Explanation of symbols and safety information | 3US
1Explanation of symbols and safety information
1.1Explanation of symbols
Warnings
Warnings are indicated in the text by a
warning triangle and a gray background.
In case of danger due to electric shock, the
exclamation point on the warning triangle is
replaced with a lightning symbol.
Signal words at the beginning of a warning are used to
indicate the type and seriousness of the ensuing risk if
measures for minimizing damage are not taken.
• NOTE indicates possible minor to medium personal
injury.
• CAUTION indicates possible minor to medium
personal injury.
• WARNING indicates possible severe personal injury.
• DANGER indicates that severe personal injury may
occur.
Important information
Important information that presents no risk
to people or property is indicated with this
symbol. It is separated by horizontal lines
above and below the text.
Additional symbols
SymbolMeaning
Ba step in an action sequence
1.2Safety precautions
When using this electrical equipment, basic safety
precautions should always be followed, including the
following:
B READ AND FOLLOW ALL INSTRUCTIONS.
B This appliance must be grounded.
B Disconnect this product from the electrical supply
before cleaning, servicing or removing the cover.
B To reduce the risk of injury, close supervision is
necessary when the product is used near children or
elderly persons.
B Warning: Mount the unit onto a flat section of wall,
well away from any potential splashes of water or
spray and away from areas where direct moist or wet
contact could occur.
B Warning: Indoor installation only, where it will NOT be
exposed to freezing.
B Warning: Do not install a check valve or any other type
of back flow preventer within ten feet of the cold
water inlet.
B The electrical installation must conform to current
National Electrical Codes.
B Warning: Do not switch the heater on if you suspect
that it may be frozen. Wait until you are sure that it
has completely thawed out.
B The Tronic 5000C Pro is designed to heat potable cold
water for domestic purposes. The heater is not
designed to accept inlet water temperatures above
86° F. Contact Bosch Thermotechnology Corp. before
specifying or installing the appliance in any other
application.
→a reference to a related part in the
document or to other related documents
•a list entry
–a list entry (second level)
Tab. 1
6 720 646 951 (2011/09)Copyright
4 | Explanation of symbols and safety informationUS
B Additional Canadian safety instructions:
– As per the Canadian Electrical Code, C22.1-02
Section 26-744, an auxiliary terminal block must be
fitted to the unit before connecting to the electrical
supply (Kit Part N° “AE Canada Kit”).
(See Page 17).
– A green terminal (or a wire connector marked “G,”
“GR,” “GROUND” or “GROUNDING”) is provided
within the control. To reduce the risk of electrical
shock, connect this terminal or connector to the
grounding terminal of the electrical service of
supply panel with a continuous copper wire in
accordance with the Canadian Electrical Code,
Part I.
– This product shall be protected by a Class A ground
fault circuit interrupter.
B Keep this manual in a safe place once the unit has
been installed as it may be needed for future
reference.
Copyright6 720 646 951 (2011/09)
2General information
2.1Disclaimer
General information | 5US
2.1.1
Commonwealth of Massachusetts
In the Commonwealth of Massachusetts a licensed
plumber or electrician must perform the installation.
(Approval number: P1-09-25).
Approval number
2.2Technical identification code
EI17E/MWIHB
EI27E/MWIHB
Tab. 2
EIElectronic Instantaneous
17Maximum output (kW)
E/M Electronic / mechanical temperature control
WWall hung
IIndoor
HHorizontal installation
BWater connections
2.3Model name and number
identification
Model NameModel Number
WH17EI 17 E/M W I H B
WH27EI 27 E/M W I H B
Tab. 3
2.4Package contents
• Tankless electric water heater.
• 4 screws and gasket.
6 720 646 951 (2011/09)Copyright
6 | General informationUS
6720646951-14.1V
G
E
L
J
H
I
N
M
FK
A
D
C
B
2.5Components Diagram
Fig. 1
AHeating module
BHeating element assembly
CHeating module PCB
DHot water outlet
ECold water inlet
FTemperature adjustment knob
GFlow transducer
HTerminal block (CANADA ONLY)
I6 way terminal block
JTemperature sensor
KControl PCB
LDouble pole thermal cut-out
MInlet water filter
NFlow regulator
Fig. 3Internal wiring schematic for single phase WH27 unit.
