Bosch BP007-1HZC-FRS, CP030-1VTN-FRT, BP007-1HZN-FRS, BP007-1HZC-FLS, BP007-1HZN-FLS Installation And Maintenance Manual

...
Page 1
Installation and Maintenance Manual
CP/BP Series
6 720 220 045
Revised 05-12
Page 2
©Copyright 2012 Bosch, Inc All rights reserved
Page 3
Table of Contents
TABLE OF CONTENTS
CP/BP Series
3
Model Nomenclature ............................................. 3
Initial Inspection ................................................... 4
General Description .............................................. 4
Moving and Storage .............................................. 4
Safety Considerations ........................................... 4
Location ................................................................ 4
Installation ............................................................ 5
Mounting Vertical Units ......................................... 5
Mounting Horizontal Units .................................... 5
Condensate Drain ................................................. 6
Duct System .......................................................... 6
Electrical ............................................................... 7
Thermostat Connections ...................................... 8
Safety Devices and the UPM Controller ................. 8
Sequence Of Operation ...................................... 10
Unit Options........................................................ 10
Fluid Differential Pressure Switch ....................... 13
Earth Coupled Systems ....................................... 15
Unit Start-up ....................................................... 15
Heat Recovery Package ....................................... 15
Water Tank Preparation ....................................... 16
HR Water Piping ................................................. 16
Typical Connection Piping ................................... 16
Water Tank Rell ................................................. 17
Initial Start up ..................................................... 17
Maintenance ....................................................... 17
In-warranty Material Return ................................ 18
Unit Specications .............................................. 18
Physical Data ................................................ 18
Dimensions ................................................... 19
Fluid Pressure Drops ..................................... 20
Air Temperature Rise/Fall .............................. 21
Refrigerant Pressure Ranges ......................... 22
Blower Performance ..................................... 23
Water Piping ....................................................... 13
Well Water Systems ............................................. 13
Fresh Water Systems ........................................... 14
MODEL NOMENCLATURE
CP/BP 048 - 1 VT C - F L T
SERIES: CP/BP
NOMINAL CAPACITY: MBTUH
VOLTAGE DESIGNATION: 1- 208-230/1/60
CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL
WATER TO REFRIGERANT HEAT EX: C - COPPER N - CUPRO-NICKEL
Typical Wiring Diagrams ...................................... 24
Unit Check-out Sheet .......................................... 28
Troubleshooting .................................................. 29
SUPPLY AIR LOCATION:
T - TOP (VT ONLY)
S - STRAIGHT THRU (HZ ONLY)
E - END BLOW (HZ ONLY)
RETURN AIR LOCATION:
L - LEFT
R - RIGHT
WATER CONNECTION LOCATION
F - FRONT
6 720 220 045
Page 4
Initial Inspection
4
CP/BP Series
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each unit as received at the job site before signing the freight bill. Verify that all items have been received and that there are no visible damages; note any shortages or damages on all copies of the freight bill. In the event of damage or shortage, remember
that the purchaser is responsible for  ling the
necessary claims with the carrier. Concealed damages not discovered until after removing the units from the packaging must be reported to the carrier within 24 hours of receipt.
GENERAL DESCRIPTION
These Packaged System Heat Pumps provide the
best combination of performance and ef ciency
available. Safety devices are built into each unit to provide the maximum system protection possible when properly installed and maintained.
The CP/BP Water-to-Air Heat Pumps are Underwriters Laboratories (UL) and (cUL) listed for safety. The water-to-Air Heat Pumps are designed to
operate with entering  uid temperature between
25°F to 80°F in the heating mode and between 50°F
to 110°F in the cooling mode. Ef ciencies and capacities will vary as entering  uid and return air
temperatures vary.
50°F Min. EWT for well water applications
suffi cient water fl ow to prevent freezing. Antifreeze solution is required for all closed loop applications where the fl uid temperature may drop below 50°F. Cooling Tower/Boiler and Earth Coupled (Geo Thermal) applications should have suffi cient antifreeze solution to protect against extreme conditions and equipment failure. Frozen water coils are not covered under warranty.
This product should not be used for temporarily
heating/cooling during construction. Doing so may affect the unit’s warranty.
MOVING AND STORAGE
If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean,
dry area. Units must only be stored or moved in the normal upright position as indicated by the “UP” arrows on each carton at all times. If unit stacking is required, stack units as follows: Vertical units less than 6 tons, no more than two high; horizontal units less than 6 tons, no more than three high. Do not stack units larger than 6 tons.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be hazardous due to system pressure and electrical
components. Only trained and quali ed personnel
should install, repair, or service the equipment. Untrained personnel can perform basic functions of maintenance
such as cleaning coils and replacing  lters.
Before performing service or maintenance operations on the system, turn off main power to the unit. Electrical shock could cause personal injury or death.
When working on equipment, always observe precautions described in the literature, tags, and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves. Use a
quenching cloth for brazing, and place a  re
extinguisher close to the work area.
The blower motor should only be operated when a duct is installed and secured to heat pump duct collar in order to avoid possible injury.
LOCATION
Locate the unit in an indoor area that allows easy
removal of the  lter and access panels, and has
enough room for service personnel to perform
maintenance or repair. Provide suf cient room to make  uid, electrical, and duct connection(s). If the unit is located in a con ned space such as a closet,
provisions must be made for return air to freely enter the space. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. These units are not approved for outdoor installation; therefore, they must be installed inside the structure being conditioned.
Do not locate units in areas that are subject to freezing.
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 5
VIBRATION
PAD
FULL SIZE
Installation
CP/BP Series
5
INSTALLATION
Remove shipping block under blower housing.
Loosen compressor mounting bolts.
The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedent over any recommendations contained in these instructions. In lieu of local codes, the equipment should be installed in accordance with the recommendations made by the National electric code, and in accordance with the recommendations made by the National Board of Fire Underwriters. All local seismic codes for seismic restraint of equipment, piping, and duct work shall be strictly adhered to.
MOUNTING VERTICAL UNITS
Vertical units up to six tons are available in left or
right air return con gurations. Vertical units should
be mounted level on a vibration absorbing pad slightly larger than the base to minimize vibration transmission to the building structure. It is not
necessary to anchor the unit to the  oor. (See
Figure #1).
MOUNTING HORIZONTAL UNITS
While horizontal units may be installed on any level surface strong enough to hold their weight, they are typically suspended above a ceiling by threaded rods. The rods are usually attached to the unit corners by hanger bracket kits (P/N 930-008). (See Figure #2). The rods must be securely anchored to the ceiling. Refer to the hanging bracket assembly and installation instructions for details. Horizontal units installed above the ceiling must conform to all local codes. An auxiliary drain pan if required by code should be at least four inches larger than the bottom of the heat pump. Plumbing connected to the heat pump must not come in direct contact with joists, trusses, walls, etc.
If the unit is located in a con ned space such as a
closet, provisions must be made for return air to freely enter the space.
VIBRATION
PAD
FULL SIZE
Figure #1 – Vertical unit on vibration pad
Figure #2 – Typical horizontal unit hanging bracket
Some applications require an attic  oor installa-
tion of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary
drain pan prevents possible condensate over ow
or water leakage damage to the ceiling. The secondary drain pan is usually placed on a ply­wood base isolated from the ceiling joists by additional layers of vibration absorbing mesh. In both cases, a 3/4” drain connected to this second­ary pan should be run to an eave and able to drain to a location that will be noticeable. If the unit is located in a crawl space, the bottom of the unit
must be at least 4” above grade to prevent  ood-
ing of the electrical parts due to heavy rains.
Locate the heat pump unit in an area that provides
suf cient room to make water and electrical
connections, allowing easy removal of the access
6 720 220 045
Page 6
6
Condensate Drain
CP/BP Series
panels, and replacement of air lters for routine
maintenance. This will ensure proper work space for service personnel to perform maintenance or repair.
