Removal/Test Tool
Smoke Detector
EN
Operating Instructions
4998153055C
© 2004 Bosch Security Systems
Technical Support: (888) 886-6189
Customer Service: (800) 289-0096
Fairport, NY 14450-9199
130 Perinton Parkway
Bosch Security Systems
DT-2
1.0 Description
The DT-2 Smoke Detector
Removal/Test Tool is used with the
Bosch Spot Smoke and Heat detectors
for accessing the detector without the
use of a ladder.
2.0 Assembly
1. Place the DT-2 on the end of a
piece of conduit (0.5 in. Conduit)
or an extension pole and tighten
the thumb screw (#3, Figure 1)
to lock it into place.
2. See Figure 2. When using the
detector's built-in test feature,
place the supplied magnet (#1)
horizontally in the magnet slot
(#2).
Note: Only use the magnet when
testing the detector. If the
magnet is in place, it will cause
the detector to signal an alarm.
3.0 Detector Removal/
Installation
1. For detectors that have a tamper
lock, it must be held down before
the detector can be removed.
2. Break away the Tamper Release
Pin (#4, Figure 1) from the DT-2
and place it in the Tamper release
pin holder (#5, Figure 1).
3. With the DT-2 on the pole, place
it on the detector so that it locks
into place.
Note: See Figure 3. Make sure that
the pole is straight underneath
the detector (#2) and line-up
the detector LED (#3) with the
LED slot (#4) in the DT-2 (#1).
The Tamper release pin (#5,
Figure 3) will fit into the hole
(#6, Figure 3) on the detector
for the tamper release.
This will make it easier to place
it on the detector.
3.1 To remove the detector
1. With the DT-2 on the detector,
turn counter-clockwise.
2. Carefully pull the detector away
from the base. Keep the detector
relatively straight so that it doesn't
fall out of the DT-2.
3.2 To replace the detector
1. Use the lock-down hole and base
arrows as a visual key. The
Tamper release pin (#5,
Figure 5) is not needed to replace
the detector.
2. Make sure that the detector is
seated in the base properly.
3. Observe the detector LED to
ensure that the detector is
operating properly.
4.0 Testing
4.1 Magnet Test
(Sensitivity/Operation
Test)
1. See Figure 4. Place the supplied
magnet in the magnet slot,
according to the detector type
that needs to be tested.
2. If the detector is a Bosch F220
Series, place the magnet in the
slot marked #6 on Figure 1. If the
detector is another Bosch model,
place the magnet in the slot
marked #7 on Figure 1.
3. Place the DT-2 over the detector
with the magnet (#2) lined-up with
the "T" on the detector cover (#1).
4. Observe the detector LED
through the viewing slot in the
DT-2 and follow the instructions
provided with the detector to
determine if the test is successful.
4.2 Canned Smoke (NFPA Go/No Go Test)
1. If using canned smoke, use a UL Listed Aerosol smoke detector tester
such as the Home Safeguard Industries' 25S to simulate an alarm.
Follow the instructions with the Aerosol smoke detector tester.
2. If the pole is hollow (such as when using 0.5 in. Conduit) hold the DT2 near the detector and spray a small amount of smoke in the bottom
of the pole. The smoke will come out of the top of the pole and test
tool.
1
4
6
Figure 1: DT-2 Top View Figure 2: DT-2 Side View
2
3
4
Figure 3: Placing DT-2 on Detector
5
7
3
1
2
6
5
1
2
T
1
Figure 4: DT-2 on Detector
2