Bosch Compress 3000 DW FI Installation And Operating Instructions Manual

Heat pump
6720804054-00.1V
Compress 3000 DW FI
HP 270-2...
Installation and operating instructions
Please read the installation instructions before installing the appliance! Please read the operating instructions before commissioning the appliance!
Please observe the safety instructions in the operating instructions! The installation location must meet the requirements for sufficient ventilation!
Installation must only be carried out by an authorised contractor!
6 720 809 134 (2013/09) EN
2 | Contents

Contents

1 Key to symbols and safety instructions . . . . . . . . . . 3
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . 3
2 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 About the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Type overview . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Data plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Description of appliance . . . . . . . . . . . . . . . . 5
3.5 Dimensions and minimum clearances . . . . . 6
3.6 Appliance layout . . . . . . . . . . . . . . . . . . . . . . 7
3.7 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . 8
3.8 Safety, control and protection devices . . . . 8
3.8.1 High Pressure Switch . . . . . . . . . . . . . . . . . . 8
3.8.2 High limit safety cut-out . . . . . . . . . . . . . . . . 8
3.8.3 Temperature sensor for air inlet . . . . . . . . . . 8
3.9 Corrosion protection . . . . . . . . . . . . . . . . . . . 8
3.10 Technical properties . . . . . . . . . . . . . . . . . . . 9
4 Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Installation location . . . . . . . . . . . . . . . . . . . 10
5.2 Installing the appliance . . . . . . . . . . . . . . . . 11
5.3 Connecting the ducts . . . . . . . . . . . . . . . . . 12
5.3.1 Open flue operation . . . . . . . . . . . . . . . . . . 12
5.3.2 Outdoor air operation . . . . . . . . . . . . . . . . . 12
5.4 Connecting the water pipes . . . . . . . . . . . . 12
5.5 Internal indirect coil connection . . . . . . . . . 13
5.6 Connecting the DHW circulation line . . . . . 14
5.7 Condensate hose connection . . . . . . . . . . . 14
5.8 DHW expansion vessel . . . . . . . . . . . . . . . . 14
5.9 Filling the cylinder . . . . . . . . . . . . . . . . . . . . 15
5.9.1 Water quality . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1 Operation modes . . . . . . . . . . . . . . . . . . . . 18
8.2 Setting the domestic hot water
temperature . . . . . . . . . . . . . . . . . . . . . . . . .18
8.3 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8.4 "Prog" submenu - Operating modes . . . . . . 19
8.4.1 "Manual" operating mode . . . . . . . . . . . . . . 19
8.4.2 "P1", "P2" and "P3" operating modes . . . . 19
8.4.3 "Full" operating mode . . . . . . . . . . . . . . . . . 19
8.4.4 "OFF" operating mode . . . . . . . . . . . . . . . . 19
8.5 "Mode" submenu - Heating mode . . . . . . . . 20
8.5.1 Electrical heating mode . . . . . . . . . . . . . . . 20
8.5.2 "Heat pump" operating mode . . . . . . . . . . . 20
8.5.3 "Combi" operating mode . . . . . . . . . . . . . . 20
8.6 "Set" submenu - Settings . . . . . . . . . . . . . . 21
8.6.1 Date - Setting the temperature unit, date,
time and day of the week . . . . . . . . . . . . . . .21
8.6.2 Prog - Programming of the operating times 21
8.6.3 "Leg" - Automatic thermal disinfection . . . 23
8.6.4 « Duct » - use of ducts . . . . . . . . . . . . . . . . . 24
8.6.5 "Purg" - Drain . . . . . . . . . . . . . . . . . . . . . . . . 24
8.6.6 "Fset" - Default settings . . . . . . . . . . . . . . . 24
8.7 "Info" submenu - Information . . . . . . . . . . . 24
8.8 Fault diagnosis . . . . . . . . . . . . . . . . . . . . . . 25
8.9 Default settings . . . . . . . . . . . . . . . . . . . . . . 25
9 Environmental protection/Recycling . . . . . . . . . . . 25
10 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.1 General inspections . . . . . . . . . . . . . . . . . . 26
10.2 Checking/replacing the magnesium anode 26
10.3 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.4 Condensate pipe . . . . . . . . . . . . . . . . . . . . . 26
10.5 Safety valve . . . . . . . . . . . . . . . . . . . . . . . . . 26
10.6 Refrigerant circuit . . . . . . . . . . . . . . . . . . . . 27
10.7 High limit safety cut-out . . . . . . . . . . . . . . . 27
10.8 Draining the cylinder . . . . . . . . . . . . . . . . . . 27
10.9 "Service" menu . . . . . . . . . . . . . . . . . . . . . . 27
6 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1 Appliance's electrical connection . . . . . . . . 16
7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.1 Before commissioning . . . . . . . . . . . . . . . . 17
7.2 Switching the appliance on/off . . . . . . . . . . 17
6 720 809 134 (2013/09) Compress 3000 DW FII
11 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.1 Faults that are displayed . . . . . . . . . . . . . . 28
11.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1

Key to symbols and safety instructions

1.1 Key to symbols

Warnings

Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTICE indicates a situation that could result in damage to property or equipment.
CAUTION indicates a situation that could result in minor to medium injury.
WARNING indicates a situation that could result in severe injury or death.
DANGER indicates a situation that will result in severe injury or death.

