WATER TO REFRIGERANT HEAT EX:
C - COPPER
N - CUPRO-NICKEL
Revised 01-11 Subject to change without prior notice
SUPPLY AIR LOCATION:
T - TOP (VT ONLY)
S - STRAIGHT THRU (HZ ONLY)
E - END BLOW (HZ ONLY)
RETURN AIR LOCATION:
L - LEFT
R - RIGHT
WATER CONNECTION LOCATION
F - FRONT
6 720 220 045
4 CP/BP Series Initial Inspection
INITIAL INSPECTION
Be certain to inspect all cartons or crates on each
unit as received at the job site before signing the
freight bill. Verify that all items have been received
and that there are no visible damages; note any
shortages or damages on all copies of the freight
bill. In the event of damage or shortage, remember
that the purchaser is responsible for ling the
necessary claims with the carrier. Concealed
damages not discovered until after removing the
units from the packaging must be reported to the
carrier within 24 hours of receipt.
GENERAL DESCRIPTION
These Packaged System Heat Pumps provide the
best combination of performance and efciency
available. Safety devices are built into each unit to
provide the maximum system protection possible
when properly installed and maintained.
The CP/BP Water-to-Air Heat Pumps are
Underwriters Laboratories (UL) and (cUL) listed for
safety. The water-to-Air Heat Pumps are designed to
operate with entering uid temperature between
25°F to 80°F in the heating mode and between 50°F
to 110°F in the cooling mode. Efciencies and
capacities will vary as entering uid and return air
temperatures vary.
50°F Min. EWT for well water applications
sufcient water ow to prevent freezing.
Antifreeze solution is required for all closed loop
applications where the uid temperature may drop
below 50°F. Cooling Tower/Boiler and Earth
Coupled (Geo Thermal) applications should have
sufcient antifreeze solution to protect against
extreme conditions and equipment failure. Frozen
water coils are not covered under warranty.
This product should not be used for temporarily
heating/cooling during construction. Doing so
may affect the unit’s warranty.
MOVING AND STORAGE
If the equipment is not needed for immediate
installation upon its arrival at the job site, it should
be left in its shipping carton and stored in a clean,
dry area. Units must only be stored or moved in the
normal upright position as indicated by the “UP”
arrows on each carton at all times. If unit stacking is
required, stack units as follows: Vertical units less
than 6 tons, no more than two high; horizontal units
less than 6 tons, no more than three high. Do not
stack units larger than 6 tons.
SAFETY CONSIDERATIONS
Installation and servicing of this equipment can be
hazardous due to system pressure and electrical
components. Only trained and qualied personnel
should install, repair, or service the equipment. Untrained
personnel can perform basic functions of maintenance
such as cleaning coils and replacing lters.
Before performing service or maintenance
operations on the system, turn off main power to
the unit. Electrical shock could cause personal
injury or death.
When working on equipment, always observe
precautions described in the literature, tags, and
labels attached to the unit. Follow all safety codes.
Wear safety glasses and work gloves. Use a
quenching cloth for brazing, and place a re
extinguisher close to the work area.
The blower motor should only be operated when a
duct is installed and secured to heat pump duct
collar in order to avoid possible injury.
LOCATION
Locate the unit in an indoor area that allows easy
removal of the lter and access panels, and has
enough room for service personnel to perform
maintenance or repair. Provide sufcient room to
make uid, electrical, and duct connection(s). If the
unit is located in a conned space such as a closet,
provisions must be made for return air to freely
enter the space. On horizontal units, allow
adequate room below the unit for a condensate
drain trap and do not locate the unit above supply
piping. These units are not approved for outdoor
installation; therefore, they must be installed inside
the structure being conditioned.
Do not locate units in areas that are subject to
freezing.
6 720 220 045
Subject to change without prior notice Revised 01-11
Installation CP/BP Series 5
INSTALLATION
Remove shipping block under blower housing.
Loosen compressor mounting bolts.
The installer should comply with all local codes
and regulations which govern the installation of
this type of equipment. Local codes and
regulations take precedent over any
recommendations contained in these instructions.
In lieu of local codes, the equipment should be
installed in accordance with the recommendations
made by the National electric code, and in
accordance with the recommendations made by
the National Board of Fire Underwriters. All local
seismic codes for seismic restraint of equipment,
piping, and duct work shall be strictly adhered to.
MOUNTING VERTICAL UNITS
Vertical units up to six tons are available in left or
right air return congurations. Vertical units should
be mounted level on a vibration absorbing pad
slightly larger than the base to minimize vibration
transmission to the building structure. It is not
necessary to anchor the unit to the oor. (See
Figure #1).
