Bosch Solution 880 Operating Manual

EN
Operators Guide
Solution 880
CC408
CC408 | Operators Guide | Notices EN | 2
Bosch Security Systems | 5/04 | 920050O.OG.112
Copyright Notice
Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd (“Bosch”). All rights are reserved.
You may download a single copy of this publication. By downloading the publication you agree that you will: (i) only use the publication for your own reference; (ii) not commercially exploit or charge any person for the use of the publication; and (iii) not modify the publication in any way without the prior written permission of Bosch.
Except as specified above or where authorised by the Copyright Act 1968 (Cth), no part of this publication may be reproduced, transmitted, modified or stored, in any form or by any means, without the prior written permission of Bosch.
Notice of Liability
This material is designed for use by tradespeople with expertise in the installation of this product. Persons without appropriate expertise should seek assistance before attempting installation.
While care was taken in the preparation of this material, Bosch Security Systems Pty Ltd and its representatives are not responsible to any person or entity for any loss or damage directly or indirectly caused by information in, or any omission from, this material.
Bosch Security Systems Pty Ltd reserves the right to make changes to features and specifications of its products at any time without prior notification.
New Zealand Telepermit Notes
The grant of a telepermit for a device in no way indicates Telecom acceptance of responsibility for the correct operation of that device under all operating conditions.
This equipment will not be used in any manner that could constitute a nuisance to other telecom customers.
Immediately disconnect this equipment should it become physically damaged and arrange for its disposal or repair.
The transmit level from this device is set at a fixed level and because of this, there may be circumstances where the performance is less than optimal. Before reporting such occurrences as faults, please check the line with a standard telepermitted telephone and do not report a fault if the telephone performance is satisfactory.
This device is equipped with pulse dialling while the Telecom standard is DTMF tone dialling. There is no guarantee that Telecom lines will always continue to support pulse dialling.
Use of dialling, when this equipment is connected to the same line as other equipment, may give rise to bell noise and also cause a false answer condition. Should such problems occur, the user should not contact the Telecom Faults Service.
This equipment is set up to carry out test calls at pre­determined times. Such test calls interrupt any other calls that may be set up on the line at the same time. The timing set for such test calls should be discussed with the installer.
The timing set for test calls from this equipment may be subject to drift. If this proves to be inconvenient and your calls are interrupted, then the problem of timing should be discussed with the equipment installer. The matter should not be reported as a fault to Telecom Faults Service.
This equipment shall not be set up to make automatic calls to the Telecom 111 Emergency Service. This equipment should not be used under any circumstances that may constitute a nuisance to other Telecom customers.
In the event of any problem with this device, the systems battery, AC mains supply, and telephone line should be disconnected. The user is to arrange with the supplier of the device to make the necessary repairs. Should the matter be reported to Telecom as a wiring fault and the fault proven to be due to this product, a call-out charge will be incurred.
