Bosch GWH-635-ES User Manual

Page 1
Page 2
Index
Index
1 Warning 2
2 Appliance details 4
2.1 Features 4
2.2 GWH-635-ES Specifications (Technical data) 4
2.4 General rules to follow for safe operation 7
2.6 Clearances 8
2.7 Mounting installation 8
2.8 Combustion air requirements 8
2.9 Venting 9
2.10 Gas piping & connections 15
2.11 Gas line sizing 17
2.12 Measuring gas pressure 17
2.12.1 Connecting Manometer 17
2.12.2 Static Pressure Test 17
2.12.3 Operating Pressure Test 17
2.13 Water connections 18
2.14 Electrical connections 19
2.15 Operating instructions 19
2.16 For your safety read before operating your water heater 19
2.17 Lighting and operating instructions 19
3 Operation instructions 21
3.1 Power 21
3.2 Temperature selection 21
3.3 Use of remote control accessory 23
3.4 Operation 23
3.5 Reset button 23
3.6 Program button 23
3.7 Locked condition 23
4 Maintenance and service 24
5 Troubleshooting 24
1 Warning
Warning: If the information in this
manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Warning: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. Upon completion of the installation, these instructions should be handed to the user of the appliance for future reference.
Featuring
Electronic Ignition and Power Venting
For your safety
Do not store or use gasoline or other flammable, combustible or corrosive vapors and liquids in the vicinity of this or any other appliance.
Warning: Carefully plan where you install the heater. Correct combustion air supply and flue pipe installation are very important. If a gas appliance is not installed correctly, fatal accidents can result from lack of air, carbon monoxide poisoning or fire.
6 Electrical diagram 27
7 GWH-635-ES Functional scheme 28
8 Interior components diagram and parts list 29
8.1 Interior components 29
8.2 Components diagram 30
8.3 Parts list 31
9 Special adjustment for measuring and adjusting CO2 levels 32
10 Protecting the environment 34
11 Fifteen Year Limited Warranty 35
2
Warning: Exhaust gas must be vented to outside using proper vent material suitable for category III vent systems and temperatures up to 480°F. Vent and combustion air connector piping must be sealed gas-tight to prevent possibility of flue gas spillage, carbon monoxide emissions and risk of fire, resulting in severe personal injury or death.
Warning: Place the heater in a location where water leaks will do NO DAMAGE to adjacent areas or lower floors.
6 720 607 072
Page 3
Warning: Field wiring connections and electrical grounding must comply with local codes, or in the absence of local codes, with the latest edition of the National Electric Code, ANSI/NFPA 70, or in Canada, all electrical wiring must comply with the local codes and the Canadian Electrical Code, CSA C22.1 Part 1.
Warning: Shock hazard line voltage is present. Before servicing the water heater, turn off the electrical power to the water heater at the main disconnect or circuit breaker. Failure to do so could result in severe personal injury or death.
What to do if you smell gas
• Close gas valve. Open windows.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Warning
Fig. 1
Warning: The heater must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures equal to or more than 0.5 psig.
FCC: This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
6 720 607 072
Fig. 2
3
Page 4
Appliance details
i
2 Appliance details
2.1 Features
Parts
• Touch Pad interface control
• High power pre-mix compact burner with low Nox emissions
• Modulating Gas Valve with constant gas:air ratio control
• Modulating water valve for improved comfort and temperature control.
Safety
• Flame sensor (ionization) rod
• Overheat sensor
• Temperature limiter
• Fan speed monitoring.
High Quality Materials for Long Working Life
• Copper heat exchanger
• High efficiency Ceramat Burner
• Compact space saver: mounts on a wall with a supplied bracket.
• Easily removable one-piece cover.
Features
• LCD Display
• On/Off and Temperature control switches
• Reset button
• Program Key (Selectable temperature default)
• Failure codes for easy diagnostic and repair.
Accessories
• Optional wireless remote control accessory to operate with the appliance
• Vent termination kit.
BOSCH is constantly improving its products, therefore specifications are subject to change without prior notice.
2.2 GWH-635-ES Specifications (Technical data)
Approved in US/Canada
Capacity
Maximum flow rate: 6.35 GPM (24 l/min) at a 45°F (25°C) rise.
Maximum output
142,968 Btu/h (41.8 kW)
Maximum input
175,000 Btu/h (51.2 kW)
Efficiency in %
Recovery efficiency 86.5%
Min. Output
31,131 Btu/h (9.1 kW)
Temperature Control
Selection range: 100°F (38°C) - 140°F (60°C) Default temperature: 122°F (50°C) Stability: +/- 2°F (+/- 1°C)
Gas Requirement
Gas connection (inches) - ¾”
Inlet gas pressure under operation (with a high hot water flow rate)*
• Propane: 11” - 14” water column
• Natural Gas: 5” - 14” water column.
* To measure Gas Pressure, see Measuring Gas Pressure, chapter 2.12.
Venting
A condensate trap is integrated into the exhaust flue gas collar of the heater, the supplied condensate drain tube must be installed to it for proper removal of condensate from the trap. See chapter 2.9 for Venting.
Water
• Hot water connection (inches) - ¾”
• Cold water connection (inches) - ¾”
• Water valve material: Polymer (PPS) (Polypropylene
Sulfid)
• Minimum water flow: 0.8 gallon/minute (3 l/m)
• Minimum recommended water pressure: 30 PSI
(2.07 bar)
• Connections:
– Bottom of heater
4
6 720 607 072
Page 5
Appliance details
Combustion
• NOx 55 ppm
• CO 250 ppm
• CO2 level set from factory, see chapter 9.
Dimensions
• Depth (in): 8 ½” (220 mm)
• Width (in): 15 ¾” (400 mm)
• Height (in): 23 ½” (600 mm)
• Weight: 47 pounds (21 kg).
Gas types
Natural Gas. LP Gas. Converting the gas type can only be done by a certified gas technician with a calibrated CO2 analyzer. Call BBTNA for conversion instructions.
Voltage
120 V AC (50/60 Hz)
Amperage
IDLE - 40 mA Operation - 2,5 A
Do not lose this manual. Please complete and return the enclosed product registration card.
Before installing the unit, be certain you have the correct heater for your type of Gas - Propane or Natural Gas. Identification labels are found on the
shipping box, and on the rating plate which is located on the right side panel of the cover.
To remove front cover
• Loosen the two Philips head screws located on front panel (beneath plastic decal shields if they are already attached, see Fig. 3)
• Lift front cover panel upward and remove.
Noise
50 db (A)
Safety devices
• Flame failure device (ionization flame rod sensor)
• Pressure relief valve (supplied with heater)
• Over heat prevention (temperature limiter).
Water resistant
IP X4 (protection against water drops)
UNPACKING THE GWH-635-ES HEATER
This heater is packed securely.
The box includes:
• Pressure relief valve (150 psi / 200,000 Btu rating)
• Bracket for wall hanging the heater
• Exhaust vent adaptor (with 4 screws and gasket provided)
• Condensate drain tube kit
• Combustion air inlet adaptor (with 3 screws and gas­ket provided)
• Plastic decal shields for covering front cover screws and control panel, installer should affix these decals to the front of the unit after installation is complete. See Fig. 3
• Installation manual
• Product registration card
Fig. 3 Remove front cover
The GWH-635-ES is not approved or designed for:
• Manufactured (mobile) homes, RV's or boats
• Heating or other recirculating/pumping applications*
• Outdoor installation (use only Outdoor Model GWH­635-ESO)
• Solar/preheat backup or high temperature booster use.
* This includes domestic hot water circulator pump loop systems that may previously exist in a home hot water system. The use of a small electric mini-tank (4-6 gallon size) should be used for this application; when designed so the pump will circulate the hot water in the mini-tank only and through the building's hot water return loop (timed or thermostatic controlled operation of the pump is commonly done). The GWH-635-ES should be plumbed in line before the mini-tank water heater, contact BBTNA if further instruction is needed.
• Energy Guide label.
