Bosch EVAX200ER, EVAX100EMR-8Z, EVAX100EMR-16Z, EVAX200, EVAX150EMR User Manual

...
P/N 1-5004 REV. C
EVAX 100
VOICE EVACUATION INTERFACE SYSTEM
INSTALLATION INSTRUCTIONS
GENERAL
The EVAX 100 is a self contained amplifier, tone generator, digital message repeater and supervisory interface. It is designed to be used in conjunction with a UL listed Fire Alarm Control Panel (FACP) to provide a Listed Voice Evacuation Alarm System.
The FACP provides all initiating circuitry and a signaling circuit to the EVAX 100. The EVAX 100 provides its own internal supervision as well as supervision for its speaker lines. Any fault is reported back to the FACP. In normal standby the supervisory circuit from the panel is connected to a matching EOLR. Should the EVAX 100 suffer an internal failure or should there be any fault on the speaker line, a contact would open and the FACP would report it as an open fault for that FACP circuit.
The EVAX 100 is designed to be powered from 120 VAC at 60 Hz. It will provide 100W to the speaker circuit. Speakers may be 25 or 70 VRMS (jumper selectable, 25 V is factory set).
MODELS
The EVX-100 is a complete Voice Evacuation Module. It is not equipped with a power transformer or a cabinet. The EVAX 100 is a complete Voice Evacuation Panel. It is equipped with a power transformer and a cabinet. The EVX-100E is a complete slave amplifier with built-in tone generator. It is capable of operating as a slave amplifier when connected to the EVX-100, which supplies source audio to the slave. It is also capable of operating as a stand-alone Voice Evacuation System with only tone and microphone amplification. Different Model numbers are derived from the amplifier sizes used together: These multiple amplifier configurations are Factory setup and pre-wired. The following are in their own cabinet with power transformers. They are complete Panels. EVAX 100 Contains: 1) EVX-100 1) Speaker Circuit EVAX 150 Contains: 1) EVX-100 and 1) EVX-50E 2) Speaker Circuits EVAX 200 Contains: 1) EVX-100 and 1) EVX-100E 2) Speaker Circuits EVAX 100E Contains: 1) EVX-100E 1) Speaker Circuit EVAX 150E Contains: 1) EVX-100E and 1) EVX-50E 2) Speaker Circuits EVAX 200E Contains: 2) EVX-100E 2) Speaker Circuits EVAX 300E Contains: 3) EVX-100E 3) Speaker Circuits EVAX 400E Contains: 4) EVX-100E 4) Speaker Circuits EVAX 500E Contains: 5) EVX-100E 5) Speaker Circuits EVAX 600E Contains: 6) EVX-100E 6) Speaker Circuits
INSTALLATION
Installer must insure that all wiring and devices installed in system meet the following standards: National Electrical Code (NFPA 70) NFPA Standard 72 Life Safety Code (NFPA 101)
Install equipment in a clean, dry environment. Avoid installation where equipment could be subjected to vibration. Remove electronic assemblies from the enclosure prior to any drilling or punching of the enclosure. Where possible, make all cable entries from the rear or sides. Before making any modifications to the enclosure, be certain that they will not interfere with assemblies or batteries.
33 Chestnut St. New Haven, CT 06511
1
(203) 752-1806 FAX 752-1906
WIRING (Refer to wiring and terminal designation diagrams)
1. Connect speaker lines to TB1 - 5(+) & 6(-). Observe polarity and insure all speakers are connected likewise. For Class "A" (Style "Z"), the returns are TB1 - 7(-) & 8(+).
2. Connect Speaker Matching EOLR to TB3 - 5 & 6. This value must be placed at the end of the speaker line as well.
3. Insure that the microphone is attached to connector P2. If the Microphone is not installed, insure that switch SN2 - 8 is in the OFF position.
4. Connect FACP signaling circuit to TB1 - 3(+) & 4(-), Alarm Polarity. Attach the appropriate EOLR for the FACP to TB3 - 3 & 4 You must use EOLR value as specified in the FACP manufactures installation instructions for the initiating appliance circuit.
5. Connect 120 VAC, 60 Hz, power to the black and white pigtail leads from transformer primary. Secure ground lead to grounding stud in cabinet.