See Unit Specications for replacement lter sizes
in the back of this manual to ensure proper clearances are provided during installation. Allow adequate room below the unit for a condensate drain trap on horizontal units.
Water freezes at 32°F. Frozen water coils are not covered under the limited product warranty. It is the installer’s responsibility to insure that the heat pump unit is installed in a location or have taken the proper precautions in order to prevent rupturing the water coil due to freezing conditions.
The heat pump unit is designed for conditioned space installation only. If the source water is subjected to conditions where ambient temperatures can fall below freezing, some form of freeze protection should be employed. In an open loop system this may entail running the water pump continuously to prevent freezing. An antifreeze solution wherever possible should be used if water will be subject to freezing. Consult the factory in these instances for guidance.
CONDENSATE DRAIN
A drain line must be connected to the heat pump and pitched away from the unit a minimum of 1/8”
per foot to allow the condensate to ow away from
the unit.
Figure #3 – Heat Pump Condensate Trapping
(Heat Pumps are not internally trapped). A vertical air vent is sometimes required to avoid air pockets (See Figure #3). The length of the trap depends on the amount of positive or negative pressure on the drain pan. A second trap must not be included.
The horizontal unit should be pitched approximately 1/4” towards the drain in both directions, to facilitate condensate removal. See Figure 4 below.
Figure #4 – Sloped horizontal unit installation
DUCT SYSTEM
A supply air outlet collar and return air duct ange
are provided on all units to facilitate duct
connections. See Unit Specications for duct collar
connection sizes in the back of this manual.
A exible connector is recommended for supply
and return air duct connections on metal duct systems. All metal ducting should be insulated with a minimum of one inch duct insulation to avoid heat loss or gain and prevent condensate forming during the cooling operation. Application of the unit to uninsulated duct work is not recommended as the unit’s performance will be adversely affected. Do not connect ducts directly to the blower outlet; factory supplied duct collars should be used for
connection. The factory provided air lter must be removed when using a lter back return air grill. The factory lter should be left in place on a free return
system.
This connection must be in conformance with local plumbing codes. A trap must be installed in the
condensate line to insure free condensate ow.
6 720 220 045
If the unit will be installed in a new installation which includes new duct work, the installation should be designed using current ASHRAE procedures for duct sizing. If the unit is to be connected to existing ductwork, a check should be made to assure that the duct system has the
Subject to change without prior notice Revised 05-12
Page 7
Electrical
CP/BP Series
7
capacity to handle the air required for the unit application. If the duct system is too small, larger ductwork should be installed. Check for existing leaks and repair as necessary to ensure a tight air seal within duct. The duct system and all diffusers
should be sized to handle the designed air ow
quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be insulated. There should be no direct straight air path thru the return air grille into the heat pump. The return air inlet to the heat pump must have at least one 90 degree turn away from the space
return air grille. If air noise or excessive air ow are
a problem, the blower speed can be changed to a
lower speed to reduce air ow. (Refer to ECM
motor speeds and settings in Table #1)
Always disconnect power to the unit before changing motor speed to prevent damage to the motor, injury or death due to electrical
shock.
ELECTRICAL
Always disconnect power to the unit before servicing to prevent injury or death due to electrical shock or contact with moving parts.
All eld wiring must comply with local and national re, safety and electrical codes. Power to the unit
must be within the operating voltage range indicated on the unit’s nameplate. On three phase units, phases must be balanced within 2%.
Operating the unit with improper line voltage or with excessive phase imbalance is hazardous to the unit and constitutes abuse and is not covered under warranty.
Properly sized fuses or HACR circuit breakers must be installed for branch circuit protection. See equipment rating plates for proper size.
The heat pump units are provided with a concentric knock-out in the front right corner post for attaching common trade sizes of conduit. Route power supply wiring through this opening. Flexible wiring and conduit should be used to isolate vibration and noise from the building structure. Be certain to connect the ground lead to the ground lug in the control box. Connect the power leads as indicated on the unit wiring diagrams.
Table 1: CP/BP Motor CFM Selection (ECM Motor)otor Only)
Units
CP/BP015 450-153 1/3 LOW MED HIGH - -
CP/BP018 450-153 1/3 - LOW - MED HIGH
CP/BP024 450-157 1/3 LOW MED HIGH - -
CP/BP030 450-154 1/3 LOW MED HIGH - -
CP/BP036 450-158 3/4 LOW MED HIGH - -
CP/BP042 450-155 3/4 LOW MED HIGH - -
CP/BP048 450-155 3/4 - LOW MED HIGH -
CP/BP060 450-156 1 LOW MED HIGH - -
CP/BP070 450-156 1 LOW - - MED HIGH
Motor Part
Number
Motor HP Tap1 Tap2 Tap3 Tap4 Tap5
6 720 220 045
Page 8
8
Thermostat Connections
CP/BP Series
THERMOSTAT CONNECTIONS
Thermostat wiring is connected to a 7 position low voltage terminal block in the electrical box. The thermostat connections and their functions are as follows:
Y Compressor Operation
G Fan
O Reversing Valve (energized in cooling)
C Transformer 24 VAC Common – 3 Connections
R Transformer 24 VAC Hot
If the unit is being connected to a thermostat with a malfunction light, this connection is made at the unit alarm output.
If the thermostat is provided with a malfunction
light powered off of the common (C) side of the transformer, a jumper between “R” and “COM”
terminal of “ALR” contacts must be made.
below or remains at freeze limit trip for 30 seconds, the controller will shut down the compressor and enter into a soft lockout condition. The default freeze limit trip is 30°F, however this can be changed to 15°F by cutting the R42 resistor located on top of DIP switch SW1.
• The optional condensate over ow protection
sensor (standard on horizontal units) is located in the drain pan of the unit and connected to the ‘COND’ terminal on the UPM board.
If the thermostat is provided with a malfunction
light powered off of the hot (R) side of the transformer, then the thermostat malfunction light connection should be connected directly to the
(ALR) contact on the unit’s UPM board.
SAFETY DEVICES AND THE UPM CONTROLLER
Each unit is factory provided with a Unit Protection Module (UPM) that controls the compressor opera­tion and monitors the safety controls that protect the unit.
Safety controls include the following:
• High pressure switch located in the refrigerant
discharge line and wired across the HPC terminals on the UPM
• Low pressure switch located in the unit
refrigerant suction line and wired across terminals LPC1 and LPC2 on the UPM.
Freeze Protection Sensor
• Optional freeze protection sensor, mounted close
to condensing water coil, monitors refrigerant temperature between condensing water coil and thermal expansion valve. If temperature drops
6 720 220 045
If freeze protection sensor is not installed, a
jumper between freeze contacts must be installed
on the UPM board otherwise unit will not start.
Subject to change without prior notice Revised 05-12
Page 9
Safety Devices and the UPM Controller
CP/BP Series
9
The UPM includes the following features:
ANTI-SHORT CYCLE TIME—5 minute delay on break timer to prevent compressor short cycling.
RANDOM START—Each controller has a unique random start delay ranging from 270 to 300 seconds to reduce the chances of multiple units simultaneously starting after initial power up or after a power interruption, creating a large electrical spike.
LOW PRESSURE BYPASS TIMER—If the compressor is running and the low pressure switch opens, then the control will keep the compressor on for 120 seconds. After 2 minutes if the low pressure switch remains open, the control will shut down the compressor and enter a soft lockout. The compressor will not be energized until the low pressure switch closes and the anti-short cycle time delay expires. If the low pressure switch opens 2–4 times in 1 hour, the unit will enter a hard lock out and need to be reset.
BROWNOUT/SURGE/POWER INTERRUPTION PROTECTION—The brownout protection in the UPM
board will shut down the compressor if the incoming power falls below 18 VAC. The compressor will remain off till the voltage goes above 18 VAC and the anti short cycle timer (300 seconds) times out. The unit will not go into a hard lockout.
