In warnings, signal words at the beginning of a warning are used to
indicate the type and seriousness of the ensuing risk if measures for
minimising danger are not taken.
The following signal words are defined and can be used in this document:
DANGER:
DANGER indicates that severe or life-threatening personal injury will
occur.
WARNING:
WARNING indicates that severe to life-threatening personal injury may
occur.
CAUTION:
CAUTION indicates that minor to medium personal injury may occur.
NOTICE:
NOTICE indicates that material damage may occur.
Important information
The info symbol indicates important information where there is no risk to
people or property.
Additional symbols
Symbol Meaning
▶a step in an action sequence
a reference to a related part in the document
•a list entry
–a list entry (second level)
Table 1
1.2Safety precautions
H General safety instructions
Failure to observe the safety instructions can result in
serious personal injury and a risk to life as well as
material losses and damage to the environment.
▶ Carry out service work at least once a year. As part
of this, check that the entire system is working
correctly. Defects must be remedied immediately.
▶ Before commissioning the heating system, read
these instructions carefully.
Control 8313 – 6720859567 (2017/03)
3
Explanation of symbols and safety instructions
H Original spare parts
The manufacturer assumes no liability for damage
caused by spare parts not supplied by the
manufacturer.
▶ Use only original spare parts and accessories from
the manufacturer.
H Risk of scalding
Risk of scalding from DHW temperatures over 60 °C.
▶ Do not draw off DHW unmixed.
H Safety of electrical devices for domestic use
and similar purposes
The following requirements apply in accordance with
EN 60335-1 in order to prevent hazards from
occurring when using electrical appliances:
“This appliance can be used by children of 8 years and
older, as well as by people with reduced physical,
sensory or mental capabilities or lacking in experience
and knowledge, if they are supervised and have been
given instruction in the safe use of the appliance and
understand the resulting dangers. Children shall not
play with the appliance. Cleaning and user
maintenance must not be performed by children
without supervision.”
“If the power cable is damaged, it must be replaced by
the manufacturer, its customer service department or
a similarly qualified person, so that risks are avoided.”
H Risk of fatal injury from electric current
▶ Observe the relevant requirements when working
on electrical installations.
▶ Installation and commissioning as well as service
and maintenance must only be carried out by an
approved and qualified contractor.
▶ Before unpacking the appliance, touch a radiator or
an earthed metal water line to discharge any
electrostatic charge in your body.
▶ Ensure that a country-specific emergency isolation
switch (emergency-off button) is present.
In the case of systems with three-phase consumers,
incorporate the emergency isolation switch into the
safety chain.
▶ Ensure that a standards-compliant disconnection
device in accordance with EN 60335-1 is available
for all-pole disconnection from the power grid. If
there is no circuit breaker present, you must install
one.
▶ Before opening the controller, disconnect all poles
of the heating system via the circuit breaker. Secure
against unintentional reconnection.
▶ Size cables according to how they are to be laid and
environmental conditions. The cable cross-section
for power outputs (e.g. pumps, mixers) must be at
2
least 1.0 mm
.
H Heating system damage due to frost
When the heating system is not in operation
(e.g. controller switched off, fault shutdown), there is
a risk of it freezing when there is frost.
▶ When shutting down or switching off for extended
periods, drain the heating and drinking water pipes
to the lowest point in order to protect the heating
system from freezing.
H Handover to the user
When handing over, instruct the user how to operate
the heating system and inform the user about its
operating conditions.
▶ Explain how to operate the heating system and draw
the user's attention to any safety relevant action
▶ Explain that conversions and repairs must only be
carried out by a competent person.
▶ Point out the need for inspections and maintenance
for safe and environmentally-compatible operation.
▶ Leave the installation instructions and the
operating instructions with the user for
safekeeping.
4
Control 8313 – 6720859567 (2017/03)
Product Information
2Product Information
This installation and maintenance instructions contain important
information for the safe and correct installation, initial commissioning,
and maintenance of this control unit.
Depending on the software version, the display and menu items shown
in the instructions may differ from those in the control unit.
The operating instructions contain information on operation of the
control unit.
▶ Observe operating instructions of the control unit and the heat
source.
2.1Declaration of Conformity
The design and operation of this product conform to European Directives
and the supplementary national requirements. Its conformity is
demonstrated by the CE designation.