6. Once power is applied to the unit, connect battery wiring harness, Red (+) / Black (-).Observe polarity. Minimum battery size is 24V 7AHr. Maximum battery size is 24AHr. (Use 2 12V batteries connected in series. See typical installation diagram). If the unit does not have its own batteries and relies on an external power supply with battery back-up, insure that switch SN2 - 7 is in the OFF position. NOTE: Wiring for batteries is Non Power-Limited. Care must be taken to insure that all Power-Limited wiring maintain a minimum spacing of ¼" from any Non Power-Limited wiring. If batteries must be located in separate enclosure, provide separate conduit run for battery wiring only.
Once all power and circuits are connected, the Green LED will remain on to indicate that the EVAX 100 is fully operational and all circuits are nominal.
OPERATION
In normal standby the Green LED will remain on.
In alarm condition the Red LED will remain on as long as the unit is in alarm. Green LED will also remain on.
Alarm Sequence Factory settings: Alarm Tone - Alarm Signal 5 seconds / Digital Message plays / Alarm Signal 5 seconds / Digital Message plays / Alarm Signal 5 seconds / Digital Message plays / unit reverts to Alarm Signal until alarm condition is cleared. If the Mic is keyed, it will override both the tone and the message so a direct broadcast may be made. If this occurs during the initial sequence the digital message will be reset and will not play.
When the Mic is keyed or when the message is played, the Green LED will dim. The intensity of the Green LED will vary with the level of the broadcast audio. This is true in Alarm condition as well.
Under a fault condition, the Yellow LED will remain on. The Green LED will flash. The number of flashes display a code depending on the specific type of fault. When there is a fault condition, the contact connecting the FACP signal circuit to the EOLR will open indicating the fault to the panel which will provide annunciation.
2
BATTERIES
The EVAX 100 contains a built-in battery charging circuit and supervision circuit. The EVAX 100 has a maximum available charging current of 1A. For 24V batteries, this relates to a maximum battery size of 24Ahr. The minimum recommended battery size 7Ahr.
OPTIONS
Refer to Terminal Designations diagram.
AUX +24VDC OUTPUT - TB2-8, 9 & 10 These terminals provide a maximum .5A of regulated 24VDC power for auxiliary functions. Do not exceed .5A load combined on these terminals. This connection may be used for auxiliary relay control control contacts which may be made or broken on the advent of an alarm condition.
CONNECTION OF AN AUX AUDIO SOURCE - TB2-1 & 2 An aux audio source from additional paging equipment may be connected to the EVAX 100 to augment an existing paging system. It is not intended for continuous signal input, but may be used for paging applications. For such operation, the Aux Audio Enable input ( TB2-6) must be powered from Int V+ (TB2-9). This is to insure that in the event of an alarm, the aux audio will not override the evacuation signal. See Wiring Diagram 5 for connection detail.
OPTIONAL SUPERVISORY CIRCUIT - TB3-1 & 2 In place of normal supervision via the signalling circuit, an alternate method may be employed using any supervisory circuit from the FACP. Connection would be made to Terminal Block 3, Ter. 1 and 2. This would provide a normally closed connection to the EOLR on Ter. 3 and 4. The relay contact in the circuit will open upon any trouble condition and report an open circuit trouble to the FACP. NOTE: Jumper shorting blocks 1 and 2 must be removed from J1 if a circuit is to be connected in this manner. See Wiring Diagram 2 for connection detail.
SPECIFICATIONS: *
AC DC Battery Voltage 120VAC 60Hz 24VDC 24VDC
Current -
Standby 0.60A 0.18A Standby + Aux. Load 1.20A 0.85A Alarm 2A Max. 2.60A 2.50A Alarm + Aux. Load 3.30A 3.10A Sine 6.5A 6.4A
*Input current measurements are determined by test conditions under UL 1711. Sine represents measurements made while unit produces a continuous non-distorted sine wave of 1 Khz into the rated load of 100W at rated output voltage. Alarm is the average current the unit experiences delivering an alarm signal, Temporal Whoop, to the rated load. Standby is the current draw of the unit with all normal power on and aux. terminals fully loaded. Battery Standby is current draw from the batteries on loss of power and otherwise normal standby.
