The transmit level from this device is set at a fixed
Copyright Notice
Unless otherwise indicated, this publication is the
copyright of Bosch Security Systems, Inc. (“Bosch”).
All rights are reserved.
You may download a single copy of this publication.
By downloading the publication you agree that you
will: (i) only use the publication for your own
reference; (ii) not commercially exploit or charge any
person for the use of the publication; and (iii) not
modify the publication in any way without the prior
written permission of Bosch.
Except as specified above or where authorized by the
Copyright Act 1968 (Cth), no part of this publication
may be reproduced, transmitted, modified or stored,
in any form or by any means, without the prior
written permission of Bosch.
Notice of Liability
This material is designed for use by tradespeople with
expertise in the installation of this product. Persons
without appropriate expertise should seek assistance
before attempting installation.
While care has been taken in the preparation of this
material, Bosch Security Systems, Inc. and its
representatives will not be responsible to any person
or entity for any loss or damage directly or indirectly
caused by information in, or any omission from, this
material.
Bosch Security Systems, Inc. reserves the right to
make changes to features and specifications of its
products at any time without prior notification.
A-Tick
The ICP-CC488 Control Panel is designed to comply
with A-Tick.
New Zealand Telepermit Notes
The grant of a telepermit for a device in no way
indicates Telecom acceptance of responsibility for the
correct operation of that device under all operating
conditions.
This equipment will not be used in any manner that
could constitute a nuisance to other telecom
customers.
Immediately disconnect this equipment should it
become physically damaged and arrange for its
disposal or repair.
level and because of this, there may be circumstances
where the performance is less than optimal. Before
reporting such occurrences as faults, please check the
line with a standard telepermitted telephone and do
not report a fault if the telephone performance is
satisfactory.
This device is equipped with pulse dialing while the
Telecom standard is DTMF tone dialing. There is no
guarantee that Telecom lines will always continue to
support pulse dialing.
Use of dialing, when this equipment is connected to
the same line as other equipment, may give rise to
bell noise and also cause a false answer condition.
Should such problems occur, the user should not
contact the Telecom Faults Service.
This equipment is set up to carry out test calls at predetermined times. Such test calls can interrupt any
other calls that may be set up on the line at the same
time. The timing set for such test calls should be
discussed with the installer.
The timing set for test calls from this equipment may
be subject to drift. If this proves to be inconvenient
and your calls are interrupted, then the problem of
timing should be discussed with the equipment
installer. The matter should not be reported as a fault
to Telecom Faults Service.
This equipment shall not be set up to make automatic
calls to the Telecom 111 Emergency Service.
This equipment should not be used under any
circumstances that may constitute a nuisance to other
Telecom customers.
In the event of any problem with this device, the
systems battery, AC MAINS supply, and telephone
line should be disconnected. The user is to arrange
with the supplier of the device to make the necessary
repairs.
Should the matter be reported to Telecom as a wiring
fault and the fault proven to be due to this product, a
call-out charge will be incurred.
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
ICP-CC488 | User's Guide | Contents EN | 3
14.1 Horn Speaker Test .........................................15
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
ICP-CC488 | User's Guide | 1. IntroductionEN | 5
1. Introduction
Congratulations on selecting the ICP-CC488 Control
Panel to protect you and your property. To obtain
the most from your unit, take time to read through
this manual and familiarize yourself with the
numerous outstanding operating features of this
system. In all aspects of planning, engineering,
styling, operation, convenience, and adaptability, we
have sought to anticipate your every possible
requirement.
Programming simplicity and speed were some of the
major considerations and we believe that our
objectives in this area were more than satisfied.
This manual explains all aspects of operating the
control panel. All system parameters and options are
detailed; however, suitability is left up to the
individual. Every system can be tailored to meet all
requirements quickly and easily.
2. Specifications
Table 1: Specifications
Temperature Range
Humidity
Power Source
Stand-By Current
Current Draw in
Alarm Condition
Current Draw in
Alarm Condition with
Codepad
Back-Up Battery
Dimensions (Case,
packed in carton)
Weight
Supplier Code
New Zealand
Telepermit
o
0
C to +45 oC
o
(+32
F to +113oF)
10% to 95%
TF008 Plug Pack –
240 V/18 VAC @ 1.3 A
65 mA
115 mA
105 mA
6 Ah/12 VDC Rechargeable
Sealed Lead Acid Battery
306 mm x 262 mm x 84 mm
(12.05 in. x 10.31 in. x 3.31 in.)
