BONFIGLIOLI Vectron Agile VABus/TCP Communications Manual

Agile
VABus/TCP Communication module CM-VABus/TCP Frequency inverter 230 V / 400 V
CONTENTS
1 GENERAL INFORMATION ABOUT THE DOCUMENTATION 6
1.1 This document 6
1.2 Warranty and liability 7
1.3 Obligation 7
1.4 Copyright 7
1.5 Storage 7
2 GENERAL SAFETY INSTRUCTIONS AND INFORMATION ON USE 8
2.1 Terminology 8
2.2 Designated use 9
2.3 Misuse 9
2.3.1 Explosion protection 9
2.4 Residual risks 10
2.5 Safety and warning signs at frequency inverter 10
2.6 Warning information and symbols used in the user manual 11
2.6.1 Hazard classes 11
2.6.2 Hazard symbols 11
2.6.3 Prohibition signs 11
2.6.4 Personal safety equipment 11
2.6.5 Recycling 12
2.6.6 Grounding symbol 12
2.6.7 ESD symbol 12
2.6.8 Information signs 12
2.6.9 Font style in documentation 12
2.7 Directives and guidelines to be adhered to by the operator 12
2.8 Operator's general plant documentation 12
2.9 Operator's/operating staff's responsibilities 13
2.9.1 Selection and qualification of staff 13
2.9.2 General work safety 13
2.10 Organizational measures 13
2.10.1 General 13
2.10.2 Use in combination with third-party products 13
2.10.3 Transport and Storage 14
2.10.4 Handling and installation 14
2.10.5 Electrical connections 14
2.10.6 Safe operation 14
2.10.7 Maintenance and service/troubleshooting 15
2.10.8 Final decommissioning 16
12/13
Agile
VABus/TCP 3
3 INTRODUCTION 17
3.1 Supported configurations 20
3.2 Initialization time 20
4 FIRST COMMISSIONING 20
5 COMMUNICATION OPTIONS 21
5.1 Control software VPlus: 21
6 ASSEMBLY/DISASSEMBLY OF COMMUNICATION MODULE 22
6.1 Assembly 22
6.2 Disassembly 23
7 VABUS/TCP INTERFACE 24
7.1 Communication modules 25
7.1.1 Installation instructions 25
7.2 Setup 26
7.3 TCP/IP address & subnet 26
7.3.1 Network without DHCP server: 26
7.3.2 Network with DHCP server: 26
7.4 TCP/IP configuration 27
7.4.1 TCP configurations tool 27
7.4.2 Parameter settings with VPlus 31
7.5 Operating behavior in the case of a communication error 33
8 PROTOCOL 34
8.1 Telegram types 35
8.1.1 Data types 35
8.1.2 Send Request / Enquiry Telegram 36
8.1.3 Setting Request / Select Telegram 37
8.1.4 System bus Node-ID 38
8.2 Telegram check 40
8.3 Timeout control 41
8.4 Resetting errors 41
9 PARAMETER ACCESS 42
9.1 Handling of datasets / cyclic writing of parameters 42
9.2 Handling index parameters / cyclic writing 43
9.2.1 Example: Writing of index parameters 43
9.2.2 Example: Reading of index parameters 44
4
Agile
VABus/TCP 12/13
10 EXAMPLE MESSA GES VA BUS/TCP 45
10.1 Reading parameters 45
10.2 Writing parameters 46
11 CONTROL OF FREQUENCY INVERTER 49
11.1 Control via contacts/remote contacts 50
11.1.1 Device state machine 52
11.2 Control via state machine 53
11.2.1 Statemachine diagram 55
11.3 Behavior in the case of a quick stop 57
11.3.1 Behavior in the case of transition 5 (disable operation) 58
11.3.2 Reference value/actual value 59
11.3.3 Example sequence 60
12 ACTUAL VALUES 61
13 PARAMETER LIST 62
13.1 Actual values (Menu “Actual ”) 62
13.2 Parameters (Menu “Para”) 63
14 APPENDIX 64
14.1 List of control words 64
14.2 List of status words 64
14.3 Warning messages 65
14.4 Application warning messages 66
14.5 Error messages 67
14.6 Conversions 67
14.6.1 Speed [1/min] into frequency [Hz] 67
14.6.2 Frequency [Hz] into speed [1/min] 67
14.7 ASCII table (0x00 – 0x7F) 68
INDEX 69
12/13
Agile
VABus/TCP 5

1 General Information about the Documentation

Compliance with the documentation is required to ensure safe operation of the frequen­cy inverter. BONFIGLIOLI VECTRON GmbH shall not be held liable for any damage
In case any problems occur which are not covered by the documentation sufficiently, please contact the manufacturer.
For better clarity, the documentation of the frequency inverter is structured according to the custom­er-specific requirements.
The present manual was created in the German language. The German manual is the original version. Other language versions are translations.
Quick Start Guide
The “Quick Start Guide” describes the basic steps required for mec hanical and electrical installa tion of the frequency i nverte r. The guide d comm issi oning s up ports yo u in t he s electi on o f nece ssary para me­ters and the configuration of the software of the frequency inverter.
User manual
The user manual documents the complete functionality of the frequency inverter. The parameters required for special purposes, for adj ustment to the application and the numerous a dditional functio ns are described in detail.
Separate user manuals are supplied for optio nal components for the frequency inverter. These manu­als complement the operating instructions and the “Quick Start Guide” for the frequency inverter.
Application manual
The application manual complements the documentation to ensure goal-directed installation and commissioning of the frequency inverter. Information on various t opics in connection with the use of the frequency inverter is described in context with the specific application.

1.1 This document

This document descr ibes the communicat ion via the VABus/TCP protocol wit h frequency inverters of
Agile
the inverters can be customized to meet the customer' s specific requirements, including applications re­quiring high functionality and dynamism.
series of devices. Thanks to the modular hardware and software structure, the frequency
WARNING
caused by any non-compliance with the documentation.
6
Agile
VABus/TCP 12/13

1.2 Warranty and liability

BONFIGLIOLI VECTRON GmbH would like to point out that the contents of this user manual do not form part of any previous or existing agreement, assurance or legal relationship. Neither are they intended to supplement or replace such agreements, a ssurances or le gal re lations hips. Any obligations of the manufacturer shall solely be based on the relevant purchase agreement which also includes the complete and solely valid warranty stipulations. These contractual warranty provisions are neither extended nor limited by the specifications contained in this documentation.
The manufacturer reserves the right to correct or am end the specificat ions, product informa tion and omissions in these operating instructions w ithout notice. The manufacturer s hall not be liable for any damage, injuries or costs which may be caused for the aforementioned reasons.
Furthermore, BONFIGLIOLI VECTRON GmbH excludes any warranty/liability claims for any personal and/or material damage if such damage is due to one or more of the following causes:
inappropriate use of the frequency inverter,
non-compliance with the instructions, warnings and prohibitions contained in the documentation,
unauthorized modifications of the frequency inverter,
insufficient monitoring of parts of the machine/plant which are subject to wear,
repair work at the machine/plant not carried out properly or in time,
catastrophes by external impact and force majeure.

1.3 Obligation

This user manual must be read before commissioning and complied with. Anybody entrusted with tasks in connection with the
transport,
assembly,
installation of the frequency inverter and
operation of the frequency inverter
must have read a nd unde rstood the user man ual and, i n parti cular, the safet y instr uctions i n order to prevent personal and material losses.

1.4 Copyright

In accordance with applicable law a gainst unfair competition, this user manual is a certificate. Any copyrights relating to it shall remain with
BONFIGLIOLI VECTRON GmbH Europark Fichtenhain B6 47807 Krefeld Germany
This user manual is intended for the operator of the frequency inverter. Any disclosure or copying of this document, exploitation and communication of its contents (as hardcopy or electronically) shall be forbidden, unless permitted expressly.
Any non-compliance will constitute an offense against the copyright law dated 09 September 1965, the law against unfair compe tition and the Civil Code and may result in claims for damages. All ri ghts relating to patent, utility model or design registration reserved.

1.5 Storage

The documentati on form an integral part of the frequency inverter. It must be stored such that it is accessible to operating staff at all times. If the frequency inverter is sold o n to other users, then this user manual must also be handed over.
12/13
Agile
VABus/TCP 7

2 General safety instructions and information on use

The chapter "Ge neral safet y instructions and informat ion on use" co ntains gener al safety inst ructions for the Operator and the Operating Staff. At the beginning of certain main chapters, some safety in­structions are included whi ch appl y to all w ork de scrib ed in t he rele vant c hapter. Special wor k-specific safety instructions are provided before each safety-relevant work ste p.

