1 | Overview
The B820 SDI2 Inovonics Interface Module
allows a control panel to interface with an
Inovonics EN4200 EchoStream Serial Receiver
through the SDI2 bus.
1
2
NOTICE!
The module reads the address
switch setting only during power
up. If you change the switch after
you apply power to the module,
you must cycle the power to
the module in order for the new
setting to be enabled.
PWR A B COM
6
RX
5
TX
4
3
Figure 1.1: Module overview
Callout ― Description
1 ― SDI2 Terminal strip (to control
panel)
2 ― Serial data port (to Inovonics
receiver)
3 ― Address switch
4 ― Heartbeat LED (blue)
5 ― TX (transmit) LED (green)
6 ― RX (receive) LED (green)
2 | SDI2 address settings
The address switch determines the address
for the B820 module. The control panel
uses the address for communications. Use
a slotted screwdriver to set the address
switch.
Set the address for the module to 1 prior to
installing it in the EN4200 housing. Figure
2.1 shows the address switches setting for
address 1.
3 | Installation
After you set the address switch for the
proper address, install the module in the
EN4200 housing, and then wire the module
to the control panel.
CAUTION!
Remove all power (AC and
battery) before making any
connections. Failure to do so
might result in personal injury
and/or equipment damage.
3.1 | Install the B820 into
the EN4200 housing
Installing the module into the housing:
1. Use a slotted screwdriver to press
the housing release tab and separate the
housing. Refer to Figure 3.1.
2. Remove the backing from the Velcro
piece found in the product packaging to
reveal the Velcro adhesive.
3. Place the Velcro’s adhesive side onto
the back of the module.
4. Remove the remaining backing to use to
secure the module in the housing.
5. Insert the B820 module into the EN4200
housing, connecting the B820’s serial data
port to the EN4200’s serial data port. Refer
to Figure 3.2.
6. Gently apply pressure to the B820
module to snap it into the housing clips
and to apply the Velcro adhesive to the
housing.
Figure 3.1: Opening the EN4200 housing
1 2 3
Figure 3.2: Installing the B820 in the EN4200 housing
Callout ― Description
1 ― Housing clips to secure the module
2 ― B820 serial data port
3 ― EN4200 serial data port
3.2 | Wire the B820 to the control panel
When you wire a B820 to a control panel, use the control panel SDI2 terminals labeled R,
Y, G, B (PWR, A, B, COM). Connect them to the module terminals labeled PWR, A, B, COM.
Refer to Figure 3.3.
Figure 2.1: Address switch
Figure 3.3: Wiring to the control panel (GV4 Series control panel shown)
3.3 | Mount the EN4200
housing
Refer to the EN4200 EchoStream Serial
Receiver Installation Instructions for
mounting instructions.
4 | LED descriptions
The B820 module includes three LEDs:
TX (transmit) LED to indicate data
transmission, RX (receive) LED to indicate
data receipt, and Heartbeat LED to
indicate the status of the SDI2 connection.
Refer to Tables 4.1 and 4.2.
Flash pattern Function
TX (transmit) ON
steady
RX (receive) ON
steady
RX (receive) 3
quick fl ashes
Table 4.1: TX and RX LED descriptions
Flash
Pattern
Flashes
once every
1 second
3 quick
fl ashes
every 1
second
ON steady LED trouble state. Module
OFF steady
Table 4.2: Heartbeat LED descriptions
Occurs when
transmitting data to
the receiver.
Occurs when
receiving data from
the receiver.
Occurs when a
wireless device is
detected.
Function
Normal state. Indicates
normal operation state.
Communication error
state. Indicates (the
module is in a “no
communication state”)
resulting in an SDI2
communication error.
is not powered (for OFF
Steady only), or some
other trouble condition
prohibits the module from
controlling the heartbeat
LED.
5 | Show the fi rmware version
To show the fi rmware version using an LED
fl ash pattern:
-
Remove the cover to the EN4200 housing.
Refer to
Section 3.1.
- If you removed the cover previously, press
and release the tamper switch spring.
The heartbeat LED stays OFF for 3 seconds
before indicating the fi rmware version. The
LED pulses the major, minor, and micro
digits of the fi rmware version, with a 1
second pause after each digit.
In the following example, the version 1.4.3
shows as LED fl ashes:
[3 second pause] *___****___*** [3 second
pause, then normal operation].
Figure 5.1: Firmware LED fl ash patterns
6 | Certifi cations
Region
US UL 365 - Police Station
Canada CAN/ULC S303 - Local Burglar
Connected Burglar Alarm Units
and Systems
UL 609 - Local Burglar Alarm
Units and Systems
UL 636 - Holdup Alarm Units
and Systems
UL 985 - Household Fire
Warning System Units
UL 1023 - Household Burglar
Alarm System Units
UL 1076 - Proprietary Burglar
Alarm Units and Systems
UL 1610 - Central Station
Burglar Alarm Units
CSFM - California Offi ce of The
State Fire Marshall
FCC Part 15 Class B
Alarm Units and Systems
CAN/ULC S304 - Signal
Receiving Centre and Premise
ICES-003 - Information
Technology Equipment (ITE)
ULC-ORD C1023 - Household
Burglar Alarm System Units
ULC-ORD C1076 - Proprietary
Burglar Alarm Units and System
7 | Specifi cations
Dimensions 3.2 in x 2.8 in x 0.60 in
Voltage
(operating)
Current
(maximum)
Operating
temperature
Relative
humidity
Terminal wire
size
SDI2 wiring Maximum distance -
Compatibility B9512G/B9512G-E
Copyright
This document is the intellectual property of
Bosch Security Systems, Inc. and is protected
by copyright. All rights reserved.
Trademarks
All hardware and software product names
used in this document are likely to be
registered trademarks and must be treated
accordingly.
Bosch Security Systems, Inc. product
manufacturing dates
Use the serial number located on the
product label and refer to the Bosch Security
Systems, Inc. website at
http://www.boschsecurity.com/datecodes/.
(82.5 mm x 70 mm x
15.25 mm)
12 V nominal
110 mA total for B820
module and the EN4200
+32°F to +122°F
(0°C to +50°C)
5% to 93% at +90°F
(+32°C) non-condensing
12 AWG to 22 AWG
(2 mm to 0.65 mm)
Wire size:
600 ft (183 m) -
22 AWG (0.65 mm)
1000 ft (305 m) 18 AWG (2 mm)
(Unshielded wire only)
B8512G/B8512G-E
B5512/B5512E
B4512/B4512E
B3512/B3512E
D9412GV4
D7412GV4
(Each control panel
supports one B820.)
SDI2 Inovonics Interface Module
B820
en Installation Guide