You can view the Declaration of Conformity on the internet
( back cover).
2.2Open Source Software
This product contains proprietary software by Bosch (licensed
according to the Bosch standard licensing conditions) and Open Source
Software (licensed according to the Open Source licensing conditions).
The special provisions stated in the license texts apply for LGPL, reverse
engineering is permitted for these components in particular.
You can find Open Source information on the DVD supplied with the
device.
2.6Accessories
• Sensor for DHW heating functions
• Function modules
2.7Product Description
The modular control system provides the perfect means of adjustment
for boilers and wall mounted boilers equipped with a SAFe burner
control unit to ensure the operating conditions for the specific product
are satisfied.
The control unit controls an EMS oil boiler or EMS gas boiler. As an
option, a modulating boiler circulation pump can be activated via a PWM
signal or a 0...10-V interface.
The standard equipment of the control unit comprises the boiler circuit
or heating circuit with mixer and DHW heating functions. So it can be
perfectly matched with the heating system, the control unit can be
extended by up to four function modules.
No parameter settings are lost in the event of a power failure. When the
power supply is restored, the user interface resumes operation.
Notice regarding systems with several heat sources
The CC 8313 control unit can control systems containing several heat
sources (cascades) in combination with the FM-CM cascade module.
For a description of this function, refer to the technical documentation
for the module.
2.8Determined use
The control unit controls and monitors heating systems in apartment
buildings, residential complexes and other buildings.
▶ Observe country-specific standards and regulations concerning
installation and operation!
2.3Product data for energy consumption
The product data on energy consumption can be found in the operating
instructions for the user.
2.4Tools, materials and miscellaneous parts
You will require the following to carry out installation, assembly and
maintenance:
• Electrical engineering tools and measuring devices
The following may also prove useful:
• A PC for commissioning and service
2.5Scope of delivery
Upon delivery:
▶ Check that the packaging is in perfect condition.
▶ Check the scope of delivery for completeness.
The scope of delivery includes:
• Digital control unit CC 8313
• User interface (HMI)
• FA outside temperature sensor
• FZ auxiliary temperature sensor for flow or return temperature
• SAFe connecting lead extensions
• SAFe BUS cable extension
• Fixing materials
• Technical documents
Control 8313 – 6720859567 (2017/03)
5
Modules and their function
t
3Modules and their function
3.1Fitted modules
All modules fitted in the control unit are listed in the following table. The
description also includes the FM-MM, FM-MW and FM-SI modules.
ModuleSlot CC 8313
BCT531 (HMI) user interfaceHMIX
Central module ZM5313AX
NM582 power supply moduleBX
Function module (e.g. FM-MM)1...4O
FM-RM function moduleCO
Table 2 Modules and their functions
[X]Standard equipment
[O]Optional equipment
2
3
4
5
6
FM-CM (cascade module)
To avoid interrupting the heating circuit numbering and as the FM-CM
has no supply voltage output, it should be mounted at slot 4 (on the far
right). If several cascade modules are used, assembly should start from
the right. With several control units, the FM-CM in the master control unit
must be installed with the address 0.
FM-RM
The module can only be installed at slot C.
FM-MW
Each control unit can only support 2 DHW heating systems, e.g. DHW
heating via the central module (ZM) and via the FM-MW.
3.2BCT531 (HMI) user interface
The user interface is equipped with a touch screen. Information is
displayed and commands entered at the touch screen.
The user interface is equipped with a USB interface for service
purposes.
The control unit address is set on reverse side.
1
1
7
8
0010005505-001
Fig. 1 Overview of slots
[1]Slot A (central module)
[2]Slot B (power supply module)
[3]Slot 1
[4]Slot 2
[5]Slot 3
[6]Slot 4
[7]Slot C
[8]User interface
3.1.1Notice regarding fitted modules
The additional modules can be installed in any free slot 1...4. In doing so,
make sure that the power supply leads from module to module. We
recommend that you insert the modules in order from left to right to
ensure the heating circuits are logically numbered.
When using the following modules, it is advisable to mount them at
specific slots.
FM-AM
The module only affects the control unit in which it is fitted. If the module
is installed in the master control unit with address 0, it is effective for the
connected boiler(s). If the module is fitted in a substation, it will respond
to the heat requirement issued by that substation.