2.5 kg
(5.51 lb.)
N771
PTC 211/98/084
ICP-CC488 –
PTC 211/98/083
Test the sirens, strobe, and zones at
weekly intervals. Refer to Section 14. Testing for further information.
3. Codepad Indicators
Figure 1: ICP-CP508W Eight Zone LED
Codepad
Figure 2: ICP-CP508LW Eight Zone LCD
Codepad
Figure 3: ICP-CP516 Sixteen Zone LED
Codepad
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
The AWAY indicator displays that the
system is armed in AWAY Mode. The
AWAY indicator flashes in unison with
the STAY indicator when
programming various options
throughout the Operators Manual.
Refer to Section 3.10.2 Arming in AWAY Mode for information on the different
methods of arming the system in
AWAY Mode.
Table 3: AWAY Indicator
The codepad is the communications interface
between you and your alarm system. Use the
codepad to issue commands. The codepad offers
both visual and audible indications that guide you
through the general operation.
The codepad incorporates numerous indicators.
There are zone indicators used to show the condition
of each zone. Four other indicators show general
status. The following pages outline a list of situations
and the relevant indicators that are seen.
The ICP-CP516 Sixteen Zone Codepad must be used
with sixteen wireless zone systems. The sixteen zone
codepads operation and display similarly to 8 zones
codepads, but also display the zones 9 through 16.
3.1 Zone Indicators
1 2 3 ….
Table 2: Zone Indicators
Indicator Definition
On Zone is unsealed.
Off Zone is sealed.
Flashing Fast
(0.25 sec on/
0.25 sec off)
Flashing Slow
(1 sec on/
1 sec off)
The zone indicators (1 to 8) display
the status of the zones. Table 2 lists the
various circumstances that the
indicators display (such as Zone
Sealed, Zone Unsealed, and so on).
Zone is in alarm condition.
Zone is manually isolated or
selected to be isolated.
Indicator Definition
On System is armed in AWAY Mode.
Off System is not armed in AWAY Mode.
3.3 STAY Indicator
The STAY indicator displays that the
system is armed in STAY Mode 1 or
STAY Mode 2. The STAY indicator also
flashes in unison with the AWAY
indicator when programming various
options throughout the Operators Manual.
Refer to Section 3.10.3 Arming in STAY Mode 1 for different methods of arming in
STAY Mode 1. Refer to Section 3.10.4 Arming in STAY Mode 2 for the method of
arming in STAY Mode 2.
Table 4: STAY Indicator
Indicator Definition
On System is armed in STAY Mode 1
or STAY Mode 2.
Off System is not armed in STAY
Mode 1 or STAY Mode 2.
Flashing
twice a sec
Flashing once
every
Zone isolating mode or setting
STAY Mode 2 zones.
Day alarm status – day alarm
turned on.
3 sec
3.4 System Disarmed
This indicator displays with the
indicator when the system is disarmed.
3.5 MAINS Indicator
The MAINS indicator displays that the
system’s AC MAINS supply is normal or
failed.
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
On AC MAINS power normal.
Flashing AC MAINS supply has failed.
3.6 Off Indicator/Zone Sealed
The
system is in the disarmed state and
flashes when a zone becomes unsealed
during the disarmed state. The
indicator stops flashing when all zones
are sealed.
indicator displays when the
3.7 On Indicator/Zone In Alarm
The
system is armed in AWAY Mode and
flashes when an alarm occurs. The
indicator resets once a valid user code
is entered.
indicator displays when the
3.8 FAULT Indicator
The FAULT indicator displays that the
system detected a system fault. Refer to
Section 9. Fault Analysis Mode on page 12
for additional information on system
faults.
Every time a new system fault is
detected (such as, FAULT indicator
flashing), the codepad begins to beep
once every minute. Pressing the [#]
button once cancels the once a min
beep and acknowledges the fault (such
as, FAULT indicator on steady).
Table 6: FAULT Indicator
Indicator Definition
On There is a system fault that
needs to be rectified.
Off The system is normal, there are
no faults.
Flashing There is a system fault that
needs to be acknowledged.
3.9 Audible Indications
Table 7 defines the audible indicators given out by
the codepad buzzer.