MALFUNCTION OUTPUT—Alarm output is Normally Open (NO) dry contact. If 24 VAC output is needed R must be wired to the ALR-COM terminal; 24VAC will be available on the ALR-OUT terminal when the unit is in alarm condition. If pulse is selected the alarm output will be pulsed. The fault output will depend on the dip switch setting for “ALARM”. If it set to “CONST’, a constant signal will be produced to indicate a fault has occurred and the unit requires inspection to determine the type of fault. If it is set to “PULSE”, a pulse signal is produced and a fault code is detected by a remote device indicating the fault. See L.E.D. Fault Indication below for blink code explanations. The remote device must have a malfunction detection capability when the UPM board is set to “PULSE”.
TEST DIP SWITCH—A test dip switch is provided to reduce all time delay settings to 10 seconds
during troubleshooting or veri cation of unit
operation. Note that operation of the unit while in test mode can lead to accelerated wear and
premature failure of the unit. The “TEST” switch must be set back to “NO” for normal operation.
FREEZE SENSOR—The freeze sensor input is active all the time, if a freeze option is not selected the freeze terminals will need a jumper. There are
2 con gurable freeze points, 30°F & 15°F. The unit
will enter a soft lock out until the temperature climbs above the set point and the anti-short cycle time delay has expired. The freeze sensor will shut the compressor output down after 90 seconds of
water  ow loss and report a freeze condition. It is recommended to have a  ow switch to prevent the unit from running if water  ow is lost.
If unit is employing a fresh water system (no
anti-freeze protection), it is extremely important to have the “Freeze” jumper R42 resistor set to 30°F in order to shut down the unit at the appropriate leaving water temperature and protect your heat pump from freezing if a freeze sensor is included.
L.E.D. FAULT INDICATION—Two L.E.D. indicators are provided:
• Green: Power L.E.D. indicates 18—30 VAC
present at the board.
• Red: Fault indicator with blink codes as follows:
- One blink—High pressure lockout
- Two blinks—Low pressure lockout
- Three blinks—Freeze sensor lockout
- Four blinks—Condensate over ow
- Five blinks—Brownout
INTELLIGENT RESET—If a fault condition is initiated, the 5 minute delay on break time period is initiated and the unit will restart after these delays expire. During this period the fault LED will indicate the cause of the fault. If the fault condition still exists or occurs 2 or 4 times (depending on 2 or 4 setting for Lockout dip switch) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout
reset. A single condensate over ow fault will cause
the unit to go into a hard lockout immediately, and will require a manual lockout reset.
6 720 220 045
Page 10
10
CP/BP Series
Sequence of Operation
LOCKOUT RESET—A hard lockout can be reset by turning the unit thermostat off and then back on when the “RESET” dip switch is set to “Y” or by shutting off unit power at the circuit breaker when the “RESET” dip switch is set to “R”.
The blower motor will remain active during a
lockout condition.
UPM BOARD DEFAULT SETTINGS—Your UPM board will come from the factory with the following default settings:
Freeze—“Terminals not jumped” on all the time
Temp—30°F
Lockout—2
Reset—“Y”
Alarm—“PULSE”
Test—“NO”
Dry Contact—“Normally Open (NO)”
Considerations
1. Always check incoming line voltage power
supply and secondary control voltage for adequacy. Transformer primaries are dual tapped for 208 and 230 volts. Connect the appropriate tap to ensure a minimum of 18 volts secondary control voltage. 24 volts is ideal for best operation.
SEQUENCE OF OPERATION
Cooling Mode
See Typical Wiring Diagrams at the end of the document. Energizing the “O” terminal energizes the unit reversing valve in the cooling mode. The fan motor starts when the “G” terminal is energized.
When the thermostat calls for cooling (Y), the loop pump or solenoid valve if present is energized and compressor will start.
Once the thermostat is satis ed, the compressor
shuts down accordingly and the fan ramps down to either fan only mode or off over a span of 30 seconds (ECM Motors).
Note that a fault condition initiating a lockout will de-energize the compressor.
Heating Mode
Heating operates in the same manner as cooling, but with the reversing valve de-energized. The compressor will run until the desired setpoint temperature on the thermostat is achieved.
Once the thermostat is satis ed, the compressor
shuts down and the fan ramps down in either fan only mode or turns off over a span of 30 seconds. Auxiliary electric heating coils are not available on the BP/CP product line.
UNIT OPTIONS HOT GAS REHEAT (HGR)
2. Long length thermostat and control wiring
leads may create voltage drop. Increase wire gauge or up-size transformers may be required to insure minimum secondary voltage supply.
3. FHP recommends the following guidelines for
wiring between a thermostat and the unit: 18 GA up to 60 foot, 16 GA up to 100 ft and 14 GA up to 140 ft.
4. Do not apply additional controlled devices to
the control circuit power supply without consulting the factory. Doing so may void equipment warranties.
5. Check with all code authorities on requirements
involving condensate disposal/over  ow
protection criteria.
6 720 220 045
Hot gas reheat allows the user to not only control space temperature, but also humidity levels within the conditioned space. An excess of moisture in the space can allow mold growth leading to damage in the structure or interior surfaces as well as reducing the air quality and creating an unhealthy environment.
The typical control of a unit is by a thermostat that senses the temperature in the space. By utilizing a humidistat in addition to the thermostat we are able to monitor the humidity levels in the space as well. The HGR option allows cooling and
dehumidi cation to satisfy both the thermostat and
humidistat.
Subject to change without prior notice Revised 05-12
Page 11
Sequence of Operation
UPM Sequence of Operation (SOO) Flow Chart
Y1=1
NO
YES
Power/Switchs/Sensor
Status Check
>
V
18VAC
YES
HPC = 1
NO
NO
Blink Code On Status LED
Soft Lockout
Record Alarm
Start Counter (If Applicable)
CP/BP Series
Lockout Can Be Set To
4 Via Dip Switch
COUNT = 2
NO
11
YES
LPC = 1
YES
FRZ
TEMP
>
LIM
YES
CON
>
YES
INITIAL
POWER UP
YES
YES
YES
NO
Start Timer
TIME
SEC
>
120
NO
YES
NO
Start Timer
TIME
SEC
>
30
CC Output = Off
NO
Blink Code On Status LED
Report Alarm Fault
0
NO
Start
Anti Short Cycle
NO
Hard Lockout
ALR Output = On/Pulse
NO
YES
CC Output = On
Start
Random Start Up
T
>
RS SEC
ASC OR
6 720 220 045
Page 12
12
CP/BP Series
Sequence of Operation
Once the thermostat reaches set point temperature and the humidity is above set point the unit will operate in the hot gas reheat mode
rst by cooling and dehumidifying then reheating
the air using hot refrigerant gas before delivering it to the space usually 2°F to 5°F below room temperature. The unit is operating as a
dehumidier. By reheating the air along a constant
sensible heat line the relative humidity of the supply air is reduced.
The moisture removal capacity of a specic heat
pump is determined by the unit latent capacity rating. A heat pump’s latent capacity can be
determined by reviewing the heat pump specication
data sheets. Depending upon the entering water and air conditions a total and sensible capacity can be interpolated from the data sheets. Subtracting sensible capacity from total capacity yields latent capacity. Dividing the latent capacity by 1069 (BTU/ LB of water vapor at 80° DB and 67° WB) yields the amount of moisture removal in pounds per hour.
Sequence of Operation - On/Off Control
The sequence of operation in the cooling and heating mode is the same as a regular heat pump.
In the reheat mode on a call from the humidistat the reheat relay coil is energized through the “H” circuit. The blower relay, reversing valve and compressor contactor are energized through the contacts of the reheat relay. See typical wiring diagrams at the end of the manual. The cooling relay remains de­energized enabling the reheat solenoid (Note: The reheat mode always operates in the cooling mode.) Should the temperature in the space increase above set point the compressor terminal Y is energized which will de-energize the reheat valve putting the unit into the straight cooling mode. A call for cooling or heating will always take precedence over hot gas reheat.