FM-SI
Due to the length of the SI connecting lead, the safety module should be
mounted at slot 1.
reset
23456
Fig. 2 User interface
[1]Touch screen
[2]Reset button (e.g. high limit safety cut-out, SAFe)
[3]Chimney sweep button (Flue gas test)
[4]Key for manual operation
[5]USB interface for service purposes (behind cover)
[6]LED status display
Function buttons
The function buttons enable
• Manual operation
• Flue gas test
• Reset (e.g. high limit safety cut-out, SAFe)
rese
0010005507-001
6
Control 8313 – 6720859567 (2017/03)
Standards, regulations and directives
System status, function status, component status
The status of the system, the functions and system components is
displayed via the Function status display ( Fig. 6, [1], page 12), the
System components status display ( Fig. 6, [15], page 12) and the
LED status display ( Fig. 2, [6]):
• Green = system in automatic mode
• Yellow = system in manual operation, Flue gas test, Service display or
Blocking fault SAFe
• Yellow flashing = Control unit coupling
• Red = Fault
Battery CR2032
The battery ensures that the time and date are not lost when the
control unit is switched off or in the event of a voltage failure
( Fig. 4, [8], page 9).
3.3Central module ZM5313
The central module controls the following functions:
• Functions of a boiler circuit or a heating circuit with mixer
• Functions of the DHW supply
• BUS communication with the SAFe burner control unit
• Function of the safety chain (SI chain)
• Function of flue gas damper
• Modulating control of boiler circulation pump (possible via 0...10 V)
3.4NM582 power supply module
The power supply module ( Fig. 1, [2], page 6) supplies voltage to the
following components:
• Control unit
• Load outputs (e.g. pumps, burners, actuators)
• Boiler controller
• Modules used and corresponding connected system components
(e.g. sensor)
It is equipped with:
• 2 safety switches (10 A) as fuse protection of the power sources for
– the central module and user interface
– the modules at slots 1...4
• ON/OFF switch, that switches the phase (L) and neutral conductor (N)
If a safety switch has tripped due to overload, the pin projects noticeably
out of it.
To switch on the safety switch:
▶ Push in the pin.
If the safety switch triggers frequently:
▶ Check the current consumption.
3.5Base module BM592
A power supply for 24 V components is available at slot C on the base
module.
• Connection: 24 V =, max. 250 mA
▶ Do not exceed the total current.
3.6FM-MM function module (accessory)
The FM-MM module regulates 2 independent heating circuits with mixer.
The module can be used more than once in the control unit. The
functions of the module are selected and adjusted via the display.
The adjustable functions and parameters are described in the menu
structure of the control unit ( Chapter 9, page 17).
3.7FM-MW function module (accessory)
The FM-MW module regulates 1 heating circuit with mixer and 1 DHW
supply system. The module can be used more than once in the control
unit. The functions of the module are selected and adjusted via the
display.
The adjustable functions and parameters are described in the menu
structure of the control unit ( Chapter 9, page 17).
3.8FM-SI function module (accessory)
The purpose of the FM-SI function module is to integrate external
safety equipment into the system or system control. When integrated
into the system control, faults are evaluated via the control unit
(observe Chapter 5.8, page 10).
Examples of external safety equipment:
• Low water indicator
• Pressure limiter
• Additional high limit safety cut-out (STB)
3.9FM-RM function module (accessory)
The module allows components (e.g. coupling relay, modem) to be
installed on a mounting rail. It can only be installed at slot C.
The maximum overall height of the components is 60 mm. The maximum
supply voltage is 230 V.
4Standards, regulations and directives
The following are some of the regulations and standards that must be
observed during installation and operation:
• Regulations for electrical installation and connection to the
electrical grid
• Pressure Equipment Directive – systems with boiler temperatures
> 110 °C
• EN 12953-6 – Shell boilers. Requirements for equipment
for the boiler
• EN 12828 – Heating systems in buildings
• ICOM Water treatment guide for commercial heating systems.
• Country-specific regulations to protect potable water
(e.g. DVGW Code of practice W551– Drinking water protection)
• Manufacturer's technical Codes of Practice (e.g. in the catalogue)
• National standards and regulations
Control 8313 – 6720859567 (2017/03)
7
Installation
5Installation
5.1Assembly
Descriptions of how the control unit is positioned at the heat source are
provided in the installation instructions for the control unit and
documentation for the heat source.
