DCN Wireless | Installation and User Instructions | System Design and Planningen | 30
8Device set-up
8.1 General
Caution
Do not put objects on top of devices. Objects
can fall through the airflow holes. A blockage of
the airflow holes can cause a risk of fire.
Caution
Do not put the devices near or above a radiator,
heat grill or in direct sunlight.
Caution
Do not cause vibration of the devices.
•Make sure that the area is clean.
•Make sure that the air is sufficiently cool.
•Make sure that there is sufficient lighting.
8.4 Ventilation
Keep a good airflow. Airflow holes are in the front, right
and left sides of all 19-inch devices (for example, the
central control unit and the audio expander).
•Put the devices on a hard and level surface.
•Put the central control unit at minimum distance of
0.10 m from walls to let sufficient air flow.
8.5 Cleaning
Caution
Do not use alcohol, ammonia or petroleum
solvents or abrasive cleaners to clean the
devices.
1 Disconnect the mains power supply from the
devices, if you want to clean the devices.
2 Use a soft cloth that is not fully moist with a weak
soap and water solution.
3 Let the device fully dry before you operate the
device again.
8.6 Storage
8.2 Cables
Use different cable ducts for the extension and mains
cables. Identify each cable with a label and divide
trunks to manageable geographic locations. In public
areas where people can touch or move above the
connectors and cables, use metal protection covers.
Refer to the applicable protection specification of the
protection covers.
8.3 Temperature
When devices are in a 19-inch rack, make sure there is
rack space between the devices to let sufficient air flow.
Forced airflow may be necessary to keep the
temperature of the devices below the maximum
temperature (refer to section 9.2). This extends the
lifetime of the devices.
Note
If the central control unit is stopped or
disconnected from the mains power supply for
more than 100 days, the values of all system
parameter are erased. This includes all the
values of the parameters of the interpreter desks
and the wireless access point. This does not
include the subscription list.
1 Disconnect the mains power supply from the
devices, if you do not use the devices for a long time.
2 Keep the devices in a clean and dry area with a
sufficient airflow.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planningen | 31
8.7 Acoustic feedback
Acoustic feedback (‘howling’) occurs when the sound of
the loudspeakers or headphones in the system is sent to
the system again by activated microphones.
table 8.1: Acoustic feedback
SourceQuick solutionStructural solution
The acoustic feedback is caused by
the loudspeakers of the contribution
devices.
Decrease the volume level of the
system. For example, with the knob
on the front of the central control
unit (refer to section 10.6.3).
Do as follows:
1 Install a feedback suppressor
between audio input 2 and audio
output 2 of the central control
unit.
2 Set the audio routing mode of
the system to Insertion (refer to
section 12.6).
The acoustic feedback is caused by
an external public address system
that is connected to the DCN
Wireless digital congress network.
The acoustic feedback is caused by
the headphones that are connected
to the contribution devices.
Decrease the volume level of the
public address system or the DCN
Wireless digital congress network.
Tell the chairmen and the delegates
to decrease the volume level of their
headphones with their contribution
devices.
Install a feedback suppressor
between audio output 1 and the
input of the external public address
system.
Install and configure the
headphones level reduction of the
contribution devices. (Refer to the
section about the contribution
devices.)
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planningen | 32
9Technical data
9.1 System electrical and electro-acoustic characteristics
9.1.1General
table 9.1: Electro-acoustic characteristics
Nominal input level:
85 dB SPL
Overload input level:
110 d B S P L
Automatic gain reduction (not for PA-floor output):
•24 dB (interpretation channels)
•12 dB (delegate loudspeaker channel)
Automatic gain reduction with:
•3 dB (2 microphones on)
•6 dB (4 or more microphones on)
Loudspeaker gain control:
24 x 1 dB and off (mute)
9.1.2Transmission links
•From delegate microphone to interpreter headphones
•From delegate microphone to delegate headphones
•From interpreter microphone to delegate headphones
•From interpreter microphone to interpreter headphones
•From auxiliary input to delegate headphones
•From auxiliary input to interpreter headphones
•From delegate microphone to auxiliary output
•From interpreter microphone to auxiliary output
table 9.2: Transmission links
Frequency response:
•125 Hz to 20 kHz (General)
•125 Hz to 3.5 kHz (Intercom links)
Harmonic distortion:
< 0.5%
Harmonic distortion @ overload:
< 1%
Crosstalk attenuation @ 4 kHz:
> 80 dB
Dynamic range:
> 90 dB
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planningen | 33
9.1.3Combined devices from input to output
•Delegate microphone with transmission link to interpreter headphones
•Delegate microphone with transmission link to delegate headphones
•Delegate microphone with transmission link to auxiliary output
•Interpreter microphone with transmission link to interpreter headphones
•Interpreter microphone with transmission link to delegate headphones
•Interpreter microphone with transmission link to auxiliary output
table 9.3: Combined devices from input to output
Typical frequency response:
125 Hz to 20 kHz
Front-to-random sensitivity index:
> 4.6 dB
Rated equivalent sound pressure level due to inherent noise:
< 25 dB(A)
Total harmonic distortion @ overload:
< 1%
Crosstalk attenuation:
> 80 dB
9.2 Environmental conditions
table 9.4: Environmental conditions
Working conditions:
Fixed, stationary, transportable
Temperature range:
•-20 to +70 °C (transport)
•+5 to +45 °C (operation)
•For EPS and contribution devices with an LCD, the maximum temperature is +40 °C.
