Bosch SM024, SM060, SM070, SM036, SM048 Installation, Operation And Maintenance Manual

SM Series Heat pump
SM024 | SM036 | SM048 | SMO60 | SM070
Installation, Operation and Maintenance Manual
6 720 220 406 (2015/02)
2 |
SM Series Heat Pump
Key to Symbols...................................................................3
Safety Warnings ................................................................ 3
Standard package.............................................................. 3
Model Nomenclature.......................................................... 3
General Description........................................................... 5
Moving and Storage ........................................................... 6
Initial Inspection ............................................................... 6
Location............................................................................ 6
Configurability .................................................................. 7
Horizontal Configurability .................................................. 7
Required Tools ............................................................ 7
Instructions - Left-Hand Unit (SM0**-1HZ-*L*-**) ............... 7
Instructions - Right-Hand Unit (SM0**-1HZ-*R*-**) ........... 10
Counter-Flow configurability............................................ 13
Vertical Configurability.................................................... 13
Required Tools .......................................................... 15
Access to Internal Components.................................... 15
Blower Re-Configuration ............................................. 17
Condensate Drain Connection Re-configuration ............. 20
HRP Switch Relocation ............................................... 21
Electric Heat Relocation.............................................. 22
Electrical Box re-configuration ..................................... 24
Reinstall All Panels ..................................................... 25
Return and Discharge Duct Flanges .................................. 25
Pre Installation Unit Preparation ...................................... 26
Corner Cap Installation Instructions .............................. 26
DPS Water Flow Proving..............................................38
Pump Relay ............................................................... 38
Comfort Alert Module .................................................38
Smart Start Assist.............................................................39
Mode of Operation Notes............... ...............................40
Heat Recovery Package .................................................... 41
Water Tank Preparation ..............................................41
HR Water Piping.........................................................41
Water Tank Refill ........................................................42
Initial Start-Up ...........................................................42
Sequence of Operation.....................................................43
Cooling Mode ............................................................ 43
Heating Mode ............................................................43
Application Considerations ..............................................45
Well Water Systems.................................................... 45
Cooling Tower/Boiler Systems ..................................... 45
Geothermal Systems ..................................................47
System Checkout .............................................................48
Unit Start-up....................................................................48
Maintenance ...................................................................49
Unit Check-Out Sheet .......................................................50
Customer Data...........................................................50
Unit Nameplate Data................................................... 50
Operating Conditions..................................................50
Auxiliary Heat ............................................................50
Troubleshooting ..............................................................51
Electronic Thermostat Installation ....................................56
Operating Temperatures and Pressures ............................ 57
Airflow Tables..................................................................62
Mounting Vertical Units ................................................... 27
Mounting horizontal Units ................................................ 27
Hanging Bracket kit..........................................................27
Condensate Drain ............................................................ 28
Duct System.................................................................... 29
Piping ............................................................................. 29
Electrical ........................................................................ 30
Safety Devices and the UPM Controller ......................... 31
ECM INTERFACE BOARD ............................................ 35
Dehumidification Method Selector ............................... 36
Constant Torque Motors (ECM).................................... 36
Options........................................................................... 37
Hot Gas Reheat (HGRH).............................................. 37
Electric Heat ............................................................. 37
Heat Recovery Package (HRP) ..................................... 37
Constant Airflow Motor............................................... 38
Water Side Pressure Drop Table........................................64
Wiring Diagrams ..............................................................65
WIRING HARNESS DRAWINGS ..........................................72
Constant Torque Motor (SM0**-***-***-T*)........................72
Constant Airflow Motor (SM0**-***-***-A*) ....................... 73
Spare Parts List ...............................................................74
Dimensional Drawings......................................................95
Horizontal - Straight Through .......................................96
Horizontal - Hanging bracket location ............................97
Counter Flow.................................................. ...........98
CF Vertical ................................................................99
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Key to Symbols | 3SM Series Heat Pump
1
2
3
4
KEY TO SYMBOLS
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of the warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in
damage to property or equipment.
CAUTION indicates a situation that could
result in minor to medium injury.
WARNING indicates a situation that could
result in sever injury or death.
DANGER indicates a situation that will result in
severe injury or death.
Important Information
This symbol indicates important information where there is no risk to property or people.
SAFETY WARNINGS
NOTE: All refrigerant discharged from this
unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
NOTE: To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. Doing so may affect the unit’s warranty. The mechanical components and filters will quickly become clogged with construction dirt and debris, which may cause system damage.
STANDARD PACKAGE
WARNING: Installation and servicing of this
equipment can be hazardous due to system pressure and electrical components. Only trained and qualified personnel should install, repair, or service the equipment.