5.2Overview of controller
1231
12
11
10
9
Fig. 3 Overview of controller
[1]Housing lid/cover
[2]User interface
[3]Touch screen
[4]Reset button (e.g. high limit safety cut-out, SAFe)
[5]Chimney sweep button (Flue gas test)
[6]Key for manual operation
[7]Cover (USB interface for service purposes, behind cover)
[8]LED status display
[9]Type plate
[10] F1-, F2 circuit breaker
[11] ON/OFF switch
[12] Back panel
reset
47
8
56
0010003622-001
5.3Electrical connection
NOTICE:
Faults/material damage due to inductive interference!
▶ Make sure all low-voltage cables are routed separately to mains
voltage cables (min. clearance 100 mm).
WARNING:
Risk to life and of system damage due to high temperatures.
All parts directly or indirectly exposed to high temperatures must be
designed to withstand these temperatures.
▶ Keep cables and electrical wiring at a safe distance from hot
components.
▶ Route cables and electrical wiring in the cable routings provided,
or above the insulation.
NOTICE:
Material damage as a result of disregarding other instructions!
If other instructions for components are disregarded, the heating system
may develop faults or be damaged due to incorrect connections/settings.
▶ Follow the directions in all instructions for the components that are to
be installed.
8
Control 8313 – 6720859567 (2017/03)
Installation
Note the following when making electrical connections:
• All electrical connections, safety measures and safety devices must
be implemented by an approved contractor, taking into account the
standards and guidelines that are applicable in each case as well as
the local regulations.
• Establish electrical connection as a fixed connection in accordance
with local/national regulations.
• Electrical connections are established as specified in the connection
diagram for the control unit and the module.
To prevent inductive influences:
▶ Make sure all low-voltage cables are routed separately to mains
voltage cables (min. clearance 100 mm).
• When installing the devices, ensure an earth connection is present.
• Do not exceed the total current stated on the data plate, and the
partial currents for each safety switch and connection.
• Before opening the control unit, disconnect all poles of the control
unit and secure against unintentional reconnection.
• Incorrect attempts to make connections under voltage may damage
the control unit beyond repair and lead to dangerous electric shocks.
▶ Establish electrical connections as specified in the connection
diagram of the control unit and the local conditions.
5.4User interface connections (HMI)
5.5Connecting the heat source to the control unit
5.5.1Connection to the SAFe
WARNING:
Danger to life due to flue gas at the installation location!
With older SAFe software versions (not permitted here), the heat source
may start automatically in unfavourable circumstances!
Unfavourable scenario: connection between heat source (with old SAFe)
and ZM5313 is interrupted.
▶ Only use heat sources with SAFe with software version ≥ Table 3.
If a boiler with SAFe burner control unit is being connected, the EMS
connection has no function!
SAFe heat sources are heat sources that are equipped with a SAFe
(burner control unit) for burner control. The SAFe is directly connected
to the higher level plant control system (e.g. Control CC 8313).
As the software version of the connected heat source determines
whether or not the control functions correctly, the software version of
the SAFe must be checked directly following connection.
Connections:
• On the ZM5313 central module at the BUS SAFe and mains
SAFe terminals
• On the SAFe at the BUS and mains SAFe terminals.
1
11
10
9
8
Fig. 4 User interface connections
[1]Slide type insert for SD card
[2]CAN-BUS connection (no function, provided for
subsequent functions)
[3]Modbus-RTU connection for Bosch/Bosch CHP module
[4]EMS connection (connection for EMS heat source with its own
basic control (control panel))
[5]Address setting of control unit
[6]Jumper (J2) for activating the Modbus-RTU terminating resistance
[7]Jumper (J1) for activating the terminating resistance CAN-BUS
[8]Battery CR2032
[9]Network connection 2 (CBC-BUS)
[10] Network connection 1 (Internet, Modbus TCP/IP, CBC-BUS)
[11] USB connection
Depending on the use and configuration, the plug-in connections on the
rear of the user interface must be occupied.