CC408 | Operators Guide | Contents EN | 3
Bosch Security Systems | 5/04 | 920050O.OG.112
Contents
1. Introduction ......................................................5
2. Specifications .................................................... 5
3. Features ............................................................. 5
4. Codepad Indicators.......................................... 6
4.1 Zone Indicators.................................................6
4.2 AWAY Indicator..............................................6
4.3 STAY Indicator ................................................6
4.4 System Disarmed..............................................6
4.5 MAINS Indicator .............................................7
4.6 Off Indicator/Zone Sealed .............................. 7
4.7 On Indicator/Zone In Alarm..........................7
4.8 FAULT Indicator ............................................. 7
4.9 Audible Indications..........................................7
5. Arming the System...........................................7
5.1 Arming in AWAY Mode.................................8
5.2 Arming in STAY Mode 1................................8
5.3 Arming in STAY Mode 2................................8
5.4 Programming STAY Mode 2 Zones ..............9
6. Disarming the System......................................9
7. User Codes........................................................9
7.1 Adding User Codes.......................................... 9
7.2 Adding Radio Remote User Codes................9
7.3 Deleting User Codes/Radio User Codes.......9
8. Radio Transmitter Operations......................10
9. Alarms .............................................................10
9.1 Duress Alarm..................................................10
9.2 Panic Alarm ....................................................10
9.3 Fire Alarm.......................................................11
9.4 Medical Alarm................................................ 11
9.5 Tamper Alarm (Access Denied) ...................11
10. Isolating Zones................................................11
10.1 Standard Isolating ..........................................11
10.2 Code to Isolate ...............................................11
11. Setting the Date and Time ............................ 11
12. Fault Analysis Mode ......................................12
12.1 AC Fail ............................................................12
12.2 System Faults ..................................................12
12.3 Fault Descriptions...........................................12
13. Telco Arm/Disarm Sequence (Call Forward
On/Off) ........................................................... 13
13.1 Telco Arm Sequence......................................13
13.2 Telco Disarm Sequence.................................13
14. Turning Outputs On/Off...............................14
15. Reset Latching Outputs................................. 14
16. Codepad ID/Buzzer Tone Change .............. 14
17. Testing............................................................. 14
17.1 Horn Speaker Test......................................... 14
17.2 Bell Test .......................................................... 14
17.3 Strobe Test...................................................... 14
17.4 Walk Test Mode............................................. 14
17.5 Test Report .....................................................14
18. Event Memory Recall.................................... 15
19. Day Alarm ...................................................... 15
20. Remote Arming By Telephone .................... 15
21. Domestic Dialling ..........................................16
21.1 Acknowledging Domestic Calls.................... 16
21.2 Programming Domestic Telephone
Numbers.......................................................... 16
21.3 Disable Domestic Dialling ............................16
22. Partitioning .....................................................17
22.1 Master Partitioned Codepad Indicators....... 17
22.1.1 Zone Indicators .............................................. 17
22.1.2 Area On/Off Indicators................................. 17
22.2.1 Area Display Indicators................................. 17
22.2.2 Status Indicators ............................................. 17
22.3 Operating From A Master Partitioned
Codepad.......................................................... 17
22.4 Operating From Area Addressable
Codepads ........................................................ 17
23. Basic Pager Reporting ...................................18
24. Glossary of Terms.......................................... 20
25. Installation Notes ........................................... 22
Figures
Figure 1: CP5 Eight Zone LED Codepad............... 6
Figure 2: CP5 Eight Zone LCD Codepad .............. 6
Figure 3: RE012 – 2 Channel Keyfob
Transmitter .............................................. 10
Figure 4: RE013 – 4 Channel Keyfob
Transmitter .............................................. 10
Figure 5: CP5 LED Codepad Showing Audible
Alarm Buttons ......................................... 10
Figure 6: Master Partitioned Codepad.................. 17
Figure 7: Basic Pager Display ................................19
CC408 | Operators Guide | Contents EN | 4
Bosch Security Systems | 5/04 | 920050O.OG.112
Tables
Table 1: Specifications ............................................. 5
Table 2: Zone Indicator ...........................................6
Table 3: AWAY Indicator....................................... 6
Table 4: STAY Indicator .........................................6
Table 5: MAINS Indicator ...................................... 7
Table 6: FAULT Indicator ......................................7
Table 7: Audible Indicators..................................... 7
Table 8: Arming Methods ....................................... 7
Table 9: Keyfob Audible/Visual Indications ......10
Table 10: Fault Condition Indicators .....................12
Table 11: Telco Arm/Disarm Dialling Digits........ 13
Table 12: Domestic Dialling Telephone Digits.....16
Table 13: Zone Status Display Descriptions.......... 18
Table 14: System Status........................................... 18
Table 15: Glossary of Terms...................................20
CC408 | Operators Guide | 1. Introduction EN | 5
Bosch Security Systems | 5/04 | 920050O.OG.112
1. Introduction
Congratulations on selecting the Solution 880 Model CC408 Control Panel to protect you and your property. To obtain the most from your unit, take the time to read through this manual and familiarise yourself with the operating features of this system. In all aspects of planning, engineering, styling, operation, convenience, and adaptability, we have sought to anticipate your every possible requirement.