WARNING: Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.
WARNING: When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing, and place a fire extinguisher close to the work area.
NOTE: To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.
Figure # 1
[1] SM Series Water-to-Air Heat Pump [2] Corner Caps Package [3] Installation and Operation Manual [4] Hanging Bracket kit (HZ unit only)
6 720 220 406 (2015/02)Revised 02-15
4 | Model Nomenclature
SM024 - 1 VT C - S LTATA - XXGAEXXXX7XXXX5XXXX SB A
SM
75VA Transformer +
Size
024
036 Refrigeration Circuit Options
H - Hot Gas Reheat - On/O
070 D - Heat Recovery Package
Voltage
1 208-230/60/1 General Electrical Options (up to 5 available per unit)
A - EMS relay
Cabinet Conguration E - Pump/valve relay
HZ - Horizontal H - Flow proving switch (DPS)
VT - Vertical N - Comfort Alert Module
CF - Downow (Counterow) S - Smart Start Assist
X - As default for non used electrical codes
Coax Options
N - Cupro-Nickel Application
G - EXTENDED RANGE (Geothermal)
Water Connections
y
F - Front (HZ only) Cabinet Construction
H - Painted Steel / 1/2" Closed Cell Foam
Return Air Conguration
Electric Heat (Dual power connection)
(Not Available with HGRH)
Discharge Air Conguration X - None
T - Top (VT only) A - 5 kW
E - End (HZ only) C - 10 kW
B - Bottom (CF only) D - 15 kW
E - 20 kW
Fan/Motor Options
Revision Level
T - Constant Torque ECM A - Current
Air Coil
T- Tin Plated
MERV13 - 2" w/ 4-SIDED FILTER RACK
MODEL NOMENCLATURE
SM Series Heat Pump
)
048 X - None
060
L - Left
R - Right
A - Constant Airow ECM
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
C - Copper
Figure # 2
S - Side (VT and CF onl
General Description | 5SM Series Heat Pump
1
2
3
4
5
6
7
9
10
3
8
10
GENERAL DESCRIPTION
SM Series Water-to-Air Heat Pumps provide the best combination of performance and efficiency available. All units are performance certified to American Heating and Refrigeration Institute (AHRI) ISO Standard 13256-1. All SM Water-to-Air Heat Pumps conform to UL1995 standard and are certified to CAN/CSA C22.2 No 236 by Intertek­ETL. The Water-to-Air Heat Pumps are designed to operate with entering fluid temperature between 20°F to 90°F in the heating mode and between 30°F to 120°F in the cooling mode
NOTE: Heat Pump operating under extreme conditions will have limitation on air/fluid flow rates and/or temperatures.
.
NOTE: 50° F Minimum Entering Water Temperature (EWT) is recommended for well water applications with sufficient water flow to prevent freezing. Antifreeze solution is required for all closed loop applications and EWT below 45°. Cooling Tower/Boiler and Geothermal applications should have sufficient antifreeze solution to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty. Other equivalent methods of temperature control are acceptable.
Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained. Each unit has externally mounted LCD error code display, allowing unit diagnosis without opening the cabinet. Basic Horizontal unit layout and connections are shown in Figure #3 . Refer to Dimensional Drawings for further detail, as well as Vertical and Counter Flow unit details. Pg#95 through Pg#95
SM Series Water-to-Air Heat Pumps are available in Vertical (VT), Horizontal (HZ) and Counter-Flow (CF) configurations. VT units are field convertible for three discharge/supply air orientations and left-hand (LH) or right-hand (RH) return configurations. HZ units have two field configurable discharge/supply air orientations.
Several factory installed options are available: Hot Gas Reheat, Electric Heat, Heat Recovery Package, Smart Start Assist, Constant Airflow Blower Motor, DPS Water Flow Proving Switch, Auxiliary Pump
Figure # 3
Relay, and Comfort Alert Module. Electric Heat and Smart Start Assist are also available as field installed accessory. See Pg#37 for more detail.
[1] LCD Error Code Display [2] Air handler access panel [3] Condensing section access panel [4] Condensate drain connection [5] Water connection [6] Heat Recovery water connection (Optional) [7] Heat Recovery disconnect switch (Optional) [8] Electrical connection knockout
6 720 220 406 (2015/02)Revised 02-15
6 | Moving and Storage
[9] Electric Heat electrical connection knockout (Optional)
[10] Blower outlet (Supply Air)
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area. Units must only be stored or moved in the normal upright position as indicated by the “UP” arrows on each carton at all times.