Relative humidity:
< 95%
9.3 Safety
According Low Voltage Directive 73/23/EEC amended by Directive 93/68 EEC.
•For European countries: according EN60065. Marking: CE
•For international countries: IEC 60065 according CB-Scheme.
•For North America:
•USA: ANSI/UL 60065
•Canada: CAN/CSA no. 60065
•Marking c-CSA-us.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planningen | 34
9.4 Electro-magnetic compatibility
table 9.5: Electromagnetic compatibility
EMC compatibility:
According ECM Directive 89/336/EEC amended by Directive 93/68/ECC
European approvals: CE marking
EMC environment: for commercial or professional use
EMC emission:
According harmonized standard EN 55103-1 (E3) (prof. audio/video equipment)
According FCC rules (FCC part 15) complying to limits for class A digital devices
EMC immunity:
According harmonized standard EN 55103-2 (E3) (prof. audio/video equipment)
9.5 Wireless devices
table 9.6: Wireless devices
Frequency
2400 - 2483.5 MHz
Max. transmitting power:
100 mW e.i.r.p.
Bandwidth:
22 MHz
Leading listed and certified country approvals:
EuropeCE
StandardTelecom
EMC
Safety
USAStandardTelecom, EMC
Safety
CanadaStandardTelecom, EMC
Safety
JapanStandard Telecom, EMCOrdinance regulating
EN 300 328
EN 301 489-1
EN 301 489-17
EN 60950-1
FCC part 15.247
ANSI / UL 60950-1
RSS 210
CSA 22.2 no. 60950-1
radio equipment: Item 19
Article 2
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | System Design and Planningen | 35
9.6 Miscellaneous
table 9.7: Miscellaneous
Basic standard ESD:
According EN 61000-4-2.
Contact discharge: 4 kV and air discharge: 8 kV
Basic standard mains harmonics and voltage fluctuations, flicker:
According EN 61000-3-2 and EN 61000-3-3
Basic standard RF electromagnetic fields:
According EN 61000-4-3
RF conducted: 150 kHz - 80 MHz: 3 Vrms
RF radiated 80 - 1000 MHz: 3 V/m
Cellular telephone (GSM) dummy test: at 20 cm speech distance
Criteria: not effecting normal operation.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 39
10.2.2 Rear view
The rear of the central control unit (refer to figure 10.1)
contains:
5 RS232 ports - Connects a PC, remote controllers or
video cameras to the central control unit (refer to
10.5.8).
6 Power inlet - Connects the central control unit to
the mains power supply with a power cable (refer to
10.5.1).
7 Ground screw - Connects the central control unit
to ground.
8 Optical network sockets - Connects the central
control unit to the optical network (refer to 10.5.3).
9 DCN sockets - Connect the central control unit to
the DCN (refer to 10.5.2).
10 Fault contact - Connects the central control unit to
devices to sense the condition of the central control
unit (refer to 10.5.7).
11 Audio inputs - Connect the central control unit to
external analog audio sources (refer to 10.5.5).
12 Audio outputs - Connect the central control unit
to external analog audio devices (refer to 10.5.6).
13 Voltage selector - Selects the voltage on which the
central control unit must operate (refer to 10.5.1).
14 Fuse holder - Prevents damage to the internal
power supply unit of the central control unit (refer to
10.5.1).