2.1 Terminology

According to the documentation, different activities must be performed by certain persons with certa in qualifications.
The groups of persons with the required qualification are defined as follows:
Operator
This is the entre preneur/company w ho/which operate s the frequency inve rter and uses it a s per the specifications or has it operated by qualified and instructed staff.
Operating staff
The term Operating Staff covers persons instructed by the Operator of the frequency inverter and assigned the task of operating the frequency inverter.
Skilled Personnel
The term Skilled Personnel covers staff that are assigned specia l tasks by the Operator of the fre­quency inverter, e .g. install ation, maint enance and s ervice/re pair and tro ubleshoo ting. Based o n their qualification and/or know-how, Skilled Personnel must be capable of identifying defects and as­sessing functions.
Qualified electrician
The term Qualified Electrician covers qualified and tra ined staff that have special technical know-how and experience with electrical installations . In addition , Qualified Electri cians must be familiar with the applicable standards and regulations, they must be able to assess the assigned tasks properly and identify and eliminate potential hazards.
Instructed person
The term Instru cted Person covers sta ff that are instructed and trained about/in the assig ned tasks and the potential hazards that might result from inappropria te behavior. In addition, instructed per­sons must have been instructed in the required protection provisions, protective m easures, the appli­cable directives, accident prevention regulations as well as the operating conditions and have their qualification verified.
Expert
The term Expert covers qualified and trained staff that have special te chnical know-how and experi­ence relating to the frequency inverter. Experts must be familiar with the applicable government work safety directives, accident prevention regulations, gui delines and genera lly accepted rules of tech nolo­gy in order to assess the operationally safe condition of the frequency inverter.
8
Agile
VABus/TCP 12/13

2.2 Designated use

The frequency inverter is designed according to the state of the art and recognized safety regula­tions.
The frequency inverters are electrical drive comp onents intended for installa tion in industrial plants or machines. Commissioning and start of operation is not allowed until it has be en verified that the ma­chine meets the requirements of the EC Machinery Directive 2006/42/EC and DIN EN 60204-1.
The frequency inverters meet the requirements of the low voltage directive 2006/95/EEC and DIN EN 61800-5-1. CE-labeling is based on these standards. Responsibility for comp liance with the EMC Directive 2004/108/EC lies with the operator. Frequency inverters are only available at specialized dealers and are exclusively intended for commercial use as per EN 61000-3-2.
No capacitive loads may be connected to the frequency inverter. The technical dat a, connection sp ecifications a nd informati on on ambient co nditions are ind icated on
the rating plate and in the documentation and must be complied with at all times.

2.3 Misuse

Any use other than that described in "Designated use" shall not be permissible and shall be consid­ered as misuse.
For, example, the machine/plant must not be operated
by uninstructed staff,
while it is not in perfect condition,
without protection enclosur e (e.g. covers),
without safety equipment or with safety equipment deactivated.
The manufacturer shall not be he ld liab le for any d am age r esulting fr om suc h misuse . The p lant ope r­ator shall bear the sole risk.

2.3.1 Explosion protection

The frequency inverter is an IP 20 protection class de vice. For this reason, use of the device in explo­sive atmospheres is not permitted.
12/13
Agile
VABus/TCP 9

2.4 Residual risks

Residual risks are special hazards involved in handli ng of the freque ncy in verter w hich can not be elim­inated despite the safety-compliant design of the device. R emaining hazards are not obvious and can be a source of possible injury or health damage.
Typical residual hazards include: Electrical hazard Danger of contact with energized components due to a defect, opened covers or enclosures or im-
proper working on electrical equipment. Danger of contact wi th energized components in fre quency inverter if no external d isconnection de-
vice was installed by the operator.
Electrostatic charging
Touching electronic components bears the risk of electrostatic discharg es.
Thermal hazards
Risk of accidents by hot machine/plant surfaces, e.g. heat sink, transformer, fuse or sine filter.
Charged capacitors in DC link
The DC link may have dangerous voltage levels even up to three minutes after shutdown.
Danger of equipment falling down/over, e.g. during transport
Center of gravity is not the middle of the electric cabinet modules.

2.5 Safety and warning signs at frequency inverter

Comply with all safety instructions and danger informa tion provided on the frequency inverter.
Safety information and warnings on the frequency inverter must not be removed.
10
Agile
VABus/TCP 12/13
risk of death or serious injury if not
risk of death or serious in jury if
risk of minor or moderate physical
Symbol
Meaning
Symbol
Meaning
Symbol
Meaning
Symbol
Meaning

2.6 Warning information and symbols used in the user manual

2.6.1 Hazard classes

The following hazard identifications and symbols are used to mark particularly important information:
DANGER
Identification of immediate threat holding a high avoided.
WARNING
Identification of immediate threat holding a medium not avoided.
CAUTION
Identification of immediate threat holding a low injury if not avoided.
NOTE
Identification of a threat holding a risk of material damage if not avoided.

2.6.2 Hazard symbols

General hazard
Electrical voltage

2.6.3 Prohibition signs

No switching; it is forbidden to switch the ma­chine/plant, assembly on
Suspended load
Hot surfaces

2.6.4 Personal safety equipment

Wear body protection
12/13
Agile
VABus/TCP 11

2.6.5 Recycling

Symbol
Meaning
to avoid waste, collect all materia ls for
Symbol
Meaning
Symbol
Meaning
Symbol
Meaning
Example
Font style
Use
1234
bold
Representation of parameter numbers
Parameter
italic, Font Times New Roman
Representation of parameter names
P.1234
bold
Representation of parameter numbers without name, e.g. in formulas
Q.1234
bold
Representation of source numbers
Recycling, reuse

2.6.6 Grounding symbol

Ground connection

2.6.7 ESD symbol

ESD: Electrostatic Discharge (can damage com­ponents and assemblies)

2.6.8 Information signs

Tips and informat ion making using the frequency inverter easier.

2.6.9 Font style in documentation

2.7 Directives and guidelines to be adhered to by the operator

The operator must follow the following directives and regulations:
Ensure that the applicable workplace-related accident prevention regulations as well as other appli- cable national regulation are accessible to the staff.
An authorized person must ensure, before using the frequency inverter, that the devi ce is used in compliance with its designated use and that all safety requirements are met.
Additionally, comply with the applicable laws, re gulations and directives of the country in whic h the frequency inverter is used.
Any additional guidelines and directives that ma y be required additionally shall be de fined by the op­erator of the machine/plant considering the operating environment.

2.8 Operator's general plant documentation

In addit ion to the user manual, the operator should issue separate internal operating instructions
for the frequency inverter. The user manual of the frequency inverter must be included in the user manual of the whole plant.
12
Agile
VABus/TCP 12/13

2.9 Operator's/operating staff's responsibilities

2.9.1 Selection and qualification of staff

Any work on the frequency inverter may only be carried o ut by qualified technical sta ff. The staff
must not be under the influence of any drugs. Note the minimum age required by law. Define the staff's responsibility in connection with all work on the frequency inverter clearly.
Work on the electri cal components may only be performed by a qualified electrician according to
the applicable rules of electrical engineering.
The operating staff must be trained for the relevant work to be performed.

2.9.2 General work safety

In addition to the user manual of the machine/plant, any applicable legal or other regulations
relating to accident prevention and environmental protection must be complied with. The staff must be instructed accordingly. Such regulations and/or requirements may include, for example, handl ing of hazardous media and materials or provision/use of personal protective e quipment.
In addition to this user manual, issue any additional directives that may be required to meet spe-
cific operating requirements, including supervision and reporting requirements, e.g . dir ectives re­lating to work organization, workflow and employed sta ff.
Unless approved of expressly by the manufacturer, do not modify the frequency inverter in any
way, including addition of attachments or retrofits.
Only use the frequency inverter if the rated connection and setup values specified by the manu-
facturer are met.
Provide appropriate tools as may be required for performing all work on the frequency inverter
properly.

2.10 Organizational measures

2.10.1 General

Train your staff in the handling and use of the frequency inverter and the machine/plant as well
as the risks involved.
Use of any individual parts or components of the frequency inverter in other p arts of the opera-
tor's machine/plant is prohibited.
Optional components for the frequency inverter must be used in accordance with their designated
use and in compliance with the rele vant documentation.

2.10.2 Use in combination with third-party products

Ple ase note that BONFIGLIOLI V ECTRON GmbH will not accept any responsibility for com patibility
with third-party products (e.g. motors, cables or filters).
In order t o enable optimum system compatibility, BONFIGLIOLI VECTRON Gm bH offers compo-
nents facilitating commissioning and providing optimum synchronization of the machine/plant parts in operation.
If you use the frequency inverter in combination with third-party products, you do this at your
own risk.
12/13
Agile
VABus/TCP 13

2.10.3 Transport and S torage

The frequency i nverters m ust be transpo rted and stor ed in an app ropriate wa y. During tr ansport
and storage the devices must remain in their original packaging.
The unit s ma y o nly be sto r ed in dr y r oom s whi ch a re prot ect ed ag ai nst d us t a nd moi stur e a nd ar e
exposed to small temperature deviations only. The requirements of DIN EN 60721-3-1 for storage, DIN EN 60721-3-2 for transport and labeling on the packaging must be met.
The duration of storage without connection to the permissible nominal voltage may not exceed
one year.

2.10.4 Handling and installation

Do not comm i ssion any damaged or de s troyed components. Prevent any mechanical overloading of t he frequency inver ter. Do not bend any components a nd
never change the isolation distances.
Do not touch any electronic construction elements and cont acts. The frequency inverter i s
equipped with components which are sensitive to electrostatic energy and can be damaged if handled improperly. Any use of damaged or destroyed components will endanger the ma­chine/plant safety and shall be considered as a non-compliance with the applicable standards.
Only install the frequency inverter in a suitable operating environment. The frequency inverter is
exclusively designed for installat ion in industrial environments.
If seals are removed from the case, this can result in the warranty becoming null and void.