WARNING: For storage If unit stacking is required, stack units as follows:
Vertical units: less than 6 tons, no more than two high.
Horizontals units: less than 6 tons, no more than three high.
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember that the purchaser is responsible for filing the necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
SM Series Heat Pump
LOCATION
Locate the unit in an indoor area that allows easy removal of the filter and access panels, and has enough room for service personnel to perform maintenance or repair. Provide sufficient room to make fluid, electrical, and duct connection(s). If the unit is located in a confined space such as a closet, provisions must be made for return air to freely enter the face of unit’s air coil. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping.
NOTE: These units are not approved for outdoor installation; therefore, they must be installed inside the structure being conditioned. Do not locate in areas that are subject to freezing.
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Configurability | 7SM Series Heat Pump
1
1
2
2
CONFIGURABILITY HORIZONTAL CONFIGURABILITY
The Horizontal Configuration water source heat pump is designed to have a field configurable blower orientation: end blow (default) and straight through. (Figure #4 and #5)
Figure # 4
1/4" hex head driver
Needle nose pliers
5/16”-1/4” ratchet wrench
NOTE: Discharge air configuration change is not possible on Heat Pumps equipped with Electric Heat Option.
Instructions - Left-Hand Unit (SM0**­1HZ-*L*-**)
1. Remove and retain end and side panels.(Figure #6)
Figure # 5
Left-Hand and Right-hand Horizontal (HZ) units have different Blower Configuration instructions.
---------------------------------------------------------------
Left- Hand unit instructions refer to Pg#7 and
Right-Hand unit instructions refer to Pg#10.
Internally mounted electric heat is only available in End Blow configuration.
Blower configuration changes should be done prior to unit being installed in the final location.
Figure # 6
2. Disconnect blower motor wiring and ground wire fastened to blower housing.(Figure#7)
Figure # 7
Required Tools
5/16" hex head driver
•3/8" hex head driver
7/16" hex head driver
Flat screw driver
Phillips screw driver
6 720 220 406 (2015/02)Revised 02-15
8 | Horizontal Configurability
SM Series Heat Pump
3. Remove and retain bracket by removing (3) screws. (Figure #8)
Figure # 8
4. Loosen blower assembly by removing (4) screws. (Figure #9)
6. Rotate the blower into its new position.(Figure#11)
Figure # 11
7. Remove and retain remaining bracket by removing (2) screws. (Figure #12)
Figure # 9
5. Remove and retain bracket by removing (2) screws. (Figure #10)
Figure # 10
Figure # 12
8. Remove the blower assembly by sliding it forward. (Figure #13)
Unit top is notched to allow blower to slide through.
Figure # 13
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Horizontal Configurability | 9SM Series Heat Pump
1
2
1
2
9. Remove and discard blower collar by removing (8) screws. (Figure #14)
Figure # 14
10. Reorient the blower assembly 180 degree with blower “belly” down and slide back into the cabinet. (Figure #15)
12. Reinstall bracket removed in step (#3) using (3) screws in the same location. (Figure#17)
Figure # 17
13. Reinstall remaining bracket using (2) screws. (Figure#18)
Figure # 15
11. Reinstall bracket in the new vertical position using (2) screws. (Figure #16)
Figure # 16
Figure # 18
14. Connect vertical and horizontal brackets by installing (4) screws. (Figure#19)
Figure # 19
15. Reconnect blower motor wiring and ground wire.
6 720 220 406 (2015/02)Revised 02-15
10 | Horizontal Configurability
2
1
3
1
1
2
2
SM Series Heat Pump
16. Remove and retain plastic Blower opening cover by removing (6) screws and reinstall it in the new location (Figure#20 and #21)
Figure # 20
Instructions - Right-Hand Unit (SM0**­1HZ-*R*-**)
1. Remove and retain end and side panels.(Figure#22)
Figure # 22
2. Disconnect blower motor wiring and ground wire fastened to blower housing.(Figure#23)
Figure # 21
17. Reinstall all unit panels.
Figure # 23
3. Remove and retain (4) screws under the blower collar. (Figure #24)
Figure # 24
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
NOTE: Air coil is in close proximity to the blower. Air coil fins are easily damaged. Great care must be taken during this step to avoid coil damage. Shipping cardboard can be used as protection during blower removal and installation.