MOUNTING HORIZONTAL UNITS
While horizontal units may be installed on any
level surface strong enough to hold their weight,
they are typically suspended above a ceiling by
threaded rods. The rods are usually attached to
the unit corners by hanger bracket kits (P/N
930-008). (See Figure #2). The rods must be
securely anchored to the ceiling. Refer to the
hanging bracket assembly and installation
instructions for details. Horizontal units installed
above the ceiling must conform to all local codes.
An auxiliary drain pan if required by code should
be at least four inches larger than the bottom of
the heat pump. Plumbing connected to the heat
pump must not come in direct contact with joists,
trusses, walls, etc.
If the unit is located in a conned space such as a
closet, provisions must be made for return air to
freely enter the space.
VIBRATION
PAD
FULL SIZE
Figure #1 – Vertical unit on vibration pad
Figure #2 – Typical horizontal unit hanging bracket
Some applications require an attic oor installation of the horizontal unit. In this case the unit
should be set in a full size secondary drain pan on
top of a vibration absorbing mesh. The secondary
drain pan prevents possible condensate overow
or water leakage damage to the ceiling. The
secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by
additional layers of vibration absorbing mesh. In
both cases, a 3/4” drain connected to this secondary pan should be run to an eave and able to drain
to a location that will be noticeable. If the unit is
located in a crawl space, the bottom of the unit
must be at least 4” above grade to prevent ooding of the electrical parts due to heavy rains.
Locate the heat pump unit in an area that provides
sufcient room to make water and electrical
connections, allowing easy removal of the access
Revised 01-11 Subject to change without prior notice
6 720 220 045
6 CP/BP Series Condensate Drain
panels, and replacement of air lters for routine
maintenance. This will ensure proper work space for
service personnel to perform maintenance or repair.
See Unit Specications for replacement lter sizes
in the back of this manual to ensure proper
clearances are provided during installation. Allow
adequate room below the unit for a condensate
drain trap on horizontal units.
Water freezes at 32°F. Frozen water coils are not
covered under the limited product warranty. It is
the installer’s responsibility to insure that the heat
pump unit is installed in a location or have taken
the proper precautions in order to prevent
rupturing the water coil due to freezing conditions.
The heat pump unit is designed for conditioned
space installation only. If the source water is
subjected to conditions where ambient
temperatures can fall below freezing, some form of
freeze protection should be employed. In an open
loop system this may entail running the water pump
continuously to prevent freezing. An antifreeze
solution wherever possible should be used if water
will be subject to freezing. Consult the factory in
these instances for guidance.
CONDENSATE DRAIN
A drain line must be connected to the heat pump
and pitched away from the unit a minimum of 1/8”
per foot to allow the condensate to ow away from
the unit.
Figure #3 – Heat Pump Condensate Trapping
This connection must be in conformance with local
plumbing codes. A trap must be installed in the
(Heat Pumps are not internally trapped). A vertical
air vent is sometimes required to avoid air pockets
(See Figure #3). The length of the trap depends on
the amount of positive or negative pressure on the
drain pan. A second trap must not be included.
The horizontal unit should be pitched
approximately 1/4” towards the drain in both
directions, to facilitate condensate removal. See
Figure 4 below.
Figure #4 – Sloped horizontal unit installation
DUCT SYSTEM
A supply air outlet collar and return air duct ange
are provided on all units to facilitate duct
connections. See Unit Specications for duct collar
connection sizes in the back of this manual.
A exible connector is recommended for supply
and return air duct connections on metal duct
systems. All metal ducting should be insulated with
a minimum of one inch duct insulation to avoid heat
loss or gain and prevent condensate forming during
the cooling operation. Application of the unit to
uninsulated duct work is not recommended as the
unit’s performance will be adversely affected. Do
not connect ducts directly to the blower outlet;
factory supplied duct collars should be used for
connection. The factory provided air lter must be
removed when using a lter back return air grill. The
factory lter should be left in place on a free return
system.
condensate line to insure free condensate ow.
6 720 220 045
If the unit will be installed in a new installation
which includes new duct work, the installation
should be designed using current ASHRAE
procedures for duct sizing. If the unit is to be
connected to existing ductwork, a check should be
made to assure that the duct system has the
Subject to change without prior notice Revised 01-11
Electrical CP/BP Series 7
capacity to handle the air required for the unit
application. If the duct system is too small, larger
ductwork should be installed. Check for existing
leaks and repair as necessary to ensure a tight air
seal within duct. The duct system and all diffusers
should be sized to handle the designed air ow
quietly. To maximize sound attenuation of the unit
blower, the supply and return air plenums should
be insulated. There should be no direct straight air
path thru the return air grille into the heat pump.