10.3 Internal settings
10.3 .1Ove rvie w
Warning
Before you open the central control unit, disconnect it from the mains power supply. Electrical
discharges from the mains power supply can kill
you.
Caution
Before you open the central control unit, take
measures to prevent electro-static discharges.
The PCBs of the central control unit (refer to figure
10.2) contain:
15 Software LEDs - Show the condition of the
software of the central control unit. When the
software runs correctly, the yellow and green LEDs
flash.
16 S600 switches - Reserved (refer to 10.3.2).
17 X605 jumper block - Enables or disables the
watchdog (refer to 10.3.5).
18 Reset switch - Starts the central control unit again.
19 Optical network processor indicator - Comes
on when the optical network processor operates
correctly.
20 S500 switches - Configure the RS232 ports of the
central control unit (refer to 10.3.3).
21 X600 jumper block - Connects and disconnects
the internal back-up battery of the central control
unit (refer to 10.3.4).
22 X104 jumper block - Connects and disconnects
the mechanical ground and the electrical ground
(refer to 10.3.6).
23 Fuse - Prevents damage to the electronic
components in the central control unit.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 40
X155
S601
T1K4K1R1
J1 F1
L1N1
M1
P1
R2
K2T2
J2 F2
L2M2
N2
P2
T3 R3
K3
J3 F3
L3
N3 M3
P3
T4
R4
J4 F4
L4
P4
N4 M4
T5
R5
P5
N5 M5
L5
J6H7F6
R6R9T6K5K6
M6P6
N6 L6
R7
T7 K7
M7P7
N7 L7
J8
T8 K8
R8
L8
P8 M8
N8
J9 G9
L9
T9 K9
P9 M9
N9
T10
K10
J10
M10
L10P10R10
N10
K11
T11
J11
R11 M11
L11P11
N11
T12
K12
J12
N12R12
L12P12
M12
T13
K13
J13
M13
R13
L13P13
N13
T14
K14
J14
P14 N14
M14
R14
L14
T15
K15
P15R15 N15 L15
M15
T16
K16
N16P16R16
L16
X600
15
B601
B602
B604
X103
X605
17 1618
S600
ON
57
2
31864
X14
G600
X1001
E1
B1
D1
A1
H1
G1
E2
B2
A2C3D2
H2
G2
E3
D3C1A3
B3
G3
H3
E4
C4C2B4 A4
D4
G4
H4
H5G7F5
E5
C5 A5D8B5
G5J5
E6
G6
H6
B6D6
C6 A6
E7
F7
B7D7
C7 A7
E8
C8 A8
F8H8
B8
G8
E9
F9H9
C9
B9D5A9
D9
A10C10
B10
D10
E10
F10
G10
H10
D11
A11
C11
B11
E11
F11
H11
G11
D12
A12
C12
B12
E12
F12
H12
G12
B13
A13
C13
D13
E13
G13
F13
H13
B14 A14
D14
C14
E14
G14
H14
F14
D15 A15
B15C15
E15
F15
H15J15 G15
S800
B16C16D16
A16
E16
F16
H16 G16J16
X1000
ON
2
31864
S1000
57
S500
B1000
F100
19
20
figure 10.2: Internal settings
Bosch Security Systems | 2007-02 | 9922 141 70691 en
21
X104
2322
DCN Wireless | Installation and User Instructions | Central Devicesen | 41
10.3.2 S600 switches
table 10.1: S600 switches (* = default)
SwitchPositionDescription
S600-1ON*
OFF
S600-2ON
OFF*
S600-3ON
OFF*
S600-4ON
OFF*
S600-5ON
OFF*
S600-6ON
OFF*
S600-7ON
OFF*
S600-8ON
OFF*
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Reserved. Do not change the position of this switch.
Enables the download of new firmware.
Normal operation.
10.3.3 RS232 configuration
Use the S500 switches to configure the RS232 ports of
the central control unit (refer to table 10.2 and table
10.3).
table 10.2: RS232 protocol (* = default)
ProtocolPort 1Port 2
S500-1S500-2S500-5S500-6
Open interfaceOffOffOffOff
TerminalOffOnOffOn
FullOn*Off*OnOff
Camera controlOnOnOn*On*
table 10.3: RS232 baudrate (* = default)
BaudratePort 1Port 2
S500-3S500-4S500-7S500-8
9.6kOffOffOffOff
19.2kOffOnOff*On*
57.6kOnOffOnOff
115.2kOn*On*OnOn
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 42
10.3.4 Internal back-up battery
Use the X600 jumper block to connect and disconnect
the internal back-up battery of the central control unit
(refer to table 10.4).