Copyright6 720 646 951 (2011/09)
General information | 9US
6720646951-03.1V
Fig. 4Internal wiring schematic for single phase WH17 unit.
2.8Function
How the water heater works:
• The Tronic 5000C Proheats water continuously as it
flows through the heater modules.
• The electronic control PCB monitors the flow rate and
the incoming water temperature and then switches
on the required number of heater elements to reach
the temperature set by the temperature adjustment
dial.
• As the flow rate or the incoming water temperature
changes, the electronic control adjusts the number of
heater elements used so that the outlet temperature
is maintained.
• The outlet water temperature can change slightly as
the flow rate changes due to the steps in power as
different heater elements are switched on and off.
• The outlet water temperature can also vary if the
maximum flow rate is exceeded (seeFig. 11) or if the
supply voltage changes.
• Each heater module is protected by an electromechanical thermal cut-out. This cut-out will only trip
in exceptional circumstances.
Contact Technical Support 800-798-8161 for further
instruction.
• The WH17 unit is supplied from two independent
voltage supplies and the WH27 unit from three
independent voltage supplies. (In Canada the unit has
just one voltage supply).
• Depending on the region of the country, the
temperature of the water supply can vary between
40 °F in winter to 70 °F in summer, with an average of
55 °F. The output temperature and maximum flow of
the heater is dependent on inlet water temperature.
6 720 646 951 (2011/09)Copyright
10 | General informationUS
2.9Technical specifications
Technical characteristicsUnitsWH17WH27
Voltage supplyV2 X 240VAC (Canada 240VAC)3 X 240VAC (Canada 240VAC)
AmperageA2 X 40A (Canada 80A)3 X 40A (Canada 120A)
Maximum outputkW17.25kW26.85kW
Temperature control range95 °F to 131 °F95 °F to 131 °F
Minimum water pressurepsi15psi15psi
Maximum water pressurepsi150psi150psi
Minimum flow rategal/min0.6 US gal / min0.8 US gal / min
Maximum flow rate(refer to Fig. 11)(refer to Fig. 11)
Weight (without water)lbs20 lbs22 lbs
The unit will work at lower supply voltages but the following changes will apply:
Maximum output15kW at 220V22.5kW at 220V
Maximum flow rate
(refer to Fig. 11)
Tab. 5
13kW at 208V20kW at 208V
84% of maximum at 220V84% of maximum at 220V
75% of maximum at 208V75% of maximum at 208V
Copyright6 720 646 951 (2011/09)
3Regulations
Any local by-laws and regulations pertaining to
installation and use of electric water heating appliances
must be observed. Please refer to the laws that should
be attended in your country.
• The electrical installation must conform to current
National Electrical Codes.
• As per the Canadian Electrical Code, C22.1-02
Section 26-744, an auxiliary terminal block must be
fitted to the unit before connecting to the electrical
supply (Kit Part N° “AE Canada Kit”).
• A green terminal (or wire connection marked “G”,
“GR”, “GROUND” or “GROUNDING”) is provided
within the control box. Aditional Canadian safety
instructions, to reduce the risk of electrical shock,
connect this terminal or connector to the grounding
terminal of the electrical service of supply panel with
a continuous copper wire in accordance with the
Canadian Electrical Code, Part I.
• In Canada this product shall be protected by a Class
A ground fault circuit interrupter.
• In the Commonwealth of Massachusetts a licensed
plumber or electrician must perform the installation.
(Approval number: P1-09-25).
• In the Commonwealth of Massachusetts a pressure
relief valve shall be installed on the cold water side by
a licensed plumber. (MGL 142 Section 19, Approval
number P1-09-25).
• The unit must be wired by a qualified electrician, in
accordance with the current version of the National
Electrical Code US) or Canadian Electric Code
(Canada).
• When the heater is not within sight of the electrical
circuit breakers, a circuit breaker lockout or
additional local means of disconnection for all nongrounded conductors must be provided that is within
sight of the appliance. (Ref NEC 422.31.).
• The power cable size and the installation must be in
accordance with the Canadian Electrical Code, C22.1-
02.
Regulations | 11US
WARNING:
California Proposition 65 lists chemical
substances known to the state to cause
cancer, birth defects, death, serious illness
or other reproductive harm. This product
may contain such substances, be their
origin from fuel combustion (gas, oil) or
components of the product itself.