2.10.5 Electrical connections

The five safety rules must be complied with. Never touch live terminals. The DC link may have dangerous voltage levels even up to three
minutes after shutdown.
When performing any work on/with the frequency inverter, alwa ys comply with the applicable
national and international regulations/laws on work on electrical equipment/plants of the country in which the frequency inverter is used.
The cables connected to the frequency inverters may not be subjected to high-voltage insulation
tests unless appropriate circuitry measures are taken before.
O nly connect the frequency inverter to suitable supply mains.
2.10.5.1 The five safety rules
When working on/in electrical plants, alwa ys follow the five safety rules:
1. Isolate
2. Take appropriate measures to prevent re-connection
3. Check isolation
4. Earth and short-circuit
5. Cover or shield neighboring live parts.

2.10.6 Safe operation

During operation of the frequency inverter, always comply with the applicable national and inter-
national regulations/laws on work on electrical equipment/plants.
Before commissioning and the start of the operation, make sure to fix all covers and check the
terminals. Check the additional monitoring and protective devices according to the applicable na­tional and international safety directives.
During operation, never open the machine/plant Do not connect/disconnect any components/equipment during operation. The machine/plant holds high voltage levels during operation, is equipped with rotating parts
(fan) and has hot surfaces. Any unauthorized removal of covers, improper use, wrong installation or operation may result in serious injuries or material damage.
14
Agile
VABus/TCP 12/13
Some components, e.g. the heat sink or brake resistor, may be hot even some time after the ma-
chine/plant was shut down. Don't touch any surfaces directly after shutdown. Wear safety gloves where necessary.
The frequency inverter may hold dangerous voltage lev els until the capacitor in the DC link is dis-
charged. Wait for at least 3 minutes after shutdown before starting electrical or mechanical work on the frequency inverter. Even after this waiting time, make sure that the equipment is deener­gized in accordance with the safety rules before starting the work.
In order to avoid accidents or damage, only qualified staff and electricians may carr y out the work
such as installation, commissioning or setup.
In the case of a defect of terminals and/or cables, immediately disconnect the frequency inverter
from mains supply.
Persons not familiar with the operation of frequency inverte rs must not have access to the fre-
quency inverter. Do not bypass nor decommission any protective facilities.
The frequency inverter may be connected to power supply every 60 s. This must be considered
when operating a mains contactor in jog operation mode. For commissioning or after an emer­gency stop, a non-recurrent, direct restart is permissible.
After a failure and restoration of the power supply, the motor may start unexpectedly if the Auto-
Start function is activated. If staff are endangered, a restart of the motor must be prevented by means of external circuitry.
Before commissioning and the start of the operation, make sure to fix all covers and check the
terminals. Check the additional monitoring and protective devices according to EN 602 04 and ap­plicable safety directives (e.g. Working Machines Act or Accident Prevention Directives).

2.10.7 Maintenance and service/troubleshooting

Visually inspect the frequency inverter when carrying out the required maintenance work and
inspections at the machine/plant.
Perform the maintenance work and inspections prescribed for the machine carefully, including the
specifications on parts/equipment replacement.
Work on the electrical components may only be performed by a qualified electrician according to
the applicable rules of electrical engineering. Only use original spare parts.
Unauthorized opening and improper interventions in th e machine/plant can lead to personal injury
or material damage. Repairs on the frequency inverters may only be carried out by the manufac­turer or persons authorized by the manufacturer. Check protective equipment regularly.
Before performing any maintenance work, the machine/plant must be disconnected from mains
supply and secured against restarting. The five safety rules must be complied with.
12/13
Agile
VABus/TCP 15

2.10.8 Final decommissioning

Electric scrap, electronic components, lubricants and other utility materials must be
mentally compatible disposal of the frequency inverter. For more details, contact the
Unless separate return or disposal agreements were made, recycle the disassembled frequency in­verter components:
Scrap metal materials
Recycle plastic elements
Sort and dispose of other component materials
treated as special waste and may only be disposed of by specialized companies.
Always comply with any applicable national disp osal regulations as regards environ­competent local authorities.
16
Agile
VABus/TCP 12/13
This manual only describes the CM-VABus/TCP and CM-VABus/TCP-2P communication
tions provided by this document.
In some chapters of these instructions, setting and display options via the PC software
for communication with the frequency inverter.
The module enables using VABus/TCP via a PLC and VPlus via the VABus/TCP protocol
parameters of the

3 Introduction

The present document describes the VABus/TCP protocol for the CM-VABus/TCP and CM-VABus/TCP-2P (switch function integrated) communication modules. After connecting VABus/TCP to the PLC, you can use an a dditional logic connect ion from VA Bus/TCP to t he VPlus softwa re running on a terminal connected via an Ethernet network.
For VABus/TCP co nnection, the frequency inverter must be equipped with the CM-VABus/TCP or CM­VABus/TCP-2P communicatio n module.
The CM-VABus/TCP and CM-VABus/TCP-2P communication modules are separate components and must be attached to the frequency inverter. This is described in chapter 6.1 “Assembly”.
VABus/TCP communication (as described in this manual) requires software version 6.1.0 or higher.
modules. This manual is not to be understood as p r oviding general/basic information on Ethernet interfaces or frequency inverters. General/basic knowledge of the m ethods and function of VABus/TCP interfaces and VABus/TCP protocol are a prerequisite for understanding and implementing the instruc-
VPlus are described as an alternative to the control unit. In this case, VPlus can use
CM-VABus/TCP or CM-VABus/TCP-2P module or
the serial interface
at the same time.
WARNING
With CM-VABus/TCP or CM-VABus/TCP-2P, controll ers ca n acces s all frequency inverter.
Changing parame ters the function of whic h is unkn own can re sult in ma lfuncti on of th e frequency inverter and dangerous situations in the plant.
Ethernet properties:
10/100 MB (10Base-T/100Base-T)
Automatic identification (Autonegotiation)
MDI/MDIX
12/13
Agile
VABus/TCP 17
Ports:
The module supports two logic TCP/IP ports for VABus/TCP communication. Each port can be used for establishing one logic connection:
Port #17220: Connection for PLC communication
Port VPlus: Connection for VPlus
When a PLC starts communicating with a frequency inverter, it creates a TCP/IP source port to send data to target port #17220 of the frequency inverter. The response of the frequency inverter is sent by 17220 to this port of the PLC.
VPlus is the software for co nfiguration and ma intenance of BO NFIGLIOLI VEC TRON frequency in vert­ers. It can conne ct wit h a f re que nc y i nvert er whil e it is com mu nica ting with a PLC . VP lus ca n est ab lis h connections to any type of industrial Ethernet CM modules.
Module variants:
There are two VABus/TCP variants. CM-VABus/TCP provides a physical inte rface for communication via VABus/TCP. A sta r-type network
topology can be used. An external switch is the star point. CM-VABus/TCP-2P provides two physical interfaces for communi cation via VABus/TCP. The foll owing
network topologies are pos s i ble:
Star-type (like in CM-VABus/TCP)
Line
18
Agile
VABus/TCP 12/13
[1] PLC [2] PC for commissioning or diagnosis (connecte d temporarily or permanently) [3] AGL with CM-VABus/TCP or CM-VABus/TCP-2P (2nd port not connected) [4] AGL with CM-VABus/TCP-2P
12/13
Agile
VABus/TCP 19

3.1 Supported configurations

Wait until the initialization phase is complete before s tarting the communication (RUN
For first commissioning, you should be familiar with the followings steps and the de­scribed functions:
Installation of module
Chapter
6.1
Selection of device control Local/Remote 412
Chapter
11
Commissioning of device functions via PLC
o Fault Reaction
Chapter
7.5
Fault reset
Chapter
8.4 • Setting reference values:
o Reference Frequency
Chapter
11.3.2
Diagnosis:
Chapter
13.1 and 14.1
Agile
frequency inverters support various types of control and reference point input:
Contacts or remote contacts
St ate machine
Contacts or remote contacts Required settings:
Control (start, stop, frequency changeover, etc.) is typically performed through
o digital contacts. o Remote contacts via field bus.
Reference values depend on the selected function. Typical:
o Reference speed/reference frequency:
Analog input. Fixed values from parameters.
o Reference percentage for technology controller or torque control
Analog input. Fixed values from parameters.
See Chapter 11 “Control of frequency inverter”. State machine:
Required settings:
Control (start, stop, change of mode, etc.) is performed via Reference values depend on the selected function. Typical:
o Reference speed/reference frequency:
Analog input. Fixed values from parameters.
o Reference percentage for technology controller or torque control
Analog input. Fixed values from parameters.
Local/Remote 412 = (remote) contacts
Local/Remote 412 = 1 – State machine
Control word
410.

3.2 Initialization time

When the frequency inve rter is turned on, the com m u nica tio n mod ul e m ust be ini t ia lize d in a dd iti on to the frequency inverter. The initialization can take up to 20 seconds.
LED).