6 720 607 072
5
Page 6
Appliance details
2.3 Dimensions and Minimum installation clearances
Fig. 4 Dimensions
1 Cover 2 On/Off switch 3 Reset button 4 LCD display 5 Program button 6 Temperature buttons
Fig. 5 Minimum clearances
Model GWH-635-ES
TOP (A) 12”
FRONT (B) 1”
BACK 0”
SIDES 1”
FLOOR (C) 12”
VENT DIAMETER 3”
Table 1 Minimum clearances
6
6 720 607 072
Page 7
Appliance details
2.4 General rules to follow for safe operation
B 1. You should follow these instructions when you
install your heater. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada: The Installation should conform with CGA B149.(1,2) INSTALLATION CODES and /or local installation codes.
B 2. Carefully plan where you install the heater. Correct
combustion air supply and vent pipe installation are very important. If not installed correctly, fatal accidents can be caused by lack of air, carbon monoxide poisoning or fire.
B 3. When the unit is installed indoors and ROOM
SEALED (twin pipe) it is permitted to be located in bathrooms, bedrooms and occupied rooms that are normally kept closed. See chapter 2.9. If the unit will be installed indoors and use indoor combustion air, the place where you install the heater must have enough ventilation. The National Fire Codes do
not allow UNSEALED gas fired water heater installations in bathrooms, bedrooms or any occupied rooms normally kept closed. See
chapter 2.5 and 2.8.
B 4. You must vent your heater. See section on
VENTING.
B 5. The appliance and its gas connection must be leak
tested before placing the appliance in operation. The appliance must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve (not supplied with heater) during any pressure testing at pressures in excess of ½ Psig (3.5 kPa).
B 6. Keep water heater area clear and free from
combustibles and flammable liquids. Do not locate the heater over any material which might burn.
B 7. Correct gas pressure is critical for the optimum
operation of this heater. Gas piping must be sized to provide the required pressure at the maximum output of the heater, while all the other gas appliances are in operation. Check with your local gas supplier, and see the section on connecting the gas supply.
B 8. Should overheating occur or the gas supply fail to
shut off, turn off the gas supply at the manual gas shut off valve, on the gas line. Note: manual gas shutoff valve is not supplied with the heater.
B 9. Do not use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater
2.5 Proper location for installing your heater
Carefully select the location of the water heater. For your safety and for proper heater operation, you must provide combustion air to the heater and a proper exhaust vent system. Follow the guidelines below:
B 1. Locate the heater where venting, gas and
plumbing connections are feasible and convenient.
B 2. It is strongly recommended that the heater be
installed as a ROOM SEALED heater (twin pipe). If the heater will be installed as an UNSEALED heater (sing368 0 Td(r)Tj3.12233 0 Td(e)Tj5.28395 0
6 720 607 072
7
Page 8
Appliance details
2.6 Clearances
The GWH-635-ES is design certified for installation on a combustible wall (see 2.7 Mounting installation) provided the floor covering below the heater is noncombustible. For installations in an alcove or closet, maintain the minimum clearances to combustible and non-combustible materials listed below. See also Fig. 5.
A. Top 12 inches (306 mm) B. Front 1 inches (25 mm) C. Back 0 inches D. Sides 1 inches (25 mm) E. Bottom 12 inches (306 mm)
Clearances from any exhaust vent pipe are dependent upon the clearance requirements of the stainless steel vent pipe manufacturer. Single wall stainless steel (AL29-4C) vent pipe (vent type rated for Category III appliances) must be used when exhaust venting this appliance. See 2.9 Venting.
2.7 Mounting installation
The GWH-635-ES is design certified for mounting on a wall. Secure the wall mounting bracket provided with the heater to a wall surface. See Fig. 6. Do not install this appliance on a carpeted wall or over floor covering which is combustible, such as carpet. The heater must be mounted on a wall using appropriate anchoring materials. If the mounting bracket is unable to line up on two wall studs it is recommended that support board(s), either 1x4's or ½" (minimum) plywood first be attached across a pair of studs and then the heater should be attached to the support boards. The heater should be kept level on the wall surface. See Fig. 6. Expansion and contraction of piping due to changing water temperature in the pipes imparts movement to the heater which, if mounted directly to a brittle, friable board, such as plasterboard, can cause failure of mounting.
Before installing the unit, be certain you have the correct heater for your type of Gas - Propane or Natural Gas. Identification labels are found on the
shipping box, and on the rating plate which is located on the right side panel of the cover.
Fig. 6 Mounting the heater
2.8 Combustion air requirements
The GWH-635-E5S is a sealeg water
heat er and it
8
6 720 607 072
Page 9
Appliance details
construction, infiltration air is normally adequate to provide air for combustion.
• Appliances located in confined spaces: The confined space must be provided with two permanent openings, one commencing within 12 inches (304.8mm) of the top and one commencing within 12 inches (304.8mm) of the bottom of the enclosure. Each opening must have a minimum free area of one square inch per:
– 1000 Btu/hr (292.81 Watts) if all air is taken from
inside the building
– 2000 Btu/hr (585.62 Watts) if all air is taken from
the outside by horizontal ducts
– 4000 Btu/hr (1171.24 Watts)if all air is taken from
the outside by direct openings or vertical ducts
Or the confined space must be provided with one permanent opening or duct that is within 12 inches (304.8mm) of the ceiling of the enclosure. This opening must have a minimum free area of one square inch per:
– 3000 Btu/hr (878.43 Watts) if all air is taken from
the outside by a direct opening or vertical duct.
Louvers, grills and screens have a blocking effect, when used, increase the sizes of your openings by 300% for wood louvers (as wood type will reduce the free air by 75%) and 40% for metal louvers (as metal will reduce the free air by 30%). Refer to the National Fuel Gas Code for complete information. In buildings of tight construction all air should be taken from outside.
NOTE: It is not recommended to use interior room air (SINGLE PIPE vent system) in areas that commonly experience below freezing temperatures. Clothes dryers, furnaces, woodstoves, bathroom or kitchen fans or other gas appliances can create negative air pressure when operating by removing air from the building. Cold air will be drawn back into the building, and if drawn through the water heater a freezing situation may occur. TWIN PIPE (room sealed) method of venting is recommended, see page 12. NOTE: When installed in beauty shops, barber shops, or other facilities where chemicals that generate corrosive or flammable products such as aerosol sprays are routinely used, shall be installed as sealed unit following the TWIN PIPE SYSTEM method of venting.
2.9 Venting
Warning: Do not reduce the vent
(exhaust and combustion) pipe sizes and do not common vent with any other vented appliance or stove.
NOTE: This appliance's exhaust must be vented to the outside1 with sealed stainless steel vent pipe (AL29-4C), the minimum vent length is 3 feet (a 90 degree vent elbow is equivalent to 2 ½ feet). The appliance's flue gasses are under positive pressure and must travel through a stainless steel 3" or 4" pipe that is sealed gas tight. NOTE: The exhaust collar on the water heater is 3" diameter and its collar must always be used, a 3" to 4" increaser will be required to be first connected to the exhaust collar when 4" venting is used. Different stainless steel vent manufacturer's have different joint systems, do not mix vent pipe or joining methods from different manufacturer's. Stainless steel vent pipe is equipped with sealing gaskets for ease of installation, proper safety and durability. The heater shall not be vented in combination with any other appliance; the appliance must only be vented with a dedicated sealed vent system.
Z flex Protech Heat Fab BBTNA
3” VENTING
3” Horizontal
Terminal 2SVSTB03 FSTB3 9390 TEE 2SVSTB03
3” Vertical
terminal
4” VENTING
Requires a 3”
to 4” Increaser 2SVI0304 FS0304TI 9374 2SVI0304
4” Horizontal
terminal
4” Vertical
terminal
Table 2 Terminals/Adapters Part Numbers
2SVSRCF03 FSRC3 5300CI 2SVSRCF03
2SVSRTF04 FSTB4 9490TEE FXHOOD
2SVSRCF04 FSRC4 5400CI ----------
Caution: The vent system must be installed by a qualified agency in accordance with these instructions. If improperly installed a hazardous condition such as explosion or Carbon Monoxide poisoning could result. BBTNA will not be responsible for improperly installed appliances.
6 720 607 072
Establish vent clearances that comply with the vent manufacturer's specifications. In all cases follow local codes. See table 3.