4. Slide blower assembly away from mounting bracket. (Figure #25)
Horizontal Configurability | 11SM Series Heat Pump
6. Remove and discard horizontal blower bracket by removing (3) screws. (Figure #27)
Figure # 27
7. Rotate the blower into its new position.(Figure#28)
Figure # 25
5. Remove and retain (1) vertical bracket by removing (2) screws. (Figure #26)
Figure # 26
Figure # 28
8. Remove and retain remaining vertical blower bracket by removing (2) screws. (Figure #29)
Figure # 29
6 720 220 406 (2015/02)Revised 02-15
12 | Horizontal Configurability
SM Series Heat Pump
9. Remove the blower assembly by sliding it forward. (Figure #30)
Unit top is notched to allow blower to slide through.
Figure # 30
10. Remove and discard blower collar by removing (8) screws. (Figure #31)
11. Reorient the blower assembly 180 degree with blower “belly” up. (Figure #32)
Figure # 32
12. Move the blower back into the cabinet. (Figure #33)
Figure # 31
Figure # 33
13. Reinstall (2) vertical blower brackets in the new horizontal position using (4) screws. (Figure #34)
Figure # 34
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
14. Secure (2) the now horizontal blower brackets
2
1
3
to the unit base using (4) screws. (Figure#35)
Figure # 35
15. Reconnect blower motor wiring and ground wire.
16. Remove and retain plastic Blower opening cover by removing (6) screws and cutting/ tearing insulation at perforations around the perimeter of cover. Reinstall it in the new location (Figure#36 and #37)
Counter-Flow configurability | 13SM Series Heat Pump
Figure # 37
17. Reinstall all unit panels.
COUNTER-FLOW CONFIGURABILITY
The Counter-Flow Configuration water source heat pump is a dedicated down flow configuration. Available from the factory in Left-hand and right­hand return air configurations.
VERTICAL CONFIGURABILITY
The Vertical (VT) Configuration water source heat pump is designed to be field configured for various configurations. This is achieved by relocating Electrical box (E-box), unit panels and reorienting blower to discharge UP, BACK OR SIDE. See Figure #37 through #41 for more detail.
The unit, as shipped from the factory, does not have configuration on the discharge air from to side or back, field configuration kit is requiered, (sold as an accessory Kit).
Figure # 36
Discharge air configuration change is not possible on Heat Pumps equipped with Electric Heat Option.
Blower, E-box and panel configuration changes should be done prior to unit being installed in the final location.
6 720 220 406 (2015/02)Revised 02-15
14 | Vertical Configurability
1
2
3
Figure # 38 Top Discharge (Default)
SM Series Heat Pump
Figure # 39 Back Discharge
Figure # 40 Side Discharge
Figure # 41
[1] Logo/Front Panel [2] Electrical Box [3] Default Configuration (can be ordered as either
right or left hand return)
Internally mounted electric heat is only available in Top Discharge configuration. See table below for details
Blower Orientation and Electric Heat
Compatibility
Up Yes Internally or Duct Mounted
Back
Blower
Side
Duct Mounted Duct Mounted
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Required steps Possible unit configurations
How to use this table:
Select desired configuration from “possible unit configurations”.
Instructions with “X” have to be performed to reconfigure the unit.
Vertical Configurability | 15SM Series Heat Pump
ACCESS TO INTERNAL COMPONENTS (PG#15)
BLOWER RE-CONFIGURATION (PG#17)
E-BOX CONFIGURATION (PG#24)
ELECTRIC HEAT RELOCATION* (PG#22)
CONDENSATE DRAIN RELOCATION (PG#20)
HRP SWITCH* (PG#21)
REINSTALL PANELS (PG#25)
*APPLIES IF OPTION IS INSTALLED [1] AIR COIL [2] E-BOX (UNIT FRONT) [3] BLOWER X APPLICABLE STEP
All heat pumps are supplied with panel belt which needs to be removed to access screws for panel removal. The panels have additional internal fasteners to prevent any air leakage.
For safety precautions two persons are required to perform this operation.
Left return,
top discharge
Right return,
top
discharge
Left return,
rear
discharge
Right
return, rear
discharge
XXXXX
X XXX
X XX
X*
X XX
X* X* X* X*
XXXXX
Access to Internal Components
1. Using a Flat Screw driver remove and retain Panel Belt by inserting the screwdriver into the slot and releasing the catch. (Figures#42and#43)
The belt is held in place by a clip on one side and an interference fit on the other end.