6 720 646 951 (2011/09)Copyright
12 | InstallationUS
4Installation
DANGER: Risk of electric shock!
B For safety reasons, disconnect the power
supply to the heater before any service or
testing is performed.
WARNING:
B This heater must be electrically grounded
in accordance with the most recent
edition of the National Electrical Code.
NFPA 70. In Canada, all electrical wiring
to the heater must be in accordance with
local codes and the Canadian Electrical
Code, CSA C22.1 Part 1.
4.1Important information
DANGER:
B The installation must only be performed
by a qualified person in accordance with
these instructions.
B Bosch Thermotechnology Corp. is not
responsible for improperly installed
appliances.
WARNING:
B The heater must only be mounted in a
vertical position with the water fittings
located at the bottom of the heater.
Under no circumstances should the
heater be mounted differently.
WARNING:
B The appliance should be located in an
area where leakage of the heater or
connections will not result in damage to
the area adjacent to the appliance or to
lower floors of the structure.
4.2Selection of place of installation
WARNING: Risk of freezing!
B Do not install the water heater in an area
where there is a chance of freezing.
Damage to the water heater as a result of
freezing will not be covered under
warranty.
• If being used in a public place, locate the heater out
of easy reach to discourage vandalism.
• Mount the unit onto a flat section of wall, well away
from any potential splashes of water or spray and
away from areas where direct moist or wet contact
could occur.
• Install the heater in a place that provides easy access
for any service or maintenace.
4.2.1Freeze prevention
WARNING:
B ELECTRICITY IS EXTREMELY
DANGEROUS. TAKE EXTRA
PRECAUTIONS AND ENSURE ALL
CIRCUIT BREAKERS ARE OFF BEFORE
PERFORMING ANY WORK TO THE
HEATER.
WARNING:
B Indoor installation only, where it will NOT
be exposed to freezing.
Introduction
Please note that the installation manual states that the
water heater must not be installed in a location where it
may be exposed to freezing temperatures. If the heater
must be left in a space that is likely to experience
freezing temperatures, all water must be drained from
the heater. See Section 6.
Freeze damage is not covered under the warranty.
Please follow these instructions. Failure to follow
instructions may result in:
• Damage or injury.
• Improper installation/operation.
• Loss of warranty.
Use ofchemical agents such as anti-freeze
are not allowed as they may cause damage
to the water heater’s internal components.
Copyright6 720 646 951 (2011/09)
4.2.2Recommended minimum clearances for
servicing
Should it be necessary to service the Tronic 5000C Pro,
observe the following clearances. These are not required
clearances, but would facilitate any service work.
Installation | 13US
4.3Mounting the water heater
WARNING:
B The heater must only be installed in the
orientation shown in Fig. 6 i.e., mounted
in a vertical position with the water
fittings located at the bottom of the
heater. Under no circumstances should
the heater be mounted differently.
B Undo the retaining screws on the front cover and take
the cover off the heater. Hold the back plate in
position against the wall and mark the four mounting
holes.
B Drill the holes and secure the heater using the four
wood screws supplied.
Fig. 5Recommended minimum clearances
WH17WH27
Top (A)12"12"
Sides0"0"
Bottom (B)6"6"
Front (C)12"12"
Tab. 6Recommended minimum clearances
Fig. 6Vertical mounting position
6 720 646 951 (2011/09)Copyright
14 | InstallationUS
4.4.1Water quality
4.4Water connections
WARNING:
B Do not install a non-return check valve
within 10 feet of the inlet.
WARNING:
B Do not apply heat or solder to
connections or pipe if they are already
connected to the unit.
NOTICE: Disclaimer
B In the Commonwealth of Massachusetts
a pressure relief valve shall be installed
on the cold water side by a licensed
plumber. (MGL 142 Section 19, Approval
number P1-09-25).
B The heater must be connected directly to the main
cold water supply and not to pre-heated water. (The
inlet water temperature must not be greater than
86 °F).
B The heater must be installed with shutoff valves on
both the inlet and outlet connections.
B It is recommended that you use ¾ inch or ½ inch
copper or high-pressure flex connections.
B Do not use plastic piping within 3 feet on either side
of heater.
B Use Teflon tape for sealing pipe threads. Do NOT use
pipe dope.
B Remember to keep the hot water pipe runs as short
as possible.