Important information

This symbol indicates important information where there is no risk to people or property.

Additional symbols

Symbol Explanation
Step in an action sequence Cross-reference to another part of the document
List entry – List entry (second level)
Table 1

1.2 Safety instructions

Installation
▶ The appliance may only be installed by an authorised
contractor.
▶ Do not install the appliance in the following locations:
–outside – in locations which promote corrosion – in locations with a risk of frost – in locations where there is a risk of explosion.
Key to symbols and safety instructions | 3
▶ Wait until the appliance is at the installation location to
remove it from its packaging.
▶ All water connections must be checked for tightness before
the appliance is connected to the power. ▶ Observe minimum clearances ( Fig. 6, page 11). ▶ The electrical connection must comply with the local
applicable regulations. ▶ Connect the appliance to an independent, earthed power
source. ▶ Install a safety valve at the appliance's cold water inlet. ▶ The drain line from the safety valve must be laid in a frost-
free location. It must remain open to the atmosphere and
always be kept in a sloped position. Minimum and maximum water temperatures: 3 °C/80 °C Minimum/maximum water pressure: 0.2 bar/2 bar below the
value of the installed safety valve
Risk of scalding at the hot water draw-off points
▶ When the appliance is in operation, temperatures in excess
of 70 °C can occur. To limit the temperature at the tap,
install a thermal DHW tempering valve.
Service
▶ The end customer is responsible for safety and
environmental compatibility during installation and service
work. ▶ The appliance may only be serviced by an authorised
contractor. ▶ Isolate the appliance from the power supply before
performing any service work.
Service and maintenance
▶ Maintenance may only be carried out by an authorised
contractor. Faulty maintenance may pose a danger to the
user and cause malfunctions in the appliance. ▶ Use only original spare parts. ▶ Have an authorised contractor perform an annual inspection
and service the appliance as needed. ▶ Any work involving cooling gas may only be carried out by
qualified contractors. ▶ Empty cylinders as described on page 27, chapter 10.8 if
necessary. ▶ Open the safety valve manually at least once a month to
ensure that it is functional. ▶ We recommend that you arrange a maintenance and
inspection contract with the manufacturer.
6 720 809 134 (2013/09)Compress 3000 DW FII
4 | Key to symbols and safety instructions
Room/inlet air
Keep the inlet air free of contaminants. It must no t contain any of the following substances:
• corrosive substances (ammonia, sulphur, halogen products, chlorine, solvents)
• fatty or explosive substances
• aerosol concentrations
No other air inlet systems may be connected to the fan.
Refrigerant
▶ Please observe the applicable environmental regulations
when using and reusing refrigerant. Do not release it into the environment! Use the refrigerant R134a. It is non ­flammable and does not damage the ozone layer.
▶ Before working on parts of the refrigerant circuit, remove
the refrigerant for safety reasons.
Please note that HFC-134a and PAG-ÖL are used during service work. This is a chlorofluorocarbon and is rated with a greenhouse potential of 1300 in the Kyoto Protocol.
Instructions to the customer
▶ Explain to the customer how the appliance works and how to
operate it.
▶ Advise the customer that he/she must not make any
modifications to the appliance or carry out any repairs on it.
Safety of electrical appliances for domestic use and similar purposes
The following requirements apply in accordance with EN 60335-1 in order to prevent hazards from occurring when using electrical appliances:
“This appliance may be operated by children aged 8 or over and by people with full physical, sensory and mental capabilities who have the necessary training and experience to use this type of appliance. They must be supervised or instructed on how to use the appliance safely and on the associated risks. Children must not play with the appliance. Children must not clean or service the appliance without supervision.”
“Damaged power cables must be replaced by the manufacturer, the service department or a qualified contractor in order to prevent hazards.”
6 720 809 134 (2013/09) Compress 3000 DW FII
Standard delivery | 5
1
6720804054-13.1V
2
3

2 Standard delivery

Fig. 1
[1] Heat pump [2] Set of printed documents for the appliance [3] Condensate drain pipe

3 About the appliance

Appliances in the HP270... series are heat pumps which use the energy in the ambient air for DHW heating.