Configuration of CAN-BUS/Modbus-RTU/EMS plug:
• Jumper for activating the Modbus-RTU terminating resistance
• Jumper for activating the CAN-BUS terminating resistance
LAN1
LAN2
USB1
+-
J1
3 2 13 2 1
J2
2 1
2
3
4
567
0010005508-001
Check SAFe version
▶ Check at the heat source whether the SAFe has at least one of the
software versions listed in table 3.
SAFeSoftware version
10V4.27
20V4.23
30V4.27
40V4.23
42V4.28
50–
1) No function with SAFe 50
1)
Table 3 SAFe version
Control 8313 – 6720859567 (2017/03)
9
Installation
5.5.2Connection to a EMS heat source
NOTICE:
Material damage due to incorrect connection!
When connecting EMS heat sources:
▶ Remove jumper at the external interlock terminal.
▶ Only connect safety equipment directly at the EMS boiler.
EMS heat sources have their own basic control (control panel,
e.g. BC10). The SAFe is connected to the control of the heat source.
If a plant control system is installed, it is superordinate to the control of
the heat source.
The user interface of the control unit and the basic control
(control panel) of the heat source are directly connected.
Connections:
• On the back of the user interface at the EMS terminals
( Fig. 4, [4], page 9) with
• Basic control of the heat source at the (EMS)-BUS terminals
When connecting a boiler via the EMS terminals:
▶ Remove jumper at the external interlock terminal.
The external interlock connection has no function in conjunction
with EMS boilers!
▶ External safety equipment that lead to blocking must be connected
to the EMS boiler directly.
5.5.3Connection via the Modbus interface
For heat sources (e.g. CHP module) that are connected via the
Modbus-RTU ( Fig. 4, [3], page 9):
▶ Connect communications cable to the Modbus-RTU connection.
▶ Consider connection to the heat source.
5.8Connection of safety equipment and the FM-SI
module
SAFe heat source
If a boiler with SAFe burner control unit is being connected, the EMS
connection has no function!
▶ Connect safety equipment or a condensates neutraliser at the FM-SI
module.
▶ Close unused SI inputs with a jumper.
When using a condensate neutraliser:
▶ Connect condensate neutraliser to SI1 input.
EMS heat source
Use of the FM-SI with EMS heat sources is not permitted if the heat
source is connected via the EMS terminal ( Fig. 4, [4], page 9).
▶ Connect external safety equipment directly to the control of the heat
source (terminal SI 17, 18).
▶ Always connect safety equipment that shuts down the heat source to
the basic control of the heat source (EMS control).
If EMS heat source was selected in the setting:
▶ Open the safety chain (terminal SI 17, 18) at the ZM5313
without fail.
▶ Do not install a jumper!
If safety equipment is connected, a jumper is installed or a Sl module is
inserted at the ZM5313, a fault display is generated.
To avoid vagabond voltages:
▶ Only connect cable shield to one control unit!
5.6Connection to other control units in the 8000 series
or to a network
The connection options are presented in Chapter 16.1, page 37.
5.7Connection of modules
Mains voltage
The 230 V power supply must be ensured for modules fitted at slots
1…4 via a plug-in connector on the power supply module. The modules
supply voltage to one another via additional plug-in connections.
If voltage is not supplied to the module or its 230 V components
(e.g. because the plug-in connector has not been inserted), the
components assigned to this module are not switched on (e.g. pumps).
This malfunction cannot be detected at the user interface itself as the
display and control functions are independent of the 230 V voltage.
5.9Remote control
If a remote control is provided for the heating circuit, this must be
connected to the BF terminals. The remote control is assigned to the
corresponding heating circuit via the coding switch in the remote
control.
5.10Other connections
Other connections may need to be established, depending on the
function of the modules.
▶ Observe documents and connection diagrams of the installed
modules!
UM10 function module
A UM10 must not be installed in a heating system if the heat source is
activated via the ZM5313. The ZM5313 takes over the UM10
functionality.