4 First commissioning

20
Agile
VABus/TCP 12/13
Interface
See
CAN connection control terminals
Instructions on Systembus or CANopen®. CM-CAN
Communication interface X21
Instructions on VABus or Modbus.
CM-232
Instructions on VABus or Modbus.
CM-485
Instructions on VABus or Modbus.
CM-PDPV1
Instructions on Profibus DP-V1.
CM-DEV
Instructions on Device Net .
CM-VABus/TCP
Instructions on VABus/TCP.
CM-EtherCAT
Instructions on Et herCAT®.
CM-EtherNet/IP
Instructions on Et herNet/IP.
CM-Modbus/TCP
Instructions on Modbus TCP.
CM-PROFINET
Instructions on PROFINET.
Optional communi­cation module (CM)
Frequency inverter terminals X12.5 and X12.6
CANopen®
and (at the same time)
Systembus
Systembus
and (at the same time)
CANopen®
Via an optional USB adapter, you can connect an U SB interface of a PC to the X21 communication interface. This enables configuration and monitoring using the PC software VPlus.
X21 (RJ45)
VPlus
USB
RJ45
Adapter

5 Communication options

Combinations of Systembus and CANopen
®
communication at the two interfaces:

5.1 Control software VPlus:

12/13
Agile
VABus/TCP 21

6 Assembly/disassembly of communication module

The CM-VABus/TCP and CM-VABus/TCP-2P communication modules are pre-
spring is supplied
for PE-connection (shield).
Danger of destruction of frequency inverter and/or communication module
Before installation of the communication module, the frequency inverter must
permissible while the
nents may be damaged.
Work steps:
1
2
3

6.1 Assembly

assembled in a case and are ready for insta llation. In addition, a PE -
CAUTION
be disconnected from power suppl y. Installation is not
Dis connect the frequency inverter from mains voltage and protect it aga inst being
Remove the cover of the module slot.
Fix the PE-spring (1). Use the screw provided at the frequency inverter.
unit is energized.
Do not touch the PCB visible on the back of the module, otherwise compo-
energized unintentionally.
Insert the communication module.
Fix the communication module (2) at the frequency inverter using the scr ew (3).
Break out the pre-punched cut-out from the cover.
Fix the cover again.
22
Agile
VABus/TCP 12/13

6.2 Disassembly

Dis connect the frequency inverter from power supply and protect it against being energized unintentionally.
Remove the cover of the module slot.
Loos en the screw (3) at the communication module.
Using a small screwdriver, unlock the hooks (4) (first right then left).
P ull communication module out of slot.
Unscrew PE-spring.
Fix the cover on the fr eq ue ncy i n ver te r.
12/13
Agile
VABus/TCP 23

7 VABus/TCP interface

This document does not provide basic information about Ethernet interfaces. Basic
required. This document describes the special properties of
parameters of the frequency
The frequency inverter can be controlled by a PLC or another master device via an Ethernet interface using the VABus/TCP protocol.
When a VABus/TCP or VABus/TCP-2P communication module is used, you can also access the fre­quency inverter using the V Plus software via Ethernet. VP lus can be used in parallel with a P LC with VABus/TCP communication.
knowledge of Ethernet is the VABus/TCP protocol.
In some sections, setting and display options via the PC software VPlus are described as an alternative to the control unit. In this case, VPlus communicate s with the frequency inverter via a serial interface or a direct Ethernet connection.
WARNING
With VABus/TCP com m uni c at ion, co nt rol ler s can a c cess all inverter.
Changing parame ters the function of whic h is unk nown can result in malfu nction of the frequency inverter and dangerous situations in the plant.
24
Agile
VABus/TCP 12/13
made in the EEPROM, as this only allows a limited number of write cycles (approx. 1
ill
CAUTION
When values are to be wri tten cyclically at a high repetition rate, no entries sh all be million cycles). If the number of permissible write cy cles is exceeded, the EEPROM w
be damaged. See chapter 9.1 “Handling of datasets / cyclic writing of parameters”.

7.1 Communication m odu les

CM-VABus/TCP
The CM-VABus/TCP communicati on module features an active RJ45 port.
CM-VABus/TCP-2P
The CM-VABus/TCP-2P co mmunication module featur es two active RJ45 p orts with integrated swit ch­ing function. This enables ea sy linking (daisy chain) of frequency in verters which are connected to a PLC.

7.1.1 Installation instructions

The VABus/TCP module is connected to the PLC or other devices using standard CAT cables and RJ45 connectors:
Ethernet standard: IEEE 802.3, 100Base-TX (fast Ethernet) Cable type: S/FTP (cable with braided shield, (ISO/IEC 11801 or EN 5 0173, CAT5e
Straight Through of Cross Over)
12/13
Agile
VABus/TCP 25

7.2 Setup

Parameters
Settings
Parameters
Settings
No.
Description
Min.
Max.
Factory setting
1432
IP address
0.0.0.0
255.255.255.255
172.22.1.25
1433
Netmask
0.0.0.0
255.255.255.255
255.255.255.0
DHCP Option 1436
Function
Module must be configured manually, no DHCP server is used. (Factory setting).
1 -
Enabled
The settings are made by a DHCP server.
By default, the parameters of the CM-VABus/TCP and CM-VABus/TCP-2P communication modules are set up as follows:
No. Description Factory setting
388 Bus Error Behaviour 1 1432 IP-Address 172.22.1.25 1433 Netmask 255.255.255.0 1434 Gateway 0.0.0.0 1435 DNS Server 0.0.0.0 1436 DHCP Option 0 1437 IP Command ­1440 Email Function 0 1441 Email Text (Body) -
The parameter settings must be adapted to the actual application.

7.3 TCP/IP address & subnet

For proper identification, each frequency i nvert er is assigned a TCP/IP address which must be unique in the system.

7.3.1 Network without DHCP server:

The address is set via parameter IP-Address 1432. In addition, the subnet mask-Netmask 1433 must be entered properly for the local network.

7.3.2 Network with DHCP server:

When a DHCP server i s used, ma nual networ k configur ation is not r equired. Se t DHCP Opti on 1436 to “1-Enabled” if you wish to use the DHCP function.
0 - Disabled
26
Agile
VABus/TCP 12/13

7.4 TCP/IP configurati on

In order to esta blish co nne ction wi th a freq uency i nve rter fe aturing a C M-VABus/TCP mod ule, you will have to configure IP settings for the CM-VABus/TCP module.
TCP/IP configuration can be perfor med in different ways.
TCP/IP configuration program, see Chapter 7.4.1 “TCP configurations tool”.
Parameter settings with VPlus via service port of frequency inverter (KP232), see Chapter 7.4.2.1
“Basic IP settings”.
Control panel.

7.4.1 TCP configurations tool

There are different ways to start the “TCP configuration tool”:
In the “Inverter Manger” window click on the “Start TCP configuratio n tool”.
Double-click on t he desktop ico n “Vectron Net work Configuration” (stand-alone application).
Once the application has started, a window will appear where you can select the Ethernet adapter via which the frequency inverter is connected:
Select the Ethernet adapter and click on “Ok”.
Once the Ethernet a dapt er has been selected, the configuration program is rea dy to search for a vaila­ble frequency inverters.
With the “Timeout ” setting, you define how l ong the TCP configuration t ool will wait for responses from the frequency inverter.
12/13
Agile
VABus/TCP 27
In the “Timeout” field, enter the required time and click on “Search”. The search is started. Upon completion of t he search a ll frequency inver ters found w ill be listed in the
left area of the window.
Click on the frequency inverter to be configured.
28
Agile
VABus/TCP 12/13
Network adapter:
Name of selected network adapter.
IP address:
IP address of network adapter.
Device name:
Device name from frequency inverter parameter User Device type:
Type of frequency inverter.
CM type:
Type of CM module, i.e.: CM – VABus/TCP.
Module status:
Current status of CM module, e.g. “Connected to PLC”.
MAC address:
MAC address of CM module.
IP address:
Current IP address of device.
Subnet mask:
Current subnet mask.
Standard gateway:
Address of standard gateway.
DNS Server:
Address of current DNS server.
Host Name:
Name of host.
DHCP activated:
Use of DHCP (yes/no).
The right part of the window shows information on the device and input fields for various settings.
Information about network adapter:
Device information:
name 29.
Device settings
Enter the device settings required for your application. In order to apply the settings to the de­vice, click on “Write IP settings”.
12/13
Agile
VABus/TCP 29
NOTE
Before clicking on “Write IP set tings”, m ake s ure tha t you are conne cted with the rig ht
frequency inverte r. To c hec k thi s, clic k on the “Wink” butt on. The con ne cte d fre q u ency
SMTP server:
smtp.provider.com
“From” address:
inverter.drive1@company.com
User name:
drive1@company.com
Password:
password
Re-enter password
password
“To” address
service.drives@company.com
NOTE
o
For documentation, all settings can b e saved in a file (type = *.eop).
inverter will flash for 10 seconds.
At the frequency i nverter , you can a cti vate a functio n which w ill se nd an e-ma il in case of an erro r. In addition, a short text can be entered and saved as the e-mail text. The required settings can only be made via VPlus. VPlus will access the freque ncy invert er via a local se rvice port ( KP232) or an Et her­net connection.
To configure the e-mail function, please refer to Chapte r 7.4.2.2 “Email”. To send an e-mail message, the frequency inverter needs various information. It must have its own e-
mail address from where the e-mail message is sent. For e-mail transmission, identification by the SMTP server (user name and password) is required. The recipient of the e-mail message must be known.
In addition, the local network must be connected to the Internet, i.e. Gateway and DNS server must be entered correctly. If you have any questions or problems, please contact your local system admin­istrator.
SMTP settings (examples):
SMTP settings saved before can be viewed by clicking on the “Read SMTP settings”. T he password will not be displayed.
SMTP settings are applied to t he module by clicking on the “Wr ite SMTP settings”. Whe n the SMTP settings are written, you will be prompte d to enter a password. The two input fie lds “Password” and “Re-enter passwo rd” must conta in the same char acter seque nce. If no entr y is made or the contents of the two input fields are different, an error message will be displayed.
All device settings are saved in the module and in the non-permanent memory of the frequency inverter. Switching of modules from one frequency inverter to another does not have an effect on the IP settings of the frequency inverter. A PLC will remain connected with the right frequency inverter after switching of the module.
SMTP settings are saved in the module only. Switching of modules from one frequency inverter to another will result in malfunction:
o No e-mail messages will be sent in case of an error. o Wrong recipient.
Wrong e-mail text.
30
Agile
VABus/TCP 12/13
MAC-ID:
unambiguous MAC-ID
Sno:
Serial number
HW:
Hardware version
SW:
Software version
Parameters

