Bosch RF3405E User Manual

RF3405E
Installation Instructions
EN
Wireless (RF) Inertia Transmitter
RF3405E | Installation Instructions |
3 4
5
P1 P2 P3 P4 P5
P6
INERTIA LOOP
BATTERY
NeverReady Batteries, Inc.
Lost Power, NV
1
2
10 mm (0.39 in.) maximum
1
OK
12 mm (0.47 in.) nominal
3
2
OK
12 mm (0.47 in.) nominal
EN | 2
Installation Instructions
for the RF3405E
Wireless (RF) Inertia T ransmitter
1.0 General Information
The RF3405E Inertia Transmitter is a magnetic and dry contact wireless transmitter with a built-in inertia sensor used for monitoring doors, windows, or other dry contact devices.
The inertia transmitter is equipped with internal reed contacts for use with an external magnet assembly and an inertia sensor for detecting shock. The transmitter can also accept a dual EOL resistor supervised dry contact input from an external device. A cover/wall tamper switch is provided.
Supervision is provided by periodically transmitting a supervisory signal to the receiver every 13 minutes if there is no other activity. All transmissions from the RF3405E send battery status information.
2.0 Mounting
Figure 1: Magnet Location
1 - Inertia transmitter 2 - Magnet 3 - Cover screw location
Figure 2: Base Plate
2.1 Mounting Considerations
2.2 Mounting the Transmitter
Refer to Figure 2 when mounting the inertia transmitter.
1. Position the base plate over the desired location. If
2. If the transmitter is already installed, remove the
The maximum range of the inertia transmitter, in open air, is approximately 300 m (98 ft.). Typically, keep this transmitter within 100 m (328 ft.) of the receiver to which it is assigned.
Mounting the inertias transmitter on metal surfaces may reduce its RF range. Mounting it on ferrous metal (iron or steel) surfaces may affect the operation of the internal magnetic contact.
Mount the inertia transmitter on the door or window frame and mount the magnet assembly on the moving portion.
The magnet assembly must be oriented as shown in
Figure 1
. The magnet must be no farther away than 10 mm (0.39 in.) from the body of the inertia sensor for normal operation.
connecting to external contacts, position the mounting plate so the wiring passes through the wire entrance (callout #5).
inertia sensor bracket by pressing the inertia sensor tab (callout #1).
1 - Inertia sensor bracket 2 - Circuit board tab 3 - 13 mm (0.51 in.) panhead mounting screws 4 - Base mounting holes 5 - Wire entrance
3. Remove the circuit board by pressing the circuit board tab (callout #2).
4. Mount the base plate using the 13 mm (0.51 in.) panhead screws (callout #3) through the base mounting holes (callout #4).
5. Refer to Section 2.4 Mounting the Inertia Sensor if the inertial sensor is used.
Bosch Security Systems | 8/03 | 47128C
RF3405E | Installation Instructions |
Orientation of the Inertia sensor is critical to the proper operation of the inertia detection function.
An UP arrow, imprinted on the body of this sensor, must always point upwards when mounted in the transmitter base.
2.0 Mounting
EN | 3
2.3 Mounting the Magnet (if used)
Position the magnet base plate over the desired location, using the mounting configuration shown in Figure 1.
Figure 3: Magnet Base Plate
2 3
1
1 - Magnet assembly 2 - 16 mm (0.63 in.) flathead screws 3 - Magnet assembly mounting holes
2.4 Mounting the Inertia Sensor
1. Mount the inertia sensor so the wires are over the notched portion of the base plate (see Figure 4).
2. Press the inertia sensor all the way into the bracket.
3. You can mount the inertia sensor in four different positions on the base plate (see Figure 5). Route the wiring in a way that prevents crimping by the cover.
Figure 5: Inertia Sensor Mounting Positions
Figure 4: Inertia Sensor Wire Placement
1 - Inertia sensor 2 - Notch in base bracket 3 - Inertia sensor base bracket
Figure 6: Inertia Sensor: Point Up
Bosch Security Systems | 8/03 | 47128C
RF3405E | Installation Instructions |
1
2
P1 P2 P3 P4 P5
P6
P1 P2 P3 P4 P5
P6
1
2
3.0 Wiring
EN | 4
3.0 Wiring
The RF3405E can be wired for an inertia sensor or an external contact, but not both.
3.1 Wiring for the Inertia Sensor
Figure 7: Inertia Sensor Wiring
1
P1 P2 P3 P4 P5
1 - Inertia sensor wires 2 - Wire jumper across loop terminals
3.2 Wiring for the External Contact
INERTIA LOOP
P6
4.0 Jumper Settings
4.1 Reed Switch Enable (Jumper P2)
If Jumper P2 is removed, the internal magnetic reed switches are enabled (see Figure 9).
Figure 9: P2 Reed Switch
2
1 - Jumper on disables internal reed switches 2 - No jumper enables internal reed switches
4.2 Setting for Inertia or External Contact
(Jumper P6)
The detector can be set to monitor the internal inertia sensor or a set of external contacts (see Figure 10).