3.1 Intended use

The appliance may only be used for DHW heating. Using the boiler for any other purpose will be considered
incorrect use. Buderus accepts no liability for any damage resulting from such use.
The appliance is not suitable for commercial or industrial applications. It is approved for household use only.

3.2 Type overview

HP 270 -2 E 1FIIVs HP 270 -2 E 0FIIVs
Table 2
[HP] Heat pump [270] Cylinder capacity (in litres) [-2] Version [E] Electronic control [1] Number of internal indirect coils in the cylinder [F] Floor installation [I] Indoor installation [I] Air supply from inside [V] Vertical installation [S] Side connections

3.3 Data plate

The data plate is located on the rear side of the appliance. There you will find details on the appliance performance, part
numbers, approval data, the coded date of manufacture (FD), serial numbers and other specifications.

3.4 Description of appliance

Appliance for DHW heating with the following properties:
• Glass-lined steel cylinder with thermal insulation using CFC­free rigid polyurethane foam.
• Cylinder is corrosion-protected using internal magnesium anode.
• The refrigerant and DHW circuits are completely separate.
• "Heat pump" operating mode stops automatically inlet temperatures below -10 °C or over 35 °C.
• Upper limit pressure switch protects the refrigerant circuit.
• R134a used as the refrigerant.
• DHW temperatures between 30 °C and 70 °C (the default setting for the DHW temperature is 50 °C).
1)
at air
1) chapter 8.5.2
6 720 809 134 (2013/09)Compress 3000 DW FII
6 | About the appliance
6720804054-03.1V
670
25
94
331
630
735
1266
916
1835
350
700
735
445
160

3.5 Dimensions and minimum clearances

Fig. 2 Appliance dimensions (in mm)
6 720 809 134 (2013/09) Compress 3000 DW FII

3.6 Appliance layout

1
2
4
3
6
11 12 13
18
24
25
16
17
3
1
5
23
21
15
22
14
19 20
6
10
9 5
4
7
2 8
6720804054-04.1V
26
6720804054-16.1V
1
2
Fig. 3 Heat pump
[1] Water inlet - G1" [2] Internal indirect coil outlet - G1" [3] Internal indirect coil inlet - G1" [4] Sensor pocket for temperature sensor (data for solar
system or electric booster heater) [5] DHW circulation line inlet - G3/4" [6] Water outlet - G1" [7] Internal indirect coil [8] Thermal insulation [9] Water inlet to condenser [10] Water outlet from condenser [11] Fan [12] Evaporator [13] Condenser (gas/water heat exchanger) [14] Compressor [15] Sensor pocket for DHW temperature sensor [16] Magnesium anode [17] Central heating resistor [18] Adjustable feet (3x) [19] Air outlet aperture [20] Air inlet aperture [21] Condensate outlet [22] Circulation pump
1) model HP270-2E1... only
1)
1)
1)
About the appliance | 7
[23] Front protective covering [24] Housing ring [25] Housing lid [26] Fastening for housing lid
Fig. 4 User interface
[1] Display [2] Setting buttons
6 720 809 134 (2013/09)Compress 3000 DW FII
8 | About the appliance

3.7 Wiring diagram

Fig. 5
[1] NTC temperature sensor for air inlet [2] Flow NTC temperature sensor [3] NTC temperature sensor in water inlet [4] Power cable [5] High Pressure Switch [6] Electrical capacitor for compressor [7] Compressor [8] High limit safety cut-out for compressor [9] Circulation pump [10] Fan [11] Resistor [12] Resistor for high-limit safety cut-out [13] Electronics box [14] NTC temperature sensor (evaporator plates) [15] Electrical capacitor for fan start [16] Electrical capacitor for fan speed

3.8 Safety, control and protection devices

3.8.1 High Pressure Switch
If the operating pressure is outside of the recommended range, the pressure switch switches off the appliance and displays a fault ( chapter 11, page 28).
3.8.2 High limit safety cut-out
The high limit safety cut-out ensures that the water temperature in the cylinder does not exceed the prescribed limit. If the temperature limit is exceeded, the DHW heating shuts down. The reset is performed manually by a certified contractor.
3.8.3 Temperature sensor for air inlet
The temperature sensor measures the temperature of the inlet air in the evaporator. If the measured value is outside the operating temperature range, DHW heating automatically switches from the "Combi" operating mode to "Electric booster heater". If the appliance is in the "Heat pump" operating mode, DHW heating is interrupted until the temperature returns to within the permissible range.