9
Page 10
Appliance details
The maximum flue gas exhaust temperature on the GWH-635-ES is 437°F (225°C)
Venting Options
Room sealed (twin pipe)
Open combustion (single pipe)
Exhaust vent is always fan assisted. Installation of exhaust vent and combustion air piping may be run vertically or horizontally and in separate directions if required.
+
The exhaust collar on the water heater is 3" diameter and its collar must always be used, a 3" to 4" increaser will be required
to be first connected to the exhaust collar when 4" venting is used. * A maximum of three 90 degree elbows are permitted in both the exhaust and combustion air vent lengths. The total vent length must be reduced by 1 ¼ feet for every 45° elbow used in the vent system. ** Stainless steel (AL29-4C) vent pipe is manufacturerd by Z-Flex, Protech and Heat Fab. NOTE: clearance distances are variable depending if the vent pipe is installed in an enclosed or unenclosed space, the exhaust flue gas temperature and the orientation of the vent pipe.
Exhaust vent diameter and material
3 or 4+ inch stainless steel (AL29-4C) sealed vent pipe
3 or 4+ inch stainless steel (AL29-4C) sealed vent pipe
* Exhaust vent maximum length
26 feet (8 m) with one elbow. Less 2½ feet for each additional 90° elbow
26 feet (8 m) with one elbow. Less 2½ feet for each additional 90° elbow
* Exhaust vent minimum length
3 feet 3 inch PVC,
3 feet See
Combustion air pipe diameter and material
aluminum or galvanized pipe
chapter 2.8
Combustion air pipe maximum length
26 feet (8 m) with one elbow. Less 2½ feet for each additional 90° elbow
See chapter 2.8
Vent pipe clearances within an unenclosed space
** See vent manufacturer's specifications
** See vent manufacturer's specifications
Vent pipe clearances within an enclosed space
** See vent manufacturer's specifications
** See vent manufacturer's specifications
Table 3
Minimum exhaust vent size and length
The appliance should be located as close to the point of termination as possible. The maximum vent length is 26 feet (8 m) with one 90 degree elbow. Subtract 2½ feet from the total vent length for each additional 90° elbow used (a maximum of three 90° elbows are permitted in the total vent length), or subtract 1 ¼ feet for every 45° elbow used. Horizontal sections of vent must pitch ¼" for every foot of horizontal length, to prevent the pooling of condensate, and be supported at 4 foot intervals with overhead hangers. Note: Listed thimbles or collars are necessary to pass through wall and ceiling partitions. If the vent system passes through combustible areas where the vent clearance requirements cannot be maintained, it is permissible to chase straight sections of sealed 3 inch single wall vent through 4 inch (or greater) Type-B vent. The distance to combustibles using this chase technique is 1 inch. Note: Type-B vent should never
be used as the actual exhaust vent system for the appliance, as it is not gas tight.
Fig. 7
Maximum exhaust vent and combustion air inlet lengths
10
Fig. 8
6 720 607 072
Page 11
Appliance details
Note: reduce 2½ ft for each 90° elbow used after the first one, reduce 1 ¼ ft for each 45° elbow.
Vent Safety System
The GWH-635-ES will shut down if inadequate exhaust venting is detected or a lack of combustion air is provided to the unit; see troubleshooting section on page 24. See error code to confirm error, correct the problem and then reset the heater before operating.
Attaching the exhaust and air inlet connection adaptors to the top of the heater
Use of the external condensate drain tube kit (supplied with the heater) on the exhaust collar
B The condensate drain tube kit must be used for all
installation types. Failure to install condensate drain will void the warranty.
B When installing the condensate drain tube kit at the
exhaust collar (see diagram below), be sure to form a trap by means of a 3" (76.2 mm) loop filled with water. The supplied tube is 3/8" ID high temperature silicone and must be attached to the condensate tapping on the exhaust collar with its supplied gear clamp (first remove screw at tapping point).
B To increase tube length, connect vinyl type tubing
after the supplied tube.
B The condensate must be disposed of according to
local regulations.
Fig. 9
Fig. 10
B Attach the flue gas exhaust accessory (8 705 504
114) to the top of the unit (position 1) using the 4 screws and gasket provided, and fully insert 3" stainless steel vent pipe into the accessory and tighten the clamp (position 2).
B Attach the combustion air inlet accessory (8 705
504 115) to the top of the unit (position 3) using the 3 screws and gasket provided, and fully insert 3" combustion air pipe into the accessory and tighten the clamp (position 4). NOTE: The appliance has the possibility to mount the combustion air inlet accessory on the top right or on the top left side of the heater. The combustion air inlet that is not used must be kept sealed.
Fig. 11
6 720 607 072
11
Page 12
Appliance details
i
i
2.9.1 Venting options
Installing this water heater as a room sealed (TWIN PIPE SYSTEM) is the recommended method. Contact BBTNA or dealer for available vent termination kits and vent materials for this water heater.
Exhaust venting shall be done with 3" or 4" stainless steel (AL29-4C) vent pipe.
Room sealed installation (TWIN PIPE SYSTEM)
Fig. 12
Combustion air pipe: 26 ft (8 m) Exhaust vent pipe: 26 ft (8 m)
Open combustion installation (SINGLE PIPE SYSTEM)
Not recommended in cold climate areas, see Chapter 2.8.
Fig. 14
Exhaust vent pipe: 26 ft (8 m)
Fig. 13
Combustion air pipe: 26 ft (8 m)
Exhaust vent pipe: A+B+C 23½ ft (7.2 m) Note: reduce 2½ ft for each 90° elbow used after the first one, reduce 1 ¼ ft for each 45° elbow. A maximum of three 90-degree elbows are permitted in both the exhaust and combustion air vent lengths.
The exhaust vent pipe and combustion air pipe can be run vertically or horizontally. Maximum length for each individual pipe is 26 feet (8 m) with one elbow, for each additional 90° elbow after the first elbow you must reduce 2½ feet from the total vent length, or 1 ¼ feet for each 45° elbow.
12
Fig. 15
Exhaust vent pipe: A+B+C 23½ ft (7.2 m)
The exhaust vent system must vent directly to the outside of the building and an adequate amount of indoor combustion air must be provided for this installation. See chapter 2.8. Connecting a one piece 90 degree elbow pipe to the combustion air inlet adaptor is necessary, this will prevent debris or objects from ever falling into the inlet opening. Note: reduce 2½ ft for each elbow used after the first one, reduce 1 ¼ ft for each 45° elbow. A maximum of three 90-degree elbows are permitted.
6 720 607 072
Page 13
Recommended exhaust vent terminator position
Fig. 16
Appliance details
Ref. Description Minimum distance
A
B
C From any internal corner 12 in
D*
E
F From a terminator facing a terminator 48 in
G Vertically between two exhaust vent terminators on the same wall 60 in
H Horizontally between two exhaust vent terminators on the same wall 12 in
I**
J From any external corner 12 in
K
Directly below an opening; operable windows, doors and any non­mechanical fresh air openings
Below a gutter, sanitary pipework or eaves 24 in
Below a gutter, sanitary pipework or eaves, protected by metal shielding
Above ground 12 in
Above a paved sidewalk 7 ft
From an opposing wall or structure facing the termination 24 in
From any other building opening, gas utility meter, service regulator or the like
Horizontally from combustion air inlet of GWH-635-ES
Vertically above or below combustion air inlet of GWH-635-ES
From the combustion air inlet of any other equipment 6 ft
Horizontally from an opening; operable windows, doors and any non-mechanical fresh air openings
36 in
12 in
36 in
36 in
12 in
L
Vertically from a wall, roof slope, or obstruction (venting through a flat or pitched roof)
see ABOVE THE ROOF
requirements on following page
Table 4
* Subject to local codes and anticipated snow level ** Other equipment that operates with a mechanical air inlet may require greater distances, reference manufacturer's instructions
6 720 607 072
13
Page 14
Appliance details
i
Supporting the exhaust vent system
The venting materials and accessories required to properly install the water heater are available from BBTNA and their distributors.