The return air inlet to the heat pump must have at
least one 90 degree turn away from the space
return air grille. If air noise or excessive air ow are
a problem, the blower speed can be changed to a
lower speed to reduce air ow. (Refer to ECM
motor speeds and settings in Table #1)
Always disconnect power to the unit before
changing motor speed to prevent damage to
the motor, injury or death due to electrical
shock.
ELECTRICAL
Always disconnect power to the unit before
Always disconnect power to the unit before
servicing to prevent injury or death due to
electrical shock or contact with moving parts.
All eld wiring must comply with local and national
re, safety and electrical codes. Power to the unit
must be within the operating voltage range
indicated on the unit’s nameplate. On three phase
units, phases must be balanced within 2%.
Operating the unit with improper line voltage
or with excessive phase imbalance is
hazardous to the unit and constitutes abuse
and is not covered under warranty.
Properly sized fuses or HACR circuit breakers must
be installed for branch circuit protection. See
equipment rating plates for proper size.
The heat pump units are provided with a
concentric knock-out in the front right corner post
for attaching common trade sizes of conduit.
Route power supply wiring through this opening.
Flexible wiring and conduit should be used to
isolate vibration and noise from the building
structure. Be certain to connect the ground lead to
the ground lug in the control box. Connect the
power leads as indicated on the unit wiring
diagrams.
Table 1: CP/BP Motor CFM Selection (ECM Motor Only)
Units
CP/BP015450-1531/3LOWMEDHIGH--
CP/BP018450-1531/3-LOW-MEDHIGH
CP/BP024450-1571/3LOWMEDHIGH--
CP/BP030450-1541/3LOWMEDHIGH--
CP/BP036450-1583/4LOWMEDHIGH--
CP/BP042450-1553/4LOWMEDHIGH--
CP/BP048450-1553/4-LOWMEDHIGH-
CP/BP060450-1561LOWMEDHIGH--
CP/BP070450-1561LOW--MEDHIGH
Revised 01-11 Subject to change without prior notice
Motor Part
Number
Motor HPTap1Tap2Tap3Tap4Tap5
6 720 220 045
8 CP/BP Series Thermostat Connections
THERMOSTAT CONNECTIONS
Thermostat wiring is connected to a 7 position low
voltage terminal block in the electrical box. The
thermostat connections and their functions are as
follows:
Y Compressor Operation
G Fan
O Reversing Valve (energized in cooling)
C Transformer 24 VAC Common – 3 Connections
R Transformer 24 VAC Hot
If the unit is being connected to a thermostat with a
malfunction light, this connection is made at the
unit alarm output.
If the thermostat is provided with a malfunction
light powered off of the common (C) side of the
transformer, the UPM board “ALR” jumper setting
must be set to “HOT”.
If the thermostat is provided with a malfunction
light powered off of the common (C) side of the
transformer, the unit must be provided with a
malfunction relay (Bosch option # 660-006) to
properly energize the light. The relay coil will be
wired across the (ALR) and (C) contacts on the
unit’s UPM board and the relay’s normally open
contacts across (ALR) and the malfunction light
connection on the thermostat. If the thermostat is
provided with a malfunction light powered off of
the hot (R) side of the transformer, then the
thermostat malfunction light connection should be
connected directly to the (ALR) contact on the
unit’s UPM board.
Always disconnect power before changing jumper
positions on the interface board and reset the unit
afterward.
SAFETY DEVICES AND THE
UPM CONTROLLER
Each unit is factory provided with a Unit Protection
Module (UPM) that controls the compressor
operation and monitors the safety controls that
protect the unit.
POWER
G
STATUS
R
C–GND
LPC2
FREEZE
TEMP
LOCKOUT
RESET
ALARM
TEST
FREEZE
LPC1 YYHPC
ON
35°F
4
R
CONT
YES
COND
UNIT PROTECTION MODULE
OFF
15°F
2
Y
PULSE
NO
CCDRY HOT
HPC
FHP P\N 641–244
DRY HOT
ALR
ALR
RRCC
Safety controls include the following:
• High pressure switch located in the refrigerant
discharge line and wired across the HPC
terminals on the UPM
• Low pressure switch located in the unit
refrigerant suction line and wired across
terminals LPC1 and LPC2 on the UPM.
• Optional freeze protection sensor located on the
leaving side of the water coil prevents unit
operation below 35°F or 15°F (depending on dip
switch setting). The freeze dip switch must be set
to “ON”.
