Bosch WH27 User Manual

TRONIC WH17 & WH27 Electric Tankless Water Heaters
Dimensions
Engineering
Submittal
Sheet
2½"
3½"
15¼"
12⅝"
12⅝"
6⅛"
4½"
12½"
InletOutlet
1¾"
5¾"
Engineering Specifi cations
Water heater shall be a Model TRONIC WH17 or, WH27.
Installation shall consist of ___Model TRONIC WH17 electric tankless water heaters as distributed by Bosch Thermotechnology Corp. and 99% thermal effi ciency. Supply voltage shall be 240VAC (208VAC, 220VAC) with a maximum output of 17.25kW.
Installation shall consist of ___Model TRONIC WH27 electric tankless water heaters as distributed by Bosch Thermotechnology Corp. with a thermal effi ciency of 99%. Supply voltage shall be 240VAC (208VAC, 220VAC) with a maximum output of 26.85kW.
The tankless water heaters shall be UL listed for the US and Canada and UPC certifi ed.
1 of 4
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances | BTC 722008302 A | 12.2011
CONSTRUCTION Water heater shall be electricity powered with compact tankless design for whole house operation and an effi ciency rating of 97%. Primary heat exchanger shall be made from composite material and the elements shall be made from
-sheathed copper. Unit shall be protected by a tough sheet metal housing. Heat exchanger shall be rated for maximum working pressure not less than 150 psig. Water heater shall be equipped with a fl ow turbine. Water connections for inlet and outlet shall be ¾” NPT male.
The controls shall contain an external output temperature selector and a high temperature safety cut-out. Unit shall be equipped with a fl ow turbine and a temperature sensor for constant output temperature. A red light shall indicate when the unit is powering one or more elements.
Bosch Thermotechnology Corporation
Tel: 1-800-798-8161 Fax: 1-603-965-7581 www.bosch-climate.us
TRONIC WH17 & WH27 Electric Tankless Water Heaters
Engineering Specifi cations
INSTALLATION All aspects of installation of Water Heater Plant shall be in strict accordance with manufacturer’s instructions. Materials shall conform to all manufacturer’s recommendations including electrical connections and wiring.
discharge water temperature shall be set through an internal set point with a fi eld adjustment of 95 to 131 degrees F. Heater shall be capable of maintaining the temperature set point +/- 3 degrees F. This shall be accomplished by switching or pulsing
the power to the electrical elements. Water heater piping shall be fi eld constructed of materials as specifi ed. Water heater shall be installed with individually isolating shutoff valves for service and maintenance.
WARRANTY
The heating modules shall carry a 10-year warranty. All other
parts and components shall carry a 1 year warranty against MODE OF OPERATION
defects in materials or workmanship. The heater shall include integral factory wired operating controls to control all operation and energy input. Control of
Technical Data
Description Unit WH17 WH27
Part number 7-736-500-682
Voltage supply VAC 240 240
Amperage A 2 x 40 (Canada 80) 3 x 40 (Canada 120)
Maximum output kW 17.25 26.85
Maximum output at 220V kW 15.00 kW 22.50
Maximum output at 208V kW 13.00 20.00
Minimum recommended wire size AWG 8 8
Thermal effi ciency % 97 97
Temperature control range ° F 95 - 131 95 - 131
Maximum inlet water temperature* ° F ≤ 86 ≤ 86
Water pressure range psi 15 - 150 15 - 150
Minimum fl ow rate GPM 0.6 0.8
Inlet / Outlet connections Inch
Weight (without water) lbs 20 22
Certifi cations
* Do not use heater for water temperature boosting applications
¾ NPT ¾ NPT
7-736-500-681
NSF/ANSI 61
U
P
C
®
2 of 4
Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances | BTC 722008302 A | 12.2011
Bosch Thermotechnology Corporation
Tel: 1-800-798-8161 Fax: 1-603-965-7581 www.bosch-climate.us
Loading...
+ 2 hidden pages