Programming simplicity and speed were some of the major considerations and we believe that our objectives in this area were more than satisfied.
This guide explains all aspects of operating the control panel. All system parameters and options are detailed. Suitability is left up to the individual. Every system can be tailored to meet all requirements quickly and easily.
2. Specifications
Table 1: Specifications
Temperature Range
0oC to +45 oC (+32
o
F to +113 oF)
Humidity
10% to 95%
Power Source
TF008 Plug Pack – 240 VAC/18 VAC @ 1.3 A
Stand-By Current
65 mA
Current Draw In Alarm Condition
115 mA
Current Draw In Alarm Condition with Codepad
105 mA
Back-Up Battery
6 Ah/12 VDC Rechargeable sealed lead acid battery
Dimensions (case, packed in carton)
30.6 cm x 26.2 cm x 8.4 cm (12.05 in. x 10.31 in. x 3.31 in.)
Weight
2.5 Kg (5.51 lb.)
Supplier Code
N771
New Zealand Telepermit
PTC 211/98/083
Malaysia Approval Number
Pending
The Austel permit issued for this product is subject to the following conditions: The Solution 880 Model CC408 Control Panel can only be powered by a Bosch Security Systems TF008 Plug Pack (Approval Number Q92128).
Test the sirens, strobe, and zones at weekly intervals. See Section 17 Testing for further information.
3. Features
The Solution 880 Control Panel uses the latest in microprocessor technology to provide you with more useful features and superior reliability and performance. The main features of the control panel are listed below:
Eight programmable User Codes
STAY Mode and AWAY Mode operation
Six programmable burglary zones
Two programmable 24-hour zones
Siren and/or dialler lockout per zone
Delayed reporting
Built-in telephone fail monitor
Day alarm
Remote arming
Answering machine bypass
Event memory recall
Upload/download programmable
Auxiliary output (Output 2)
Relay output
Eight radio remote user codes
Entry and exit warning beeper
EDMSAT – satellite siren compatible
Separate fire alarm sound
Dual reporting
Sensor watch
Dynamic battery testing
Automatic arming/automatic disarming
AC fail and system fault indicators
Walk Test Mode
Monitored siren output (Output 1)
Strobe output
Telco arm/disarm sequence (call forwarding)
CC408 | Operators Guide | 4. Codepad Indicators EN | 6
Bosch Security Systems | 5/04 | 920050O.OG.112
4. Codepad Indicators
Figure 1: CP5 Eight Zone LED Codepad
Figure 2: CP5 Eight Zone LCD Codepad
The codepad is the communications interface between you and your alarm system. Use the codepad to issue commands. The codepad offers both visual and audible indications that guide you through the general operation.
The codepad incorporates numerous indicators. There are zone indicators that show the condition of each zone and four other indicators for general status. The following pages outline a list of situations and the relevant indicators that are seen.
4.1 Zone Indicators
1 2 3 ….
The zone indicators (1 to 8) display the status of the zones. Table 2 lists the various situations that the indicators display (such as, Zone Sealed/Zone Unsealed).
Table 2: Zone Indicator
Zone Indicator Definition
On Zone is unsealed. Off Zone is sealed. Flashing Fast
(0.25 seconds on/
0.25 seconds off)
Zone is in alarm condition.
Flashing Slow (1 second on/ 1 second off)
Zone is manually isolated or selected to be isolated.
4.2 AWAY Indicator
The AWAY indicator displays the system is armed in AWAY Mode. The AWAY indicator also flashes in unison with the STAY indicator when programming various options throughout the Operators Guide.
See Section 5.1 Arming in AWAY Mode for information on the different methods of arming the system in AWAY Mode.
Table 3: AWAY Indicator
AWAY Indicator
Definition
On System is armed in AWAY Mode. Off System is not armed in AWAY Mode.
