Bosch WGES24-75WR, WGES24-75WW, WGEC24-75WW, WGEC24-75WR Specsheet

Fire Alarm Systems | WGE Weatherproof Strobes and Horn Strobes
WGE Weatherproof Strobes and Horn Strobes
www.boschsecurity.com
u Wide voltage range, 16 to 33 VDC or FWR
u 75 cd strobe meets ADA 4.28.3 requirements
The Gentex WGE family of weatherproof strobes and horn strobes offer dependable visible and audible alarms. The horns have a synchronizable (using the AVSM Synchronization Module) chime and whoop tones. You can select high or low volume and choose a 2400 Hz (remote signaling) tone or a low frequency (1500 Hz to 3000 Hz) mechanical sounding tone where doors could prevent hearing the other tone. They are easily field‑changeable from temporal Code 3 to a continuous tone. They are shipped from the factory on the temporal lower frequency mode, and come standard with a rugged die‑cast metal mounting plate. The strobes have a low operating current and a minimum flash rate of 1 Hz regardless of the input voltage. These devices are equipped with the SuperSlide feature to test supervision and the Instant Voltage Verification feature for measuring voltage drop draw. The GOE Outdoor Enclosure is included with each unit. The unit and GOE enclosure must be used together to meet the UL outdoor listing.
outdoor enclosure
u Jumper selection for high or low frequency and for
temporal Code 3 or continuous tone patterns
u Separate horn and strobe functions; silences horn
while strobes remain flashing
Certifications and approvals
Gentex Corporation holds these Listings and Approvals:
Region Certification
USA UL ULSZ: Audible-signal Appliances
(ANSI/UL 464), ULSZ7: Audible-signal Appliances Certified for Canada (CAN/ ULC-S525), UVAV: Visual-signal Appli­ances for Fire-protective Signaling Sys­tems (ANSI/UL 1638), and UEES7: Visu­al-signal Appliances Certified for Canada [CAN/ULC-S526 (1987)]
CSFM see our website
Installation/configuration notes
Compatible Products
The following products are compatible with these strobes and horn strobes:
Control Panels:
Active1: FPA-1000 family and FPD-7024 family
2 | WGE Weatherproof Strobes and Horn Strobes
Legacy1: D10024A, D9412, D8024, D70242, and D7022
3
Synchronization Modules:
AVSM‑R and AVSM‑W
1
For synchronization, use the AVSM‑R or AVSM‑W Synchronization
Modules with these control panels.
2
When used with a D7039 Multiplex Expansion Module, the D7024
becomes an addressable fire alarm control panel (FACP).
3
The D7022 must be set for 24 VDC operation and requires the AVSM‑R
or AVSM‑W Synchronization Modules for synchronization.
Mounting Considerations
For an outdoor application or a severe environment (NEMA 3R) application, the WGES Strobes and WGEC Horn Strobes must be surface mounted on a flat wall in a GOE Outdoor Enclosure. The enclosure is supplied. Knockout holes are sized for 3/4‑inch conduit and matching connector. Use a watertight conduit fitting.
Wiring
Notice
Do not use these units in coded or pulsed signaling circuits.
Mechanical
Candela Rating 75 cd
Dimensions (HxWxD):
• without GOE enclosure
5 in. x 4.5 in. x 2.5 in. (12.7 cm x
11.4 cm x 6.4 cm)
• with GOE enclosure 5.75 in. x 4.75 in. x 4.2 in. (14.6 cm x
12.1 cm x 10.6 cm)
Alarm Ratings
Notice
The sound output for the temporal (Code 3) tone is rated lower because the time the horn is off is averaged into the sound output rating. When the horn is producing a tone in the temporal mode its sound pressure is the same as the continuous mode.
Horn (Continuous, 2400 Hz)
Audible Device Current
28 mA RMS; 48 mA FWR
(maximum)
Sound output at 10 ft (3 m) at 24 VDC
High output: 86 dBA; Low output: 78 dBA
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1 Strobe or horn strobe with finish plate
1 Die‑cast mounting plate
1 GOE outdoor enclosure
1 Plastic test card
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Strobe Current (maximum) 180 mA RMS; 245 mA FWR
Voltage (Input):
• nominal 24 VDC or FWR
• range 16 VDC or FWR to 33 VDC or FWR
Horn (Continuous, Mechanical)
Audible Device Current
25 mA RMS; 44 mA FWR
(maximum)
Sound output at 10 ft (3 m) at 24 VDC
High output: 84 dBA; Low output: 76 dBA
Horn (Temporal Code 3, 2400 Hz)
Audible Device Current
28 mA RMS; 48 mA FWR
(maximum)
Sound output at 10 ft (3 m) at 24 VDC
High output: 83 dBA; Low output: 75 dBA
Horn (Temporal Code 3, Mechanical)
Audible Device Current
25 mA RMS; 44 mA FWR
(maximum)
Sound output at 10 ft (3 m) at 24 VDC
High output: 81 dBA; Low output: 73 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
Environmental
Temperature (Operating):
• Indoor +32°F to +120°F (0°C to +49°C)
• Outdoor -31°F to +150°F (-35°C to +66°C)
Loading...
+ 2 hidden pages