Fire Alarm Systems | WGE Weatherproof Strobes and Horn Strobes
WGE Weatherproof Strobes and Horn
Strobes
www.boschsecurity.com
The Gentex WGE family of weatherproof strobes and horn strobes offer dependable visible and audible alarms. The horns have a synchronizable (using the AVSM Synchronization Module) chime and whoop tones. You can select high or low volume and choose a 2400 Hz (remote signaling) tone or a low frequency (1500 Hz to 3000 Hz) mechanical sounding tone where doors could prevent hearing the other tone. They are easily field changeable from temporal Code 3 to a continuous tone. They are shipped from the factory on the temporal lower frequency mode, and come standard with a rugged die cast metal mounting plate. The strobes have a low operating current and a minimum flash rate of 1 Hz regardless of the input voltage.
These devices are equipped with the SuperSlide feature to test supervision and the Instant Voltage Verification feature for measuring voltage drop draw. The GOE Outdoor Enclosure is included with each unit. The unit and GOE enclosure must be used together to meet the UL outdoor listing.
uWide voltage range, 16 to 33 VDC or FWR
u75 cd strobe meets ADA 4.28.3 requirements
uListed for outdoor use when used with the GOE outdoor enclosure
uJumper selection for high or low frequency and for temporal Code 3 or continuous tone patterns
uSeparate horn and strobe functions; silences horn while strobes remain flashing
Certifications and approvals
Gentex Corporation holds these Listings and Approvals:
Region |
Certification |
|
|
|
|
USA |
UL |
ULSZ: Audible-signal Appliances |
|
|
(ANSI/UL 464), ULSZ7: Audible-signal |
|
|
Appliances Certified for Canada (CAN/ |
|
|
ULC-S525), UVAV: Visual-signal Appli- |
|
|
ances for Fire-protective Signaling Sys- |
|
|
tems (ANSI/UL 1638), and UEES7: Visu- |
|
|
al-signal Appliances Certified for Canada |
|
|
[CAN/ULC-S526 (1987)] |
|
CSFM |
see our website |
|
|
|
Installation/configuration notes
Compatible Products
The following products are compatible with these strobes and horn strobes:
Control Panels:
Active1: FPA-1000 family and FPD-7024 family
2 | WGE Weatherproof Strobes and Horn Strobes
Legacy1: D10024A, D9412, D8024, D70242, and D70223
Synchronization Modules:
AVSM R and AVSM W
1 For synchronization, use the AVSM R or AVSM W Synchronization Modules with these control panels.
2 When used with a D7039 Multiplex Expansion Module, the D7024 becomes an addressable fire alarm control panel (FACP).
3 The D7022 must be set for 24 VDC operation and requires the AVSM R or AVSM W Synchronization Modules for synchronization.
Mounting Considerations
For an outdoor application or a severe environment (NEMA 3R) application, the WGES Strobes and WGEC Horn Strobes must be surface mounted on a flat wall in a GOE Outdoor Enclosure. The enclosure is supplied. Knockout holes are sized for 3/4 inch conduit and matching connector. Use a watertight conduit fitting.
Wiring
Notice
Do not use these units in coded or pulsed signaling circuits.
The input terminals accept wires with diameters between 18 AWG and 12 AWG (ISO 0.75 mm2 and 4 mm2).
Parts included
Quant. Component
1Strobe or horn strobe with finish plate
1Die cast mounting plate
1GOE outdoor enclosure
1Plastic test card
1Hardware pack
1Literature pack
Technical specifications
Electrical
Strobe Current (maximum) |
180 mA RMS; 245 mA FWR |
|
|
|
|
Voltage (Input): |
|
|
|
|
|
• |
nominal |
24 VDC or FWR |
|
|
|
• |
range |
16 VDC or FWR to 33 VDC or FWR |
|
|
|
Environmental |
|
|
|
|
|
Temperature (Operating): |
|
|
|
|
|
• |
Indoor |
+32°F to +120°F (0°C to +49°C) |
|
|
|
• |
Outdoor |
-31°F to +150°F (-35°C to +66°C) |
|
|
|
Mechanical
Candela Rating |
75 cd |
|
|
|
|
Dimensions (HxWxD): |
|
|
|
|
|
• |
without GOE |
5 in. x 4.5 in. x 2.5 in. (12.7 cm x |
|
enclosure |
11.4 cm x 6.4 cm) |
|
|
|
• |
with GOE enclosure |
5.75 in. x 4.75 in. x 4.2 in. (14.6 cm x |
|
|
12.1 cm x 10.6 cm) |
|
|
|
Alarm Ratings
Notice
The sound output for the temporal (Code 3) tone is rated lower because the time the horn is off is averaged into the sound output rating. When the horn is producing a tone in the temporal mode its sound pressure is the same as the continuous mode.
Horn (Continuous, 2400 Hz)
Audible Device Current |
|
28 mA RMS; 48 mA FWR |
(maximum) |
|
|
|
|
|
Sound output at 10 ft (3 m) at |
|
High output: 86 dBA; Low output: |
24 VDC |
|
78 dBA |
|
|
|
|
|
|
Horn (Continuous, Mechanical) |
|
|
Audible Device Current |
|
25 mA RMS; 44 mA FWR |
(maximum) |
|
|
|
|
|
Sound output at 10 ft (3 m) at |
|
High output: 84 dBA; Low output: |
24 VDC |
|
76 dBA |
|
|
|
|
|
|
Horn (Temporal Code 3, 2400 Hz) |
|
|
Audible Device Current |
|
28 mA RMS; 48 mA FWR |
(maximum) |
|
|
|
|
|
Sound output at 10 ft (3 m) at |
|
High output: 83 dBA; Low output: |
24 VDC |
|
75 dBA |
|
|
|
|
|
|
Horn (Temporal Code 3, Mechanical) |
|
|
Audible Device Current |
|
25 mA RMS; 44 mA FWR |
(maximum) |
|
|
|
|
|
Sound output at 10 ft (3 m) at |
|
High output: 81 dBA; Low output: |
24 VDC |
|
73 dBA* |
|
|
|
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.