Right return,
left
discharge
Left return,
right
discharge
Required Tools
5/16" hex head driver
•3/8" hex head driver
7/16" hex head driver
Flat screw driver
Phillips screw driver
•1/4" hex head driver
Needle nose pliers
Figure # 42
6 720 220 406 (2015/02)Revised 02-15
16 | Vertical Configurability
1) UP
2) AWAY
1) UP
2) AWAY
Figure # 43
2. Remove and retain Condensing Section access panels (bottom panel) by removing (3) screws. (Figure #44)
SM Series Heat Pump
Figure # 45
Figure # 44
3. Remove and retain Air Handler Panel by lifting up and out as shown in Figure #46. Remove panel about 12" away from the cabinet and unplug LCD screen wiring. (Figures #45 and#46)
The unit panel mounted diagnostic display is connected to the heat pump controls with a wire harness. Use care when removing the display panel and carefully disconnect and reconnect the harness when repositioning the panel.
Figure # 46
4. Repeat steps 1–3 for all three sides.
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Blower Re-Configuration
This instruction details re-configuration of blower from UP to SIDE discharge. Re­configuration to other side uses similar steps.
1. Remove and retain diagonal support brackets on Front and Back sides of the unit. (Figure #47)
Vertical Configurability | 17SM Series Heat Pump
Figure # 49
4. Remove screws on both sides of the blower securing vertical blower bracket to horizontal support.(Figure#50)
Figure # 47
2. Unplug electrical connections of Blower motor and ground wire connected to blower housing. (Figure #48)
Figure # 48
3. Remove and retain blower motor and inlet ring assembly by removing (3) bolts securing blower motor bracket and screws securing the blower inlet ring. (Figure #49)
Figure # 50
5. Remove and retain blower assembly by lifting up. (Figure #51)
Air coil is in close proximity to the blower and air coil fins are easily damaged. Great care must be taken during this step to avoid coil damage. Shipping cardboard can be used as protection during blower removal and installation.
Removing the blower motor and blower wheel greatly simplifies handling of the blower assembly and reduces the chance of damaging heat pump components.
6 720 220 406 (2015/02)Revised 02-15
18 | Vertical Configurability
1
2
FRONT OF THE PANEL VIEW
Figure # 51
6. Remove and discard blower collar. (Figure #52)
Discharge air configuration change is not possible on Heat Pumps equipped with Electric Heat Option.
SM Series Heat Pump
7. Remove and retain side panel blower opening cover by removing (6) phillips head screws and cutting/tearing insulation at perforations around the perimeter of cover.(Figures #53 and #54)
Figure # 53
Figure # 52
Figure # 54
8. Reinstall blower opening cover in the TOP panel. (Figure #55)
Figure # 55
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Vertical Configurability | 19SM Series Heat Pump
9. Remove and retain (2) horizontal blower support brackets by removing (4) screws in each. (Figure #56)
Upper bracket contains two push-in rubber bump stops.
Figure # 56
10. Reinstall brackets removed in Step (9) on the same side of the unit as the blower outlet. (Figure #57)
11. Remove and retain vertical brackets from blower by removing (4) screws, (2) on each side of the blower. (Figure #58)
Figure # 58
12. Reinstall vertical brackets in new orientation. (Figure #59)
Ensure bracket with push-in rubber bump stops is installed in the top position.
Figure # 57
Figure # 59
13. Reinstall the blower assembly in the new desired location, using the existing holes. (Figure
#60)
NOTE: Be aware of blower housing proximity to air side coil and potential for coil damage.
Figure # 60
6 720 220 406 (2015/02)Revised 02-15
20 | Vertical Configurability
SM Series Heat Pump
14. Reinstall blower motor and inlet ring assembly by reversing Step #6. (Figure #61)
Figure # 61
15. Reconnect blower motor electrical plug and ground wire.
16. Reinstall diagonal bracket(s). (Figure #62)
Condensate Drain Connection Re­configuration
When re-configuring the unit from Left-Hand Return to Right-Hand Return it is necessary to relocate condensate drain connection from FRONT left corner post to BACK left corner post.(Figure#63)
Figure # 63
1. Cut the condensate drain hose on the inside of cabinet.
Be sure to retain the spring
2. Remove and retain condensate drain plastic fitting and grommet from the hose by pulling it away from the hose (barb style connection). (Figure#64)
Figure # 62
Figure # 64
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Vertical Configurability | 21SM Series Heat Pump
3. Locate the BACK left condensate drain and remove and retain plastic plug covering the cutout. (Figure#65)
Figure # 65
4. Reinstall the removed plastic plugs in the original Condensate Drain Location.
5. Route the flexible plastic tube from FRONT left corner post to BACK left. (Figure#66)
NOTE: Avoid kinking the hose and/or creating a dip which could act as a second internal p-trap. Double trapped drain lines will not drain properly.