Fig. 17 Horizontal side wall venting installation
(combustion air piping not being shown)
Fig. 18 Above the roof clearance requirements from
rain cap (combustion air piping not being shown)
B A condensate drain tube must be attached to the
exhaust collar of the heater for all vent type applications, see page 11.
Fig. 19 Vertical venting installation (combustion air
piping not being shown)
A condensate drain tube must be attached to the exhaust collar of the heater for all vent type applications, see page 11.
14
6 720 607 072
Page 15
Appliance details
Gas piping
Inlet gas particle screen
2.10
Before connecting the gas supply, check the rating plate on the right side of the heater to be sure that the heater is rated for the same gas to which it will be connected. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada: The Installation should conform with CGA B149 INSTALLATION CODES and/or local installation codes.
GAS LINE SIZING
The gas supply piping should be sized according to the National Fuel Gas Code for a maximum draw of 175,000 BTUH. First determine the effective length of the gas supply line by measuring the actual length of piping, and then adding 5 ft. (1.52m) for every elbow or “T” to the actual length. Use the charts in Fig. 22 to determine the pipe diameter necessary to accommodate the BTU (Wh) demand of the unit. If there are more gas drawing appliances on the line, size according to the maximum amount of BTU (Wh) demand.
Note: It is important that if any flexible gas line is used, above or below ground between the gas supply meter/ regulator and the water heater, that it be sized properly. Consult the gas sizing specification tables provided by the flexible gas line manufacturer and sample CSST flexible gas line tables in Figure 22.
Gas piping & connections
Fig. 20 Vertical venting installation - Masonry
Chimney (combustion air piping not being shown)
A condensate drain tube must be attached to the exhaust collar of the heater for all vent type applications, see page, see page 11.
6 720 607 072
Fig. 21
B Install a manual gas shut off valve, on the gas supply
line.
B The use of a union when connecting gas pipe to the
gas inlet connection is critical, this will facilitate any necessary servicing and cleaning of the inlet gas particle screen.
B Flexible gas line connectors are not recommended
because they are commonly undersized and restrict gas flow. Oversize appliance connector if one must be used.
the diameter of any flexible gas
15
Page 16
Appliance details
Follow boxed numbers for piping just one 635-ES (example: ¾” B.I. Natural Gas pipe for 20 ft (6.1m). will handle 190,000 btu’s (55.7 kWh). For multiple appliances combine the total btu input load and then refer to applicable chart below.
Nominal Iron Length of Black Iron Pipe, Feet Pipe Internal
Size, Diameter
inches inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200
1/4 0.364 32 22 18 15 14 12 11 11 10 9 8 8 7 6
3/8 0.493 72 49 40 34 30 27 25 23 22 21 18 17 15 14
1/2 0.622 132 92 73 63 56 50 46 43 40 38 34 31 28 26
3/4 0.824 278 190 152 130 115 105 96 90 84 79 72 64 59 55
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100
1 1/4 1.380 1050 730 590 500 440 400 370 350 320 305 275 250 225 210
1 1/2 1.610 1600 1100 890 760 670 610 560 530 490 460 410 380 350 320
2 2.067 3050 2100 1650 1450 1270 1150 1050 990 930 870 780 710 650 610
* EHD = Equivalent Hydraulic Diameter. The greater the value of EHD, the greater the gas capacity of the tubing
.
Maximum Capacity of Semi-Rigid (flexible, non corrugated) Tubing in Thousands of BTU per Hour of
Undiluted Liquefied Petroleum Gases (at 11 inches Water Column Inlet Pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
* Source National Fuel Gas Code NFPA 54, ANSI Z223.1 - No Additional Allowance is necessary for an ordinary number of fittings
FOR LP GAS
Maximum Capacity of Pipe in Thousands of BTU per Hour of Undiluted Petroleum Gases (at 11 inches Water Column Inlet Pressure) (Based on a Pressure Drop of 0.5 Inch Water Column).
Copper
Outside Length of Tubing, Feet diameter Inch 10 20 30 40 50 60 70 80 90 100
3/8 39 26 21 19 _ _ _ _ _ _
1/2 92 62 50 41 37 35 31 29 27 26
5/8 199 131 107 90 79 72 67 62 59 55
3/4 329 216 181 145 131 121 112 104 95 90
Nominal
Iron Pipe
Black Iron Pipe
Size,
Length of Pipe, Feet
Inches
10 20 30 40 50 60 70 80 90 100 125 150
1/2 275 189 152 129 114 103 96 89 83 78 69 63
3/4 567 693 315 267 237 217 196 185 173 162 146 132
1 107 732 590 504 448 409 378 346 322 307 275 252
1 1/4 220 149 121 103 913 834 771 724 677 630 567 511
1 1/2 330 229 185 155 141 127 118 108 102 976 866 787
* EHD = Equivalent Hydraulic Diameter. The greater the value of EHD, the greater the gas capacity of the tubing.
Tube size, inches EHD*
10 20 30 40 50 60
1/2
18 EHD
82 58 47 41 37 34
3/4
23 EHD
161 116 96 83 75 68
1
30 EHD
330 231 188 162 144 131
1 1/4
37 EHD
639 456 374 325 292 267
Length of Flexible Corrugated Stainless Steel Tubing (CSST), Feet
Tube size inches EHD*
10 20 30 40 50 60
1/2
18 EHD
129 91 74 64 58 53
3/4
23 EHD
254 183 151 131 118 107
1
30 EHD
521 365 297 256 227 207
1 1/4
37 EHD
971 661 528 449 397 359
Length of Flexible Corrugated Stainless Steel Tubing (CSST), Feet
FOR NATURAL GAS
Maximum Capacity of pipe in Cubic Feet of Gas per Hour for Gas Pressure of 0.5 Psig or less and a Pressure drop of 0.3 in Water Column (0.75mbar).(Based on a 0.60 Specific Gravity Gas) Btu numbers given in thousands.
Fig. 22
16
6 720 607 072
Page 17
Appliance details
i
2.11 Gas line sizing
B It is strongly recommended that the Natural Gas pipe
be Black Iron pipe the entire distance from the outside meter to the inlet of the gas connection. ¾” Black Iron pipe up to 20 feet (6.1m) and 1” Black Iron pipe up to 70 feet (21.34m) distances. Flex line is NOT recommended, but if used, then oversize the diameter of the flex pipe, keep the length to a minimum and try to keep the flex line as straight as possible.
B It is strongly recommended that the LP Gas pipe be
semi-rigid copper or Black Iron pipe from the outside regulator to the inlet of the gas connection. For semi­rigid copper piping: 5/8” up to 10 feet (3.05m) and ¾” up to 30 feet (9.14m) distances. For Black Iron piping: ½” up to 20 feet (6.1m) and ¾” up to 80 feet (24.38m) distances. Flex line is NOT recommended, but if used, then oversize the diameter of the flex pipe, keep the length to a minimum and try to keep the flex line as straight as possible.
THESE FIGURES ARE FOR GWH-635­ES SUPPLY ONLY, ALL OTHER APPLIANCES IN THE BUILDING MUST BE INCLUDED IN THE PIPE SIZING.
2.12 Measuring gas pressure
2.12.1 Connecting Manometer
B Shut off gas. B Remove front cover and locate inlet gas pressure
measuring point (see Fig. 24).
B Loosen screw inside test point fitting (do not remove)
and connect manometer tube on test point.
2.12.2 Static Pressure Test
B Turn gas supply back on. B Operate all other gas appliances on same gas piping
system at maximum output.
B Record static gas pressure reading in table 5.
2.12.3 Operating Pressure Test
B ON/OFF switch in position OFF (0). B Press and hold "Program" (M) button and turn ON/
OFF switch to ON position.
National Fuel Gas Code requires that a sediment trap (drip leg) be installed on gas appliances not so equipped. Also, a manual gas shut off valve must be installed on the gas supply line within close proximity of the water heater and be visible from the water heater.
Warning: The heater must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures equal to or more than 0.5 psig.
The water heater must not be piped with gas supply pressures in excess of 0.5 psig. If overpressure has occurred, such as through improper testing of the gas lines or malfunction of the supply system, the gas valve must be checked for safe operation. When connections are made, check for gas leaks at all joints. Apply some soapy water to all gas fittings. Soap bubbles are a sign of a leak.