Figure 8: External Contact Wiring
1
P1
INERTIA LOOP P2 P3
P6
P4 P5
2
1.5 k
2.2 k
1 - Wire jumper across inertia terminals 2 - Length of contact loop can be up to 6 m (20 ft.) 3 - Normally closed (NC) contact
The wire jumper in the Loop terminals must be ON when using the Inertia function. The wire jumper in the Inertia terminals must be ON when using the External contact function.
Figure 10: Set Inertia or External Contact
3
1 - External contact 2 - Inertia sensor
Bosch Security Systems | 8/03 | 47128C
RF3405E | Installation Instructions |
4.0 Jumper Settings
EN | 5
4.3 Minor and Gross Attack (Jumper P1)
If Jumper P1 is installed, the inertia detector reacts only to Gross Attacks (major movement). Minor movement or a series of taps does not activate the inertia detector. Jumper P4 and Jumper P5 settings determine the sensitivity of the inertia detector to Gross Attack (see Section 4.5).
Jumper P6 must be set for Inertia to enable these settings. See Figure 11.
Figure 11: P1 Attack Monitor
1
P1 P2
2
P3
P6
P4 P5
1 - No jumper for minor and gross attacks 2 - Jumper on for gross attack only
4.4 Pulses for Minor Attack (Jumper P3)
The setting of Jumper P3 determines the number of repetitive pulses needed to activate the inertia detector to a Minor Attack.
If Jumper P3 is removed, the inertia detector reacts to four repetitive pulses. This setting is only valid if Jumper P1 is set for Minor Attack and Jumper P6 is set for Inertia. See Figure 12.
4.5 Sensitivity for Gross Attack (Jumpers P4 and P5)
These settings are valid only if Jumper P6 is set for Inertia.
Figure 13: Gross Attack Jumper Settings
1
2
3
4
P4
P4
P4
P4
1 - Low sensitivity 2 - Low/Medium sensitivity 3 - Medium/High sensitivity 4 - High sensitivity
P5
P1 P2 P3
P5
P5
P5
P4 P5
P6
Figure 12: Attack Pulses
1
2
1 - Jumper on for eight repetitive pulses 2 - No jumper for four repetitive pulses
Bosch Security Systems | 8/03 | 47128C
P1 P2 P3
P6
P4 P5
RF3405E | Installation Instructions |
Dimensions (H x W x D)
Transmitter: 2.7 cm x 2.4 cm x 16.9 cm (1.06 x 0.94 in. x 6.65 in.) Magnet: 1.9 cm x 1.3 cm x 16.9 cm (0.75 in. x 0.51 in. x 2.36 in.)
Operating Temperature
-20°C to +60°C (-4°F to +151°F); 0% to 95% relative humidity (non-condensing)
Frequency Band
433.42 MHZ
Maximum RF Power
Less than 10 mW
Operating Voltage
Supplied by a 3 VDC lithium battery
Battery Life
A minimum of 3 years under normal operating conditions with recommended battery types (2 years if using the inertia sensor).
Recommended Battery Types
Duracell DL123A Energizer EL123AP Panasonic CR123A
Compatible Receiver
RF3227E
Supervisory Internal
13 minutes nominal
5.0 Installing the Battery
EN | 6
5.0 Installing the Battery
Be sure to observe the battery polarity (see Figure 14).
Figure 14: Battery Installation
NeverReady Batteries, Inc.
Lost Power, NV
P1
INERTIA LOOP P2 P3
P6
P4 P5
6.0 Programming the Panel
There is a two-part ID sticker located on the housing of the RF3405E (see Figure 15). You need the number on this sticker to program the inertia transmitter into the control panel.
Refer to the panel Programming Guide for programming information on wireless type devices.
Figure 15: ID Sticker
8.0 Specifications
Table 1: Specifications
Bosch Security Systems | 8/03 | 47128C
ID: XXXXXXXXX
YYYYYYY
!
ID: XXXXXXXXX
7.0 Testing the Detector
Once the detector is mounted, you can place it in Test Mode for 15 minutes by opening and then closing the detector cover, or by pushing both tamper springs then releasing one or both of them (if the cover is off). The LED flashes once (and then continues flashing dimly) to indicate it is in Test Mode. During the testing time, the LED flashes twice each time a Minor Inertia Attack occurs, a magnetic contact changes state (open or close), or any time the external contact (if used) changes state. The LED flashes three times for a Gross Inertia Attack.
If any jumpers are changed during Test Mode, the LED flashes once to indicate the change.
RF3405E | Installation Instructions |
EN | 7
Notes:
Bosch Security Systems | 8/03 | 47128C
Bosch Security Systems 130 Perinton Parkway Fairport, NY 14450-9199 USA www.boschsecurity.us Customer Service: (800) 289-0096 Technical Support: (888) 886-6189
© 2003 Bosch Security Systems Subject to change | Printed in the USA 47128C
Loading...