10
Control 8313 – 6720859567 (2017/03)
6Operation of the control unit
6.1Control elements of the control unit and the user interface
Operation of the control unit
1
10
9
8
Fig. 5 Control elements
[1]Touch screen
[2]Activation code (registration code)
[3]Reset button (e.g. high limit safety cut-out, SAFe)
[4]Chimney sweep button (for Flue gas test)
[5]Manual operation key
[6]USB connection (e.g. for service purposes)
[7]LED status display
[8]Data plate
[9]F1-, F2 circuit breaker
[10] ON/OFF switch
reset
7
32645
0010005509-001
Control 8313 – 6720859567 (2017/03)
11
Operation of the control unit
t
6.2Function buttons and system status
Function buttons
The function buttons enable
• Manual operation
• Flue gas test
• Reset (e.g. high limit safety cut-out, SAFe)
System status, function status, component status
The status of the system, the functions and system components is
displayed via the Function status display ( Fig. 6, [1], page 12), the
System components status display ( Fig. 6, [15], page 12) and the
LED status display ( Fig. 5, [7]):
• Green = system in automatic mode
• Yellow = system in manual mode, Flue gas test, Service display or
Blocking fault SAFe
• Yellow flashing = Control unit coupling
• Red = Fault
rese
123456
6.3Operating and display elements of the touch screen
Whether menu items can be displayed or selected depends on which
modules are inserted and which settings have been made.
The displays shown are examples. The display of the symbols depends
which software is installed, which modules are inserted and which
settings have been made.
The operating instructions contain information on operation of the
control unit.
▶ Observe operating instructions of the control unit and the heat
source.
The following displays can be called up via the touch screen:
• Heat source in the system
• Heat consumers and heat distributors in the system
• Monitor data
• Setting parameters for commissioning and system optimisation.
These parameters are protected by a code.
15
50 °C
on/o
14
Fig. 6 Operating and display elements
[1]Display of system, subsystem or function
[2]Status display of active menu level
[3]Display of temperature set (set temperature)
[4]Display of operating mode set
[5]Display of time program set
[6]Display of Internet connection
[7]Display of system components
[8]Advanced functions for heating circuit, DHW
[9]Display of time
[10] Press field to switch between display types on the display
[11] Information menu
30 %
12:00
10111213
[12] Press field to go back to the previous level/screen
[13] Press field to return to the system overview
[14] Advanced functions of the heat source
[15] Status display of system components
The symbols used are listed in Chapter 23.3 on page 51,
accompanied by an explanation.
9
0010005510-001
7
8
12
Control 8313 – 6720859567 (2017/03)
Operation of the control unit
6.4Operating the appliance
The operating instructions contain information on operation of the
control unit.
▶ Observe the operating instructions of the control unit.
A description of operation of the control unit from the contractor's
standpoint is provided below.
Changes to parameters can be made in a number of different ways,
depending on the menu item.
• Changing numerical value
Numerical values can be changed by entering the number directly.
A keyboard opens when you tap the numerical field.
▶ Type in numerical values and .
If the values you entered are invalid, the previous value will be
displayed.
• Scale
You can change the value by tapping the Plus and Minus keys.
• Selection box
Tap this field to open a selection box. Tap on the required parameter/
function to select it.
• Label text field ( Chapter 6.6, page 13)
• Off/On
Tap on the required parameter/function to select it.
To save the changes:
▶ Tap Save field.
To cancel the operation:
▶ Tap Cancel field.
If parameters are linked to settings, a temperature, for example, can only
be selected/modified if the function is set to On.
Fields that are not active are highlighted in grey.
-30-22-15-70
0010007715-001
6.6Labelling a text field
In some cases, the selection box contains an empty field/User-defined
which can be labelled by entering text.
▶ Tap on the empty field.
A keyboard opens.
▶ Enter a suitable text for the length of the field.
▶ Confirm entry with
To save the changes:
▶ Tap Save field.
To cancel the operation:
▶ Tap Cancel field.
6.7Labelling the text field of the FM-SI module
(accessory)
You can name the inputs of the FM-SI safety module according to the
connected safety equipment.
If other devices are connected, you can assign your own names to these
by entering text in an empty field. If fields have been selected but not
saved, the selection is reset.
To label a field:
▶ Tap the field.
The pre-selection opens.
▶ Select name.
-or-
▶ Tap FM-SI field.
A keyboard opens.
▶ Enter a suitable text for the length of the field and tap to apply.
To save the change:
▶ Tap Save field.
To cancel the operation:
▶ Tap Cancel field.
3124
65
Fig. 8 Labelling a text field
[1]FM-SI1
[2]Name of safety equipment
[3]Free
[4]Allocated
[5]Cancel
[6]Save
0010009240-001
Control 8313 – 6720859567 (2017/03)
13
Function keys of the user interface
t
t
6.8Calling up the service menu
The Service menu is protected against unauthorised use. The Service
menu is intended exclusively for approved heating contractors.