7.4.2 Parameter settings wi t h VPlu s

7.4.2.1 Basic IP settings
IP settings can be made via the interface X21 and the USB/Com Port adapter. Various parameters are available for module information and IP settings.
Parameter
Module Info 1431 shows basic module data:
For IP setting, five parameters are a va ilable.
No. Description 1432 1433 1434 1435 1436
IP address Netmask Gateway DNS Server DHCP Option
They define the IP settings a nd/or use of DHCP . When the DHCP option is activated, t he IP settings will be made by the DHCP server when the module is started.
Each setting comprises four values. Please c ontact your IT administrator for permissible values . The four values of the parameters are assigned on the display to four datasets (“Data Set 1” to “Data Set 4”). However, they do not depend on changes of the se data sets directly. The dataset s are only pro­vided for clear representation of the values.
To make IP settings, click on the first entry (e.g. Parameter 1432
IP-Address “Data Set 1”).
Enter the required value and go to the next input field by pressing the “TAB” button.
12/13
Agile
VABus/TCP 31
The new settings will be saved in a buffer memory, but not transmitted to the module.
On the network side, they will not be active.
NOTE
Before applying the new IP settings to the module, make sure that the “R/W” button is
The module will reject non-perm issible IP settings and will restore t he last permissible
will be
Parameters
No.
Description
1440
Email Function
1441
Email Text (Body)
Reference:
Frequency inverter type, frequency inverter name (from parameter 29 User
E-mail text:
Optional text (max. 40 characters), defined in parameter 1441 Email Text
In the case of incorrect entries, the values can be overwritten. Old values can be re­stored via parameter 1437
IP-Command = “1 – Reload IP-Settings”.
The “R/W” activates the “Upd ate all parameters in curre nt window regularly” function:
activated.
Apply the new IP settings to the module via parameter 1437
IP-Command = “0 – Apply”.
settings automatically. After execution of the “Apply” command, all IP settings reset and the new settings will be overwritte n by the old settings.
7.4.2.2 Email
When an error occur s in the frequen cy inverter, an e-mail message can be sent automatically to re­port the incident to the Service department, for example. To activate the e-mail function and define the e-mail text, two parameters are used:
The contents of t he e-mail message is pre-defined. The reference heading is given and cannot be edited.
name), IP address, error number
(Body).
Example:
Reference: AGL Main Drive machine no. 5, 172.22.5.145, F0400 Please contact Mr. Doe, extension 2121.
32
Agile
VABus/TCP 12/13
Bus Error Behaviour 388
Function
1 -
Error
“Fault” status will be activated immediately. Factory setting.
Control command “Disable voltage” a nd switch to “switch on disa­bled” status.
Control command “Quick stop” and switch to “switch on disabled” status.
Control command “Disable operation” and switch to “Error” status once the drive has been shut down.
Control comma nd “Quick stop ” and switch to “Error” status once the drive has been shut down.
= 2…5 are evaluated depending on

7.5 Operating behavior in the case of a communication error

The operating behavior in the case of errors in VABus/TCP comm unicatio n can be pa ramete rized. The required behavior can be set up via
0 - no response Operating point is maintained.
2 - Stop
3 - Quick stop
4 - Shutdown + Error
5 - Quick stop + Erro r
The parameter settings Bus fault behavior 388 parameter Local/Remote 412.
For evaluation of settings 2…5, parameter Local/Remote 412 must be set to value “1 - Control via statemachine”.
Bus Error Behaviour 388.
12/13
Agile
VABus/TCP 33

8 Protocol

The VABus protocol was originally developed for the serial interface (RS232/RS485 ) and adapted to the CM integrated in the data block of the TCP/IP protocol. VABus/TCP and VABus use a similar structure. The handshake procedures and the data representation are different. VA Bus uses HEX VABus/TCP uses binary data. The protocol structure of VABus/TCP aims at fast processing and min mum protocol overhead.
Read/write commands and VABus/TCP data are integrated in the TCP/IP data range.
The VABus and VABus/TCP protocol enable operation as a pure Master/Slave system. A PC, a PLC or any type of computer system is the bus Master.
Two types of requests are used:
Send request (inquiry telegram) for the request for reading parameters in the frequency inverter by the bus Master.
Enquiry request (select telegram) for handing over parameter values or parameter settings to the frequency inverter by the bus Master.
Send/positioning requests and send/positioning responses use defined data structures which are ar­ranged in frames. Ea information for parameter access.
The header byte is divided in 8 control bits, only bits 6 and 7 are used. Bits 0 to 5 are not used a nd must have value “0”. If one or more of these bits has/have value “1”, the error message “syntax error in received telegram” will be returned as the response.
-VABus/TCP module. The VABus/TCP protocol uses the TCP/IP protocol. The VABus data is
-ASCII data, while i-
ch frame comprises a header byte and different numbers of bytes containing
34
Agile
VABus/TCP 12/13
Data Types Used
Data type abb.
string of characters
Parameter values with decimal places are transferred without decimal point. Depending on the number of decimal places, the values are multiplied by 10, 100 or 1000. The number of decimal places for the corresponding parameters is set in the frequency. In this way it is made sure that the sent parameter values are processed correctly.

8.1 Telegram types

8.1.1 Data types

The number of data bytes depends on the type of the corresponding parameter. A maximum of 99 data bytes can be transferred.
Type Number of data types "w" Value Bit number
uInt
Int Integer 04 -32768 ... +37767 16
Long Long 08 -231 ... +231-1 32
String
unsigned
Integer
04 0 … 65535 16
variable, up to 99 - variable
Example: Frequency value with data type long:
Value to be transferred = 100.25. The numerical value transmitted in the telegram is 10025, which corresponds to 0x2729 in HEX format. Since the data type is long, 8 data bytes are transferred ("wwwwwwww").
00002729
Example: Current value with data type Int:
The value to be transmitted is 10.3 A. The numerical value transmitted in the telegram is 103, which corresponds to 0x67 in HEX format. Since the data type is int, 4 data bytes are transferred ("wwww").
0067
12/13
Agile
VABus/TCP 35
Send request PLC  frequency inverter:
Byte
0
1 2 3 4 5
Header
NoB
SYS
DS
P.-No.
7 6 5…0 LSB
MSB
R/W 0 0 4 nn
nn
nnnn
Header:
Bit 7 R/W
0 = Send request
NoB:
Byte number
Number of relevant bytes ([Byte 2] – [Byte 5])
NoB will always be “4” for send requests.
SYS:
Addresses frequency inverters which are connected to a TCP/IP module via CAN System Bus.
SYS = 0 for direct addressing of frequency inverter in Ethernet connection (SYS = 0…63)
DS:
Data set number of parameter (0, 1 … 4)
P. No.:
Parameter number (0 … 1599)
Send response frequency inverter  PLC:
Byte
0
1 2 3 4 5 6 7 8 9 … n
Header
NoB
SYS
DS
P.-No.
data
7 6 5…0 LSB
MSB
uint/int data
R/W E 0
nn
nn
nn
nnnn
LSB
MSB
long data
LSB
MSB
string data
first
character
last
character
Header:
Bit 7 R/W
0 = Send response
Bit 6 E
0 = no error 1 = error
if (E == 1)
NoB:
Byte number
Number of relevant bytes
SYS:
returns value SYS from the reques t frame
DS:
returns dataset number from the request frame
P. No.:
returns parameter number from the request frame
data:
requested parameter value, byte number depending on data type

8.1.2 Send Request / Enquiry Telegram

byte 6+7 contains error code ( NoB = 6)
If no response from the frequency inverter is received within a given response time (see chapter 8.3, "Timeout control"), or if the frequency inverter returns incorrect data, the inquiry telegram is repeated three times (maximum of three transmissions possible).
NAK signals an error. An error may have different causes. Errors ma y be caused by incorrect data or an incorrect string.
36
Agile
VABus/TCP 12/13
Positioning request PLC  frequency inverter:
Byte
0
1 2 3 4 5 6 7 8 9 … n
Header
NoB
SYS
DS
P.-No.
data
7 6 5…0 LSB
MSB
uint/int data
R/W 0 0
nn
nn
nn
nnnn
LSB
MSB
long data
LSB
MSB
string data
first
character
last
character
Header:
Bit 7 R/W
1 = Setting request
NoB:
Byte number
Number of relevant bytes
([Byte 2] … [Byte 5] + Number of data bytes)
SYS:
Addresses frequency inverters which are connected to a TCP/IP module via CAN System Bus.
SYS = 0 for direct addressing of frequency inverter in Ethernet connection
DS:
Data set number of parameter (0,1 …, 4, 5, 6 … 9)
P. No.:
Parameter number (0 … 1599)
data:
parameter value to be written, byte number depending on data type
Setting response frequency inverter  PLC:
Byte
0
1 2 3 4 5 6 7 8 9 … n
Header
NoB
SYS
DS
P.-No.
data
7 6 5…0 LSB
MSB
uint/int data
R/W E 0
nn
nn
nn
nnnn
LSB
MSB
long data
LSB
MSB
string data
first
last
Header:
Bit 7 R/W
1 = Setting response
Bit 6 E
0 = no error 1 = error
if (E == 1)
NoB:
Byte number
Number of relevant bytes
([Byte 2] … [Byte 5] + number of data bytes)
SYS:
returns value SYS from the reques t frame
DS:
returns dataset number from the request frame
P. No.:
returns parameter number from the request frame
data:
returns written parameter value, byte number depending on data type