After the heater has been plumbed, and before you
wire it, flush it with water to remove any debris or
loose particles. Heater must be full of water and air
purged before power is turned on. Failure to do so
may result in damage to the product that is not
covered by warranty.
B After flushing and filling the heater with water, (with
power off) disconnect the inlet connection and
inspect the filter screen for any debris that may have
been flushed through the system.
The inlet and outlet connections are clearly
marked on the heater. They each have a
¾ inch NPT connector.
Water quality can have an impact on appliance longevity
and may not be covered under the manufacturer's
warranty.
B For water analysis data call your local water
department, or if on a well, have well water analyzed
periodically.
If water quality exceeds one or more of the values
specified below, Bosch recommends consulting a
local water treatment professional for water
softening/conditioning options.
DescriptionMax. Levels
pHpH6.5 - 8.5
TDS
(total Dissolved Solids)
Total hardnessmg/l or ppm
mg/l or ppm500
100
Aluminummg/l or ppm2.0
Chloridesmg/l or ppm250
Coppermg/l or ppm1.0
Ironmg/l or ppm0.3
Manganesemg/l or ppm0.05
Zincmg/l or ppm5.0
Table 7
4.5Electrical connections
WARNING:
B The unit must be wired by a qualified
electrician, in accordance with the
current version of the National Electrical
Code US) or Canadian Electric Code
(Canada).
When the heater is not within sight of the
electrical circuit breakers, a circuit breaker
lockout or additional local means of
disconnection for all non-grounded
conductors must be provided that is within
sight of the appliance. (Ref NEC 422.31.).
B Check the pressure of the main water supply. To
operate correctly, the heater needs the running
pressures mentioned in Tab. 5.
Copyright6 720 646 951 (2011/09)
As per the Canadian Electrical Code, C22.102 Section 26-744, an auxiliary terminal
block must be fitted to the heater before
connecting to the electrical supply. This is
available as a kit from Bosch
Thermotechnology Corp. Part Number “AE
Canada Kit”. (Contact 800-798-8161).
US wiring
• The minimum recommended wire size is 8 AWG. (The
terminal block will accept cables up to 6 AWG size).
• The cable entry is via the 1¼ inch cable entry hole on
the bottom right hand edge of the back plate.
• Strip back the insulation on the power wires about
½ inch. Connect the live wires to the terminals
marked “L1” and “L2.” There are two pairs of live
wires in the WH17 and three pairs of live wires in the
WH27. (See Fig. 7 and Fig. 8, page 16).
• Any insulation on the ground wires should be stripped
back about ¾ inch. The ground leads must be
connected to the pillar terminal marked “GR”. (See
Fig. 7 and Fig. 8, page 16).
• Make sure the terminal block screws are tightened
securely. Loose connections can cause wires to heat
up.
• Make sure that the ground wires are wrapped around
its terminal stud and into the saddle washer. The nut
should be tightened securely.
• Attach the front cover and tighten the retaining
screws.
Installation | 15US
6 720 646 951 (2011/09)Copyright
16 | InstallationUS
The WH17 requires two independent 240V AC circuits protected by two separate and independent double pole
breakers (as shown) rated at 40A each.
Canada Wiring - auxiliary terminal block and
connections
Fitting the auxiliary terminal block (see diagram below).
Fig. 9For Canada only (Not for U.S.A.)
Connecting the supply cable - Canada only - not for the
USA.
The WH17 requires an 80A 240V AC
single phase supply protected by an 80A
double pole circuit breaker.
The WH27 requires a 120A 240V AC
single phase supply protected by a 120A
double pole circuit breaker.
• The power cable size and the installation must be in
accordance with the Canadian Electrical Code, C22.1-
02.
• The incoming hole diameter on auxiliary terminal
block can accept up to 1/0 AWG size cables.
• The cable entry is via the 1 ¼ inch cable entry hole on
the bottom right hand edge of the backplate.
• Strip back the insulation on the power wires about
½ inch. Connect the ungrounded conductors to the
terminals “L1” and “L2” on the auxiliary terminal
block.
• Any insulation on the ground wire should be stripped
back about ¾ inch. The ground lead must be
connected to the pillar terminal marked “GR.”
• Make sure the terminal block screws are tightened
securely. Loose connections can cause wires to heat
up.