Unauthorised access will invalidate the warranty!
The Service menu can only be accessed from the system overview.
To call up the Service menu:
▶ Tap and hold for roughly 5 seconds.
12:00
1
Fig. 9 Call up Service menu
[1]Fault history, Service display
In the Service menu tap the symbol to select the Settings or the
symbol to select the Monitor data.
When the key is pressed the locking fault is unlocked and the
functions are reset (e.g. following triggering of the high limit safety cutout or resetting of the SAFe).
To unlock a function:
▶ Key Hold down for 2 seconds.
rese
rese
0010007084-001
2
Fig. 10 Service menu
[1]Symbols for available functions
[2]Monitor data
12:00
0010008706-001
7.2Chimney sweep button (flue gas test)
WARNING:
Risk of scalding from hot water!
Setting the set temperature > 60 °C creates a risk of scalding.
▶ Do not draw off DHW unmixed.
To perform the flue gas test:
▶ Observe the relevant national requirements for limiting flue losses
from the heating system.
The flue gas test is switched on if required at the heat source
( Technical documentation of heat source) or at the control unit.
▶ Ensure heat consumption within the heating system.
▶ Starting from the initial position, hold the key down for several
seconds.
The flue gas test starts immediately.
The parameters for defining the conditions under which the flue gas
test is carried out are shown in the display.
▶ Setting parameters (e.g. modulation).
▶ Tap Save.
The heat source is operated at the set output.
14
Control 8313 – 6720859567 (2017/03)
If a preset parameter (e.g. minimum boiler output) is exceeded or
undercut when making the adjustment, a warning message appears that
must be confirmed. The parameter remains at the previous value.
To exit the view:
▶ Tap Cancel.
The flue gas test continues.
3
77
Function keys of the user interface
Emergency operation
The “emergency operation” operating mode is activated automatically if
the user interface is faulty or if communication with the control unit via
the internal BUS is interrupted.
In the “emergency operation” operating mode, the heat source heats
continuously without setback at a boiler temperature of 60 °C. All pumps
connected to the central module (boiler circulation pump, pump of
heating circuit 00, DHW pump and DHW circulation pump) are switched
on.
The SR mixing valve is de-energised and must be adjusted manually if
necessary. The installed function modules cannot be triggered by the
BCT531 user interface and do not work.
The LED status display lights up red in the “emergency operation
”operating mode.
2
Fig. 12 Flue gas test
[1]Save
[2]Cancel
[3]Modulation
The LED status display ( Fig. 11, [4], page 14) lights up yellow during
the flue gas test and is accompanied by a constantly recurring pop-up
window.
To conclude the flue gas test:
▶ Press key again.
If the flue gas test is not ended manually, it ends automatically after
30 minutes.
1
0010009474-001
7.3Key for manual operation, emergency operation
WARNING:
Risk of scalding from hot water!
Setting the set temperature > 60 °C creates a risk of scalding.
▶ Do not draw off DHW unmixed.
Key for manual operation
Press the key to ensure the “Manual operation” operating mode is
available if e.g. the user interface has failed or the internal control unit
communication has been disrupted. The heat source heats continuously
without setback at a boiler temperature of 60 °C. The pumps and mixers
of the heating circuits, the DHW heating of the central module and the
function modules continue running normally. The LED status display
lights up yellow.
Manual operation
The “manual operation” operating mode can be set and adjusted for
every function separately.
▶ Observe the operating instructions of the control unit.
Control 8313 – 6720859567 (2017/03)
15
Commissioning
8Commissioning
8.1Notes on commissioning
▶ Ensure there is sufficient heat load available
(e.g. by the DHW heating).
Otherwise the heat source will switch off.
Different messages are displayed according to the application.
8.2Control unit settings
With this control unit, a number of temperatures are specified by the
SAFe of the heat source.
The temperature values are set or modified via the touch screen.
Long burner run times can be ensured by optimising the settings at the
control. Rapid temperature fluctuations in the heat source are avoided.
Gentle temperature transitions extend the service life of the heating
system.
8.2.1Setting the control unit address
Each connected control unit must be given a different address if several
control units are networked. A fault is indicated on the display of the user
interface if the same address is allocated more than once.