Danger: If you have a leak, shut off the gas. Tighten appropriate fittings to stop leak. Turn the gas on and check again with a soapy solution. Never test for gas leaks using a match or flame.
Fig. 23
B As soon as '188' is displayed, release "Program"
button and the display should read P2.
B Press , until P1 appears. Note: While in this mode the appliance will run
constantly at maximum power and allow maximum water flow.
B Turn on high volume of hot water flow (at least 6
gpm) and heater will ignite. B Record operating gas pressure reading in table 5. Gas pressures lower than 5" W.C. for Natural Gas or
11" W.C. for LPG will result in insufficient degree rise to the hot water being used, and must be corrected. See Gas Connections, chapter 2.10.
Fig. 24 Gas pressure measuring (left tapping)
6 720 607 072
17
Page 18
Appliance details
Static Gas Pressure Reading (see Chapter 2.12)
enter here: ___________________
Operating Gas Pressure Reading (see Chapter 2.12)
enter here: ___________________
Table 5
HIGH ALTITUDE OPERATION
Altitude Natural
0 - 4,000 ft (0 - 1,219 m)
4,000 ft - 7,000 ft (1,219 m - 2,134 m)
Above 7,000 ft (above 2,134 m)
Gas:
no
modification
CO2 adjustment with flue gas analyzer required See chapter9 for instructions.
Liquid
Propane:
no
modification
Not approved
For operation at
elevations
above 2,000 ft
(610 m) the
equipment ratings shall be reduced at the
rate of 4% for each 1,000 ft
(305 m) above
sea level
Table 6
2.13 Water connections
When facing the heater, the ¾” cold water inlet is on the bottom right and the hot water outlet is on the bottom left. Install the heater centrally in the building if possible and make hot water piping runs as short as possible.
local codes if more stringent). Never sweat any rigid piping directly to or beneath the water connections, damage can occur to the internal water valve from heating of the pipe. Plastics or other PEX type plumbing line materials are not suitable for connecting directly to the water heater. Keep water inlet and outlet pipes to no less than ¾" (19.05mm) diameter to allow the full flow capacity. If the cold and hot connections to the heater are reversed, the heater will not function. Be certain there are no loose particles or dirt in the piping. Blow out or flush the lines before connecting to the water heater. Full port valves should be installed on both the cold water supply and hot water outlet lines to facilitate servicing the heater (see Fig. 26). For installation on a private well system with the use of a pressure tank, the lowest pressure range setting recommended is 30-50 psi (2.07 and 3.45bar).
Connecting the pressure relief valve (PRV)
A listed pressure relief valve supplied with the heater must be installed at the time of installation. No valve is to be placed between the PRV and the heater. No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be a minimum of 4” above a drain and installed such that it allows complete drainage of both the PRV and the line. The location of the PRV must be readily accessible for servicing or replacement, and be mounted as close to the water heater as possible. See Fig. 26. To install the PRV, a suitable fitting connected to an extension on a “T” fitting can be sweated to the hot water line. Support all piping.
Fig. 25
B THE USE OF A UNION WHEN CONNECTING
BOTH WATER PIPES TO THE INLET AND OUTLET CONNECTIONS IS RECOMMENDED, THIS WILL FACILITATE ANY NECESSARY SERVICING AND REQUIRED CLEANING OF THE INLET WATER PARTICLE SCREEN.
Although water piping throughout the building may be other than copper, we recommend that copper, galvanized or suitably rated stainless steel flex line piping be used for the water heater connections (follow
18
Fig. 26 Plumbing Connections and Pressure Relief
Valve
6 720 607 072
Page 19
Appliance details
i
2.14 Electrical connections
Warning: For safety reasons,
disconnect the power supply to the heater before any service or testing is performed.
Warning: This heater must be electrically grounded in accordance with the most recent edition of the National Electrical Code. NFPA 70. In Canada, all electrical wiring to the heater should be in accordance with local codes and the Canadian Electrical Code, CSA C22.1 Part 1. Do not rely on the gas or water piping to ground the metal parts of the heater.
The GWH-635-ES requires an electrical power supply from a 120VAC 60Hz circuit and must be properly grounded. A means for switching off the 120VAC power supply must be provided. The heater is wired as shown in the wiring diagram (chapter 6, Fig. 37).
2.15 Operating instructions
B Before proceeding with the operation of the heater
make sure that the system is filled with water.
B Turn off power supply to heater. B Open the cold water inlet supply to the heater fully. B Open a hot water faucet to permit the water to fill the
heater and the piping and to eliminate the air trapped in the system.
B Close the hot water faucet after the water flows freely
and all the air has escaped from the system. Turn on power supply to heater. The water heater is now ready to operate.
NOTE: A default temperature setting of 122 F will appear on the display screen.
2.16 For your safety read before operating your water heater
Warning: If you do not follow these
instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with electronic ignition for lighting the main burners. When turning the heater on, follow these instructions exactly. B. Before operating the unit, set the On/Off switch to the On ( I ) position.
WHAT TO DO IF YOU SMELL GAS
B Do not try to light any appliance. B Do not touch any electric switch; do not use any
phone in your building.
B Immediately call your gas supplier from a neighbors
phone. Follow the gas supplier’s instructions.
B If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to turn the on/off control switch. Never use tools. Follow these instructions exactly. If control switch is jammed, close the gas supply and call a qualified service technician. Attempted forceful repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
2.17 Lighting and operating instructions
B 1. STOP! Read the previous safety information. B 2. The gas valve must be shut off by putting the ON/
OFF switch to position (0). Wait five (5) minutes to clear out any gas. If you smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
B 3. This appliance is equipped with electronic ignition
for lighting the main burners. When turning the heater on, follow these instructions exactly.
B 4. Set the ON/OFF switch to the (I) position. In this
position, the water heater is ready to use.
B 5. Open a hot water tap. B 6. The burners will remain on until the hot water tap
is turned off.
6 720 607 072
19
Page 20
Appliance details
i
NOTE: on a first time initial instal­lation or after gas line work has been done, existence of air in the gas line will cause ignition delay when the hot water is turned on. This will result in an error (EA) on the units display screen. This is normal. When this occurs, leave the hot water running and wait 3-5 seconds, then reset the unit (Fig. 26, pos. 2). Wait for (EA) to disap­pear. The heater will begin to at­tempt ignition again, if the (EA) reappears then repeat this same process until all air has been bled from the gas line.
When the heater is in operation you will hear its power vent fan and burner operating. Upon turning off the hot water flow the power vent fan will continue to operate for up to 60 seconds to exhaust all flue gases. The power vents fan speed is variable depending on the rate of hot water used and the burner output.
TO TURN OFF GAS TO APPLIANCE
B Turn off the manual gas shut off on the supply line to
the heater and set the ON/OFF switch to the OFF (0) position. Note: a manual gas shut off valve is not supplied with the heater.
20
6 720 607 072
Page 21
3 Operation instructions
Fig. 27
1 On/Off switch 2 Reset button 3 Program Key 4 Increasing temperature selector 5 Decreasing temperature selector 6 LCD display
Operation instructions
B Press buttons and in order to reach
requested temperature.
3.1 Power
On
B To start the appliance switch the button to position
(I). LCD display the default temperature - temperature factory setting 122°F (50°C).
Fig. 28
Off
B To shut down the appliance switch the button to
position (0).
Fig. 29
If the outlet water temperature is set too high, the heater can produce temperatures that are too hot. A temperature balance shower valve can automatically mix in cold water to reduce such hot water temperature. In the event of any temperature instability with the use of a temperature balance shower valve, refer to shower valve manufacturer's instructions for internal adjustment setting. Adjustments should be made to the hottest setting in the shower valve. Additionally the temperature control of the heater can be lowered to produce a more comfortable hot water temperature.