• Make sure that the ground wire is wrapped around its
terminal stud and into the saddle washer. The nut
should be tightened securely.
• Attach the front cover and tighten the retaining
screws.
Fig. 10 For Canada only (Not for U.S.A.)
B Connect the red wires from the left hand terminal of
the new block to the L1 terminals in the unit. (There
are two red wires required in the WH17 and three in
the WH27).
B Connect the blue wires from the right hand terminal
of the new block to the L2 terminals in the unit.
(There are two blue wires required in the WH17 and
three in the WH27).
B Push and click the auxiliary terminal block onto the
louvered rail in the backplate.
6 720 646 951 (2011/09)Copyright
18 | InstallationUS
95100105110130115120125135
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Outlettemperature(ºF)
MaxFlowRate(USgal/min)
OutlettemperaturevsMaximumflowratesetting
(basedonincomingwatertemperatureof55ºF)
17kWHeater
27kWHeater
6720646951-09.1V
131
4.6.2Adjusting the temperature dial
4.6Starting up
4.6.1Checking for leaks and purging air
B Verify all circuit breakers supplying power to the
water heater are turned off.
B The temperature adjustment is made using the dial on
the bottom edge of the unit. The adjustment is
between approximately 95 °F and 131 °F. Turning the
dial clockwise increases the temperature setting as
indicated by the marking on the unit.
B Open all hot water taps supplied by the water heater
and inspect all water connections for leaks.
B With all hot water taps still open, inspect each tap to
ensure all air in the lines has been purged out.
B With the air purged and taps still flowing, turn on all
circuit breakers supplying the water heater.
B Close all hot water taps and proceed to the next
section.
4.6.3Adjusting the flow
B Open fully both inlet and outlet shut-off valves at the
heater, then:
B Turn on fully the highest flowing hot water faucet
(e.g., bathtub) served by the water heater.
B Adjust the outlet shut-off valve until the water flow
rate from the hot faucet corresponds to the value
given in Fig. 11 below.
Fig. 11
For example:
• For the WH17 unit, using the outlet ball valve, ensure
the flow rate does not exceed 2.3 gallons/minute.
• For the WH27 unit, using the outlet ball valve, ensure
Before leaving the site, the installer should
demonstrate the unit to the user and give
them this guide.
the flow rate does not exceed 3.5 gallons/minute.
These figures are based on an inlet water temperature of
55 °F and a supply voltage of 240 volts. If the inlet water
temperature is lower than 55 °F, or if the supply voltage
is less than 240 volts, then the outlet temperature will be
lower than what is shown in Fig. 11. If a higher outlet
water temperature is desired, then reduce the flow rate
and/or supply the unit with 240 volts.
Copyright6 720 646 951 (2011/09)
5Operation instructions
5.1Before using the water heater
WARNING:
B Do not use the unit if you think it may be
frozen, as this could result in serious
damage to the unit. Wait until you are
sure that it has completely thawed out
before you switch it on.
B Check that the power is switched on at the circuit
breaker panel.
B Turn on the hot water faucet FULLY.
The hot water temperature can be changed
by adjusting the temperature dial on the
bottom surface of the unit. (The dial adjusts
the temperature typically between 95°F and
131°F. The factory sets the temperature dial
at the lowest position).
Operation instructions | 19US
• If the unit has been used recently, run the water
through for a few seconds to let the temperature cool
down. You may initially get a short burst of very hot
water that was in the plumbing lines from previous
use.
• If a second outlet connected to the unit is also turned
on, the hot water will be shared between the two.
6 720 646 951 (2011/09)Copyright
20 | MaintenanceUS
6Maintenance
Draining the heater
Due to the shape of the heat exchangers and connecting
pipe, it is extremely difficult to get all of the water out of
the heater. Follow the procedure below to best minimize
the chance of freezing:
B Disconnect electric supply.
B Disconnect cold and hot water pipes from fittings on
bottom of heater. Allow water to drain out (have a
catch basin ready).
B After allowing all water to drain out, the heater should
be blown out with low pressure compressed air to
remove as much water as possible from water heater
modules. Bursts of air work better than continuous
flow.
Remember, these suggestions are only made to help
minimize the potential for freeze damage and are not to
be construed as the guaranteed method for dealing with
freeze possibilities.