3
EVAX 100
TERMINAL DESIGNATIONS
TB1: TER 1 & 2 - Power Input 24-32V AC/DC @ 6.5A (NOTE 3) TER 3 & 4 - FACP Signal Circuit Input - 10mA max. (Alarm Polarity shown) (NOTE 3) TER 5 & 6 - 25/70 VRMS Speaker Loop Style Y/Z (Class “A”/”B” start) (NOTE 1, 3) TER 7 & 8 - 25/70 VRMS Speaker Loop Style Z (Class “A” return) (NOTE 1, 3)
TB3: TER 1 & 2 (NOTE 3)
Optional FACP Supervisory Circuit See installation instructions for details (32V - 0.4A max.). Factory set for none - J1
TER 3 & 4
FACP Signal/Supervisory Circuit EOLR
TER 5 & 6
Matching EOLR for speaker supervisory circuit
TER 7 (NOTE 2,4) General purpose output (pulls to circuit neg on fault condition) 32V - 0.2A max. Not for Fire Protective Signaling use.
TER 8 (NOTE 2,4) Trouble input +24 VDC 5mA
NOTES:
1 - Power Limited 2 - Non-Supervised 3 - Supervised 4 - Terminating equipment must be installed in same room as EVAX 100.
TB1
1 2 3
TB31
2 3 4
5
YEL
6
GRN
7 8
RED
MESSAGE
GAIN
Switch Network Detail
GAIN
S1
1
2
MIC
J1
FAULT
NORMAL
ALARM
SN2 SN1
5 6 7 8
4
1 8
J2
1 2 3
OFF
ON
TB2
U6
11 10
9 8 7 6 5 4
3 2 1
P2
TB2: TER 1 - Circuit Neg
TER 2 (NOTE 2)
Aux Audio Input (0.5V nominal, 1VRMS - 1mA max.)
TER 3 (NOTE 2,4) PreAmp In/Out (600 Ohm 0dBm)
TER 4 (NOTE 2,4) Master - Circuit Neg Slave - Signal Com
TER 5 (NOTE 2,4) Signal Active Master - Out / Slave - In
TER 6 (NOTE 2) Aux Audio Enable (+24V)(32V - 5mA max.)
TER 7 (NOTE 2) Aux Signal Activate (+24V) (32V - 5mA max.)
TER 8 (NOTE 1,2,4) Alarm Voltage +24V when unit is in alarm condition (0.1A)
TER 9 (NOTE 1,2) Int V+ (+24V) disconnected in alarm condition (.25A)
TER 10 (NOTE 1,2) V+ (+24V .5A)
TER 11 (NOTE 4) Mic PTT (+24V 0.1A)
FACTORY DEFAULT SWITCH / JUMPER SETTINGS:
SN1
1 = OFF 8 sec. initial delay 2 = ON 3 = OFF 4 = ON 8 sec. repeat delay 5 = OFF 6 = ON Message On 7 = OFF 3 Repeats 8 = ON
SN2 1 = OFF Temporal Whoop Signal 2 = OFF 3 = OFF 4 = X 5 = X Do not use 6 = X 7 = ON Battery connected 8 = ON Mic connected
4
J1 A/B 1 - 2 = SHORT
J2 25 VRMS 2-3 = SHORT 70 VRMS 1-2 = SHORT
To change output voltage move shorting block.
FIRE ALARM CONTROL PANEL
SIGNAL
CIRCUIT
ALARM POLARITY
_
+
INPUT POWER
XFMR
120 VAC
Supervised
Non-Power Limited
Supervised - Power Limited
Supervised
FACP
E
EOLR
O L
E
EOLR
CIRCUIT)
O L
MATCHING
(SPEAKER
EVAX 100
TYPICAL INSTALLATION
Supervised - Power Limited
CLASS “B” (Style “Y”)
WIRING
TB1
1 2 3 4 5 6 7 8
TB2
11 10
9 8 7 6 5 4 3 2 1
P2
TB31
2 3 4
5 6 7 8
MESSAGE
GAIN
YEL
GRN
RED
MIC
GAIN
1
2
J1
FAULT
NORMAL
ALARM
J2
1 2 3
E O
EOLR
WIRING
FF II RR EE
L
FF II RR EE
FF II RR EE
Standard Life Safety Speakers, Strobes connected and powered separately
Break wire to maintain supervision. Do not loop wire around speaker terminals
FF II RR EE
FF II RR EE
CLASS “A” (Style “Z”)
TB1
5 6 7 8
Supervised - Power Limited
WIRING DIAGRAM 1
EOL
Input Power connection is Non-Power Limited. DO NOT route any Power Limited wiring within ¼" of Input cabling.