8. Reinstall condensate drain plastic fitting and bushing in its new location.(Figure#67)
Figure # 67
HRP Switch Relocation
The HRP Pump Disconnect Switch is shipped loose inside unit E-Box, to be connected to either FRONT right corner post or BACK right corner post.(Figure#68)
Figure # 66
6. Measure and cut the condensate drain hose to the appropriate length.
7. Insert spring onto condensate drain hose.
Figure # 68
1. From the inside of the unit remove (2) wires connected to HRP Pump Disconnect Switch.
6 720 220 406 (2015/02)Revised 02-15
22 | Vertical Configurability
1
2
SM Series Heat Pump
2. Identify a rectangular knockout and remove it. Along with insulation.(Figure#69)
Figure # 69
3. Route HRP Pump Disconnect switch wires to the new switch location.
NOTE: Do not route wiring over potentially hot surfaces or exposed sharp edges. Damage to wiring could result.
4. Install HRP Switch.
5. Reconnect the Switch wires.
2. Remove and retain the Electric Heat Element cover(s) by removing (4) screws in each.(Figure#71)
Figure # 71
3. Disconnect high voltage wiring a the Electric Heat Elements. (Figure#72)
Electric Heat Relocation
When changing the unit from Left-Hand Return to Right-Hand Return, it’s required to relocate Electric Heat Components to the opposite side of the blower in order to allow field servicing.
Electric Heat comes with (1) or (2) heating element inserts, depending on capacity. This instruction shows (1) heating element insert. Perform the same steps for the second insert, if present.
1. Identify Electric Heat components. (Figure#70)
Figure # 72
4. Remove and retain Electric Heat Element(s).(Figure#73)
Figure # 70
[1] Electric Heat Electrical Box
[2] Electric Heat Elements.
Figure # 73
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Vertical Configurability | 23SM Series Heat Pump
5. Disconnect main Electric Heat E-box plug.(FIgure#74)
Figure # 74
6. Remove and retain Electric Heat E-box by removing (2) screws.(Figure#75)
8. Remove and retain Blower collar cover(s). (FIgure#77)
Figure # 77
9. Re-install Electric Heat Elements in the new location. Ensure High Temperature Cutouts are located on the left side. (Figure#78)
Figure # 75
7. Re-install Electric Heat E-box in the new location. (Figure#76)
Figure # 76
Figure # 78
10. Route the Unit E-box to Electric Heat wiring harness to the new Electric Heat Element location.
11. Connect wiring harness to the connector on the side of Electric Heat E-Box. (Figure#79)
Figure # 79
6 720 220 406 (2015/02)Revised 02-15
24 | Vertical Configurability
HT-4
HT-3
HT-2
HT-1
HLS-1
HLS-2
HLS-3
HLS-4
BLACK
RED
SM Series Heat Pump
12. Reconnect high voltage wiring from Electric Heat E-Box and Heating Element(s) matching wire number to terminals as shown.(Figure#80)
Figure # 80
13. Re-install Electric Heat Elements Cover(s). (Figure#81)
CAUTION: take great care to ensure all wires are disconnected and none of the wires are 'snagged' on any components
Figure # 82
4. Reroute all of the disconnected wire bundles to the opposite side of the heat pump.
Figure # 81
Electrical Box re-configuration
E-box is designed to be removable to support field configuration of unit: Left-Hand Return and Right­Hand Return, and also to allow full access to compressor during servicing.
The Electrical box (E-Box) has a set of plugs that allows complete removal from the system while keeping the majority of its internal connections. (FIgure#123 & #124, Pg#72 and Pg#73)
1. Disconnect wiring harness by unplugging the following plugs: P18, P19, P20 and P23 (P12 if unit is equipped with Electric Heat). (FIgure#123 & #124, Pg#72 and Pg#73)
2. Disconnect compressor plugs at compressor.
3. Remove and retain Electric Box by removing (2) screws. (Figure #82)
NOTE: Do not route wiring over potentially hot surfaces or exposed sharp edges. Damage to wiring could result.
5. Install E-box in its new location by installing (2) screws. (Figure #83)
Figure # 83
6. Reconnect all the wiring disconnected in Step #1.
NOTE: Ensure all connectors are properly oriented and are fully engaged.
7. Identify and re-route LCD wiring harness to the new location.
Panel containing LCD always mounts on the same side as E-Box.
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Return and Discharge Duct Flanges | 25SM Series Heat Pump
8. Swap FRONT panel (containing LCD) to the BACK
Reinstall All Panels
1. Re-route the LCD wiring to the new location and reconnect LCD screen wiring. Reinstall panels. (Figure #84)
Panel containing LCD and Bosch Logo must be installed on the same side as Electrical Box.
