal reception.
Incompatible SW The wireless access
point has a incompatible software version.
Invalid Software The central control unit
cannot start. The central control unit does not contain the correct software.
Downloading The central control unit
downloads software.
Note
When the condition of the central control unit changes, the Main menu item shows a message (refer to table 10.21). Such a message goes out of view when you push the knob.
Note
If you do not turn or push the knob for three minutes, the display automatically goes back to the Main menu item. The display does not automatically go back to the Main menu item from these menu items and their sub-menus:
•2ASource/Volume
4Ia Assign Operator
4Ib Assign Chairman
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 54
10.6.5 Monitoring
Use the 2 Monitoring menu item to open the Monitoring sub-menu (refer to table 10.22).
table 10.22: Monitoring sub-menu (* = default)
Menu item Parameter Value Description
2A Source/Volume Signal:
Floor Input 1 Input 2 Output 1 Output 2
Vol u m e level:
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
The signal that is available on the headphones socket of the central control unit and its volume level.
10.6.6 DCN-WCCU Enquiry
Use the 3A CCU menu item to open the CCU sub-menu. The menu items in this sub-menu give general data about the central control unit (refer to table
10.23).
Note
This data must be mentioned in all service requests and failure reports.
table 10.23: DCN-WCCU Enquiry sub-menu (* = default)
Menu item Parameter Value (read-only) Description
3Aa Serial Number --- e.g. 20.0.00362 The hexadecimal serial
number of the central control unit.
3Ab HW Version --- e.g. 3.0 The version number of the
hardware of the central control unit.
3Ac FPGA Version --- e.g. 1.06 The version number of the
FPGA firmware of the central control unit.
3Ad SW Version --- MM.mm.bbbb
e.g. 2.20.1234
3Ae FW Version --- e.g. 4.00.1234 The version number of the
The version number of the software of the central control unit.
MM: Major release no.
mm: Minor release no.
bbbb: build no.
firmware of the central control unit.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 55
10.6.7 DCN-WAP Enquiry
Use the 3B WAP menu item to open the WAP sub-menu. The menu items in this sub-menu give general data about the wireless access point (refer to table 10.23).
Note
This data must be mentioned in all service requests and failure reports.
table 10.24: DCN-WAP Enquiry sub-menu (* = default)
Menu item Parameter Value (read-only) Description
3BA WAP Serial Number --- e.g. 1E.0.00001 The hexadecimal serial
number of the wireless access point.
3Bb WAP HW Version --- e.g. 01.00 The version number of the
hardware of the wireless access point.
3Bc WAP FPGA Version --- e.g. 01.00 The version number of the
FPGA firmware of the wireless access point.
3Bd WAP SW Version --- MM.mm.bbbb
e.g. 2.20.0055
The version number of the software of the wireless access point.
MM: Major release no.
mm: Minor release no.
bbbb: build no.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 56
10.6 .8 S etup
Use the 4 Setup menu item to open the Setup sub-menu. You can use the menu items in this sub-menu to configure the central control unit and the system (refer to table 10.25 and table 10.26).
table 10.25: Setup sub-menu (* = default)
Menu item Parameter Value Description
4A Wireless Mode --- On*
Sleep Off Subscription
4B Loudspkr --- --- Gives access to the
4C Mic. Mode Mode:
Open* Override PTT
4D Level Signal:
Input 1 Input 2 Output 1 Output 2
4E Routing I/O 2 --- Mode:
4F Att. Tones Event:
Priority Voting
4G Mic. Priority --- Temporarily off*
NOM:
1, 2*, 3 1, 2*, 3 1, 2*, 3
Level:
-6 to 6 dB (0 dB*)
-6 to 6 dB (0 dB*)
-24 to 6 dB (0 dB*)
-24 to 6 dB (0 dB*)
Recorder* Equalized PA Mix-minus Insertion
Chime:
Off, 1*, 2, 3 Off*, 1, 2, 3
Permanently off
Sets the mode of the wireless network (refer to
12. 3) .
Loudspkr sub-menu (refer to 10. 6. 9) . The microphone mode of the DCN and the maximum number of activated delegate microphones (refer to
12. 4) . The nominal levels of the audio inputs and the audio outputs of the central control unit.
The audio routing mode of the central control unit (refer to 12.6).
The attention chimes of the system (refer to 12.7).
The action taken by the system when the chairman releases the priority button (refer to
12. 8) .
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devices en | 57
table 10.26: Setup sub-menu (* = default)
Menu item Parameter Value Description
4H Floor Distr. --- On*, Off Enables or disables floor
distribution (refer to 12.9).
4I Intercom ... --- --- Gives access to the
Intercom sub-menu (refer to 10.6.10).
4J Wireless --- --- Gives access to the
Wireless sub-menu (refer to 10.6.11). When the wireless access point is not connected, the central control unit shows Not Available.
4K De-Init ... --- --- Gives access to the
De-initialization menu item (refer to 10. 6.12) .
4L Unit Name --- Name:
CCU* Custom name
4M Defaults ... --- --- Gives access to the Reset
The name of the central control unit (max. 16 characters).
menu item (refer to
10. 6.13)
10.6 .9 L ou ds pk r
Use the menu items in the 4B Loudspkr sub-menu to set the levels of the bass and treble output to the loudspeakers of the contribution devices (refer to table
10.27).
table 10.27: Loudspkr sub-menu (* = default)
Menu item Parameter Value Description
4Ba Bass --- -12 to 12 dB (0 dB*) The level of the bass
output.
4Bb Treble --- -12 to 12 dB (0 dB*) The level of the treble
output.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
Loading...
+ 63 hidden pages