Note
When your central control unit is new, you must
energize the central control unit to charge the
internal back-up battery. The internal back-up
battery is fully charged after 24 hours.
table 10.4: X600 jumper block (* = default)
Jumper shuntDescription
1 and 2 *Connects the internal back-up
battery. When you stop the
central control unit, the memory
of the central control unit is not
erased.
2 and 3Disconnects the internal
back-up battery. When you stop
the central control unit, the
memory of the central control
unit is immediately erased. The
memory of the central control
unit contains:
•The license code
•The settings of the
interpreter desks.
Note
You only have a license code when you use the
system in combination with:
•The PC Control Software
•A remote controller
Note
The subscription list is not erased when the
internal back-up battery is empty. The
subscription list is stored in another location.
10.3.5 Watchdog
Use the X605 jumper to enable or disable the watchdog
of the central control unit (refer to table 10.5).
table 10.5: X605 jumper block (* = default)
Jumper shuntDescription
PresentThe watchdog is disabled. The
central control unit does not
start again after an error.
Not present*Enables the watchdog. The
central control unit starts again
after an error.
Note
When you disable the watchdog, the system
can operate incorrectly.
10.3.6 Ground
Use the X104 jumper block to connect and disconnect
the system ground and the ground of the central control
unit (refer to table 10.6). For example, you can connect
the system ground and the ground of the central control
unit to prevent hum.
table 10.6: X104 jumper block (* = default)
Jumper shuntDescription
1 and 2Connects the system ground
and the ground of the central
control unit.
2 and 3 *Disconnects the system ground
and the ground of the central
control unit.
Note
When you connect the system ground to the
ground of more than one device in the system,
you can create ground loops. Ground loops can
cause hum.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 43
10.4 Installation
Install the central control unit in a 19-inch rack system
or on a flat surface. Four feet and two brackets are
supplied with the central control unit (refer to figure
10.3).
figure 10.3: Installation
table 10.7: Physical characteristics
Dimensions (h x w x d), flat surface:
92 x 440 x 400 mm (without brackets, with feet)
Dimensions (h x w x d), 19-inch rack system:
88 x 483 x 400 mm (with brackets, without feet)
Weight:
6.7 kg (without brackets, without feet)
Note
When you install the central control unit in a
19-inch rack system, the central control unit
extends 36 mm in front of the brackets.
10.5 External connections
10.5 .1Power su pp ly
To connect the central control unit to a mains power
supply do as follows:
Note
The DCN-WCCU is configured for a voltage of
220 - 240 V(AC). The DCN-WCCU-UL is
configured for a voltage of 100 - 120 V(AC).
1 Set the voltage selector on the rear of the central
control unit to the correct position (refer to table
10.8).
table 10.8: Voltage selector
Power supply voltageVoltage selector
90 to 132 V(AC)115
198 to 264 V(AC)230
2 Make sure that the fuse holder in the rear of the
central control unit contains the correct fuse (refer to
table 10.9).
table 10.9: Fuses
Voltage selector Fuse
115T2.5A 250 V (UL 248)
230T2AH 250 V (IEC 60127)
3 Connect a locally approved power cable to the
central control unit (refer to figure 10.4).
Bosch Security Systems | 2007-02 | 9922 141 70691 en
figure 10.4: Power supply
DCN Wireless | Installation and User Instructions | Central Devicesen | 44
LED
4 Connect the power cable to a power supply.
Warning
Make sure that the mains power supply is
grounded. Electrical discharges from the mains
power supply can kill you.
10.5 .2 D CN
Connect the trunk of the DCN to the DCN sockets of
the central control unit (refer to figure 10.5).
LED
figure 10.5: DCN
Each DCN socket has a red LED that comes on if there
is an overload (refer to figure 10.5 and 3.5.4).
table 10.10: DCN connection
Number of connections:
2x DCN socket
Location:
Rear side
Power supply:
max. 65 W (refer to figure 2.1)
10.5.3 Optical network
Connect the trunk of the optical network to the optical
network sockets of the central control unit with optical
network cables (refer to figure 10.6).
figure 10.6: Optical network
Each optical network socket has a red LED that comes
on if there is an overload (refer to figure 10.6 and 3.5.4).
table 10.11: Optical network connections
Number of connections:
2x proprietary sockets
Location:
Rear side
Nodes:
2
Power supply:
max. 65 W (refer to figure 3.1)
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 45
Audio In
2
3
4
1
5
10.5.4 Headphones
You can connect headphones to the headphones socket
of the central control unit. The headphones must have a
3.5 mm plug (refer to figure 10.7).