4.3 STAY Indicator
The STAY indicator displays the system is armed in STAY Mode 1 or STAY Mode 2. The STAY indicator also flashes in unison with the AWAY indicator when programming various options throughout the Operators Guide.
See Section 5.2 Arming in STAY Mode 1 for different methods of arming in STAY Mode 1. See Section 5.3 Arming in STAY Mode 2 to arm in STAY Mode 2.
Table 4: STAY Indicator
STAY Indicator
Definition
On System is armed in STAY Mode 1 or
STAY Mode 2.
Off System is not armed in STAY Mode 1
or STAY Mode 2.
Flashing twice a second
Zone Isolating Mode or setting STAY Mode 2 zones.
Flashing once every 3 seconds
Day alarm status – day alarm turned on.
4.4 System Disarmed
This indicator displays with the indicator when the system is disarmed.
CC408 | Operators Guide | 5. Arming the System EN | 7
Bosch Security Systems | 5/04 | 920050O.OG.112
4.5 MAINS Indicator
The MAINS indicator displays the systems AC mains supply is normal or failed.
Table 5: MAINS Indicator
MAINS Indicator Definition
On AC mains power normal. Flashing AC mains supply failed.
4.6 Off Indicator/Zone Sealed
The
indicator displays when the system is in the disarmed state and flashes when a zone becomes unsealed during the disarmed state. The indicator stops flashing when all zones are sealed.
4.7 On Indicator/Zone In Alarm
The
indicator displays when the system is armed in AWAY Mode and flashes when an alarm occurs. The indicator resets once a valid user code is entered.
4.8 FAULT Indicator
The FAULT indicator displays the system detected a system fault. See Section 12. Fault Analysis Mode for additional information on system faults.
Every time a new system fault is detected (such as, FAULT indicator flashing), the codepad beeps once every minute. Pressing the [#] button once cancels the once a minute beep and acknowledges the fault (such as, FAULT indicator on steady).
Table 6: FAULT Indicator
FAULT Indicator
Definition
On There is a system fault that must be
rectified. Off The system is normal, there are no faults. Flashing There is a system fault that must be
acknowledged.
4.9 Audible Indications
Table 7 defines the audible indicators
generated by the codepad buzzer.
Table 7: Audible Indicators
Audible Indicator Definition
One short beep A button was pressed on the
codepad, or end of exit time when armed in STAY Mode 1 or STAY
Mode 2. Two short beeps The system accepted your code. Three short beeps The requested function was
executed. One long beep Indicates the end of exit time when
armed in AWAY Mode, or the
requested operation was denied or
aborted. One beep every
second
Walk Test Mode is currently active
or warning before automatic arming
takes place. One short beep
every minute
There is a system fault waiting to
be acknowledged.
5. Arming the System
There are several ways to arm the system depending on whether you are:
Leaving the premises and require all active zones to be in a ready state for an intruder.
Remaining in the premises and only require part of the system to be in a ready state for an intruder.
If a zone is not sealed at the end of exit time, the zone is automatically isolated and constantly displays on the remote codepad. The zone becomes an active part of the system when the zone reseals. For example, if a window is left open after exit time expires, the window is not an active part of the system until the window is closed. Opening the window after exit time expired causes an alarm condition.
Table 8 defines the different methods for arming the system.
Table 8: Arming Methods
AWAY Mode
Arms the entire system. See Section 5.1 Arming in AWAY Mode.
STAY Mode 1
Arms all zones except those programmed to be automatically isolated by the installer. See Section 5.2 Arming in STAY Mode 1.
STAY Mode 2
Arms all zones except those programmed to be automatically isolated by the Master Code holder. See Section 5.3 Arming in STAY Mode 2.
CC408 | Operators Guide | 5. Arming the System EN | 8
Bosch Security Systems | 5/04 | 920050O.OG.112
Forced Arming
The feature of arming the system when a zone is not sealed is known as forced arming. If the system does not arm and a long beep is heard, forced arming is not permitted. If this is the case, ensure that all zones are sealed or manually isolated before arming the system.