U6
S1
SN2 SN1
Battery Wire Harness Supervised - Non Power Limited Charging Current 1A max.
EVAX 100
CABINET LAYOUT
XFMR
1 2 345 6 7 8
1 2 3 4 5 6 7 8
TB3
TB1
TB2
11 10 9 8 7 6 5 4 3 2 1
Black
++
Red
--
--
12V
Battery
Battery
++
Jumper Wire Is Provided
ALL wiring from terminal blocks is Power Limited. Use K.O. at top or side of cabinet for wire routing.
12V
12V 7AHr.
Battery
Battery cabling is Non-Power Limited. DO NOT route any Power Limited wiring within ¼" of Input cabling.
12V 7AHr.
Battery
5
FIRE ALARM CONTROL PANEL
SIGNAL
CIRCUIT
ALARM POLARITY
FIRE ALARM CONTROL PANEL
SUPERVISORY
ZONE
EVAX 100
WIRING DIAGRAM 2
OPTIONAL SUPERVISORY
CIRCUIT APPLICATION
_
Supervised - Power Limited
+
TB1
ZONE EOLR
MATCHING
EOLR
(SPEAKER
CIRCUIT)
1 2 3
1
2
TB3
1 2
E
3
O L
4
E
5
O L
NORMALLY
6
CLOSED
7
TROUBLE
8
CONTACT
J1
4
*
1 2 3
5 6 7 8
J2
TB2
11 10
9 8 7 6 5 4 3 2 1
TO Next Device or EOLR
Power and Speaker connections remain unchanged.
NOTE: Jumper shorting blocks on J1
*
must be removed for this application.
ADDRESSABLE
CONTROL MODULE
CLOSES FOR
ALARM ACTIVATION
ADDRESSABLE
LOOP
ADDRESSABLE
MONITOR MODULE
N.O.
Addressable Modules must be located within 20' and interconnection must be in conduit.
24VDC
0.01A max
Supervised - Power Limited
Non Supervised - Power Limited
MONITOR
MATCHING
(SPEAKER
MODULE
EOLR
EOLR
CIRCUIT)
EVAX 100
ADDRESSABLE SYSTEM
APPLICATION
TB1
1 2 3 4 5 6 7 8
1
2
CLOSED
J1
*
J2
1 2 3
TB3
1 2
E
3
O L
4
E
5
O
6
L
NORMALLY
7 8
TROUBLE CONTACT
TB2
WIRING DIAGRAM 3
Power and Speaker connections remain unchanged.
11 10
9 8 7 6 5 4 3 2 1
NOTE: Jumper shorting blocks on J1
*
must be removed for this application.
6
FIRE ALARM CONTROL PANEL
SIGNAL CIRCUIT
ALARM POLARITY
-
+
TO ADDITIONAL EXPANDERS
EVAX 100
WIRING DIAGRAM 4
MULTIPLE UNIT
CONNECTION DETAIL
Non-Supervised wiring must be only run in the same cabinet or between cabinets which are piped together within the same room at a maximum of 20’.
TB1
1 2 3 4 5 6 7 8
J1
TB3
1 2
MASTER
3 4 5
FAULT
YEL
6
GRN
NORMAL
7 8
RED
ALARM
MESSAGE
MIC
GAIN
GAIN
EVX-100
S1
SN2 SN1
TB2
11 10
9 8 7
J2
1 2 3
6 5 4 3 2 1
P2
U6
FACP EOLR
TB1
TB3
1 2
E
3
O
4
L
5
YEL
6
GRN
7 8
RED
MESSAGE
GAIN
1 2 3 4 5 6 7 8
J1
*
SLAVE
J2
FAULT
1 2 3
NORMAL
ALARM
MIC
GAIN
EVX-100E
S1
SN1
TB2
11 10
9 8 7 6 5 4 3 2 1
P2
Supervised
*NOTE: Switch SN1-6 and SN1-8 must be in OFF position for all Slave modules. All Power and Speaker connections remain unchanged. J1 A/B Shorting blocks removed for pass-through supervision.