2 3 1
figure 10.7: 3.5 mm headphones plug, connection
table 10.12: 3.5 mm headphones plug, connection
NumberSignal
1Left
2Common
3Right
Note
You can also connect mono headphones to the
headphones socket.
10.5.5 Audio inputs
You can connect an external analog audio source to the
audio inputs of the central control unit. The central
control unit has two audio inputs. Each audio input has
(refer to figure 10.8):
•1 XLR socket for balanced signals. The electric
•1 double cinch socket for unbalanced signals.
circuits behind the XLR sockets contain
transformers.
Note
The audio inputs change stereo signals in mono
signals.
You can select the signal that is available on the
headphones socket with the configuration menu (refer
to 10.6.5).
figure 10.8: Audio input, connection
table 10.13: Audio input, connection
PinTypeSignalDescription
1XLRXternalShield/ground
2LivePositive
3Return Negative
4CinchLiveSignal in
5ReturnShield/ground
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 46
Audio Out
1
3
4
2
5
You can select the procedure that is used to send audio
signals through the central control unit with the audio
routing modes (refer to 10.6.8).
Note
You can only connect line level sources to the
audio inputs of the central control unit. It is not
possible to connect microphone sources.
table 10.14: Audio input details, line level signals
Number of connections:
•1x XLR socket for each audio input
•1x double cinch socket for each audio input
Location:
Rear side
Cable:
Shielded cable
Maximum level:
Refer to appendix A
Nominal level:
Refer to appendix A
Frequency response:
-3 dB @ 30 Hz and 20 kHz
Impedance:
•XLR: 22 kΩ
•Cinch: 12 kΩ
Signal-to-noise ratio:
> 85 dBA @ max. level
CMRR:
> 60 dB @ 100 Hz
> 50 dB @ 1 kHz
Crosstalk attenuation:
> 85 dB @ max. level
Distortion:
< 0.1% @ 100 Hz @ -3 dB of the max. input
10.5.6 Audio outputs
You can connect an audio recording device or a public
address system to the audio outputs of the central
control unit. The central control unit has two audio
outputs. Each audio output has (refer to figure 10.9):
•1 XLR plug for balanced signals. The electric circuits
behind the XLR plugs contain transformers.
•1 double cinch socket for unbalanced signals.
Note
The two cinch sockets contain the same mono
signal.
figure 10.9: Audio output, connection
table 10.15: Audio output, connection
PinTypeSignalDescription
1XLRXternalShield/ground
2LivePositive
3Return Negative
4CinchLiveSignal out
5ReturnShield/Ground
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 47
OK Fail
You can select the procedure that is used to send audio
signals through the central control unit with the
available audio routing modes (refer to 10.6.8).
table 10.16: Audio output details
Number of connections:
•1x XLR plug for each audio output
•1x double cinch socket for each audio output
Location:
Rear side
Cable:
Shielded cable
Maximum level:
Refer to appendix A
Nominal level (audio output 1):
Refer to appendix A
Nominal level (audio output 2):
Refer to appendix A
Frequency response:
-3 dB @ 30 Hz and 20 kHz
Impedance:
< 100 Ω
Signal-to-noise ratio:
> 89 dBA @ max. level
Crosstalk attenuation:
> 85 dB @ max. level
Distortion:
< 0.1% @ 100 Hz @ - 3 dB of the max. input
10.5.7 Fault contact
Use the fault contact to send the condition of the central
control unit to external devices. If the central control
unit operates correctly, the OK pins are internally
connected. The central control unit internally connects
the Fail pins when:
•The central control unit is stopped.
•The internal power supply unit operates incorrectly.
•The central control unit does a reset.
figure 10.10: Fault contact
table 10.17: Fault contact
Number of connections:
4-pole plug
Location:
Rear side
Signal:
Potential-free change-over relay
Voltage:
Max. 24 V(DC), 15 V(AC)
Current:
Max. 500 mA
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 48
10.5.8 RS232 ports
You can connect a PC, remote controllers or video
cameras to the RS232 ports of the central control unit
(refer to the DCN Next Generation Installation and
User Instructions). The central control unit has 2 RS232
ports (refer to figure 10.11). You can set the protocol
and the baudrate of the RS232 ports with the S500
switches (refer to 10.3.3).