Hot Gas Reheat Controllers
There are several ways to control heat pumps with hot gas reheat. You should choose the means that best
suits your specic application. See typical wiring
diagrams and the end of the manual for some possible control sequences. Most heat pump compatible
thermostats in conjunction with a humidistat are acceptable for use, (Note: “O” output for reversing valve energized in cooling mode is required.) Combination thermostats/humidistat are also available.
Special Considerations
Some applications require special consideration to maximize the performance of the hot gas reheat function:
• Low Temperature Well Water
• Indoor Pool Dehumidifying During Winter Months
Consult the factory for special application considerations.
Low Temperature Well Water
When low temperature well water is utilized as the water source (below 55°F), a means of establishing two
ow rates, one for the cooling/reheat mode and one for
heating mode is recommended. In the cooling mode at
low entering water temperatures and standard ow
rates discharge pressures and corresponding discharge gas temperatures are relatively low. At these conditions when the reheat mode is initiated the low temperature discharge gas can reduce reheat capacity. A means to
reduce the water ow rate and elevate the discharge
pressure/ temperature in cooling/reheat mode should be provided. Conversely, at low entering water temperatures in the heating mode system suction pressure is reduced causing a loss in heating capacity. A
means of providing higher ow in the heating mode
should be provided. The simplest way to accomplish the above is to install water regulating valves.
Indoor Pool Dehumidifying During Winter Months
It is important to remember that when in the reheat mode the heat pump is cooling and reheating. A secondary means of heating the space during the
dehumidication mode should be provided. The
indoor space temperature should be kept at least 2°F above the pool water temperature. If this is not done the warm pool water attempts to heat the space and the humidity levels increase exponentially. The heat pump is normally sized to handle the design latent load moisture removal. A
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 13
Fluid Differential Pressure Switch
CP/BP Series
13
second heat pump or resistance heat should be provided to handle the structural loss load.
A protective coating is highly recommended for all
pool applications due to the highly corrosive chemical environment.
FLUID DIFFERENTIAL PRESSURE SWITCH (DPS)
The function of the differential switch is to prevent or stop compressor operation should the water supply fail. This will prevent the unit from locking out on a safety requiring manual reset to restart.
The switch is piped between the water entering and leaving connections. Should the pressure drop fall below set value the switch will open de-energizing the DPS relay thereby stopping the compressor.
The controller has an adjustment to change the minimum pressure differential required to open the
switch and may require  eld adjustment.
The blower operation will not be affected by this option.
The start-up process should include checking the
operation of the switch when installed. This should be done after the system is balanced. Adjustment should be made if necessary.
Operating Pressures and Temperatures
Operating pressures and temperatures in the reheat mode vary slightly from standard cooling mode operat­ing characteristics. The variations are as follows:
Discharge Pressure: (-) 5 to 20 PSIG
Discharge Gas Temperature: (-) 5°F to 15°F
Suction Pressure: (+) 5 to 10 PSIG
Suction Gas Temperature: (+) 5°F to 10°F
WATER PIPING
Water piping exposed to extreme low ambient temperatures are subject to freezing. Remember water freezes at 32°F.
Supply and return piping must be as large as the water connections on the heat pump (larger on long
runs). Never use  exible hoses of a smaller inside
diameter than that of the water connections on the unit. The heat pump units are supplied with either a copper or optional cupro-nickel condenser.
Galvanized pipe or fi ttings are not recommended for use with these units due to the possible galvanic corrosion.
Both the supply and discharge water lines will sweat if subject to low water temperature. These lines should be insulated to prevent damage from condensation.
All manual  ow valves used in the system must be
ball valves. Globe and gate valves must not be used due to high pressure drop and poor throttling characteristics.
Never exceed the recommended water  ow rates.
Serious damage or erosion of the water to refrigerant heat exchanger could occur.
Improper heat exchanger water fl ow due to piping, valve arrangement or improper pump operation is hazardous to the unit and constitutes abuse which will void the heat exchanger and compressor warranty.
All heat pump units are equipped with female pipe
thread  ttings. Consult the speci cation sheets for sizes. Te on tape sealer should be used when
connecting water piping connections to the units to ensure against leaks and possible heat exchanger fouling. Do not over tighten the connections. Flexible hoses should be used between the unit and the rigid system to avoid possible vibration. Ball valves should be installed in the supply and return lines for unit
isolation and unit water  ow balancing.
No unit should be connected to the supply or return piping until the water system has been completely
cleaned and  ushed to remove any dirt, piping
chips or other foreign material. Supply and return hoses should be connected together during this process to ensure the entire system is properly
 ushed. After the cleaning and  ushing has taken
place the unit may be connected to the water loop and should have all valves wide open.
WELL WATER SYSTEMS
Copper is adequate for ground water that is not high in mineral content. Should your well driller express
6 720 220 045
Page 14
14
CP/BP Series
Fresh Water Systems
concern regarding the quality of the well water available or should any known hazards exist in your area, we recommend proper testing to assure the well water quality is suitable for use with water source equipment. In conditions anticipating moderate scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In well water applications water pressure must always be maintained in the heat exchanger. This can be accomplished with either control valve or a bladder type expansion tank.
When well water is used exclusively for supplying water to the heat pump, the pump should operate only when the heat pump operates. A 24 volt double pole-single throw (DP/ST) contactor (Figure #6) can be used to operate the well pump with the heat pump.
POWER SUPPLY
C Y1
Y1
UNIT
TERMINAL
STRIP
(24VAC)
DP/ST RELAY
Figure #7
Pressure/temperature ports are recommended in
both the supply and return lines for system ow balancing. The water ow can be accurately set by
measuring the water-to-refrigerant heat exchangers
water side pressure drop. See the unit specication sheets for the water ow and pressure drop
information in the back of this manual.
The discharge water from the heat pump is not contaminated in any manner and can be disposed of in various ways depending on local codes (i.e.
discharge well, dry well, storm sewer, drain eld,
stream, pond, etc.)
When using a single water well to supply both domestic water and the heat pump care must be taken
to insure that the well can provide sufcient ow for
both. In well water applications a slow closing solenoid valve must be used to prevent water hammer.
Solenoid valves should be connected across Y and C on the interface board for all. Make sure that the VA draw of the valve does not exceed the contact rating of the thermostat.
FRESH WATER SYSTEMS
POWER TO PUMP
Figure #6
When two or more units are supplied from one well, the pump can be wired (Figure #7) to operate independently from either unit. An upsized VA transformer may be required in either case.
POWER SUPPLY
Y1
C
UNIT
TERMINAL
STRIP
(24VAC)
Y1
C
2 DP/ST RELAYS
POWER
TO PUMP
The Units shall be designed to operate throughout the
range of entering uid temperature of 50°F to 110°F in
the cooling mode and 50°F to 80°F in the heating mode. Units shall have an operating range of 25 °F to 80°F in the heating mode when equipped with the optional extended range. In the cooling mode, heat is rejected from the Bosch unit into the water loop. A cooling tower provides evaporative cooling to the loop water thus maintaining a constant supply temperature to the unit. When utilizing open cooling towers, chemical water treatment is mandatory to ensure the water is free from corrosive elements.
A secondary heat exchanger (plate frame) between the unit and the open cooling tower may also be used. It is imperative that all air be eliminated from the closed loop side of the heat exchanger to insure against fouling.
In the heating mode, heat is absorbed from the water loop. A boiler can be utilized to maintain the loop at the desired temperature.
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 15
UEarth Coupled System
CP/BP Series
15
Water piping exposed to extreme low ambient temperatures is subject to freezing.
Pressure/temperature ports are recommended in both
supply and return lines for system ow balancing. Water ow can be accurately set by measuring the water-to-
refrigerant heat exchangers water side pressure drop.
See specication sheets for water ow vs. pressure
drop information in the back of this manual.