Table 7: Audible Indicators
Audible
Indicator
One short beep A button was pressed on the
Two short beeps The system accepted your
Three short
beeps
One long beep Indicates the end of Exit Time
One beep every
sec
One short beep
every min
Definition
codepad, or Exit Time ended
when armed in STAY Mode 1
or STAY Mode 2.
code.
The requested function was
executed.
when armed in AWAY Mode, or
the requested operation was
denied or aborted.
Walk Test Mode is currently
active or a warning before
automatic arming takes place.
There is a system fault waiting
to be acknowledged.
3.10 Arming the System
There are several ways to arm the system depending
on whether you are:
• Leaving the premises and require all active zones
to be in a ready state for an intruder.
• Remaining in the premises and only require part
of the system to be in a ready state for an
intruder.
If a zone is not sealed at the end of Exit Time, the
zone is automatically isolated and constantly
displayed on the remote codepad. The zone becomes
an active part of the system when the zone is
restored.
For example, if a window is left open after Exit Time
expired, the window is not an active part of the
system until the window is closed. Opening the
window after Exit Time expired causes an alarm
condition.
Table 8 defines the different methods for arming the
system.
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
programmed to be automatically
isolated by the installer. Refer to
Section 3.10.3 Arming in STAY Mode
1.
STAY Mode 2 Arms all zones except those
programmed to be automatically
isolated by the Master Code holder.
Refer to Section 3.10.4 Arming in STAY Mode 2.
3.10.1 Forced Arming
The feature of arming the system when a zone is not
sealed is known as forced arming. If the system does
not arm and a long beep is heard, forced arming is
not permitted. If this is the case, you must ensure
that all zones are sealed or manually isolated before
you can arm the system. Refer to Section 8. Isolating Zones on page 11.
3.10.2 Arming in AWAY Mode
When you leave your premises and require all zones
to be in a ready state to detect intrusion, arm the
system in AWAY Mode.
There are two different methods for arming the
system in AWAY Mode. Method one is standard and
always operates. Method two is optional and can be
disabled by your installer if you do not want to use
single button arming.
Table 9: How to Arm the System in AWAY
Mode
Method
One
Enter your user code followed by
the [#] button (for example,
[2580#]).
Two beeps sound and the AWAY
indicator displays. Exit Time starts
counting.
Method
Two
Hold down the [#] button until two
beeps sound.
The AWAY indicator displays and
Exit Time starts counting.
3.10.3 Arming in STAY Mode 1
STAY Mode 1 is only used when the perimeter and
unused areas of the premises need to be armed to
detect an intruder from entering the premises. At the
same time, you can move freely within an area that is
automatically isolated.
There are two different methods for arming the
system in STAY Mode 1. Method one is standard
and always operates. Method two is optional and
may be disabled by your installer if you do not want
to use single button arming.
Entry Guard Timer for STAY Mode 1
When arming the system in STAY Mode 1, an
optional entry timer called Entry Guard Timer for
STAY Mode 1 is available. Use this entry timer to
delay the sirens if a zone is not automatically isolated
and activated an alarm condition. Entry Guard
Timer For STAY Mode 1 is the delay time used for
all zones except 24-hour zones when the system is
armed in STAY Mode 1 or STAY Mode 2.
If the Entry Guard Timer for STAY Mode 1 is
programmed and a zone was not automatically
isolated is activated, the codepad beeps twice a sec
until the entry timer expires or the system is
disarmed. If the alarm condition is not reset by
entering your user code followed by the [#] button
(such as, [2580#]) before the entry timer expires, the
sirens activate into alarm. Only your installer can
program this feature.
Table 10: How to Arm the System in STAY
Mode 1
Method One
Method Two
Enter your user code followed by the [*]
button (for example, [2580*]).
Two beeps sound and the STAY
indicator displays. Exit Time starts
counting.
Any zones programmed to be
automatically isolated in STAY Mode 1
flash until Exit Time expires. At the end of
Exit Time, all zones selected to be
automatically isolated turn off and the
codepad gives one short beep.
Hold down the [*] button until two beeps
sound.
The STAY indicator displays and Exit
Time starts counting.
Any zones programmed to be
automatically isolated in STAY Mode 1
flash until Exit Time expires. At the end of
Exit Time, the zone indicators turn off
and the codepad gives one short beep.