3.9 Corrosion protection

The internal wall of the DHW cylinder is glass-lined (double coating), making it neutral when in contact with water and therefore suitable for potable water.
As an additional corrosion protection measure, the cylinder is equipped with a magnesium anode. This must be inspected at regular intervals and replaced if necessary.
The first inspection must take place 6 months after installation.
In regions with more corrosive water, safety measures (filter, etc.) must be taken, and the magnesium anode must be serviced more frequently.
6 720 809 134 (2013/09) Compress 3000 DW FII
About the appliance | 9

3.10 Technical properties

Unit HP270-2E0... HP270-2E1...
Heating output - in accordance with EN255-3, air temperature 20 °C, heating water from 15 °C to 45 °C
Output kW 1,7 Total heating output (including electric booster heater) kW 3,7 Performance coefficient (COP) 4,3 Heat-up time h 5:00 Heat loss in 24h kWh/day 0,74
Heating output - in accordance with EN16147, XL cycle, air temperature 15 °C, heating water from 10 °C to 54 °C, Tref > 52.5 °C
Performance coefficient (COP) 3,20 Heat-up time h 8:48 Heat loss in 24h kWh/day 1,08 DHW volume, corresponds to water at a temperature of 40 °C, available after
heating
Heating output - in accordance with EN16147, XL cycle, air temperature 7 °C, heating water from 10 °C to 54 °C, Tref > 52.5 °C
Performance coefficient (COP) 2,79 Heat-up time h 10:38 Heat loss 24h kWh/day 0,97
Air inlet
Air flow rate (without/with pipework) - fan speed "SP1" m3/h 380/300 Air flow rate (without/with pipework) - fan speed "SP2" m3/h 490/300 Operating temperature °C -10 ... +35
Refrigerant circuit
Refrigerant R134a g 400 Maximum pressure bar 27
DHW
Cylinder capacity l 270 260 Area of heat exchanger (internal indirect coil) m Maximum outlet temperature without/with electric booster heater °C 60/70 DHW volume per day, corresponds to a water temperature of 40 °C, air
temperature 20 °C, heating water from 15 °C to 60 °C Maximum operating pressure bar/MPa 10/1
Electrical details
Mains power supply V ~230 (+10%/-10%) Frequency Hz 50 Current rating (without/with electric booster heater) O 2.6/11.3 Max. rated consumption kW 0.6 Total heating output of the electric booster heater kW 2.0 Total max. rated consumption (including electric booster heater) kW 2.6 IP rating I IP rating (without/with pipework) IP 21/24
General data
Table 3
l
2
l
372
-1.3
1200
6 720 809 134 (2013/09)Compress 3000 DW FII
10 | Transport and storage
Unit HP270-2E0... HP270-2E1...
Sound pressure level with pipework (at a distance of 2 m) dB(A) 40 Dimensions, W x H x D mm 700 × 1835 × 735 Net weight (without packaging) kg 108 125
Table 3

Manual transport

4 Transport and storage

NOTICE: Damage caused by straps!
WARNING: Transport damage!
▶ Take care when handling the appliance. ▶ To avoid dropping and damaging the
appliance, do not pivot it.
NOTICE: Transport damage! ▶ To avoid transport damage, do not
remove the protective packaging. Wait until the appliance is at the installation location to remove the protective packaging.
▶ Transport and set down the appliance
carefully. Jerky movements can damage the internal glass-lined coating, the components and their connections or the external casing.
▶ Use suitable means of transport to bring
the appliance to the installation location (special car, pallet truck, etc).
Straps can be placed around the cylinder in order to position the appliance in its final location.

5 Installation

▶ The appliance may only be installed by an authorised
contractor.
▶ The heat pump installation must follow the applicable
regulations.
▶ Check that all pipe connections are intact and have not
shaken loose during transportation.
▶ Remove the front protective covering
(Fig. 3, [23]).
▶ Make sure that the straps do not scratch
or make indentations on the surface of the appliance.
▶ Do not attach straps to the appliance
connections.

General information

The appliance is delivered on a single pallet and is protected against transport damage by special packaging.
The appliance must be stored and transported vertically in its original packaging temperatures of -20 °C to +60 °C are permissible for storage and transport.
1) Horizontal transportation is permitted over short distances, provided that the conditions described above are fulfilled.
6 720 809 134 (2013/09) Compress 3000 DW FII
1)
and the cylinder must be empty. Ambient

5.1 Installation location

Please note the following when choosing the installation location:
• The appliance must be installed in a dry, frost-free room. The supply air temperature must be betw een -10 °C and 35 °C in order to optimise the appliance performance.
• The appliance must be installed on a sufficiently strong and level surface.
• The air outlet and air inlet must not be in locations where there is a risk of explosion cause by gas, steam or dust.
• Ensure that condensate drains correctly.
• The surf ace below the appliance must be strong enough (the appliance weighs about 400 kg when the cylinder is filled,
NOTICE: Refrigerant leak! ▶ Only authorised contractors are
permitted to maintain and repair the refrigerant circuit.
Loading...
+ 22 hidden pages