EARTH COUPLED SYSTEMS
Closed loop and pond applications require specialized design knowledge. No attempt at these installations should be made unless the dealer has received specialized training. Utilizing Bosch’s Ground Loop Pumping Package (GLP), makes the installation easy. Anti-freeze solutions are utilized when low operating conditions are expected to occur. Refer to the GLP installation manuals for
more specic instructions. A wrapped water coil
option is required for this application.
• Verify that duct work has been properly fastened
to supply and return duct collars
• Make sure return air lters are positioned correctly in the lter rack if removed during installation
UNIT START-UP
1. Set the thermostat to the highest setting.
2. Set the thermostat system switch to “COOL”,
and the fan switch to the “AUTO” position. The reversing valve solenoid should energize. The compressor and fan should not run.
3. Reduce the thermostat setting approximately 5
degrees below the room temperature.
4. Verify the heat pump is operating in the cooling
mode.
5. Turn the thermostat system switch to the “OFF”
position. The unit should stop running and the reversing valve should de-energized
6. Leave the unit off for approximately (5) minutes
to allow for system equalization.
System Checkout
After completing the installation, and before energizing the unit, the following system checks should be made prior to initial startup:
• Verify that the supply voltage to the heat pump is
in accordance with the nameplate ratings
• Make sure that all electrical connections are tight
and secure
• Check the electrical fusing and wiring for the
correct size
• Verify that the low voltage wiring between the
thermostat and the unit is correct
• Verify that the water piping is complete and correct
• Check that the water ow is correct, and adjust if
necessary
• Check the blower for free rotation, and that it is
secured to the shaft
• Verify that vibration isolation has been provided
• Unit is serviceable. Be certain that all access
panels are secured in place
• Verify that the blower support has been removed
7. Turn the thermostat to the lowest setting. The
compressor and fan should not run.
8. Set the thermostat switch to “HEAT”.
9. Increase the thermostat setting approximately
5 degrees above the room temperature.
10. Verify the heat pump is operating in the
heating mode.
11. Set the thermostat to maintain the desired
space temperature.
12. Check for vibrations, leaks, etc...
13. Instruct the owner on the unit and thermostat
operation
HEAT RECOVERY PACKAGE
The Heat Recovery package is a factory mounted option. It consists of a forced pumped unit that employs a circulating pump to move water through a double wall/vented heat exchanger and returns the heated water to the water tank. The water is heated by superheated refrigerant discharge gas from the compressor. This waste heat of the cooling mode captured by the heat recovery increases the capacity
and efciency of the heat pump unit. If the air
temperature is uncomfortable coming from the air
6 720 220 045
Page 16
16
CP/BP Series
Water Tank Preparation
vents in the heating mode the heat recovery may need to be turned off. In the heating mode the heat recovery captures heat that would normally be used for space heating.
If heat recovery unit is installed in an area where freezing may occur, the unit must be drained during winter months to prevent heat exchanger damage. Heat exchanger ruptures that occur due to freezing will void the heat recovery package warranty along with the heat pump warranty.
WATER TANK PREPARATION
1. Turn off electrical or fuel supply to the water heater.
2. Attach garden hose to water tank drain connection and run other end of hose out doors or to an open drain.
3. Close cold water inlet valve to water heater tank.
4. Drain tank by opening drain valve on the bottom of the tank, then open pressure relief valve or hot water faucet.
5. Once drained the tank should be ushed with
cold water until the water leaving the drain hose is clear and free of sediment.
6. Close all valves and remove the drain hose.
7. Install HR water piping.
HR WATER PIPING
All hot water piping should be a minimum of 3/8t
O.D. copper tube to a maximum distance of fteen (15) feet. For distances beyond fteen feet but not
exceeding sixty (60) feet use 1/2” copper tube. Separately insulate all exposed surface of both connecting water lines with 3/8” wall closed cell insulation. Install isolation valves on supply and return to the heat recovery. (Figure #8)
TYPICAL CONNECTION PIPING
6 720 220 045
Figure 8
Subject to change without prior notice Revised 05-12
Page 17
MaWater Tank Rell
CP/BP Series
17
WATER TANK REFILL
1. Open the cold water supply to the tank.
2. Open a hot water faucet to vent air from the system
until water ows from the faucet, then close.
3. Depress the hot water tank pressure relief valve handle to ensure there is no air remaining in the tank.
4. Carefully inspect all plumbing for water leaks. Correct as required.
5. Purge all air from HR by depressing the schrader valve on the HR Unit. Allow all air to bleed out until water appears at the valve.
6. Before restoring the power or fuel supply to the water heater, adjust the temperature setting on the tank thermostat(s) to ensure maximum utilization of the heat available from the refrigeration system and conserve the most energy. On tanks with both upper and lower elements and thermostats, the lower element should be turned down to 100° F, while the upper element should be adjusted to
120° F. Depending upon the specic needs of the
customer, you may need to adjust the upper element differently. On tanks with a single thermostat lower the thermostat setting to 120° F or the “LOW” position.
7. After thermostat adjustments are completed, replace access cover and restore electrical or fuel supply to water heater.
INITIAL START-UP:
1. Make sure all valves in heat recovery water piping system are open. NEVER OPERATE HR PUMP DRY.
2. Turn on the heat pump. The HR pump should not run if the compressor is not running.
3. Turn HR switch to the “ON” position. The pump will operate if entering water temperature to HR is below 120° F.
4. The temperature difference between the water entering and leaving the heat recovery should be 5° to 15° F.
MAINTENANCE
1. Filter changes or cleanings are required at
regular intervals. The time period between lter
changes will depend upon type of environment the equipment is used in. In a single family home, that is not under construction, changing
or cleaning the lter every 60 days may be sufcient. In other applications such as motels,
where daily vacuuming produces a large
amount of lint, lter changes may be need to be as frequent as biweekly. See unit specications for replacement lter sizes. Note that horizontal units containing two lters are taped together
at the factory to facilitate removal. This should
be done by end user as new lters are installed.
Operating the unit with improper line voltage or with excessive phase imbalance is hazardous to the unit and constitutes abuse and is not covered under warranty.
2. An annual “checkup” is recommended by a licensed refrigeration mechanic. Recording the performance measurements of volts, amps, and water temperature differences (both heating and cooling) is recommended. This data should be compared to the information on the unit’s data plate and the data taken at the original startup of the equipment.
3. The condensate drain should be checked
annually by cleaning and ushing to insure
proper drainage.
4. Periodic lockouts almost always are caused by
air or water ow problems. The lockout
(shutdown) of the unit is a normal protective measure in the design of the equipment. If continual lockouts occur, call a mechanic immediately and have them check for: water
ow problems, water temperature problems, air ow problems or air temperature problems.
Use of the pressure and temperature charts for the unit may be required to properly determine the cause.
5. Allow the unit to operate for 20 to 30 minutes to ensure it is functioning properly. The pump should shut off when the water temperature entering the heat recovery reaches 120°F.
6 720 220 045
Page 18
18
CP/BP Series
In-Warranty Material Return
IN-WARRANTY MATERIAL RETURN
When contacting your Representative for service or replacement parts, refer to the model and serial number of the unit as stamped on the data plate attached to the unit.
Material may be returned to the factory only with permission of an authorized factory representative. A “Warranty Return Material” tag must be attached to the returned material. Assure that all of the information
as called for on the tag is  lled out completely and
accurately to expedite handling and insure prompt issuance of credits.
UNIT SPECIFICATIONS
Freight charges for all items returned to the factory shall be prepaid. The return of the part does not constitute an order for a replacement. Therefore, a purchase order must be entered through your nearest representative. The order shall include the part number, model number, and serial number of the unit involved. If the part is within the warranty period, and after our inspection of the returned part proves that the failure is due to faulty material or workmanship a credit or replacement part will be issued.
Parts returned without a completed “Warranty
Return Material” tag will not be credited.
Table 4: Physical Data
Model
BP007
BP009
BP012
BP015
BP018
CP/BP024
CP/BP030
CP/BP036
CP/BP042
CP/BP048
CP/BP060
CP/BP070
Clearance
Front
(in.)