8.1.3 Setting Request / Select Telegram

Via the select telegram, the data are sent to the frequency inverter.
character
character
byte 6+7 contains error code ( NoB = 6)
12/13
Agile
VABus/TCP 37
The System Bus Node-ID 900 is required for addressing networked inverters. If there is no System Bus, or if the System Bus master is addressed, the SYS character is always filled with the zero character (
Node-ID
Node-ID
900
Function
SYS character
If the Node-ID 900 is not zero, the SYS character is determined as follows:
For example,
Node-ID
900 of 7 will result in character 0x47 = “G”. Refer to System Bus description.
The procedure shown in the illustration will work in the following Field B use s:
Instead of the PLC, you can use a standard PC with an appropriate interface.

8.1.4 System bus Node-ID

-1 0
1 ... 63
0x30). The
No System Bus at inverter. “-1” = 0xFFFF The inverter is the System Bus master. “0” = 0x30 The inverter is the System Bus slave with the
specified ID.
900 has values ranging from 0 to 63.
SYS character = (char)(SysNode-ID Nr + 0x40)
0x41 .. 0x7F
VABus VABus/TCP
38
Agile
VABus/TCP 12/13
The addresses in a System Bus branch m ust be assigned unambiguously. Since several System Bus branches can opera ted independently due to the different Ethernet clients, identical System Bus ad­dresses are possible in the network. The disti nction is made based on the dif ferent Ethernet address­es.
In the case of VABus, the network address is a serial address ranging from 1 to 127. In the case of VABus/TCP , the network address is an IP address in t he format aaa.bbb.ccc.ddd, with
each block of n umbers ranging from 0 to 255.
12/13
Agile
VABus/TCP 39

8.2 Telegram check

The frequency inverter and the bus Master check the telegrams for correctness. Depending on the syntax, address and text part (content, checksum).
In case the telegram contains errors, the frequency inverter either returns NAK or it does not re­spond at all. The possible causes are listed below:
no response
wrong telegram structure
wrong control character
wrong address
telegram addressed to address 32 (Broadcast); in this case, the frequency inverter does not reply.
If an error occurs during parameter access, the freq uency inverter will return an error message (Bit
VABus SST-Error-Register 11
type of telegram, the corresponding reaction takes place. The telegrams are checked for correct
E = “1” in read/write response). Bytes 6 and 7 contain the error code.
Error no. Meaning
0 no error 1 Non-permissible parameter value. 2 Non-permissible dataset 3 parameter not readable (write-only) 4 parameter not writable (read-only) 5 EEPROM read error 6 EEPROM write error 7 EEPROM checksum error 8 Parameter cannot be written while drive is running
9 Values of data sets are different 10 not available 11 unknown parame ter 12 not available 13 Syntax error in received telegram 14 data type of parameter does not correspond to the number of bytes in the telegram 15 unknown error 20 selected System Bus node not available 30 Syntax error in received telegram
40
Agile
VABus/TCP 12/13
Bus Error Behaviour 388
Function
1 -
Error
“Fault” status will be activated immediately. Factory setting.
Control command “Disable voltage” and switch to “switch on disa­bled” status.
Control command “Quick stop” and switch to “switch on disabled” status.
Control command “Disable operation” and switch to “Error” status once the drive has been shut down.
Control comma nd “Quick stop ” and switch to “Error” status once the drive has been shut down.
The parameter settings Bus Error Behaviour 388 = 2…5 are evaluated depending on parameter
For evaluation of settings 2…5, parameter
-
Control via statemachine”.
Some errors will occur again after an error reset. In such cases, it may be necessary to

8.3 Timeout control

After first data exchange via the PLC Port #17220, a timeout check will be activated. If no data is exchanged for more than 10 seconds, the frequency will respond in the way set in parameter
Error Behaviour
PLC”.
0 - no response Operating point is maintained.
2 - Stop
3 - Quick stop
4 - Shutdown + Error
5 - Quick stop + Erro r
388. and switch to fault status with error message F2714 “C ommunication Loss to
Bus
Local/Remote 412.
Local/Remote 412 must be set to value “1

8.4 Resetting errors

Depending on the settings and operating state of the device, errors can be reset in different ways:
In controller via Parameter Set bit 7
By pressing the stop button of the control panel: Resetting by pressing the STOP button is only possib le if Parameter control via the control panel.
Via parameter A reset via a digital signal can only be carried o ut when parameter or when an input with the ad dition (hardware) is selected in the case of physical inputs.
Control word 410 = 0x8000.
Error acknowledgment 103 which is assigned a logic signal or a digital input
take certain measures (e.g. moving from a limit switch in the non-disabled direction).
Local/Remote 412 = 1 - Statemachine:
Local/Remote 412 permits
Local/Remote 412 permits this
12/13
Agile
VABus/TCP 41
NOTE
sively without a writing cycle on the EEPROM. Such dat a will be lost in the case of a
Writing on virtual dataset in RAM
Parameters
EEPROM
RAM
Dataset 0
0
5
Dataset 1
1
6
Dataset 2
2
7
Dataset 3
3
8
Dataset 4
4
9

9 Parameter access

9.1 Handling of datasets / cyclic writing of parameters

The parameter values are accessed based on the parameter number and the required dataset. There are parameters the values of which are present once (dataset 0) as well as parameters the values of which are present four times (dataset 1...4). These are used for dataset switching.
If parameters which are present four times in the datasets are set to Dataset = 0, the four datasets are set to the same transmitted value. A read access with data set = 0 to such parameters is only successful if all four data se ts are set to the same value. I f this is not the case, an error w ill be sig­naled.
The values are entered automatically in the EEPROM of the controller. When values are
to be written cyclically, no entries shall be m ade in the EEPROM, as this only allow s a limited number of write cycles (approx. 1 milli on cycles). When t he number of pe rmissi­ble write cycles is exceeded, the EEPROM will be destroyed.
In order to avoid this, data which is written cyclicall y can be entered in the RAM exclu­power failure and have to be written again after Power off/on.
This mechanism is started when the target dataset is increa sed by five when spe cifying the dataset.
42
Agile
VABus/TCP 12/13
Function
Parameters
Index range
Indexing pa­rameters
Write
and read
Write
PLC function
1343 FT-Instruction
1352 FT-Commentary
Multiplexer
1252 Mux Input
01); 1…16
171); 18…33
1250 Write 1251 Read
CANopen® Multiplexer
1422 CANopen Mux Input
01); 1…16
171); 18…33
1420 Write 1421 Read
1) When the indexing parameter = 0, all indexes will be written upon parameter ac­cess in EEPROM. 17 or 33 will write all indexes in RAM.
the RAM and not the EEPROM.
In the RAM, the data is not protected against loss of power. Once power supply is
ing the data set (IND).
Typically, index parameters are wr itten during commissioning.
Writing of Parameter 1344 PL C Inp ut 1 (Type int), in Index 34 in RAM ( Inde x 34 for write access) with parameter value 2380.
Index = 1341 + 0x 2000 = 0x253D, value (int) = 34 = 0x0022
Index = 1344 + 0x2000 = 0x254 0, val ue (int ) = 238 0 = 0x09 4C
If various parameters in an index are to be edited, it will be sufficient to set i ndex access via

9.2 Handling index parameters / cyclic writing

Index parameters are used for various AGL functions. Here, 16 or 32 indexes are used instead of the 4 data sets. For each function, the individual indexes are addressed separately via an index access parameter. Via the indexing parameter, you can select if the data is to be written to EEPROM or RAM.
(Function Ta­ble)
EEPROM
RAM
1344 FT-Input 1 1345 FT-Input 2 1346 FT-Input 3 1347 FT-Input 4 1348 FT-Parameter 1
01); 1…32
331); 34…65
1341 Write 1342 Read
1349 FT-Parameter 2 1350 FT-Target Output 1 1351 FT-Target Output 2
NOTE
The values are entered automatically in the EEPROM of the controller. However, only a limited number of write cycles is permissible for the EE PROM (approx. 1 million cy­cles). When this number is exceeded, the EEPROM will be destroyed.
Values w hich are written cyclically at a high repetition rate should be written to
disrupted, the data must be written again.
This procedure is started when the target data set is increased by five when specify-

9.2.1 Example: Writing of index parameters

12/13
1341 once first.
Agile
VABus/TCP 43

9.2.2 Example: Reading of index parameters

In order to read an index parameter, you will have to set the indexing parameter to the relevant index first, then you can read the parameter.
Reading from parameter PLC input 1 1344 type int), in Index 1 with paramete r value
6.
Index = 1342 + 0x2000 = 0x253E, val ue (int ) = 1 = 0x00 01
Index = 1344 + 0x2000 = 0x254 0, val ue (int ) = 6 = 0x0006
If various parameter of an index are to be read, it will be sufficient to set index access via
1342 once first.
44
Agile
VABus/TCP 12/13
Byte
... 0 1 2 3 4 5
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
> 40
Bytes
7 6 5…0 LSB
MSB 0 0 0 04
00
02
74 01
Byte
... 0 1 2 3 4 5 6 7
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40 7 6 5…0 LSB
MSB
uint/int
LSB MSB
0 0 0
06
00
02
74 01
6E
05
Byte
... 0 1 2 3 4 5
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
> 40
Bytes
7 6 5…0 LSB
MSB 0 0 0 04
00
01
E1 01
Byte
... 0 1 2 3 4 5 6 7 8 9
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40 7 6 5…0 LSB
MSB
long data
LSB MSB
0 0 0
08
00
01
E1 01
E8
03
00
00

10 Example messages VABus/TCP

This chapter describes some examples of telegrams for VABus/TCP.