5.1 Arming in AWAY Mode
When you leave your premises and require all zones to be in a ready state to detect intrusion, you arm the system in AWAY Mode. When returning to your premises, disarm your system (see Section 6. Disarming the System) so you do not sound a false alarm.
There are two different methods for arming the system in AWAY Mode. Method one is standard and always operates. Method two is optional and may be disabled by your installer if you do not want to use single button arming.
Arming in AWAY Mode, Method 1
Enter your user code followed by the [#] key (for example, [2 5 8 0 #]). Two beeps sound and the AWAY indicator displays. Exit time starts counting.
Arming in AWAY Mode, Method 2
Hold down the [#] key until two beeps sound. The AWAY indicator displays and exit time starts counting.
5.2 Arming in STAY Mode 1
STAY Mode 1 is only used when the perimeter and unused areas of the premises must be armed to detect if an intruder is entering the premises. At the same time it allows you to move freely within an area that is automatically isolated.
Only your security company can program zones automatically isolated in STAY Mode 1.
There are two different methods for arming the system in STAY Mode 1. Method one is standard and always operates. Method two is optional and may be disabled by your installer if you do not want to use single button arming.
Entry Guard Timer for STAY Mode 1
When arming the system in STAY Mode 1, an optional entry timer called Entry Guard Timer For STAY Mode 1 is available. Use this entry timer to delay the sirens if a zone is not automatically isolated and triggers an alarm condition. Entry Guard Timer For STAY Mode 1 is the delay time used for all zones except 24-hour zones when the system is armed in STAY Mode 1 or STAY Mode 2.
If the Entry Guard Timer For STAY Mode 1 is programmed and a zone not automatically isolated is triggered, the codepad beeps twice per second until the entry timer expires or the system disarms. If the alarm condition is not reset by entering your user code followed by the [#] key (for example, [2 5 8 0 #]) before the entry timer expires, the sirens activate into alarm. Only your installer can program this feature.
Arming in STAY Mode 1, Method 1
Enter your user code followed by the [*] key (for example, [2 5 8 0 *]). Two beeps sound and the STAY indicator displays. Exit time starts counting.
Any zones programmed to be automatically isolated in STAY Mode 1 flash until exit time expires. At the end of exit time, all zones selected to be automatically isolated turn off and the codepad gives one short beep.
Arming in STAY Mode 1, Method 2
Hold down the [*] button until two beeps are heard. The STAY indicator displays and exit time starts counting.
Any zones programmed to be automatically isolated in STAY Mode 1 flash until exit time expires. At the end of exit time, the zone indicators turn off and the codepad emits one short beep.
5.3 Arming in STAY Mode 2
STAY Mode 2 is only used when the perimeter and unused areas of the premises must be armed to detect an intruder from entering the premises while you move freely within an area that is automatically isolated. Any Master Code user can program zones to be automatically isolated in STAY Mode 2.
Entry Guard Timer For STAY Mode 2
When arming the system in STAY Mode 2, an optional entry timer called Entry Guard Timer For STAY Mode 2 is available. Use this entry timer to delay the sirens if a zone is not automatically isolated and triggered into alarm condition. Entry Guard Timer for STAY Mode 2 is the delay time used for all zones except 24-hour zones when the system is armed in STAY Mode 1 or STAY Mode 2.
If the Entry Guard Timer For STAY Mode 2 is programmed and a zone not automatically isolated triggers, the codepad beeps twice a second until the entry timer expires or the system disarms. If the alarm condition is not reset by entering your user code followed by the [#] button (for example, [2 5 8 0 #]) before the entry timer expires, the sirens activate into alarm. Only your installer can program this option.
CC408 | Operators Guide | 6. Disarming the System EN | 9
Bosch Security Systems | 5/04 | 920050O.OG.112
Arming in STAY Mode 2
Hold down the [0] button until two beeps sound. The STAY indicator lights and exit time starts counting.