NOTE: Maximum number of units to be cascaded is 15
EVAX 100
WIRING DIAGRAM 5
AUX AUDIO ENABLE
CONNECTION DETAIL
TB1
1 2 3 4 5 6 7 8
1 2 3
TB3
5 6 7 8
4
Customer Provided
TB2
1
2
J1
J2
1 2 3
11 10
9 8 7 6 5 4 3 2 1
Interrupted V+
Aux Audio
Enable
Dry Contact
N.O.
Aux Audio
Input
7
EVX-100E
EXPANDER
INSTALLATION INSTRUCTIONS
The EVX-100E is a self contained amplifier, tone generator, power supply and supervisory interface. It is designed to be used in conjunction with the EVAX 100 to provide additional speaker output power. It may also be used stand-alone in conjunction with a Fire Alarm Control Panel to provide voice evacuation where an automatic message is not desired.
Installation and operation are identical to the EVAX 100 with the exception that no digital message is present. When used in conjunction with the EVAX 100, the Expander will act as a slave; reproducing the tone and message generated by the master. When used as a stand-alone, the Expander will connect to the FACP, exactly as the EVAX 100 does, to provide automatic tone in alarm and voice override capability with the microphone.
All terminal designations and volume controls are identical to the EVAX 100. One exception is that on the Expander SN1 determines Tone, Master/Slave, Battery and Mic. There is no SN2.
Factory defaults for SN1 are:
Expander as Slave
1 = OFF Temporal Whoop Signal 2 = OFF 3 = OFF
4 = OFF 5 = OFF
6 = OFF Slave (ON = Master setting) 7 = ON Batteries connected (OFF = No Batteries) 8 = OFF No Mic (ON = Mic connected)
Expander as Master / Stand-Alone
1 = OFF Temporal Whoop Signal 2 = OFF 3 = OFF
4 = OFF 5 = OFF
6 = ON Master setting 7 = ON Batteries connected (OFF = No Batteries) 8 = ON Mic connected
8
33 Chestnut St. New Haven, CT 06511 (203) 752-1806 FAX 752-1906
FIRE ALARM CONTROL PANEL
FACP EOLR
+
-
E O L
SIGNAL CIRCUIT
ALARM POLARITY
TB1
1 2 3 4 5 6 7 8
J1
*
TB3
1
SLAVE
2 3 4 5
FAULT
YEL
6
GRN
NORMAL
7 8
RED
ALARM
MESSAGE
MIC
GAIN
GAIN
EVX-100E
P3
P5
EVAX 100
Application Notes
MULTIPLE UNIT
CONNECTION DETAIL
Systems may come from the factory with 14 pin ribbon cable connecting a pair of modules. The ribbon cable connects to the polarized headers as shown below, with the red stripe indicating pin #1 at the top. Supervision wiring and FACP signal circuit wiring is not affected.
TB1
1 2 3 4 5 6 7 8
TB2
11 10
9 8 7
J2
1 2 3
6 5 4 3 2 1
P2
MESSAGE
TB3
1 2 3 4 5
YEL
6
GRN
7 8
RED
MIC
GAIN
GAIN
P3
J1
MASTER
FAULT
NORMAL
ALARM
EVX-100
P4
TB2
11 10
9 8 7
J2
1 2 3
6 5 4 3 2 1
P2
P4
U6
Non-Supervised wiring must be only run in the same cabinet or between cabinets which are piped together within the same room at a maximum of 20’.
S1
SN1
Supervised
S1
SN2 SN1
*NOTE: Switch SN1-6 and SN1-8 must be in OFF position for all Slave modules. All Power and Speaker connections remain unchanged. J1 A/B Shorting blocks removed for pass-through supervision.
NOTE: Maximum number of units to be cascaded is 15. Ribbon cable is only used within
the same cabinet. Connections made between units in multiple cabinets, see wiring
diagram # 4
33 Chestnut St. New Haven, CT 06511 (203) 752-1806 FAX 752-1906
Loading...