Figure # 84
RETURN AND DISCHARGE DUCT FLANGES
Return and discharge opening duct flanges are shipped unfolded. Flanges bend lines are perforated allowing easy bending using standard sheet metal pliers or channel locks. (Figure #90)
Bend flanges one at a time.
NOTE: When re-installing panel, the “RED” cable from the LCD connector must be connected to the “R” terminal of the LCD PCB. The LCD will not work any other way.
2. Reinstall belts. (Figure#85)
Figure # 85
6 720 220 406 (2015/02)Revised 02-15
26 | Pre Installation Unit Preparation
T
B
A
T2
T1
T1
T1
T2
T2
A
A
A
A
SM Series Heat Pump
PRE INSTALLATION UNIT PREPARATION Corner Cap Installation Instructions
Each corner cap is stamped with one the following identifiers: T, T1,T2 B, B1, B2, A.
1. Identify Letter code on each Corner Cap. (Figure#86)
Figure # 86
2. In preparation for installation identify each Corner Cap location. (VT & CF Figure#87 and HZ Figure#88)
3. Remove adhesive backing and install each Corner Cap. (Figure#89 and#90)
Ensure cabinet surface is clean and free of debris to ensure proper Corner Cap Adhesion.
Figure # 87
Figure # 88
Figure # 89
Figure # 90
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Mounting Vertical Units | 27SM Series Heat Pump
VIBRATION PAD FULL SIZE
MOUNTING VERTICAL UNITS
Vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to minimize vibration transmission to the building structure. It is not necessary to anchor the unit to the floor. (Figure #91).
On VT and CF Units Condensate Drain pan is internally sloped. There is no internal P-Trap.
The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling.
The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4”drain connected to this secondary pan should be run to an eave at a location that will be noticeable.
If the unit is located in a crawl space, the bottom of the unit must be at least 4” above grade to prevent flooding of the electrical parts due to heavy rains.
HZ Units Condensate Drain pan is NOT internally sloped.
NOTE: Horizontal (HZ) units must be installed pitched toward the Condensate Drain Connection 1/8” per foot.
HANGING BRACKET KIT Installation Instructions
All horizontal units come with hanging bracket installation kit to facilitate suspended unit mounting using threaded rod.Hanging brackets are to be installed as shown in Figure #92.
Figure # 91
MOUNTING HORIZONTAL UNITS
While horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. The manufacturer recommends these be attached to the unit corners by hanger bracket kits. The rods must be securely anchored to the ceiling. Refer to the hanging bracket assembly and installation instructions for details.
WARNING: Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan if required by code, should be at least four inches larger than the bottom of the heat pump.
Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc. Some applications require an attic floor installation of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh.
Figure # 92
This kit includes the following: (5) Brackets (5) Rubber Vibration isolators (8) Screws #10x1/2 (not used for these models) (10) Bolts 1/4-28x12” Hex bolt
The following are needed and are to be field provided:
Threaded rod (3/8“ max dia) Hex nuts Washers (1-3/4“ min O.D.)
6 720 220 406 (2015/02)Revised 02-15
28 | Condensate Drain
1. Remove and discard factory provided screws from locations where hanging brackets will be installed shown in Figure #93
Figure # 93
2. Mount 5 brackets to unit corner post using the Bolts provided in the kit as shown on Figure # 94
SM Series Heat Pump
WARNING:Rods must be securely anchored
to the ceiling
WARNING: Do not re-use screws removed from the unit on step 1 to mount the hanging brackets to the unit.
Figure # 94
WARNING: Follow all applicable codes and
requirements when hanging this unit, selecting threaded rod material, etc.
Figure # 95
CONDENSATE DRAIN
Figure # 96
A drain line must be connected to the heat pump and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the unit.
When converting unit from left-hand return to right-hand return, condensate drain connection must be relocated. Refer to Pg#20.
3. Install rubber grommet onto the brackets as shown in Figure # 95
4. Hang the unit and assemble the field provided Thread rod, nuts and washers on to the brackets as shown in Figure # 95
This connection must be in conformance with local plumbing codes. A trap must be installed in the condensate line to insure free condensate flow.
HZ Heat Pump Drain Pan is not internally sloped.
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Duct System | 29SM Series Heat Pump
A vertical air vent is sometimes required to avoid air pockets. The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
DUCT SYSTEM
A supply air outlet collar and return air duct flange are provided on all units to facilitate duct connections.
Supply air duct and return air duct flanges are shipped unfolded with unit.