36 0.46 140 / 165 160 / 185
36 0.46 154 / 172 174 / 192
36 0.66 166 / 173 186 / 205
36 0.66 191 / 190 208 / 218
36 0.66 195 / 198 212 / 222
36 0.81 229 / 307 242 / 340
36 1.14 269 / 358 292 / 404
36 1.14 281 / 369 304 / 415
36 1.11 334 / 400 360 / 465
36 1.11 340 /405 366 / 470
36 1.13 396 / 452 422 / 520
36 2.27 444 / 494 470 / 562
Water Coil
Volume
(gals.)
Installation Weight
(Vertical / Horizontal)
(lbs.)
Shipping Weight
(Vertical / Horizontal)
(lbs.)
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 19
Unit Specications
Table 2: Dimensions
CP/BP Series
19
Vertical
Model
Width Depth Height Width Depth Height Width Height Width Height
BP007 21.50 21.50 32.75 21.50 43.00 17.00 11.75 7.75
BP009 21.50 21.50 32.75 21.50 43.00 17.00 11.75 7.75
BP012 21.50 21.50 32.75 22.00 45.00 19.50 7.75
BP015 21.50 21.50 39.50 22.00 45.00 19.50 13.75 13.75 18.0
BP018 21.50 21.50 39.50 22.00 45.00 19.50 13.75 13.75 18.0
BP024 21.50 26.25 47.50 26.00 54.50 22.00 13.75 15.75
BP030 24.25 33.50 47.50 30.00 68.00 22.00 15.75 15.75
BP036 24.25 33.50 47.50 30.00 68.00 22.00 15.75 15.75
BP042 26.00 33.50 58.50 30.00 79.00 22.00 17.75 17.75
Unit
(In)
Horizontal
Unit
(In)
Supply Air
Connection
(In)
H: 7.75
V: 11.75
Return Air
Connection*
H: 18.0 V: 17.5
H: 18.0 V: 17.5
H: 18.0 V: 17.5
H: 30.0 V: 22.0
H: 34.0 V: 28.0
H: 34.0 V: 28.0
H: 46.5 V: 28.0
(In)
14.0
14.0
14.0
H: 16.0 V: 18.0
H: 16.0 V: 18.0
H: 18.5 V: 22.0
H: 18.5 V: 22.0
H: 18.5 V: 22.0
H: 18.5 V: 30.0
Replacement Fil-
ter Nominal Size*
(In)
H: 15"x20"x1" (1) V: 15"x20"x1" (1)
H: 15"x20”x1” (1) V: 15"x20”x1” (1)
H: 18"x20”x1” (1)
V: 18”x20”x1” (1)
H: 18"x20”x1” (1) V: 20"x20”x1” (1)
H: 18"x20"x1" (1) V: 20"x20"x1" (1)
H: 20”x30”x1” (1)
V: 24"x24"x1” (1)
H: 18"x20"x1" (2) V: 24"x30"x1" (1)
H: 18"x20"x1" (2) V: 24"x30"x1" (1)
H: 24"x20"x1" (2) V: 16"x30"x1" (2)
BP048 26.00 33.50 58.50 30.00 79.00 22.00 17.75 17.75
BP060 26.00 33.50 66.50 30.00 89.00 22.00 17.75 17.75
BP070 26.00 33.50 66.50 30.00 89.00 22.00 17.75 17.75
CP024 21.50 26.25 47.50 26.00 54.50 22.00 13.75 15.75
CP030 24.25 33.50 47.50 30.00 68.00 22.00 15.75 15.75
CP036 24.25 33.50 47.50 30.00 68.00 22.00 15.75 15.75
CP042 26.00 33.50 58.50 30.00 79.00 22.00 17.75 17.75
CP048 26.00 33.50 58.50 30.00 79.00 22.00 17.75 17.75
CP060 26.00 33.50 66.50 30.00 89.00 22.00 17.75 17.75
CP070 26.00 33.50 66.50 30.00 89.00 22.00 17.75 17.75
* H = Horizontal Unit; V = Vertical Unit
H: 46.5 V: 28.0
H: 54.0 V: 28.0
H: 54.0 V: 28.0
H: 30.0 V: 22.0
H: 34.0 V: 28.0
H: 34.0 V: 28.0
H: 46.5 V: 28.0
H: 46.5 V: 28.0
H: 54.0 V: 28.0
H: 54.0 V: 28.0
H: 18.5 V: 30.0
H: 18.5 V: 38.0
H: 18.5 V: 38.0
H: 18.5 V: 22.0
H: 18.5 V: 22.0
H: 18.5 V: 22.0
H: 18.5 V: 30.0
H: 18.5 V: 30.0
H: 18.5 V: 38.0
H: 18.5 V: 38.0
H: 24"x20"x1" (1) V: 16"x30"x1" (1)
H: 28"x20"x1" (2) V: 20"x30"x1" (2)
H: 28"x20"x1" (2) V: 20"x30"x1" (2)
H: 20”x30”x2” (1)
V: 24"x24"x2” (1)
H: 18"x20"x2" (2) V: 24"x30"x2" (1)
H: 18"x20"x2" (2) V: 24"x30"x2" (1)
H: 24"x20"x2" (2) V: 16"x30"x2" (2)
H: 24"x20"x2" (2)
V: 16"x30"x2" (2)
H: 28"x20"x2" (2)
V: 20"x30"x2" (2)
H: 28"x20"x2" (2)
V: 20"x30"x2" (2)
6 720 220 045
Page 20
20
CP/BP Series
Unit Specications
Table 3:
Model
007
009
012
Fluid Pressure Drops
Flow Rate
(GPM)
1 1.4 0.61
1.5 2.9 1.26 5.5 2.1 0.91
2 4.9 2.11 7 3.2 1.41
3 10.1 4.38 10 6.1 2.67
4 16.9 7.34 13 9.9 4.28
1.5 2.3 1.00
2 3.9 1.68 7.5 4.8 2.09
2.5 5.8 2.51 10 8.1 3.51
3.25 9.3 4.03 12.5 12.1 5.25
4 13.5 5.85 15 16.8 7.29
2 1.7 0.72
3 3.4 1.50 8.75 4.2 1.82
4 5.8 2.51 10.5 5.8 2.53
Pressure
Drop (FOH)
Pressure
Drop (PSI)
Model
030
036
042
Flow Rate
(GPM)
4 1.2 0.51
5 2.3 1.01
7 2.8 1.22
Pressure
Drop (FOH)
Pressure
Drop (PSI)
015
018
024
5.5 10.2 4.45 13.25 8.9 3.85
7 15.8 6.88 16 12.4 5.41
2 1.6 0.69
3 3.3 1.44 10.67 6.0 2.61
4 5.5 2.41 12 7.4 3.22
5.5 9.8 4.28 14 9.8 4.25
7 15.2 6.60 16 12.4 5.41
3 4.1 1.80
4 7.0 3.02 12 6.2 2.69
5 10.4 4.52 15 9.2 4.02
6.5 16.7 7.25 17.5 12.2 5.30
8 24.2 10.53 20 15.5 6.74
3 2.0 0.87
4.5 4.1 1.80 13.5 4.9 2.12
6 6.9 3.01 17 7.4 3.22
8 11.6 5.06 20.5 10.4 4.50
048
060
070
8 3.6 1.55
9 3.7 1.60
10 2.8 1.24
10 17.4 7.56 24 13.8 5.98
Note
1- Temperature at which pressure drop applies (PD varies as the uid temperature)
2-Data is for Water
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 21
Unit Specications
Table 5: Air Temperature Rise/Fall
CP/BP Series
21
Entering Fluid
Temp °F
30
40
50
60
70
COOLING HEATING
Entering Air Temp °F Air Temp Drop °F Entering Air Temp °F Air Temp Rise °F
75/63 21.9 - 27.2 60 20.0 - 28.5
80/67 22.9 - 28.5 70 19.0 - 27.0
85/71 23.8 - 29.5 80 17.7 - 25.2
75/63 20.5 - 25.8 60 23.3 - 32.8
80/67 21.5 - 27 70 22.0 - 31.0
85/71 22.3 - 28.1 80 20.5 - 29.0
75/63 19.2 - 24.7 60 26.5 - 37.1
80/67 20.1 - 25.8 70 25.1 - 35.1
85/71 20.9 - 26.8 80 23.4 - 32.7
75/63 17.9 - 23.8 60 29.8 - 41.4
80/67 18.7 - 24.9 70 28.2 - 39.1
85/71 19.5 - 25.8 80 26.3 - 36.4
60 16-8 - 25.1
70 15.9 - 23.7
80 14.8 - 22.1
80
85
90
100
110
75/63 16.6 - 23.0 60 32.7 - 45.7
80/67 17.4 - 24.0 70 30.9 - 43.1
85/71 18.1 - 25.0 80 28.8 - 40.2
75/63 16.0 - 22.6
80/67 16.8 - 23.6
85/71 17.4 - 24.5
75/63 15.4 - 22.2
80/67 16.1 - 23.2
85/71 16.8 - 24.1
75/63 14.2 - 21.4
80/67 14.9 - 22.4
85/71 15.4 - 23.3
75/63 13.0 - 21.1
80/67 13.7 - 22.1
85/71 14.2 - 23.0
6 720 220 045
Page 22
22
CP/BP Series
Table 6: Refrigerant Pressure Ranges
COOLING HEATING
Entering
Fluid
Temp
°F
30
40
50
60
70
80
90
100
110
Fluid
Δ T
5 68 - 79 233 - 266 71 - 84 246 - 281
10 65 - 76 222 - 255 68 - 80 235 - 269
15 59 - 71 216 - 248 62 - 75 228 - 261
5 113 - 147 138 - 156 117 - 152 142 - 161 119 - 155 145 - 164 80 - 95 244 - 282 85 - 100 257 - 297
10 113 - 147 145 - 164 117 - 152 150 - 170 119 - 155 153 - 173 77 - 91 237 - 274 82 - 96 250 - 289
15 113 - 147 151 - 170 117 - 152 156 - 175 119 - 155 159 - 179 72 - 86 226 - 262 76 - 90 238 - 276
5 115 - 149 164 - 185 119 - 154 170 - 191 121 - 157 173 - 195 95 - 113 255 - 302 100 - 119 269 - 319
10 115 - 149 173 - 194 119 - 154 178 - 200 121 - 157 182 - 204 91 - 109 248 - 290 96 - 115 261 - 306
15 115 - 149 179 - 200 119 - 154 184 - 207 121 - 157 188 - 211 86 - 103 237 - 282 90 - 108 250 - 297
5 117 - 151 194 - 218 121 - 156 200 - 224 123 - 159 204 - 229 111 - 133 270 - 324 117 - 141 285 - 342
