Bosch RF280E Installation Instructions Manual

RF280E Series
Installation Instructions
EN
Wireless (RF) Photoelectric Smoke Detectors
Trademarks
Trademarks
Chamber Check® is a registered trademark of Bosch Security Systems in the United States.
1.0 Overview
The RF280E Series Photoelectric Smoke Detectors are open-area wireless smoke detectors designed for use with commercial fire protective signaling and household fire warning systems.
For commercial and industrial installations, allow spacing of 30 ft (9 m) between detectors.
An Alarm and Test LED flashes approximately every 26 sec to verify the detector has battery power and the smoke sampling circuitry is functioning. The LED flashes every 0.5 sec in an alarm, allowing the user to verify individual detector alarms. The detector automatically resets after 3 min if the alarm condition no longer exists.
The detector can be manually reset by pressing the Test button. If there is an alarm after the Test button is pressed, the detector re-alarms in 20 to 30 sec. After the alarm condition clears, the control panel alarm can be cleared by a control panel reset command.
Supervision is provided by transmitting a low power level signal to the receiver every 13 min if there is no other activity. All transmissions from the RF280E Series send battery status information to the control panel.
Figure 1: Modifying the Lock-In Tab
1
2
1 - Base locking tab 2 - Lock-In feature. Break away to access.
3. Remove the detector from the mounting plate by twisting the base counterclockwise.
4. Install the mounting plate in the desired location, and do not attach the detector to the mounting plate at this time.
5. Install the two lithium batteries (Item 1 in Figure 2) in the detector’s base and observe the polarity. These batteries are supplied in a separate package.
Figure 2: Installing the Batteries
1
2.0 Mounting
The detector’s maximum wireless range in open air is approximately 984 ft (300 m). In normal residential or commercial applications, keep the detector within 328 ft (100 m) of the control panel receiver it is assigned to. Temporarily mount the detector using double-sided tape, and test it from the desired location before permanently mounting it.
1. Remove the detector’s dust cover. You can replace the dust cover during construction periods, but remove it when the alarm system is enabled.
2. The mounting plate has a base locking tab that, if used, requires you to press the locking tab towards the mounting surface to release the detector. If you do not want the Lock-In feature, do not make changes to the mounting plate. Use the Lock-In feature by modifying the base locking tab as shown in Figure 1.
1 - Lithium batteries (2) 2 - Programming serial number
6. A two-part sticker on the detector’s base (Item 2 in Figure 2) contains the nine-digit programming serial
number. Remove one of the stickers and store it in a safe place. You need the number to program the detector from the control panel.
7. Connect the detector to the mounting plate and twist it clockwise.
167770187
167770187
2
Bosch | 12/04 | 43177D2
RF280E Series | Installation Instructions | 4.0 Testing
3.0 Programming
Refer to your control panel wireless reference guide for programming information.
4.0 Testing
4.1 Operational
Notify all concerned parties before and after performing maintenance or testing the fire alarm system.
1. When the system is free of alarms, check each detector to ensure the red Alarm and Test LED flashes approximately every 26 sec. This verifies the detector is operating properly.
2. Test each detector to ensure it causes a control panel alarm.
3. Alarm the detector by pressing and holding the Test button for 9 to 12 sec.
The LED lights, the sounder sounds, and a Test Report is sent to the control panel.
4. Release the Test button to end the test.
4.2 Sensitivity
The detector’s calibration is important in determining its continued operation. Depending on local regulations, the frequency of calibration testing might be required more often than once a year.
Test the detector’s sensitivity by pressing the Test button and observing the Alarm and Test LED.
4.3 Manual Test
1. Press and hold the Test button (Item 1 in Figure 3).
2. Observe the Alarm and Test LED (Item 2 in Figure 3). The detector can take up to 12 sec to enter Test Mode.
Figure 3: Sensitivity Testing Components
1
2
1 - Test button 2 - Alarm and Test LED 3 - Cover latch
If the detector is within the factory-marked
calibration range, it goes into alarm and the LED steadily lights.
If the detector is too sensitive, the LED rapidly
flashes four times (once every 0.5 sec) and the detector goes into alarm with the LED steadily on.
If the detector is not sensitive enough, the LED
slowly flashes twice (once every 2 sec) and the detector goes into alarm with the LED steadily on.
If the detector is not operational, it does not signal
an alarm. Return the unit for repair.
3
4.4 Visual Check
The RF280E Series includes the Chamber Check™ Automatic Trouble Indication. The detector uses this feature to automatically indicate when its calibration is out of the factory-listed range.
Check the detector’s sensitivity by visually inspecting it and observing the Alarm and Test LED’s flash rate. Normally, the flash rate is once every 26 sec. When the detector is out of the sensitivity range, the LED quickly flashes twice every 26 sec to indicate low sensitivity. The LED quickly flashes twice every 15 sec for high sensitivity, indicating a dirty chamber.
3Bosch | 12/04 | 43177D
Loading...
+ 5 hidden pages