Fold the duct flange outwards along the perforated line. Refer to unit Dimensional Drawings for physical dimensions of the collar and flange. (Pg#95 through Pg#95)
A flexible connector is recommended for supply and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of one inch duct insulation to avoid heat loss or gain and prevent condensate forming during the cooling operation. Application of the unit to the no insulated duct work is not recommended as the unit’s performance will be adversely affected.
NOTE: Do not connect discharge ducts directly to the blower outlet.
PIPING
Supply and return piping must be as large as the unit connections on the heat pump (larger on long runs).
NOTE: Never use flexible hoses of a smaller inside diameter than that of the fluid connections on the unit.
SM units are supplied with either a copper or optional cupro-nickel condenser. Copper is adequate for ground water that is not high in mineral content.
Proper testing is recommended to assure the well water quality is suitable for use with water source equipment. When in doubt, use cupro­nickel.
In conditions anticipating moderate scale formation or in brackish water a cupro-nickel heat exchanger is recommended.
Refer to water quality table on page #30 Both the supply and discharge water lines will
sweat if subjected to low water temperature. These lines should be insulated to prevent damage from condensation. All manual flow valves used in the system must be ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics.
The factory provided air filter must be removed when using a filter back return air grill. The factory filter should be left in place on a free return system.
If the unit will be installed in a new installation which includes new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit is to be connected to existing duct work, a check should be made to assure that the duct system has the capacity to handle the air required for the unit application. If the duct system is too small, larger duct work should be installed. Check for existing leaks and repair.
The duct system and all diffusers should be sized to handle the designed air flow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path thru the return air grille into the heat pump. The return air inlet to the heat pump must have at least one 90 degree turn away from the space return air grille. If air noise or excessive air flow are a problem, the blower speed can be changed to a lower speed to reduce air flow.
NOTE: Never exceed the recommended water flow rates as serious damage or erosion of the water-to-refrigerant heat exchanger could occur.
Always check carefully for water leaks and repair appropriately. Units are equipped with swivel female pipe thread fittings. Consult Unit Dimensional Drawings. (Pg#95 through Pg#95)
Teflon tape sealer should be used when connecting water piping connections to the units to insure against leaks and possible heat exchanger fouling.
NOTE: Do not overtighten the connections.
Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit isolation and unit water flow balancing.
6 720 220 406 (2015/02)Revised 02-15
30 | Water Quality
WATER QUALITY
Table 1: Water Quality
SM Series Heat Pump
POTENTIAL PROBLEM
SCALING
CORROSION
Water Characteristic Acceptable Value
Copper Cupro-Nickel
pH (Acidity/Alkalinity) 7-9 7-9 Hardness (CaCO3,
MgCO3) Ryznar Stability Index Langelier Saturation Index Hydrogen Sulfide (H2S) < 0.5 ppm * 10-50 ppm Sulfates Chlorine Chlorides Carbon Dioxide Ammonia Ammonia Chloride Ammonia Nitrate Ammonia Hydroxide
< 350 ppm < 350 ppm
6.0 - 7.5 6.0 - 7.5
-0.5 - +0.5 -0.5 - +0.5
< 125 ppm < 125 ppm < 0.5 ppm < 0.5 ppm < 20 ppm < 150 ppm < 50 ppm < 50 ppm < 2 ppm < 2 ppm < 0.5 ppm < 0.5 ppm < 0.5 ppm < 0.5 ppm
< 0.5 ppm < 0.5 ppm Ammonia Sulfate Dissolved Solids
IRON FOULING
EROSION
* No "rotten egg" smell present at < 0.5 ppm H2S. ** Equivalent to 30 mesh strainer
Iron (Fe2+ Iron Bacteria Potential)
Iron Oxide Suspended Solids < 10 ppm, < 600 μm size ** < 10 ppm, < 600 μm size ** Maximum Water Velocity
ELECTRICAL
Refer to electrical component box layout. (Figure #97)
WARNING: Field wiring must comply
with local and national electric codes.
WARNING: Power to the unit must be
within the operating voltage range indicated on the unit nameplate or on the performance data sheet.
< 0.5 ppm < 0.5 ppm
< 1,000 ppm < 1,500 ppm
< 0.2 ppm < 0.2 ppm
< 1 ppm < 1 ppm
6 ft/sec 6 ft/sec
NOTE: Operation of unit on improper line voltage or with excessive phase imbalance will be hazardous to the unit, constitutes abuse and may void the warranty.
Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See unit nameplate for maximum fuse or breaker size.
SM Series Heat Pump6 720 220 406 (2015/02) Subject to change without prior notice
Loading...
+ 70 hidden pages