The RF3405E Inertia Transmitter is a magnetic and dry
contact wireless transmitter with a built-in inertia sensor
used for monitoring doors, windows, or other dry
contact devices.
The inertia transmitter is equipped with internal reed
contacts for use with an external magnet assembly and
an inertia sensor for detecting shock. The transmitter
can also accept a dual EOL resistor supervised dry
contact input from an external device. A cover/wall
tamper switch is provided.
Supervision is provided by periodically transmitting a
supervisory signal to the receiver every 13 minutes if
there is no other activity. All transmissions from the
RF3405E send battery status information.
Refer to Figure 2 when mounting the inertia transmitter.
1.Position the base plate over the desired location. If
2. If the transmitter is already installed, remove the
•The maximum range of the inertia transmitter, in
open air, is approximately 300 m (98 ft.).
Typically, keep this transmitter within 100 m
(328 ft.) of the receiver to which it is assigned.
•Mounting the inertias transmitter on metal
surfaces may reduce its RF range. Mounting it on
ferrous metal (iron or steel) surfaces may affect
the operation of the internal magnetic contact.
•Mount the inertia transmitter on the door or
window frame and mount the magnet assembly
on the moving portion.
The magnet assembly must be oriented as
shown in
Figure 1
. The magnet must be no
farther away than 10 mm (0.39 in.) from the
body of the inertia sensor for normal
operation.
connecting to external contacts, position the
mounting plate so the wiring passes through the
wire entrance (callout #5).
inertia sensor bracket by pressing the inertia sensor
tab (callout #1).
1.Mount the inertia sensor so the wires are over the
notched portion of the base plate (see Figure 4).
2. Press the inertia sensor all the way into the bracket.
3. You can mount the inertia sensor in four different
positions on the base plate (see Figure 5). Route the
wiring in a way that prevents crimping by the cover.
Figure 5:Inertia Sensor Mounting Positions
Figure 4:Inertia Sensor Wire Placement
1 - Inertia sensor
2 - Notch in base bracket
3 - Inertia sensor base bracket
Figure 6:Inertia Sensor: Point Up
Bosch Security Systems | 8/03 | 47128C
RF3405E | Installation Instructions |
1
2
P1
P2
P3
P4
P5
P6
P1
P2
P3
P4
P5
P6
1
2
3.0 Wiring
EN | 4
3.0Wiring
The RF3405E can be wired for an inertia
sensor or an external contact, but not both.
If Jumper P2 is removed, the internal magnetic reed
switches are enabled (see Figure 9).
Figure 9:P2 Reed Switch
2
1 - Jumper on disables internal reed switches
2 - No jumper enables internal reed switches
4.2Setting for Inertia or External Contact
(Jumper P6)
The detector can be set to monitor the internal inertia
sensor or a set of external contacts (see Figure 10).
Figure 8:External Contact Wiring
1
P1
INERTIA LOOP
P2
P3
P6
P4
P5
2
1.5 kΩ
2.2 k
Ω
1 - Wire jumper across inertia terminals
2 - Length of contact loop can be up to 6 m (20 ft.)
3 - Normally closed (NC) contact
The wire jumper in the Loop terminals must
be ON when using the Inertia function. The
wire jumper in the Inertia terminals must be
ON when using the External contact function.
Figure 10:Set Inertia or External Contact
3
1 - External contact
2 - Inertia sensor
Bosch Security Systems | 8/03 | 47128C
RF3405E | Installation Instructions |
4.0 Jumper Settings
EN | 5
4.3Minor and Gross Attack (Jumper P1)
If Jumper P1 is installed, the inertia detector reacts only
to Gross Attacks (major movement). Minor movement
or a series of taps does not activate the inertia detector.
Jumper P4 and Jumper P5 settings determine the
sensitivity of the inertia detector to Gross Attack (see
Section 4.5).
Jumper P6 must be set for Inertia to enable these
settings. See Figure 11.
Figure 11:P1 Attack Monitor
1
P1
P2
2
P3
P6
P4
P5
1 - No jumper for minor and gross attacks
2 - Jumper on for gross attack only
4.4Pulses for Minor Attack (Jumper P3)
The setting of Jumper P3 determines the number of
repetitive pulses needed to activate the inertia detector
to a Minor Attack.
If Jumper P3 is removed, the inertia detector reacts to
four repetitive pulses. This setting is only valid if
Jumper P1 is set for Minor Attack and Jumper P6 is set
for Inertia. See Figure 12.
4.5Sensitivity for Gross Attack
(Jumpers P4 and P5)
These settings are valid only if Jumper P6 is set for
Inertia.
Be sure to observe the battery polarity (see Figure 14).
Figure 14:Battery Installation
NeverReady Batteries, Inc.
Lost Power, NV
P1
INERTIA LOOP
P2
P3
P6
P4
P5
6.0Programming the Panel
There is a two-part ID sticker located on the housing of
the RF3405E (see Figure 15). You need the number on
this sticker to program the inertia transmitter into the
control panel.
Refer to the panel Programming Guide for programming
information on wireless type devices.
Figure 15:ID Sticker
8.0Specifications
Table 1:Specifications
Bosch Security Systems | 8/03 | 47128C
ID: XXXXXXXXX
YYYYYYY
!
ID: XXXXXXXXX
7.0Testing the Detector
Once the detector is mounted, you can place it in Test
Mode for 15 minutes by opening and then closing the
detector cover, or by pushing both tamper springs then
releasing one or both of them (if the cover is off). The
LED flashes once (and then continues flashing dimly) to
indicate it is in Test Mode. During the testing time, the
LED flashes twice each time a Minor Inertia Attack
occurs, a magnetic contact changes state (open or close),
or any time the external contact (if used) changes state.
The LED flashes three times for a Gross Inertia Attack.
If any jumpers are changed during Test Mode, the LED
flashes once to indicate the change.
RF3405E | Installation Instructions |
EN | 7
Notes:
Bosch Security Systems | 8/03 | 47128C
Bosch Security Systems
130 Perinton Parkway
Fairport, NY 14450-9199 USA
www.boschsecurity.us
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189