The address is set [5] at the control unit on the back of the user
interface.
▶ Remove the user interface.
▶ Set the control unit address (e.g. using a screwdriver).
Address Description
0Stand-alone control unit (default setting):
• The controller operates alone.
Master (lead control unit):
• The master activates the heat source.
• Always connect the outside temperature sensor to the
master.
• The master recognises if an address has been allocated
more than once. A fault is indicated on the display of the
user interface.
• All networked controllers transfer their set values to the
master. The master uses them to generate the overall set
value.
• Only 1 master is permitted in each network!
1...15Slave (control units subordinate to the master):
• The address 0 must never be assigned to a slave.
• Each address is only allocated once.
Table 4 Control unit addresses
8.2.2Terminating resistors
The terminating resistors J1 and J2 ( Fig. 13, [6], [7], page 16) are
closed in the delivered condition (activated = inserted). If a network is
established via the BUS connections ( Fig. 13, [2], [3], page 16), the
jumpers must be opened here and closed at the last BUS node.
11
10
9
8
LAN1
LAN2
USB1
+-
J1
3 2 13 2 1
J2
2 1
567
0010005508-001
Fig. 13 Back of the user interface
[1]Slide type insert for SD card
[2]CAN-BUS connection
(no function, provided for subsequent functions)
[3]Modbus-RTU connection for CHP module
[4]EMS connection (connection for EMS heat source
with its own basic control (control panel))
[5]Address setting of control unit
[6]Jumper for activating the Modbus-RTU terminating resistance
[7]Jumper for activating the CAN-BUS terminating resistance
[8]Battery CR2032
[9]Network connection 2 (CBC-BUS)
[10] Network connection 1 (Internet, Modbus TCP/IP, CBC-BUS)
[11] USB connection
1
2
3
4
16
Control 8313 – 6720859567 (2017/03)
Menu structure
Chapter 6 from page 11 describes how to operate and call the menus
9Menu structure
The control unit electronics have 2 levels, in which system-dependent
settings are made. The levels and parameters displayed depend on the
installed modules and the factory defaults. The parameters that are not
required for the selected function are not displayed.
Parameters that are not active are highlighted in grey.
The functions of the most frequently used modules FM-MM, FM-MW and
FM-SI are described in these instructions, in addition to the basic
functions of the control unit.
Main menuExplanation/FunctionFurther information
General
characteristic data
Module selectionFor selecting whether modules are detected and installed automatically or manuallychapter 9.2, page 18
Boiler
characteristics
Heating circuit data Setting of different heating circuit data (e.g. heating circuit system, maximum flow temperature)
Domestic hot water Water treatment settingschapter 18, page 27
ResetReset values in the main menu and service menu to the default settings.chapter 14, page 37
VersionShows the software versions of the user interface, the control unit and the Open Source informationChapter 2.2, page 5,
Control unitSave or load configurationschapter 20.1, page 44
ConnectivityActivation and setting of network connectionChapter 9.6, page 28
Function testCheck whether system components (e.g. pumps) are correctly connected.
Lock screenOption for locking the screen.chapter 9.7, page 29
Manual operationWhen the key is pressed, the heat source operates using stored values.chapter 7.3, page 15
Monitor dataShows set values and actual values of the system. Tap the symbol to display the values in the
FaultShows the faults in the heating system. The user interface can only display the faults for the
Table 5 Main menu
Settings of the control unit, of heating system parameters and the house propertieschapter 9.1, page 18
Setting of different boiler data, depending on heat source
If a FM-SI is installed: settings for the safety equipment.
and display of current heating curves of the relevant heating circuit
The displays depend on which modules are installed. Depending on the operating conditions, there may
be a time delay between the demand and display.
bottom bar.
control unit it is connected to.
with the user interface.
In the following tables, the default settings are highlighted in bold in the
"Settings/Adjustment range" column.
chapter 9.3.1, page 19
chapter 9.4.1, page 21
chapter 9.5, page 27
chapter 15, page 37
Chapter 9.6, page 28
chapter 17, page 43
chapter 19, page 44
chapter 11.3, page 32
Chapter 20.5, page 45
and chapter 20.6,
page 45
Control 8313 – 6720859567 (2017/03)
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.