3.2 Temperature selection
To select water temperature outlet:
6 720 607 072
21
Page 22
Operation instructions
Hot Water Flow and Temperature with Various Inlet Temperature (lpm/Celsius)
0.00
4.00
8.00
12.00
16.00
20.00
24.00
35 40 45 50 55 60 65
Hot water temperature (ºC)
Hot Water Flow (l/min)
Inlet (ºC) 4 Inlet (ºC) 10 Inlet (ºC) 16 Inlet (ºC) 21
Hot Water Flow and Temperature with Various Inlet Temperature (gpm/Fahrenheit)
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
90 100 110 120 130 140 150
Hot water temperature (ºF)
Hot Water Flow (GPM)
Inlet (ºF) 40 Inlet (ºF) 50 Inlet (ºF) 60 Inlet (ºF) 70
Programming the heater to display temperature readings in Celsius is possible, contact BBTNA for instruction.
Setting the water temperature
The desired temperature of the hot water can be adjusted on the front control panel of the heater. The GWH-635-ES has an electronically controlled gas valve that modulates the burner input in response to both varying hot water flow rates and/or changes in any incoming and outgoing water temperatures.
Fig. 30 Flow/temperature charts
22
6 720 607 072
Page 23
3.3 Use of remote control accessory
i
Operation instructions
Fig. 34 Reset button
If the problem persists, contact your installer.
Fig. 31 Remote control
The wireless remote control accessory and the temperature selector buttons on the front of the water heater operate identically. Contact your distributor or BBTNA to order if the remote control accessory is preferred. Modification of the water heaters interior control unit (Fig. 29, component 12) is required when programming the remote control with this heater.
NOTE: up to 6 remote controls can be programmed for one single water heater, each with a range distance of 98 ft (30 m).
3.4 Operation
B When a hot water tap is opened, main burner ignites
and LCD displays indication .
Fig. 32
B LCD blinks until selected temperature is reached.
3.5 Reset button
If the LCD shows the error symbol . See the error code on LCD and consult “Troubleshooting” section.
3.6 Program button
Program button can be used/programmed in the appliance and in the remote control.
Programming “Program” function
Programming actions are similar for both controls (appliance control pad and wireless remote control).
Fig. 35 “Program” key
B Press buttons and to select temperature to
be memorized.
B Hold “Program” button for 3 seconds to save
temperature.
When LCD stops blinking. Temperature is saved on “Program”.
Using “Program” function
In order to select memorized temperature
B Press “Program” key.
LCD shows pre-memorized temperature, which is now the hot water selected temperature.
3.7 Locked condition
This condition is only valid for appliances with more then 1 controller (appliances with remote control).
Fig. 33
After following instructions indicated in “Troubleshooting” section
B press reset button in order to make the appliance
ready-to-work.
6 720 607 072
Fig. 36 Locked condition
Whenever LCD shows the temperature setting cannot be adjusted because the appliance is in use by a user which already selected a different temperature. Appliance will be automatically unlocked after closing hot water tap.
23
Page 24
Maintenance and service
4 Maintenance and service
Warning: Always turn off the electrical
power supply, turn off the manual gas valve and turn off the manual water control valves whenever servicing.
The unit should be checked once a year by a gas technician. If repairs are needed, the repairs should be done by a gas technician
To remove front cover
B Remove plastic decals on front panel (Page 5, Fig.
3).
B Loosen the two Philips head screws located behind
decals.
B Lift front cover panel upward and remove.
Systems and parts that should be checked at least once a year
Reference diagrams on pages 29 and 30.
• Venting system
• Burners -see page 29 for observation window
• Manual operation of the pressure relief valve to insure correct operation
• Periodic cleaning of the water filter screen, see Fig. 25, chapter 2.13.
• Flushing the heat exchanger with a descaling solution if mineral build up is evident. Scale build up will shorten the life of the water heater, descale heat exchanger thoroughly and repeat annually depending on mineral content of ground water.
5 Troubleshooting
Introduction
The GWH-635-ES burner is activated by a water flow valve. Numerous water related problems can cause this water valve to malfunction such as: Insufficient water flow volume to activate the burners at its minimum flow requirement; Dirt in the water flow valve causing it to malfunction; Sediment build-up in faucet aerators, or shower heads; Uneven pressures between cold and hot (with single lever mix valves); and Plumbing crossovers. These water flow related problems can cause the heater to deliver less than its full output, or to fail to ignite or to shut down completely. Problems stated below in upper case and in bold face should be investigated when there is a problem with the performance of the water heater but there is NO error code on the heater's LCD display or wireless remote control. Any failures that result in a displayed error code are referenced on page 26. A Functional Scheme of the GWH-635-ES is detailed on page 28. If there is a problem with the installation, venting or operation of the
unit, the heater will communicate the source by these error codes.
BURNERS DO NOT IGNITE WHEN HOT WATER IS TURNED ON
Cold incoming water connection made to
wrong side of heater
Make sure cold water inlet connection is plumbed to the right side of heater when facing unit
Water flow rate at hot water tap is too low A minimum of 0.8 gallon/minute (3 l/m) is required to activate the heater
Cold water inlet filter screen is dirty Remove water inlet filter screen and clean. The screen is located at the inlet connection to the water heater, disconnecting the main cold supply line at the heater is required. Check and clean faucet aerator screens too.
Crossover in plumbing The heater activates when there is sufficient water flow through its water valve, a minimum of 0.8 gallon/ minute (3 l/m) is required. If there is a crossover in the plumbing, the necessary hot water flow rate through the unit may not be reached, even though the flow at the hot water tap is sufficient. A plumbing crossover can be caused by a failed washer at a single lever faucet, incorrect plumbing or a faulty mixing valve in the piping. The crossover will create a back pressure on the water heater and prevent an adequate flow of water through it. To confirm there is no crossover in the plumbing, shut off the cold water supply feed to the water heater. Individually open each of the hot water taps. There should be no water flowing under a constant pressure. If there is a constant flow of water then the plumbing crossover must be corrected before the heater can operate properly.
WATER IS TOO HOT
Temperature selection too high Lower temperature adjustment on heater or wireless remote control accessory, see chapter 3.2.
WATER IS NOT HOT ENOUGH
Temperature selection too low Increase temperature adjustment on heater or wireless remote control accessory, see chapter 3.2
Btu input is too low due to inadequate gas line
sizing
See specifications in chapter 2.10 - 2.12. The GWH-635-ES requires adequate gas pressure to reach desired temperatures, to compensate for inadequate gas supply or lack of gas pressure the GWH-635-ES will effectively reach the selected output temperature by reducing the hot water flow rate. Its motorized water valve makes this adjustment
24
6 720 607 072
Page 25
Troubleshooting
Cold water is mixing with the hot water outlet
(crossover)
Test by following 4th bullet under BURNERS DO NOT IGNITE WHEN HOT WATER IS TURNED ON.
LOW WATER FLOW/PRESSURE
Too many hot water applications are being
used simultaneously or too much flow is being demanded
The GWH-635-ES will effectively support two 2.0-
2.5 gpm shower heads simultaneously or multiple sink applications. Greater draws will result in increased pressure drop and reduced flow at taps. See flow/temperature chart on page 22.
Btu input is too low due to inadequate gas line
sizing
See specifications in chapter 2.10 - 2.12. The GWH-635-ES requires adequate gas pressure to reach expected temperatures and flow rates, to compensate for inadequate gas supply or lack of gas pressure the GWH-635-ES will effectively reach the selected output temperature, but only by reducing the hot water flow rate. Its motorized water valve makes this adjustment. Proper gas pressure will need to be delivered before the motorized water valve will allow greater flow rates through it. Lowering the set temperature will also allow increased water flow rate through the motorized water valve. See flow/temperature chart on page 22.
Cold water inlet filter screen is dirty Remove water inlet filter screen and clean. The screen is located at the inlet connection to the water heater, disconnecting the main cold supply line at the heater is required. Check and clean faucet aerator screens too.
Adjustments should be made to the hottest setting in the shower valve. Additionally the temperature control of the heater can be lowered to produce a more comfortable hot water temperature.
Inlet water pressure is erratic due to
fluctuating supply water pressure
For installation on a private well system with the use of a pressure tank, the lowest pressure range setting recommended is 30-50 psi (2.07-3.45 bar). The use of a pressure reducing valve after the pressure tank is also an effective way to maintain a constant water pressure to the water heater. Watts brand 25AUB­¾” or N35B-¾” pressure relief valves or equivalent are suggested.
