Bosch EVAX25E, EVAX50E, EVAX25ER Installation Manual

EVX-25E / EVX-50E
EXPANDER
INSTALLATION INSTRUCTIONS
The EVX-25E/ EVX-50E is a self contained amplifier, tone generator, power supply and supervisory interface. It is designed to be used in conjunction with the EVAX 25/ 50 to provide additional speaker output power. It may also be used stand-alone in conjunction with a Fire Alarm Control Panel to provide voice evacuation where an automatic message is not desired.
Installation and operation is identical to the EVAX 25/ 50 (see Installation Instructions P/N 1-5001 Rev. D). With the exception that no digital message is present. When used in conjunction with the EVAX 25/ 50 the Expander will act as a slave reproducing the tone and message generated by the master. When used as a stand-alone, the Expander will connect to the FACP exactly as the EVAX 25/ 50 does to provide automatic tone in alarm and voice override capability.
All terminal designations and volume controls are identical to the EVAX 25/ 50. One exception is that on the Expander SN1 determines Tone, Master/Slave, Battery and Mic. There is no SN2.
Factory defaults are: Expander as Slave 1 = OFF Temporal Whoop Signal 2 = OFF 3 = OFF
4 = OFF 5 = OFF
6 = OFF Slave (ON = Master setting) 7 = ON Battery connected (OFF = No Batteries) 8 = OFF No Mic (ON = Mic connected)
Expander as Master / Stand-Alone 1 = OFF Temporal Whoop Signal 2 = OFF 3 = OFF
4 = OFF 5 = OFF
6 = ON Master setting 7 = ON Battery connected (OFF = No Batteries) 8 = ON Mic connected
Switch Network Detail
1 8
OFF = 0 (UP)
ON = 1 (DOWN)
SN1 Tone Selection
SW 1/2/3 Sets the tone generated by the amplifier when it is operating in Master mode.
7 Settings: 0/0/0 Temporal Whoop
1/0/0 Hi / Lo Tone 0/1/0 Sine Wave 0/0/1 1 kHz Sine Wave 1/1/0 March Time Beep (880 Hz) 1/0/1 Slow Whoop 0/1/1 Code 3 Beep
For ratings and specifications see Installation Instructions P/N 1-5001 Rev. E
P/N 1-5002 REV. D
FIRE ALARM CONTROL PANEL
SIGNAL
CIRCUIT
ALARM POLARITY
INPUT POWER
120 VAC
Supervised
Non-Power Limited
EVX-25E / 50E
FIRE ALARM CONTROL PANEL
SIGNAL CIRCUIT
ALARM POLARITY
-
+
EVAX 25E / 50E
_
Supervised - Power Limited
+
Supervised - Power Limited
XFMR
FACP EOLR
MATCHING
EOLR
(SPEAKER
CIRCUIT)
TYPICAL INSTALLATION
TB1
1 2 345 6 7 8
1
J1
TB3
E O L
E O L
2
1 2 3 4
YEL
5 6
GRN
7 8
RED
YEL
GROUND
MSG
FAULT
GAIN
S1
*
FAULT
NORMAL
NORMAL
ALARM
MIC
GAIN
SN1
Battery Wire Harness
Supervised - Non Power Limited
Charging Current 1A max.
Supervised - Power Limited
CLASS “B” (Style “Y”)
WIRING
Standard Life Safety Speakers, Strobes connected and powered separately
Break wire to maintain supervision. Do not loop wire around speaker terminals
TB2
J5
1
11 10
2
9 8 7
J2
1 2 3
70V 25V
6 5 4 3 2 1
P2
FF II RR EE
II
II
RR
RR
EE
EE
CLASS “A” (Style “Z”)
WIRING
FF II RR EE
TB1
5 6 7 8
Supervised - Power Limited
FF
FF
For Fire Emergency Use Only
-
12V
Battery
+
Jumper Wire is Provided
E O
EOLR
L
FF II RR EE
EOL
-
12V
Battery
+
EVAX 25 / 50
Master / Slave Connection Detail
Non-Supervised - Power Limited Non-Supervised wiring
TO ADDITIONAL EXPANDERS
must be only run in the same cabinet or between cabinets which are piped together within the same room at a maximum of 20’.
120 VAC
Supervised
1 2 345 6 7 8
Non-Power Limited
1
J1
2
FAULT
YEL
NORMAL
ALARM
MIC
GAIN
1 2 3
70V 25V
J2
EVX-25 / 50
SN2 SN1
TB2
J5
1
11 10
2
9 8 7 6 5 4 3 2 1
P2
U6
FACP
EOLR
TB1
TB3
1 2
E
3
O
4
L
5 6 7 8
MSG GAIN
1 2 345 6 7 8
1
J1
2
SLAVE
FAULT
YEL
GRN
NORMAL
NORMAL
RED
ALARM
YEL
GROUND
MIC
FAULT
GAIN
EVX-25E / 50E
SN1
S1
J2
1 2 3
70V 25V
TB2
J5
1
11 10
2
9 8 7 6 5 4 3 2 1
P2
14 pin ribbon cable
(factory supplied) may be used
in place of hard wired connections
on TB2-11,5,3,1
Supervised ­ Power Limited
TB1
TB3
1 2
MASTER
3 4 5 6
GRN
7 8
RED
YEL
GROUND
MSG
FAULT
GAIN
S1
*NOTE: Switch SN1-6, SN1-8 must be in OFF position for all Slave modules. All Power and Speaker connections remain unchanged.
J1 Shorting blocks removed from slave units for pass-through supervision.
33 Chestnut St. New Haven, CT 06511 (203) 752-1806 FAX 752-1906