10 117 - 151 204 - 228 121 - 156 211 - 235 123 - 159 215 - 240 106 - 129 258 - 311 112 - 136 273 - 329
15 117 - 151 211 - 235 121 - 156 218 - 242 123 - 159 222 - 247 101 - 122 251 - 302 106 - 128 265 - 319
5 119 - 153 228 - 254 122 - 158 235 - 262 125 - 161 240 - 267 129 - 158 282 - 343 136 - 167 297 - 362
10 119 - 153 238 - 265 122 - 158 246 - 273 125 - 161 251 - 279 124 - 150 274 - 333 131 - 159 289 - 351
15 119 - 153 246 - 273 122 - 158 254 - 281 125 - 161 259 - 287 117 - 146 262 - 320 123 - 154 276 - 337
5 121 - 155 265 - 294 124 - 160 273 - 303 127 - 163 279 - 309 148 - 184 299 - 366 156 - 194 315 - 387
10 121 - 155 276 - 306 124 - 160 285 - 316 127 - 163 291 - 322 143 - 176 286 - 352 151 - 185 302 - 371
15 121 - 155 285 - 315 124 - 160 294 - 325 127 - 163 300 - 332 136 - 169 278 - 343 143 - 179 294 - 362
5 123 - 157 306 - 337 126 - 162 316 - 348 129 - 165 322 - 355
10 123 - 157 319 - 351 126 - 162 329 - 363 129 - 165 336 - 370
15 123 - 157 329 - 362 126 - 162 339 - 373 129 - 165 346 - 381
5 124 - 159 351 - 387 128 - 164 363 - 399 131 - 167 370 - 407
10 124 - 159 367 - 403 128 - 164 378 - 416 131 - 167 386 - 424
15 124 - 159 376 - 413 128 - 164 388 - 426 131 - 167 396 - 435
5 126 - 161 403 - 441 130 - 166 416 - 455 133 - 169 424 - 464
10 126 - 161 419 - 458 130 - 166 432 - 472 133 - 169 441 - 482
15 126 - 161 429 - 470 130 - 166 443 - 485 133 - 169 452 - 495
70 °F 75 °F 80 °F 60 °F 70 °F
Suction Discharge Suction Discharge Suction Discharge Suction Discharge Suction Discharge
Entering Air Temp (Dry Bulb) Entering Air Temp (Dry Bulb)
Unit Specication
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as a guide only and should not be used to estimate system charge.
This chart assumes rated air ow and 80º d.b./67º w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering uid temperatures below 50º assumes the use of antifreeze.
As a result of continuing research and development, specications are subject to change without notice.
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 23
Unit Specications
Table 7: Blower Performance
Model
BP007
BP009
BP012
BP015
BP018
CP/BP024
CP/BP030
CP/BP036
CP/BP042
CP/BP048
CP/BP060
CP/BP070
Motor
Speed
High 430 420 390 360 335 310 260 - - - - -
Medium 420 390 365 335 310 270 - - - - - -
Low 370 360 340 315 285 245 - - - - - -
High 430 420 390 360 335 310 260 - - - - -
Medium 420 390 365 335 310 270 - - - - - -
Low 370 360 340 315 285 245 - - - - - -
High 450 435 415 400 385 360 330 305 - - - -
Medium 425 405 385 375 360 335 310 - - - - -
Low 390 380 365 350 335 315 290 - - - - -
High 590 555 500 475 450 435 415 390 - - - -
Medium 530 490 455 425 400 365 335 - - - - -
Low 440 395 360 325 290 250 - - - - - -
High 700 665 635 605 560 525 510 475 440 - - -
Medium 615 590 550 510 480 440 400 - - - - -
Low 520 490 440 400 380 360 - - - - - -
High 950 920 900 885 855 830 800 780 720 690 630 -
Medium 830 810 780 750 735 690 630 610 590 - - -
Low 700 675 650 615 550 520 - - - - - -
High 1200 1190 1180 1155 1130 1110 1080 1060 1035 995 925 900
Medium 1070 1040 1015 1005 980 960 935 920 910 885 850 815
Low 930 905 880 855 840 815 790 755 745 675 - -
High 1440 1410 1385 1360 1290 1225 1165 1095 1030 940 860 -
Medium 1310 1275 1270 1250 1220 1190 1150 1075 1000 930 840 -
Low 1155 1120 1080 1050 1035 1020 1000 975 950 920 - -
High 1710 1680 1650 1630 1600 1530 1440 1350 1300 1250 - -
Medium 1500 1470 1440 1400 1360 1345 1330 1275 - - - -
Low 1275 1240 1195 1185 1125 1085 - - - - - -
High 2000 1885 1870 1845 1815 1770 1745 1720 1710 1700 1680 -
Medium 1750 1700 1660 1625 1615 1590 1565 1540 1500 - - -
Low 1500 1470 1440 1400 1360 1345 1330 - - - - -
High 2370 2325 2300 2275 2255 2200 2190 2150 2100 2060 2050 2030
Medium 2090 2080 2030 1995 1950 1925 1900 1865 1820 1770 1730 1680
Low 1745 1700 1650 1620 1590 1560 1530 1490 1450 1390 - -
High 2400 2350 2325 2300 2260 2205 2200 2195 2167 2105 2085 2060
Medium 2125 2100 2050 1990 1975 1950 1890 1850 1815 1810 1780 1730
Low 1800 1750 1700 1675 1620 1580 1565 1510 1470 1410 - -
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
CP/BP Series
Available External Static Pressure (ins., Gauge. Wet coil and lter included)
23
6 720 220 045
Page 24
24
CP/BP Series
TYPICAL WIRING DIAGRAMS 1 Stage - 1 Phase - ECM Motor
Typical Wiring Diagrams
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 25
Typical Wiring Diagrams
1 Stage - 1 Phase - Direct Drive Motor
CP/BP Series
25
6 720 220 045
Page 26
26
CP/BP Series
1 Stage - 1 Phase - Direct Drive Motor - Hot Gas Reheat
Typical Wiring Diagrams
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 27
Typical Wiring Diagrams
1 Stage - 1 Phase - ECM Motor - Hot Gas Reheat
CP/BP Series
27
6 720 220 045
Page 28
28
CP/BP Series
Unit Check-Out Sheet
UNIT CHECK-OUT SHEET
Customer Data
Customer Name ________________________________________________ Date __________________________________ Address ________________________________________________________ __________________________________________________________________ Phone __________________________________________________________ Unit Number _________________________
Unit Nameplate Data
Unit Make ______________________________________________ Model Number _________________________________________ Serial Number_______________________________ Refrigerant Charge (oz) _____________________
Compressor: RLA ____________________ LRA ______________
Blower Motor: FLA (or NPA) __________ HP _______________
Maximum Fuse Size (Amps) ________________
Minimum Circuit Ampacity (Amps) _________
Operating Conditions
Cooling Mode Heating Mode
Entering / Leaving Air Temp
Entering Air Measured at:
Leaving Air Measured at:
Entering / Leaving Fluid Temp
Fluid Flow (gpm)
Compressor Volts / Amps
Blower Motor Volts / Amps
Source Fluid Type
Fluid Flow (gpm)*
Fluid Side Pressure Drop*
Suction / Discharge Pressure (psig)*
Suction / Discharge Temp*
Suction Superheat*
Entering TXV / Cap Tube Temp*
Liquid Subcooling*
* Required for Troubleshooting ONLY