NOISY BURNER / HEATER DURING OPERATION
• CO2 range is out of adjustment. The cover must be in place to confirm CO2 readings. Operating with the cover removed may cause a noisy or unstable burner. See Chapter 9, CO2 adjustments can only be done by a certified gas technician with a calibrated CO analyzer.
2
HOT WATER TEMPERATURE FLUCTUATES / UNIT DEACTIVATED
Unbalanced pressure in water lines Any restriction caused by the water heater in the hot water system can result in uneven pressures between the cold and the hot. In such cases when mixing cold water at the tap (manually or automatically through a mix-type shower valve) the lower hot water pressure may be overpowered by the higher cold water pressure in the building and cause the hot water flow rate to fall below the minimum rate required. A pressure balance valve will help to resolve this symptom.
Temperature balance valves If the outlet water temperature is set too high, the heater can produce temperatures that are too hot. A temperature balance shower valve can automatically mix in cold water to reduce such hot water temperature. In the event of any temperature instability with the use of a temperature balance shower valve, refer to shower valve manufacturer's instructions for internal adjustment setting.
6 720 607 072
25
Page 26
Troubleshooting
Display Cause Solution
E9 Temperature limiter opened circuit
(overheat). Trips at 220F (104C).
EA No ionization during safety time (safety time
out). Note: appliance makes 3 ignition attempts before entering error mode “EA”.
EC The ionization signal momentarily
disappeared more then 5 times in less then 30 seconds.
FA Leakage error (gas valves do not close gas
circuit).
F7 Ionization error (flame sensing at stand-by). Check control unit.*
E0 Internal software/hardware failure. Check control unit.*
A7 Hot water temperature sensor/receiver
defect (from control unit).
A9 Hot water temperature sensor/receiver mis-
assembled (from control unit).
Note: if display shows “A9” flashing, the appliance can be operated normally, but performance may be affected.
Check connections.* Check heat exchanger condition.*
Check gas pressure.* Check that gas is not diluted with air, as a result from recent gas pipeline rework.*. Check if vent terminal is blocked (especially when the appliance starts up for some seconds and then looses ionization signal).* Check ionization electrode.* Check for a proper ground.*
Check gas valve and control unit.*
Check water temperature sensor/receiver and connections.* Check room area temperature where heater is located, it must be above 36°F (2°C)
Close water tap and allow 30 seconds for purging time. Open water tap and wait for 2 minutes to see if A9 message is deleted from the display. Check that the water temperature sensor/receiver is properly assembled in the water pipe.* Check that the water temperature sensor/receiver is in proper condition.*
C1 FAN rotation too low at start-up (from
control unit).
C6 FAN rotation too low at operation (from
control unit).
C7 No rotational speed sensor signal from FAN Check fan and connections.*
CA Water flow signal over specified maximum
value
E2 Inlet temperature sensor fault Check water temperature sensor/receiver and
A2 Overheat protection fault Check connections to the overheat protection.*
Check supply voltage.* Check fan and connections.* Check control unit.* Check if vent terminal is blocked or if vent terminal is according with Check CO2 levels (see chapter9).*
Check supply voltage.* Check fan and connections.* Check control unit.* Check if vent terminal is according with
chapter 2.9
Check control unit.* Check CO2 levels (see chapter9).*
Check water valve and flow sensor.*
connections.* Check room area temperature where heater is located, it must be above 36°F (2°C)
Check sensor continuity.* Check heat exchanger sealings and walls.*
chapter 2.9
.*
. *
Table 7
26
* By installer or service technician only.
6 720 607 072
Page 27
6 Electrical diagram
Electrical diagram
Fig. 37 Electrical scheme
1 Intlet water temperature sensor 2 Ionization sensor 3 Water flow sensor 4 Over heat protection 5 Temperature limiter 6 Gas valve 7 Fan 8 Water valve 9 AC Plug 10 Ignition electrode 11 Display PCB 12 ON/OFF switch 13 Fuse T 2,5A 14 Fuse T 3,15A 15 Terminal block 16 Ground post 17 Outlet water temperature sensor
6 720 607 072
27
Page 28
GWH-635-ES Functional scheme
7 GWH-635-ES Functional scheme
Fig. 38 Functional scheme
28
6 720 607 072
Page 29
Interior components diagram and parts list
8 Interior components diagram and parts list
8.1 Interior components
Fig. 39 Components
1 Cover 2 On/Off switch 3 Reset button 4 LCD display 5 Program button 6 Temperature switches 7 Flue gas collector 8 Mixer 9 Heat exchanger 10 Observation window 11 Inlet air duct 12 Control unit 13 Exhaust fan 14 Water valve 15 Gas valve
6 720 607 072
Fig. 40 Appliance overview
29
Page 30
Interior components diagram and parts list
8.2 Components diagram
Fig. 41 Components Diagram
30
6 720 607 072
Page 31
Interior components diagram and parts list
8.3 Parts list
Item Description Reference
1 Front cover 8 705 421 837
2 Shield 8 705 506 661
3 Heat exchanger 8 705 406 285
4 Heat exchanger top gasket 8 704 701 052
5 Clip 8 716 102 607
6 Heat exchanger bottom gasket 8 704 701 054
7 O-ring 8 700 205 147
8 Temperature sensor 8 700 400 015
9 Washer 1/2" 8 710 103 045
10 Wireform spring 8 714 606 002
11 Air inlet duct 8 705 700 097
12 Water filter 8 700 507 001
13 O-ring 8 700 205 134
14 Water valve with engine 8 708 505 016
15 Main burner 8 708 120 515
16 Fan / Burner gasket 8 704 701 050
17 Set of electrodes 8 708 107 020
18 Exhaust Fan 8 707 204 039
19 Gas / Air Mixer 8 705 700 115
20 Mixer / Fan gasket 8 704 701 059
21 Gas valve washer 8 704 701 062
22 Gas valve 8 707 021 019
23 Gas valve washer 8 700 103 014
24 Remote control 8 707 207 153
25 Control unit 8 707 207 133
26 Ignition cable 8 704 401 220
27 Cables / 24V 8 704 401 214
28 Cables 8 704 401 239
29 Power supply cord 8 704 401 221
30 Overheat cutoff fuse 8 700 400 019
31 Flue gas exhaust accessory 8 705 504 137
32 Combustion air inlet accessory 8 705 504 115
33 Flue gas collector 8 705 700 100
34 Flue gas collector collar 8 705 700 114
35 Cold water pipe 8 700 715 156
36 Hot water pipe 8 700 715 155
37 Air inlet screen 8 700 507 069
38 Crossover tube 8 700 715 247
39 Overheat sensor (ECO) 8 707 206 204
40 Clip - Heat exchanger 8 701 201 028
41 Clip - Over heat fuse 8 701 201 024
42 Gasket Exhaust 8 700 103 710
43 Gasket Set Combustion Chamber 8 704 701 046
44 O-ring air duct 8 700 205 149
Table 8
6 720 607 072
31
Page 32
Special adjustment for measuring and adjusting CO2 levels
9 Special adjustment for measuring and adjusting CO2 levels
The CO2 can only be adjusted by a certified gas technician with a calibrated CO2 analyzer.
Caution: One factor that may affect
CO2 levels is improper gas pressure. Please see Chapter 2.12 for the procedure to measure gas pressure and record your findings below:
Static Gas Pressure: “ WC
P1 Operating Pressure: “ WC
The P1 minimum operating pressure is 5" WC for Natural Gas and 11"WC for Propane. Do not proceed in adjusting CO2 until pressure has been verified to be at or above these levels, but not to exceed 14” WC.
A. Once Pressure is good
B Turn ON/OFF switch to the OFF (O) position. B Remove brass flat head screw on the exhaust collar
as seen in Fig. 42.
B Insert CO2 analyzer probe into the measuring port.
The tip of the probe should be in the center of the flue pipe (approx 1.5" inserted).
B. Measuring CO2 (Cover Installed):
B Open hot water taps to achieve a flow rate of at least
4 gallons per minute. (1 tub and 2 sinks should be sufficient).