15
9 6
figure 10.11: RS232 port, connection
table 10.18: RS232 port, connection
PinDefinitionDescription
1DCDData Carrier Select
2RxDReceive Data
3TxDTransmit Data
4DTRData Terminal Ready
5SGSignal Ground
6DSRData Set Ready
7RTSRequest To Send
8CTSClear To Send
9RI Ring Indicator
table 10.19: RS232 ports
Number of connections:
2x 9-pole SUB-D socket
Location:
Rear side
Maximum cable length:
9600 baud: 15 m, >9600 baud: 3 m
Signal levels:
EIA RS232-C interface specifications
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 49
10.6 Configuration menu
10.6 .1Ove rvie w
Use the configuration menu of the central control unit to
configure the central control unit and the system (refer
to figure 10.12).
Main
Fault status
1
2Monitoring
3Enquiry
2A
Source/
Volume
3A CCU
3Aa
3B WAP
3Ba
Serial Number
3Ab
HW Version
3Ac
FPGA Version
3Ad
Serial Number
3Bb
HW Version
3Bc
FPGA Version
3Bd
SW Version
3Ae
FW Version
SW Version
4H
Floor Distr.
4I
Intercom
4Ia
Assign Operator
4Ib
Menu item
Menu item with sub-menu
4L
4K
De-init
Wireless
4J
4Ja
Auto mic off
4Jb
Assign Chairman
4M
Defaults
Unit Name
System ID
4Jc
Repetition
4Jd
WAP
4F
4E
Routing I/O2
4D
Level
Mic. Mode
4C
Loudspkr
4B
4Ba
4A
Setup
Back
figure 10.12: Configuration menu
Bosch Security Systems | 2007-02 | 9922 141 70691 en
4
<
Wireless
Mode
Bass
4Bb
Treble
4G
Mic. Priority
Att. Tones
DCN Wireless | Installation and User Instructions | Central Devicesen | 50
10.6.2 Navigation and operation
10.6.2.1 Menu items
The configuration menu consists of menu items. Refer
to figure 10.13 for the parts of a menu item.
Main menu
number
figure 10.13: Menu item parts
10.6.2.2 Number and characters
Identify menu items by the main menu number
sub-menu character. The number identifies the main
menu to which the menu item is connected. The
characters identify the sub-menus to which the menu
item is connected.
10.6.2.3 Menu title
Each menu item has a title. The title gives a short
description of the function of the menu item.
10.6.2.4 Parameters and values
Most menu items have one or more parameters. To
make adjustments, change the values of the parameters.
10.6.2.5 VU meter
Some menu items have a VU meter. The VU meter
shows the volume levels of signals. The VU meter has
seven rows.
Sub-menu
character
ValueVU meter
Menu item
title
Parameter
10.6.2.6 To open the main menu
To open the main menu, push the knob in the Main
menu item. The main menu number and the menu item
title flash.
10.6.2.7 To go through the main menu
•Turn the knob clockwise in the main menu to go to
the next menu item in the main menu.
•Turn the knob counterclockwise in the main menu to
go to the previous menu item in the main menu.
10.6.2.8 To open a sub-menu
When the display shows a menu item that has three dots
(...), the menu item gives access to a sub-menu. To open
the sub-menu, push the knob in a menu item that has
three dots. (The last sub-menu character and the menu
item title flash.)
Note
To open the Setup sub-menu, you must
push and hold the knob for more than 3
seconds.
10.6.2.9 To select menu items in a sub-menu
•Turn the knob clockwise in a sub-menu to go to the
next menu item in the sub-menu.
•Turn the knob counterclockwise in a sub-menu to go
to the previous menu item in the sub-menu.
10.6.2.10 To open a menu item
1 Turn the knob to select the applicable menu item.
2 When the display shows the correct menu item, push
the knob to open the menu item. The display shows
a cursor.
table 10.20: VU meter
VU meterDescription
One row onNo signal
Seven rows onMaximum signal
TriangleClipped signal
MinusMuted by control input
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 51
10.6.2.11 To select a parameter
1 Open the correct menu item (refer to 10.6.2.10).
2 Turn the knob to move the cursor to the parameter
that is shown.
3 On the parameter, push the knob. The parameter
flashes.
4 Turn the knob to go to the applicable parameter.
5 When the display shows the applicable parameter,
push the knob to select the parameter. The display
shows a cursor.