Any zones programmed to be automatically isolated in STAY Mode 2 flash until exit time expires. At the end of exit time, all zones selected to be automatically isolated extinguish and the codepad provides one short beep.
5.4 Programming STAY Mode 2 Zones
You can only program zones to be automatically isolated in STAY Mode 2 if you have a Master Code.
How to Program STAY Mode 2 Zones
1. Enter your four-character Master Code, followed by the [4] and [#] keys (for example, [2 5 8 0 4 #]). Three beeps sound and the STAY indicator flashes.
2. Enter the zone number to be automatically isolated, followed by the [*] key (for example, [1 *] = Zone 1, [2 *] = Zone 2). The selected zone flashes. If you make a mistake, enter the same zone number followed by the [#] key to clear the incorrect zone. To select additional zones to be automatically isolated in STAY Mode 2, repeat Step 2 as many times as required.
3. To exit this mode, press the [#] key when you have selected all zones to be automatically isolated in STAY Mode 2. Two beeps sound and the STAY and AWAY indicators turn dark.
6. Disarming the System
When you enter the premises after the system is armed in AWAY Mode, or if you have armed the system in STAY Mode 1 or STAY Mode 2, you must disarm the system before entry time expires to disable detection devices that activate an alarm. Only your installer can program the entry time.
If there was an alarm condition prior to disarming the system, a flashing zone indicator displays indicating a previous alarm on that zone.
How to Disarm the System
Enter your user code followed by the [#] key (for example, [2 5 8 0 #]). Two beeps sound.
7. User Codes
7.1 Adding User Codes
Only the Master Code holder can add or change other system user codes, including the Master Code. Up to eight user codes can be programmed to operate the system.
How to Add a User Code
1. Enter your four-character Master Code, followed by [1] and [#] (for example, [2 5 8 0 1 #]). Three beeps sound and the STAY and AWAY indicators flash.
2. Enter the user code number (1 to 8) followed by the [#] key (for example, [2 #] = User 2, [8 #] = User 8). Two beeps sound and the selected user number displays on the codepad indicators.
3. Enter the digits required for the new code followed by the [#] key (for example, for user code 5768, enter [5 7 6 8 #]). Two beeps sound and the STAY and AWAY indicators turn dark. To add or change other user codes, repeat this procedure as many times as required.
7.2 Adding Radio Remote User Codes
Only the Master Code holder can add or change other system user codes, including the Master Code. Up to eight radio user codes (User Codes 9 to 16) can be programmed to operate the system.
How to Add a Radio Remote User Code
1. Enter your four-character Master Code, followed by the [1] and [#] keys (for example, [2 5 8 0 1 #]). Three beeps sound and the STAY and AWAY indicators flash.
2. Enter the radio remote user code number (9 to
16), followed by the [#] key (for example, [9 #] = User 9, [1 6 #] = User 16). Two beeps sound and the selected user number displays on the codepad indicators.
3. Press any button on the keyfob so the system learns the ID number. Two beeps sound and the STAY and AWAY indicators extinguish. To add or change other radio remote user codes, repeat this procedure as many times as required.
7.3 Deleting User Codes/Radio User
Codes
Only the Master Code holder can delete other system user codes.
How to Delete a User Code
1. Enter your four-character Master Code, followed by the [1] and [#] keys (for example, [2 5 8 0 1 #]). Three beeps sound and the STAY and AWAY indicators flash.
2. Enter the user code number (User Code 1 to 8, Radio User Code 9 to 16), followed by the [#] key (for example, [2 #] = User 2, [1 6 #] = User
16). Two beeps sound and the selected user number displays on the codepad indicators.
3. Press the [*] key to delete the selected user code. Two beeps sound and the STAY and AWAY indicators turn dark. To delete other user codes, repeat this procedure as many times as required.
Loading...
+ 19 hidden pages