B Record the CO2 reading in P2 below. (Analyzer
reading may take several minutes to stabilize).
B Press the ‘+’ button until P1 appears. Unit will ramp
up to high fire and the flow should increase. B Record the CO2 reading in P1 below. P2 CO2 Reading: % CO
P1 CO2 Reading: % CO
2
2
Compare your readings to those found in table 9 under the “With Front Cover” column. If CO2 readings are off make adjustments as outlined below.
Note: The “Without Front Cover” column give approximate values with the cover off to ease the adjustment process. Final readings should be taken with the cover on.
C. Adjusting CO2: Note: P1 adjustment will change the P2 reading.
Confirm the P1 value BEFORE adjusting the P2 level.
Fig. 42
B While holding the Program (M) button, move the ON/
OFF switch to ON (I) position (see Fig. 43). As soon as ‘188’ flashes on the display, release the Program button. The display should now read P2.
1. P1 CO2 level off: B Loosen yellow painted Philips screw (1) and cover
should rotate down (2) revealing a brass slotted
screw. Fig. 44. B Adjusting the slotted screw counter clockwise will
raise P1 CO2 levels and clockwise will lower P1
CO2 levels. Adjustments to the slotted screw will
also change P2 CO2 levels.
2. P2 CO2 level off: B Remove yellow painted #40 Torx cover from the front
of the gas valve. (Fig. 45) A plastic #40 Torx screw
will be revealed. B Adjusting the plastic #40 Torx screw counter
clockwise will lower P2 CO2 levels and clockwise
will raise P2 CO2 levels.
Note: These screw adjustment are very sensitive and may take several minutes to stabilize.
3. Verify both P1 and P2 are within the ranges specified in table 1 under the “With Front Cover” column. Repeat steps 1 and 2 as necesssary until CO2 values are within the specified ranges.
Fig. 43
32
6 720 607 072
Page 33
Special adjustment for measuring and adjusting CO2 levels
D. Returning to Service:
1. Return slotted cover to original position.
2. Reinstall Torx cover.
3. Remove CO2 analyzer probe and reinstall flathead screw in exhaust collar.
4. Turn ON/OFF switch to the OFF (O) position and then back to the ON (I) position.
5. Heater is ready for normal operation.
Without Front
Cover
Nat. Gas Nat. Gas
max. input P1 9.1 ± 0.1 % 9.7 ± 0.1 %
min. input P2 9.4 ± 0.1 % 9.7 ± 0.1 %
LP Gas LP Gas
max. input P1 10.1 ± 0.1 % 10.7 ± 0.1 %
min. input P2 10.4 ± 0.1 % 10.7 ± 0.1 %
* Final reading must be confirmed with the front cover on, CO2 levels increase when the cover is installed.
With Front
Cover
Table 9
Final Readings
P2 CO2 Reading: % CO
P1 CO2 Reading: % CO
2
2
Fig. 45
Fig. 44
6 720 607 072
33
Page 34
Protecting the environment
10 Protecting the environment
Packing
The packing box may be fully recycled as confirmed by the recycling symbol .
Components
Many parts in the heater can be fully recycled in the end of the product life. Contact your city authorities for information about the disposal of recyclable products.
Saving water resources:
B Make sure you close all the taps after any use. Avoid
leaving the taps dripping. Repair any leaking tap.
B Whenever possible use taps with built-in water flow
limiters. They will give you the same comfort level while saving water.
B Define the temperature you want, in the appliance or
with the remote control. This way you have the precise water flow needed (mixing cold water to regulate temperature will increase the water flow with consequent waste of water).
For increased safety shut off the appliance from the main water supply if your are staying away from home for a considerable time. At below freezing temperatures, disconnect the plumbing connections to the heater and allow the heater to drain. To prevent any freeze damage, introduce short bursts of compressed air (20-40 psi) through these connections to remove the residual water in the horizontal pipes and water valve.
34
6 720 607 072
Page 35
11 Fifteen Year Limited Warranty
i
Fifteen Year Limited Warranty
General
BOSCH PRO water heaters are warranted by the Manufacturer (BOSCH) through BBT North America. BBT North America (BBTNA) will furnish a replacement heat exchanger and will furnish a replacement of any other part which fails in normal use and service within the applicable periods specified below, in accordance with the terms of this warranty. The BBTNA replacement will be warranted for the unexpired portion of the original warranty. This warranty will be valid only for water heaters in possession of the original purchaser as recorded on the warranty card.
The Heat Exchanger
If the heat exchanger fails within fifteen (15) years after the original installation and operation, BBTNA will furnish a replacement heat exchanger. However, if the water heater is installed in other than a single family dwelling, this heat exchanger warranty is limited to two (2) years from date of original installation and operation.
Exceptions
This warranty will not apply:
1. to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided;
2. to damage or abuse, accident, neglect or freezing and other acts of nature;
3. to damage resulting from operation with either the flame sensor rod or overheat sensor removed;
4. to failure of the heat exchanger resulting from the operation of the water heater in a corrosive atmosphere or at water temperatures exceeding the maximum rating, or if the water heater is not supplied with potable water;
5. to defects or damage cause by any attachment or modification, including any energy-saving device.
All Other Parts
If any other part fails within three (3) years after original installation and operation, BBTNA will furnish a replacement part free of charge.
Shipping costs
In addition to supplying the replacement part(s), BBTNA will provide ground service delivery for these parts. Expedited or upgraded shipping will be charged to the customer.
of the original water heater or a replaced water heater. Certain service labor allowances are available to PHCC member contractors, dependent on prior authorization by BBTNA.
NOTE: the water heater must be free of damaging scale deposits and not subject to gas pressures greater than those shown on the rating plate, which must not be altered, defaced or removed.
How to Make a Claim
Any claim for warranty parts should be made to your local dealer, distributor or to BBTNA. If BBTNA, please contact the Technical Support Department:
BBT NORTH AMERICA Bosch Group 340 Mad River Park
Waitsfield, VT 05673 Phone 866-330-2730 www.boschpro.com
In most cases, the dealer or distributor will be able to promptly honor your claim and subsequently notify BBTNA. However, all replacements are made subject to validation by BBTNA of in-warranty coverage. The damaged or defective item must be made available in exchange for the replacement.
Miscellaneous
No one is authorized to make any other warranties on behalf of BBTNA. It is expressly understood that the replacement warranty of BBTNA shall be in lieu of any and all other warranties, express or implied, including warranties of merchantability or fitness for a particular use or purpose, and further that BBTNA shall not be liable for any loss or damage directly or indirectly arising from the use of the hot water heater, or for any consequential damages arising from such use (including damages from water leakage). BBTNA sole liability with respect to any defect shall be for the replacement of the defective part(s). Some states do not allow such limitations and exclusions, so the above may not apply to you. This warranty gives specific legal rights. You may also have other rights which vary from state to state.
Service Labor Costs
This warranty does not cover any labor costs associated with service, removal or re-installation of part(s). All such costs must be borne by the Purchaser. Additionally, this warranty does not cover any labor costs associated with service, removal or re-installation
6 720 607 072
35
Page 36
Installer Checklist, to be performed by installer upon installation
Serial Number ___ ___ ___ ___ ___ ___ ___ ___
(8 digit serial number is located on rating plate on right side panel)
Gas Pressure Reading* Static__________ Operating__________
Building Water Pressure __________ Range if on Well system __________
Installing Company _____________________________________________
Installer name _____________________________________________
Address _____________________________________________
Phone _____________________________________________
* See Chapter 2.12 and gas pressure table (to be filled out by installer)
Installation manual should be left with the owner after the installation is tested and completed
Replacement Parts available from:
BBT NORTH AMERICA Bosch Group
Bosch Water Heating 340 Mad River Park Waitsfield, VT 05673
VULCANO Termodomésticos S.A.
Estrada de Cacia
3801 - 856 Aveiro - PORTUGAL
Phone 866-330-2730 Fax (802) 426-6924 www.boschpro.com techsupport@boschpro.com
Recycled paper © 2005 BBT NORTH AMERICA,
Waitsfield, VT all rights reserved
Loading...