10.6.2.12 To change the value of a parameter
1 Select the applicable parameter (refer to 10.6.2.11).
2 Turn the knob to move the cursor to the value.
3 Push the knob. The value flashes.
4 Turn the knob to go to the value.
5 When the display shows the correct value, push the
knob to select the value. The display shows a cursor.
10.6.2.13 To close a menu item
1 Turn the cursor to the last character that identifies
the menu item.
2 Push the knob to close the menu item. The last
character and the menu item title flash.
10.6.2.16 Example
For an example, do as follows to change the level of
audio input 2 of the central control unit:
Note
Make sure that when you do this example, you
start from the Main menu item.
1 Push the knob to open the main menu.
2 Turn the knob to go to 4 Setup ...
3 Push-and-hold the knob for 3 seconds to open the
sub-menu.
10.6.2.14 To close a sub-menu
1 Turn the cursor to go to the second last character
that identifies the menu item.
2 Push the knob to close the sub-menu. The last
character and the menu item title flash.
10.6.2.15 To close the main menu
1 From the main menu, turn the primary knob
clockwise to go to the < Back menu item.
2From the < Back menu item, push the knob to go to
the Main menu item.
4 Turn the knob to go to 4D Level.
5 Push the knob to open the menu item.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 52
6 Turn the knob to move the cursor to the parameter
that is shown.
7 On the parameter, push the knob.
8 Turn the knob to go to Output 2.
9 Push the knob to select Output 2.
12 Turn the knob to change the value.
Note
In this example, the knob is turned
counterclockwise to decrease the value from
0 dB to -18 dB. Turn the knob clockwise to
increase the value.
13 Push the knob to select the value.
14 Turn the knob to go to the main menu number.
10 Turn the knob to move the cursor to the value that is
shown.
Note
In this example, the value is 0 dB. It is possible
that your display shows a different value.
11 On the value, push the knob.
15 Push the knob to go back to the main menu.
16 Turn the knob clockwise to go to the < Back menu
item.
17 Push the button to go to the Main menu item.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 53
10.6 .3 M ai n
When you start the central control unit, the display first
shows Starting. The display then shows the Main menu
item:
The Main menu item contains:
•An indicator that shows the volume level of the
loudspeakers of the contribution devices. Turn the
knob to change the volume level (refer to 12.6).
•The name of the central control unit. The default
name is CCU. You can change the name with the
4L Unit Name menu item (refer to 10.6.8).
•The microphone mode and the maximum number
of activated microphones. You can change the
microphone mode and the maximum number of
activated microphones with the 4C Mic. Mode menu
item (refer to 10.6.8).
Note
When a PC is connected to the central control
unit, the Main menu item also shows PC.
10.6.4 Fault status
Use the 1 Fault Status menu item to see the condition
messages of the central control unit. If there is more
than one message, the display shows the most important
message (refer to table 10.21).
table 10.21: Messages (low to high importance)
MessagesDescription
No FaultThe central control unit
operates correctly.
Low BatteryThe battery pack of a
wireless device is
empty within 1 hour.
Bad SignalA wireless device has a
bad signal reception.
Incompatible SWThe wireless access
point has a
incompatible software
version.
Invalid SoftwareThe central control unit
cannot start. The
central control unit
does not contain the
correct software.
DownloadingThe central control unit
downloads software.
Note
When the condition of the central control unit
changes, the Main menu item shows a message
(refer to table 10.21). Such a message goes out
of view when you push the knob.
Note
If you do not turn or push the knob for three
minutes, the display automatically goes back to
the Main menu item. The display does not
automatically go back to the Main menu item
from these menu items and their sub-menus:
•2ASource/Volume
•4Ia Assign Operator
•4Ib Assign Chairman
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 54
10.6.5 Monitoring
Use the 2 Monitoring menu item to open the Monitoring
sub-menu (refer to table 10.22).
table 10.22: Monitoring sub-menu (* = default)
Menu itemParameterValueDescription
2A Source/VolumeSignal:
Floor
Input 1
Input 2
Output 1
Output 2
Vol u m e level:
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
-31 to 0 dB (16 dB*)
The signal that is available
on the headphones
socket of the central
control unit and its volume
level.
10.6.6 DCN-WCCU Enquiry
Use the 3A CCU menu item to open the CCU
sub-menu. The menu items in this sub-menu give
general data about the central control unit (refer to table
10.23).