______________ / _____________ ______________ / _____________
_______________________________ ______________________________
_______________________________ ______________________________
______________ / _____________ ______________ / _____________
______________________________ ______________________________
______________ / _____________ ______________ / _____________
______________ / _____________ ______________ / _____________
_______________________________ ______________________________
______________________________ ______________________________
______________________________ ______________________________
______________ / _____________ ______________ / _____________
______________ / _____________ ______________ / _____________
_______________________________ ______________________________
_______________________________ ________________________________
_______________________________ ________________________________
Auxiliary Heat
Unit Make ______________________________________________ Model Number _________________________________________ Serial Number_______________________________ Max Fuse Size (Amps) __________________________________ Volts / Amps_____________________ /______________________ Entering Air Temperature Leaving Air Temperature _______________________________
_______________________________
Bosch Group 601 NW 65th Court Fort Lauderdale, FL 33309
6 720 220 045
Phone: (954) 776-5471 Fax: (800) 776-5529
http://www.fhp-mfg.com
Subject to change without prior notice Revised 05-12
Page 29
Troubleshooting
TROUBLESHOOTING
Problem Possible Cause Checks and Corrections
Entire unit does not run
Blower operates but compressor does not
Power Supply Off Apply power, close disconnect
Blown Fuse Replace fuse or reset circuit breaker. Check for correct fuses
Voltage Supply Low If voltage is below minimum voltage specied on unit data plate,
contact local power company.
Thermostat Set the fan to “ON”, the fan should run. Set thermostat to “COOL”
and lowest temperature setting, the unit should run in the cooling mode (reversing valve energized). Set unit to “HEAT” and the highest temperature setting, the unit should run in the heating mode (reversing valve deenergized). If neither the blower or compressor run in all three cases, the thermostat could be miswired or faulty. To ensure miswired or faulty thermostat verify that 24 volts is available at the low voltage terminal strip between “R” and “C”, “Y” and “C”, and “O” and “C”. If the blower does not operate, verify 24 volts between terminals “G” and “C”. Replace the thermostat if defective.
Thermostat Check setting, calibration, and wiring
Wiring Check for loose or broken wires at compressor, capacitor, or contactor
Safety Controls Check UPM board red default L.E.D. for Blink Code
CP/BP Series
29
Unit off on high pressure control
Unit off on low pressure control
Unit short cycles
Compressor overload open
Compressor motor grounded
Compressor windings Open
Discharge pressure too high
Refrigerant charge The unit is overcharged with refrigerant. Reclaim refrigerant, evacuate
High pressure Check for defective or improperly calibrated high pressure switch.
Suction pressure too low
Refrigerant charge The unit is low on refrigerant. Check for refrigerant leak, repair,
Low pressure switch
Unit oversized Recalculate heating and or cooling loads.
Thermostat Thermostat installed near a supply air grill; relocate thermostat.
Wiring and controls Check for defective or improperly calibrated low pressure switch.
If the compressor is cool and the overload will not reset, replace compressor
Internal winding grounded to the compressor shell. Replace compressor.
After compressor has cooled, check continuity of the compressor windings. If the windings are open, replace the compressor
In “COOLING” mode: Lack of or inadequate water ow. Entering water
temperature is too warm. Scaled or plugged condenser.
In “HEATING” mode: Lack of or inadequate air ow. Blower inoperative, clogged lter or restrictions in duct work
and recharge with factor recommended charge.
In “COOLING” mode: Lack of or inadequate air ow. Entering air temperature is too cold. Blower inoperative, clogged lter or
restrictions in duct work
In “HEATING” mode: Lack of or inadequate water ow. Entering water
temperature is too cold. Scaled or plugged condenser.
evacuate and recharge with factory recommended charge.
Check for defective or improperly calibrated low pressure switch.
Readjust heat anticipator.
6 720 220 045
Page 30
30
CP/BP Series
Troubleshooting
Insufcient
cooling or heating
UPM board trouble shooting
Unit undersized
Loss of conditioned air by leakage
Airow
Refrigerant charge
Compressor
Reversing Valve
Operating pressures
TXV
Moisture, noncondensables
Compressor will not run, no fault blink code
Recalculate heating and or cooling loads. If excessive, possibly adding insulation and shading will rectify the problem
Check for leaks in duct work or introduction of ambient air through doors or windows
Lack of adequate air ow or improper distribution of air. Replace dirty lter
Low on refrigerant charge causing inefcient operation
Check for defective compressor. If discharge is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor.
Defective reversing valve creating bypass of refrigerant from discharge of suction side of compressor. Replace reversing valve
Compare unit operation pressures to the pressure/temperature chart for the unit.
Check TXV for possible restriction or defect. Replace if necessary.
The refrigerant system may be contaminated with moisture
or noncondensables. Reclaim refrigerant, replace lter dryer,
evacuate the refrigerant system, and recharge with factory recommended charge.
Yes
UPM Board
is Good
Is Green
Power LED
light on and
no Red
Blink Code?
Yes
No
Is there
power to
the “Y” Call
(C-Y)?
- Check all
power supplies
- Check all
safety switches
Yes
No
Is there 24 V
power from
C to CC?
Check
thermostat
settings and
configurations
for heat
pumps, and
wiring
No
Check for Red
Blink Code.
If Red Blink
Code is not
present, replace
UPM Board
6 720 220 045
Subject to change without prior notice Revised 05-12
Page 31
Notes
CP/BP Series
31
6 720 220 045
Page 32
601 N.W. 65th Court, Ft. Lauderdale, FL 33309 Phone: 954-776-5471 | Fax: 954-776-5529 www.boschtaxcredit.com | www.bosch-climate.us
Loading...