3.10.4 Arming in STAY Mode 2
STAY Mode 2 is only used when the perimeter and
unused areas of the premise need to be armed to
detect an intruder from entering the premise. At the
same time, allowing you to move freely within an
area that is automatically isolated. Any Master Code
user can program zones to be automatically isolated
in STAY Mode 2.
Only your security company can program zones
automatically isolated in STAY Mode 1.
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
When arming the system in STAY Mode 2, an
optional entry timer called Entry Guard Timer for
STAY Mode 2 is available. Use this entry timer to
delay the sirens if a zone is not automatically isolated
and activated into alarm condition. Entry Guard
Timer for STAY Mode 2 is the delay time used for
all zones except 24-hour zones when the system is
armed in STAY Mode 1 or STAY Mode 2.
If the Entry Guard Timer for STAY Mode 2 is
programmed and a zone that was not automatically
isolated activates, the codepad beeps twice a sec until
the entry timer expires or the system is disarmed. If
the alarm condition is not reset by entering your user
code followed by the [#] button (for example,
[2580#]) before the entry timer expires, the sirens
activate into alarm. Only your installer can program
this option.
How to Arm the System in STAY Mode 2
Hold down the [0] button until two beeps sound.
The STAY indicator displays and Exit Time starts
counting.
Any zones programmed to be automatically isolated
in STAY Mode 2 flash until Exit Time expires. At
the end of Exit Time, all zones selected to be
automatically isolated extinguish and the codepad
emits one short beep.
3.10.5 Programming STAY Mode 2 Zones
Programming zones to be automatically isolated in
STAY Mode 2 are only carried out if you have a
Master Code.
How to Program STAY Mode 2 Zones
1. Enter your four character Master Code, followed
by [4] and the [#] button (for example,
[25804#]). Three beeps sound and the STAY
indicator flashes.
2. Enter the zone number to be automatically
isolated, followed by the [*] button (for example,
[1*] = Zone 1, [2*] = Zone 2).
The selected zone flashes. If you make a mistake,
enter the same zone number followed by the [#]
button to clear the incorrect zone.
To select additional zones to be automatically
isolated in STAY Mode 2, repeat Step 2 as many
times as required.
3. Press the [#] button to exit this mode when you
finish selecting all zones to be automatically
isolated in STAY Mode 2. Two beeps sound and
the STAY and AWAY indicators turn off.
4. Disarming the System
When you enter the premises after the system is
armed in AWAY mode, or if you armed the system
in STAY Mode 1 or STAY Mode 2, you must disarm
the system to disable detection devices that activate
an alarm.
If there was an alarm condition prior to disarming
the system, a flashing zone indicator displays,
indicating a previous alarm on that zone.
How to Disarm the System
Enter your user code followed by the [#] button (for
example, [2580#]). Two beeps sound.
5. User Codes
5.1 Adding User Codes
Only the Master Code holder can add or change
other system user codes, including the Master Code.
Up to eight user codes can be programmed to
operate the system.
How to Add a User Code
1. Enter your four character Master Code, followed
by [1] and the [#] button (for example,
[25801#]).
Three beeps are heard and the STAY and
AWAY indicators flash.
2. Enter the User Code number (1 to 8), followed
by the [#] button (for example, [2#] = User 2,
[8#] = User 8). Two beeps are heard and the
selected user number displays on the codepad
indicators.
3. Enter the digits required for the new code
followed by the [#] button (for example, for User
Code 5768, enter [5768#]). Two beeps are heard
and the STAY and AWAY indicators turn off.
To add or change other User Codes, repeat this
procedure as many times as required.
5.2 Adding Radio Remote User Codes
Only the Master Code holder can add or change
other system user codes. Up to eight radio user codes
(User Codes 9 to 16) can be programmed to operate
the system.
How to Add a Radio Remote User Code
1. Enter your four character Master Code, followed
by [1] and the [#] button (for example,
[25801#]).
Three beeps sound and the STAY and AWAY
indicators flash.
2. Enter the radio remote user code number (9 to
16), followed by the [#] button (for example,
[9#] = User 9, [16#] = User 16). Two beeps are
heard and the selected user number displays on
the codepad indicators.
Bosch Security Systems, Inc. | 12/08 | F01U089456-02
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.