10.1 Reading parameters

Example 1:
Reading of parameter Request: Master frequency inverter
Response: Frequency inverter  Master
Rated speed 372 (0x0174) in dataset2.
Bytes
The sent hexadecimal value is 0x056E = Decimal 1390. Parameter places. Thus, the rated speed is 1390 min
-1
.
Example 2:
Reading of parameter
Fixed frequency 2 481 (0x01E1) in dataset 1.
Request: Master frequency inverter
Response: Frequency inverter  Master
Bytes
data
Rated speed 372 has no decimal
The sent hexade cimal value is 0x03E8 = De cimal 1000. Parameter decimal places. Th us, the frequency is 10.00 Hz.
12/13
Fixed frequency 2 481 has two
Agile
VABus/TCP 45
Example 3:
Byte
... 0 1 2 3 4 5
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
> 40
Bytes
7 6 5…0 LSB
MSB 0 0 0 04
00
00
0c 00
Byte
... 0 1 2 3 4 5 6 7 8 9
10
11
12
13
14
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40
Bytes
7 6 5…0 LSB
MSB
String data (hexadecimal and string)
0 0 0
0D
00
00
01 E1
36
2E
32
2E
30
20
53
54
4F
6 . 2 . 0 S T O
Byte
... 0 1 2 3 4 5 6 7
TCP/IP
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
uint/int data
LSB MSB
1 0 0
06
00
04
78 01
96
00
Byte
... 0 1 2 3 4 5 6 7
TCP/IP
Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
uint/int data
LSB MSB
1 0 0
06
00
04
78 01
96
00
Reading of parameter
Inverter software version 12 (0x000c) in dataset 0.
Request: Master frequency inverter
Response: Frequency inverter  Master
The sent hexadecimal value is ASCII encoded. In the example, the ASCII string is green. For conver­sion between hexadecimal and ASCII value, refer to the relevant table in the appendix.

10.2 Writing parameters

Example 1:
Writing of parameter
Rated mech. power 376 (0x0178) in dataset 4.
The rated mechanical power is to be set to 1.50 kW. Parameter imal places. Thus the value to be sent is 150 = 0x0 0 96.
Request: Master frequency inverter
Bytes
Response: Frequency inverter  Master
Bytes
The response is the reflected signal of the request message.
Rated mech. Power 376 has two dec-
46
Agile
VABus/TCP 12/13
Byte
... 0 1 2 3 4 5 6 7
TCP/IP
Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
uint/int data
LSB MSB
1 0 0
06
00
04
78 01
00
00
Byte
... 0 1 2 3 4 5 6 7
TCP/IP
Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
uint/int data
LSB MSB
1 1 0
06
00
04
78 01
01
00
Byte
... 0 1 2 3 4 5 6 7 8 9
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
long data
LSB MSB
1 0 0
08
00
09
E2 01
62
11
00
00
Byte
... 0 1 2 3 4 5 6 7 8 9
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
long data
LSB MSB
1 0 0
08
00
09
E2 01
62
11
00
00
Example 2:
Writing of non-permissible value 0 in parameter
Rated mech. power 376 (0x0178) in dataset 2.
Request: Master frequency inverter
Bytes
Error response: Frequency inverter  Master
Bytes
Example 3:
Writing of parameter
Fixed frequency 3 482 (0x01E2) in dataset 9 (= RAM for dataset 4) of frequen-
cy inverter. The fixed frequency is to be set to 44.50 Hz. Parameter
es. Thus the value to be sent is 4450 = 0x00001162. Request: Master frequency inverter
Fixed frequency 3 482 has two decimal plac-
Bytes
Response: Frequency inverter  Master
Bytes
The response is the reflected signal of the request message.
12/13
Agile
VABus/TCP 47
Byte
... 0 1 2 3 4 5 6 7 8 9
TCP/IP Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
long data
LSB MSB
1 0 0
08
00
09
E2 01
40
0D
03
00
Byte
... 0 1 2 3 4 5 6 7
TCP/IP
Header
Header
NoB
SYS
DS
P.-No.
data
> 40
7 6 5…0 LSB
MSB
uint/int data
LSB
MSB
1 1 0
06
00
09
E2 01
01
00
For explanations of error codes, see 8.2 “Telegram check”.
Example 4:
Writing of parameter
Fixed frequency 3 482 (0x01E2) in dataset 9 (= RAM for dataset 4) of frequen-
cy inverter. The frequency is t o be set to 2000.00 Hz (non-permissible value). Parameter
has two decimal places. Thus the value to be sent is 20000 = 0x00030D40. Request: Master frequency inverter
Bytes
Error response: Frequency inverter  Master
Bytes
Fixed frequency 3 482
48
Agile
VABus/TCP 12/13
The frequency inverter can generally be controlled via three operation modes. The op-
412.
Parameters
Settings
No.
Description
Min.
Max.
Factory
setting
412
Local/Remote
0
44
44
For operation with a Field bus, only opera tion mode s 0, 1 and 2 are re levant. The other settings refer to the control option via the control unit.
Operation mode
Function
Control via (Chapter 11.1)
The Start and Stop commands as well as the direction of
Control via (Chapters 11.2)
The frequency inverter is controlled via the control word.
Control via (Chapter 11.1)
The Start and Stop commands as well as the direction of control word.
Parameter Local/Remote 412 is dataset switchable, i.e. you can switch between the
The data set switching can be effected locally via con trol contacts at the digital inputs
Dataset selection 414 is used.
Parameters
Settings
No.
Description
Min.
Max.
Factory set-
ting
414
Data set selection
0 4 0
With Data set selection 414 = 0, data set switching via contact inputs will be active. If
if the frequency inverter is not enabled.
Via parameter Active data set 249, the currently selected data set can be read. Active
dependent of
Data set selection 414

11 Control of frequency inverter

eration modes can be selected via the data set switchable parameter Local/Remote
0 -
contacts
1 -
state machine
rotation are controlled via digital signals.
2 -
remote contacts
rotation are controlled via virtual digital signals of the
different operation modes by selecting another data set.
of the frequency inverter or via the bus. For data set swit ching via the bus, paramet er
Data set selection 414 is set to 1, 2, 3 or 4, the selected data set is a ctivated a nd data
set switching via the contact inputs is deactivated. If Data set selection 414 is set to 5, data set switching via contact inputs will be active
data set 249, indicates the active data set (value 1, 2, 3 or 4). This is in
whether the data set switching was done via contact inputs or
.
12/13
Agile
VABus/TCP 49
11.1 Control via
In operation mode “Control via contacts” or “Control via remote contacts” (Parameter
Local/Remote
n-
puts or via the individual bits of the v irtual digital signals in the control
c-
tion of these input s is described in the frequency inve rter user manual.
Control word (
Local/Remote
412 = 2)
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
0
STOA and STOB
1
IN1D
2
IN2D
3
IN3D
4
IN4D
5
IN5D
6
MFI1D
7
MFI2D
8
-
9
-
10
-
11
-
12
-
13
-
14
-
15
-
The digital inputs set via the control word can be monitored using parameter Digital
I
on at function is used, please ensure that Parameter trol via remote contacts” is set in all data sets used.
contacts/remote contacts
412 = 0 or 2), the frequency inverter is controlled directly via digital i
word. The fun
nputs 250. Digital input S1IND will only be displayed if controller release is switched
STOA and STOB and the control word (Bit 0) was set. If the data set switching
Local/Remote 412 is set to “2 – Con-
50
Agile
VABus/TCP 12/13
Status word
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
0
Ready to switch on
1
Switched on
2
Operation enabled
3
Fault
4
Voltage enabled
5
Quick stop (Low active)
6
Switch on disabled
7
Warning
8
-
9
Remote
10
Target reached
11
Internal limit active
12
-
13
-
14
-
15
Warning 2
If operation mode “Control via remote contacts” is used, controller release must be
Bit 0 of the control
The frequency inverters support an external 24 V power supply for the frequency invert-
between
enabled” of t he sta tus w or d sh o w s the cur re nt m ains p ow er s uppl y
s-
Bit 4 “Power supply – enabled” = 1 signals “Mains voltage on”, drive ready for starting.
turned on at STOA (Terminal X11.3) and STOB (Terminal X13.3) and word must be set in order to be able to start the drive.
er control electronics. Even when mains voltage is disconnected, c ommunication the controller (PLC) and the frequency inverter is still possible.
Bit 4 “Power sup pl y – status:
Bit 4 “Power supply – enabled” = 0 signals “No mains voltage”, starting of dri ve not po sible.
12/13
Agile
VABus/TCP 51