Note
This data must be mentioned in all service
requests and failure reports.
3Aa Serial Number---e.g. 20.0.00362 The hexadecimal serial
number of the central
control unit.
3Ab HW Version---e.g. 3.0The version number of the
hardware of the central
control unit.
3Ac FPGA Version---e.g. 1.06The version number of the
FPGA firmware of the
central control unit.
3Ad SW Version---MM.mm.bbbb
e.g. 2.20.1234
3Ae FW Version---e.g. 4.00.1234The version number of the
The version number of the
software of the central
control unit.
•MM: Major release no.
•mm: Minor release no.
•bbbb: build no.
firmware of the central
control unit.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 55
10.6.7 DCN-WAP Enquiry
Use the 3B WAP menu item to open the WAP
sub-menu. The menu items in this sub-menu give
general data about the wireless access point (refer to
table 10.23).
Note
This data must be mentioned in all service
requests and failure reports.
3BA WAP Serial Number---e.g. 1E.0.00001 The hexadecimal serial
number of the wireless
access point.
3Bb WAP HW Version---e.g. 01.00The version number of the
hardware of the wireless
access point.
3Bc WAP FPGA Version---e.g. 01.00The version number of the
FPGA firmware of the
wireless access point.
3Bd WAP SW Version---MM.mm.bbbb
e.g. 2.20.0055
The version number of the
software of the wireless
access point.
•MM: Major release no.
•mm: Minor release no.
•bbbb: build no.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 56
10.6 .8 S etup
Use the 4 Setup menu item to open the Setup
sub-menu. You can use the menu items in this
sub-menu to configure the central control unit and the
system (refer to table 10.25 and table 10.26).
table 10.25: Setup sub-menu (* = default)
Menu itemParameterValueDescription
4A Wireless Mode---On*
Sleep
Off
Subscription
4B Loudspkr------Gives access to the
4C Mic. ModeMode:
Open*
Override
PTT
4D LevelSignal:
Input 1
Input 2
Output 1
Output 2
4E Routing I/O 2---Mode:
4F Att. TonesEvent:
Priority
Voting
4G Mic. Priority---Temporarily off*
NOM:
1, 2*, 3
1, 2*, 3
1, 2*, 3
Level:
-6 to 6 dB (0 dB*)
-6 to 6 dB (0 dB*)
-24 to 6 dB (0 dB*)
-24 to 6 dB (0 dB*)
Recorder*
Equalized PA
Mix-minus
Insertion
Chime:
Off, 1*, 2, 3
Off*, 1, 2, 3
Permanently off
Sets the mode of the
wireless network (refer to
12. 3) .
Loudspkr sub-menu (refer
to10. 6. 9) .
The microphone mode of
the DCN and the
maximum number of
activated delegate
microphones (refer to
12. 4) .
The nominal levels of the
audio inputs and the audio
outputs of the central
control unit.
The audio routing mode of
the central control unit
(refer to 12.6).
The attention chimes of
the system (refer to 12.7).
The action taken by the
system when the
chairman releases the
priority button (refer to
12. 8) .
Bosch Security Systems | 2007-02 | 9922 141 70691 en
DCN Wireless | Installation and User Instructions | Central Devicesen | 57
table 10.26: Setup sub-menu (* = default)
Menu itemParameterValueDescription
4H Floor Distr.---On*, OffEnables or disables floor
distribution (refer to 12.9).
4I Intercom ...------Gives access to the
Intercom sub-menu (refer
to 10.6.10).
4J Wireless ------Gives access to the
Wireless sub-menu (refer
to 10.6.11). When the
wireless access point is
not connected, the central
control unit shows Not
Available.
4K De-Init ...------Gives access to the
De-initialization menu item
(refer to10. 6.12) .
4L Unit Name---Name:
CCU*
Custom name
4M Defaults ...------Gives access to the Reset
The name of the central
control unit (max. 16
characters).
menu item (refer to
10. 6.13)
10.6 .9 L ou ds pk r
Use the menu items in the 4B Loudspkr sub-menu to set
the levels of the bass and treble output to the
loudspeakers of the contribution devices (refer to table
10.27).
table 10.27: Loudspkr sub-menu (* = default)
Menu itemParameterValueDescription
4Ba Bass----12 to 12 dB (0 dB*)The level of the bass
output.
4Bb Treble----12 to 12 dB (0 dB*)The level of the treble
output.
Bosch Security Systems | 2007-02 | 9922 141 70691 en
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.