Check inlet water filter screen once a year
B Check that the power is switched off at the circuit
breaker panel.
B Shut off the installer supplied cold water isolation
valve to the heater. If one is not installed, install
before proceeding.
B Open nearest hot water tap to relieve pressure in the
plumbing lines.
B Position a bucket under the cold water inlet
connection of the heater to catch any water that may
drain.
B Disconnect the cold water plumbing connection from
the inlet (bottom right of heater) to access filter
screen.
B Remove filter, clean with water and inspect for
damage. If the filter is at all damaged, it should be
replaced.
B Replace the filter into the inlet housing
B DO NOT leave the filter out.
B DO NOT remove the flow regulator (located behind
the filter).
B DO NOT clear the filter by back flushing.
B NEVER use an air line to blow out the heater (the flow
transducer will be permanently damaged).
B Before switching power back on, open all hot water
taps and inspect each tap to ensure all air in the lines
has been purged out. With the air purged and taps still
flowing, turn on all circuit breakers supplying the
water heater.
B Close all hot water taps and proceed for normal
operation.
Copyright6 720 646 951 (2011/09)
Using an ohmmeter to check for premature element failure
On WH17 model, there is no middle element
Maintenance | 21US
Fig. 12 Heating elements
Meter probesOhm Readings
Outer to Outer10.5 ± 0.6 Ohms
Middle to Middle11.7 ± 0.8 Ohms
Inner to Inner15.1 ± 1 Ohms
Tab. 8
Meter probesOhm Readings
Outer to Outer10.5 ± 0.6 Ohms
Middle to Middle11.7 ± 0.8 Ohms
Inner to Inner21.0 ± 1.2 Ohms
Tab. 9
6 720 646 951 (2011/09)Copyright
22 | TroubleshootingUS
7Troubleshooting
DANGER: Risk of electric shock!
B Always switch off the electricity supply to
the unit before you remove the cover.
Cold water only – Neon light off
Flow rate is too lowVerify the flow rate out of fixture is at or above the minimum activation rate
required for the unit to activate. (Activation rates: WH17 = 0.6 GPM, WH27 = 0.8
GPM).
Plumbing crossoverTo test for a plumbing crossover, turn off power supply to the heater. Close
installer supplied cold water shut off valve (if none installed, install before
proceeding). Open all hot water taps supplied by the heater. Wait 5 minutes and
check all taps. Any water running is a sign of a plumbing crossover. Consult a local
plumber or service person for help in correcting a plumbing crossover. To return
the heater to service, reinstall cover, open the inlet water supply to the heater and
open all hot water taps. Let all taps run until there is no air coming out of the
fixtures. Shut off all hot water taps. Turn power supply on to the heater. Return
heater to service. (This procedure will prevent the heating elements from burning
out).
The flow transducer is not
spinning
Turn off the power supply to the heater and remove the cover. Observe if the flow
transducer "spins" when the water is turned on. Please note the flow transducer
spins at a high speed and can appear to be stopped when actually spinning. It is
recommended to observe the flow transducer without water flowing, then turn on
a hot water tap while observing the flow transducer. If the flow transducer is not
spinning, remove and flush flow transducer, noting the Do's and Dont's on page 20.
See the technical support section of www.bosch-climate.us for more detailed
instruction on removing the flow transducer.
Important: If you are unable to perform the tasks listed
below, or need additional assistance please contact your
original installer/licensed electrician.
No electricity at the heater
or one of the supplies has
failed
One or more of the heating
module thermal cut-outs
has tripped
The power supply voltage
has dropped
Tab. 10
Have a licensed electrician verify proper wiring and adequate voltage on the
terminal block inside the water heater. See the “Electrical connections” section on
page 14 of this manual.
Turn off the power to the heater, remove the cover and locate the thermal cutouts
on the top of each heating module. Check for continuity through each cutout.
(Less than 0.5 Ohms). A continuity value greater than 0.5 Ohms indicates that the
cutout has tripped or is faulty. A cutout will only trip in exceptional circumstances
and it is essential that the cause is determined and resolved. Verify the heater's
inlet filter screen and all outlets served by the heater are clear of debris. Ensure
the heater is not being fed preheated water. This water heater is designed for cold
water feed only.
Contact Technical Support 800-798-8161 for further instructions.