The factory default for the Freeze setting is in
“ON” position. If the freeze stat option is not
ordered, the switch must be repositioned to the
“OFF” position.
• Condensate overow protection sensor located in
the drain pan of the unit and connected to the
‘COND’ terminal on the UPM board.
The UPM includes the following features:
• ANTI-SHORT CYCLE TIME—5 minute delay on
break timer to prevent compressor short cycling.
• RANDOM START—Each controller has a unique
random start delay ranging from 270 to 300 seconds to
reduce the chances of multiple units simultaneously
starting after initial power up or after a power
interruption, creating a large electrical spike.
• LOW PRESSURE BYPASS TIMER—If the compressor is
running and the low pressure switch opens, then the
control will keep the compressor on for 120 seconds.
After 2 minutes if the low pressure switch remains
open, the control will shut down the compressor and
enter a soft lockout. The compressor will not be
6 720 220 045
Subject to change without prior notice Revised 01-11
Thermostat Connections CP/BP Series 9
energized until the low pressure switch closes and the
anti-short cycle time delay expires. If the low pressure
switch opens 2–4 times in 1 hour, the unit will enter a
hard lock out and need to be reset.
• BROWNOUT/SURGE/POWER INTERRUPTION
PROTECTION—The brownout protection in the UPM
board will shut down the compressor if the
incoming power falls below 18 VAC. The compressor
will remain off till the voltage goes above 18 VAC and
the anti short cycle timer (300 seconds) times out.
The unit will not go into a hard lockout.
• MALFUNCTION OUTPUT—The controller has a set of
wet contacts for remote fault indication or dry contacts
for communication with a DDC controller or BMS. The
fault output will depend on the dip switch setting for
“ALARM”. If it set to “CONST’, a constant signal will be
produced to indicate a fault has occurred and the unit
requires inspection to determine the type of fault. If it is
set to “PULSE”, a pulse signal is produced and a fault
code is detected by a remote device indicating the fault.
See L.E.D. Fault Indication below for blink code
explanations. The remote device must have a malfunction
detection capability when the UPM board is set to “PULSE”.
• TEST DIP SWITCH—A test dip switch is provided
to reduce all time delay settings to 5 seconds
during troubleshooting or verication of unit
operation. Note that operation of the unit while in
test mode can lead to accelerated wear and
premature failure of the unit. The “TEST” switch
must be set back to “NO” for normal operation.
• FREEZE SENSOR—This is optional and can be set
to ignore or monitor a freeze sensor. There are 2
congurable freeze points, 35°F & 15°F. The unit
will enter a soft lock out until the temperature
climbs above the set point and the anti-short cycle
time delay has expired. The freeze sensor may not
provide protection in the case of loss of ow in the
heating mode. A ow switch or pressure
differential switch is recommended to prevent unit
operation in case of loss of ow.
• L.E.D. FAULT INDICATION—Two L.E.D. indicators
are provided:
• Green: Power L.E.D. indicates 18—30 VAC
present at the board.
• Red: Fault indicator with blink codes as follows:
- One blink—High pressure lockout
- Two blinks—Low pressure lockout
- Three blinks—Freeze sensor lockout
- Four blinks—Condensate overow
- Five blinks—Brownout
• INTELLIGENT RESET—If a fault condition is initiated,
the 5 minute delay on break time period is initiated
and the unit will restart after these delays expire.
During this period the fault LED will indicate the
cause of the fault. If the fault condition still exists or
occurs 2 or 4 times (depending on 2 or 4 setting for
Lockout dip switch) before 60 minutes, the unit will
go into a hard lockout and requires a manual lockout
reset. A single condensate overow fault will cause
the unit to go into a hard lockout immediately, and
will require a manual lockout reset.
• LOCKOUT RESET—A hard lockout can be reset by
turning the unit thermostat off and then back on
when the “RESET” dip switch is set to “Y” or by
shutting off unit power at the circuit breaker
when the “RESET” dip switch is set to “R”.
The blower motor will remain active during a
lockout condition.
• UPM BOARD DEFAULT SETTINGS—Your UPM
board will come from the factory with the
following default settings:
• Freeze—“ON”
• Temp—35°F
• Lockout—2
• Reset—“Y”
If unit is employing a fresh water system (no
anti-freeze protection), it is extremely important to
have the “Freeze” switch set to 35°F in order to
shut down the unit at the appropriate leaving
water temperature and protect your heat pump
from freezing if a freeze sensor is included.
Revised 01-11 Subject to change without prior notice
• Alarm—“CONT”
• Test—“NO”
• Hot/Dry Alarm—“HOT”
6 720 220 045
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.