This is likely an issue with the incoming power supply. Have a qualified electrician
measure voltage on the water heater’s terminal block while operating at maximum
flow and maximum temperature setting. The WH17 & WH27 models are rated for
240V and will also operate at 220V or 208V with reduced maximum flow rate.
Copyright6 720 646 951 (2011/09)
Cold water only – Neon light off
Troubleshooting | 23US
The inlet water temperature
is too cold
Verify the heater is sized appropriately for it’s geographic location. Turn
temperature knob located on the bottom of the water all the way clockwise for
maximum temperature setting. Ensure flow rates are within the heater’s
specifications. Refer to Fig. 11 on page 18 of the manual. Use of an isolation valve
on the hot water outlet to control flow rate is recommended.
One of the power supplies
is not on
Have a licensed electrician verify adequate voltage on the terminal block inside the
water heater. Verify circuit breakers serving the heater are not tripped. See the
“Electrical connections” section on page 14 of this manual.
Premature element failureShut off power to the unit and remove cover. Use an ohmmeter to verify correct
resistance on each element. If readings are different than listed specifications on
page 21, contact Technical Support 800-798-8161 for further instruction.
Tab. 10
Water not hot enough - Neon light on
The water supply is
connected to the outlet of
Verify plumbing connections are correct (SeeFig. 2). Reconnect the water supply
to the inlet of the unit (marked blue).
the unit
One or more of the heating
module thermal cut-outs has
tripped
Turn off the power to the heater, remove the cover and locate the thermal cutouts
on the top of each heating module. Check for continuity through each cutout.
(Less than 0.5 Ohms). A continuity value greater than 0.5 Ohms indicates that the
cutout has tripped or is faulty. A cutout will only trip in exceptional circumstances
and it is essential that the cause is determined and resolved. Verify the heater's
inlet filter screen and all outlets served by the heater are clear of debris. Ensure
the heater is not being fed preheated water. This water heater is designed for
cold water feed only.
Contact Technical Support 800-798-8161 for further instructions.
Temperature dial is turned
too low
Turn the temperature dial located on the bottom of the water heater clockwise for
hotter temperatures. Refer to Fig. 11 for outlet temperature vs. flow rate variance.
Water flow is too highAdjust water flow to stay within the water heater’s specifications. See Fig. 11 of
this manual.
Tab. 11
6 720 646 951 (2011/09)Copyright
24 | TroubleshootingUS
Water flow too low
There are restrictions in the
plumbing
Water supply pressure too
low
Outlet shut-off valves are set
too low
Tab. 12
Water Temperature too Hot
Temperature dial set too
high
Obstructions in the water path can restrict the flow of water through the heater.
Verify the heater’s inlet filter screen, faucet aerators, showerheads and whole
house filters are clear of debris. Verify proper flow on the outlet side of the heater
with the hot water pipe disconnected. Maximum flow rates for each unit are as
follows. WH17 = 2.3gpm, WH27 = 3.5gpm.
Verify incoming water supply is at least 30psi. For people on well systems, the
recommended pressure range is 30-50psi.
Adjust installer supplied outlet valve as described below:
• Completely open both installer supplied inlet and outlet shut-off valves at the
heater. (if none installed, install before proceeding).
• Completely open hot water on the highest flowing hot water fixture served by
the heater (i.e. bathtub).
• Slowly close the outlet shut-off valve, slowing the water flow rate until the
temperature at the hot water faucet corresponds to the values given on Fig. 11
of the manual, or desired water temperature is reached.
Turn the temperature knob located on the bottom of the water heater
counterclockwise for cooler temperatures.
There are restrictions in
the plumbing
Inlet water temperature is
too warm
Tab. 13
Obstructions in the water path can restrict the flow of water through the heater
causing overheating. Verify the heater’s inlet filter screen, faucet aerators,
showerheads and whole house filters are clear of debris. Verify proper flow on the
outlet side of the heater with the hot water pipe disconnected. Opening hot water
isolation valve fully may be necessary. Maximum flow rates for each unit are as
follows. WH17 - 2.3gpm, WH27 - 3.5gpm.
Verify the heater is being feed with cold water only. This water heater is not
designed for preheated water or recirculation applications. Increase flow rate where
ever possible. Replacing low flow showerheads and aerators with higher flowing
(GPM) ones may be necessary.
Copyright6 720 646 951 (2011/09)
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.