11.1.1 Device state machine

State machine:
4
switched on
0x23
5
operation
enabled
0x37
1
not ready to
switch on
0x00
8
fault 0x08
quitt fault
start drive
stop drive
Status word
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Switched on
1 0 0 0 1
1
Operation enabled
1 1 0 1 1
1
Fault x x 1 x x x
“x” means any value.
Bit 7 “Warning” can dis pla y a de vice -internal warning message at any time. The current warning is evaluated by reading the warning status with parameter
Bit 10 “Target reached” is set when the specified reference value is reached. In the
a-
For "Target reached“, there is a hysteresis (tolerance range) which can be set via the parameter
Bit 11 “Internal limit value active” indicates that an internal limit is active. This ma y be the current limit, the torque limit or the overvoltage control. All fun ctions will result in the reference value being left or not reached.
Bit 15 “Warning 2” sig nals a critical ope rating state w hich will result in a fault sw itch-off of the frequency inverter within a short time. This bit is set if there is a delayed warning relating to the motor temperature, heat sink/inside temperature, Ixt monitoring or mains phase failure.
special case of power failure re gulation, the bit i s also set when t he powe r failure regul tion reaches the frequency 0 Hz (see frequency inverter Operating Instructions).
Max. control deviation 549 see frequency inverter operating instructions).
52
Agile
VABus/TCP 12/13
Warnings 270.
In this operation mode “Control via state machine” (Local/Remote 412 = 1), the fre­quency inverter is addressed via the control word of the state machine.
Transition 4 and 4’ to status “Operation enabled” is only possible if the release (STOA and STOB) and Start Clockwise or Start Anticlockwise are set.
Parameter Control word 410 is applicable to the frequency inverter if parameter Lo-
cal/Remote
Control word
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
0
Switch on
1
Enable voltage
2
Quick stop (Low active)
3
Enable operation
4
No function
5
No function
6
No function
7
Fault reset
8
No function
9
No function
10
No function
11
No function
12
No function
13
No function
14
No function
15
No function
The actual value parameter Status word 411 shows the current operating status.

11.2 Control via state machine

412 is set to “1 – Control via statemachine.
12/13
Agile
VABus/TCP 53
Status word
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
0
Ready to switch on
1
Switched on
2
Operation enabled
3
Fault
4
Voltage enabled
5
Quick stop (Low active)
6
Switch on disabled
7
Warning
8
No function
9
Remote
10
Target reached
11
Internal limit active
12
No function
13
No function
14
No
15
Warning 2
Agile
frequency inverters support an external 24 V power supply for the inverter control
n-
Bit 4 “Voltage enabled” = 1 signals “Mains voltage on”, drive ready for start.
function
electronics. Even when mains voltage is disconnected, communication between the co troller (PLC) and the frequency inverter is still possible.
Bit 4 “Voltage enabled” of the status word s hows the current mains power supply status: Bit 4 Voltage enabled” = 0 signals “No mains voltage”, starting of drive not possible.
54
Agile
VABus/TCP 12/13
State machine:
Control word:
The device control commands are triggered by the following bit patterns in the status word.
Control word
Command
Bit 7
Bit 3
Bit 2
Bit 1
Bit 0
Fault reset
Enable
Quick
(Low
active
Enable
Switch on
Shutdown
X X 1 1 0
2, 6, 8
Switch on
X 0 1 1 1
3
Enable operation
X 1 1 1 1
4
Disable voltage
X X X 0 X
7, 9, 10, 12
Quick stop (Low active)
X X 0 1 X
7, 10, 11
Disable operation
X 0 1 1 1
5
Fault reset
0  1
x x x x 15
“X” means any value.
Transition 3 (command “Switch On” [0x07]) will only be processed if Bit 4 “Voltage ena-

11.2.1 Statemachine diagram

operation
stop
voltage
Transitions
bled” of the Status word is set.
12/13
Agile
VABus/TCP 55
Transition 4’ will only be processed if Bit 4 “Voltage ena b led” of the status word is
Release: = (STOA and STOB) AND (Start clockwise OR Start anticlockwise)
Status word:
The status word indicates the operating status.
Status word
State
Bit 6
Bit 5
Bit 3
Bit 2
Bit 1
Bit 0
Switch on
Quick stop
active)
Fault
Operation
Switched
Ready to
Switch on disabled
1 X 0 0 0
0
Ready to switch on
0 1 0 0 0
1
Switched on
0 1 0 0 1
1
Operation enabled
0 1 0 1 1
1
Quick stop active
0 0 0 1 1
1
Fault reaction active
0 X 1 1 1
1
Fault 0 X 1 0 0 0
“X” means any value.
Bit 7 “Warning” can be set at any time. It rep orts a device-internal wa rning. Th e cause
Warnings
270.
Bit 9 “Remote” is set if the operation mode is set to “Co ntrol via state machine” (Lo-
cal/Remote
Bit 10 “Target reached” is set when the specified reference value is reached.
In the special case of power failure regulation, the bit is also set when the power failure
et via the
parameter Max. control deviation 549 see frequency inverter Operating Instructions).
Bit 11 “Internal li mit value active” indicates that an internal limit is active. T his may be the current limit, the torque limit or the overv oltage control . All functions will result in the reference value being left or not reached.
Bit 15 “Warning 2” signals a critical o pe rating sta te which will result in a fault switch-off of the frequency inverter within a s hort time. This bit i s set if there is a dela yed wa rning relating to the motor temperature, heat sink/inside temperature, Ixt monitoring or mains phase failure.
set.
The frequency inverter can only be controlled if the logic operation is true. The logic
inputs for Start Clockwise and Start Anticlockwise can be connected directly with “On” or “Off” (parameter
Start clockwise 68 and Start anticlockwise 69).
Digital inputs (STOA and STOB) must be set. This results in:
disabled
(Low
enabled
on
switch on
of the warning is evaluated by reading the warning status with parameter
412 = 1) and controller release is turned on.
regulation reaches the frequency 0 Hz (see frequency inverter operating instructions). For "Target reached“, there is a hysteresis (tolerance range) which can be s
56
Agile
VABus/TCP 12/13
In quick stop, the paramete rs Switch-Off Threshold 637 (percent of parameter Maxi-
(holding time after falling short of the
. In the case of a quick stop,
The emergency stop ramps are set via parameters
Emergency Stop Anticlockwise
f
s
Start Quick Stop
OFF
change of state
t
Switch-off Threshold Stop Fct.
637
Emergency Stop Clockwise
424
425
Emergency S top Anticlockwise
Holdig Time Stop Function
638
If frequency/speed reaches the value zero during the s wit ch-off time, the drive continues
off time has elapsed. This e nsures that the
drive is at a standstill when the state changes.

11.3 Behavior in the case of a quick stop

mum Frequency 419) and Holding time 638
Switch-Off Threshold) are relevant. Maximum Frequency the drive is stopped via emergency stop ramps.
425.
Emergency Stop Clockwise 424 and
to be supplied w ith current until the switch-
12/13
Agile
VABus/TCP 57

11.3.1 Behavior in the case of transition 5 (disable operation)

The behavior in transi tion 5 from “Operation enabl ed” to “Switched On” can be config­ured via parameter State transition 5 392.
Parameters
Settings
No.
Description
Min.
Max.
Factory set-
ting
392
State transition 5
0 2 2
Operation mode
Function
-
Coast to stop
Immediate transition from “Operation enabled” to “Switched On”, drive coasts to a standstill
-
DC brake
Activation of DC br ake, at the end of DC deceleratio n, there is the change from “Operation enabled” to “Switche d On”
-
Ramp
Transition with normal ramp, when the drive has come to a "Switched On"
Setting 1 “Direct current brake” is only p ossible with applications with U/f chara cteristic control (e.g. configuration 110). Other configurations do not support this operation
If the frequency inverter is operated with a configuration which does not support the
oriented control),
In this case, the operation mode is not offered in the selection men us of the control unit KP500 and the control software VPlus.
By default, State-transition 5 392 is se t to operation mode “2 - Ram p” For configura-
is also changed,
if necessary.
The behavior in transition 5 is only relevant for configurations without Motion Control
If State-transition 5 392 was triggered with “1 - DC brake ”, a new c ontrol w ord wil l only
a-
parameterized for the DC
brake has elapsed.
If parameter State-transition 5 392 = “ 2 - Ramp” is set, the control word can be set to
r-
ates to its set reference value again and remains in the state “operation enabled”.
The change of sta te from “Op eration enable d” to “Swit ched On” is done after the va lue
and the set holding time has elapsed
ntext, parameters
Maximum Frequency
419) and Holding time 638 (Holding tim e after passing of threshold) are relevant.
0
1
2
mode.
standstill, there is the change from “Operation enabled” to
operation mode Direct Current Brake (e.g. configuration 210, field­value "1" cann ot be used.
tions with torque control, the default value is “0 - coasting”. If the configura tion i s c hange d, the value set for State-transition 5 392
(parameter Configuration 30 ≠ x40).
be accepted after completion of the transition process. The change of state from “Oper tion enabled” to “Starte d” is done a fter the Braki ng time 632
“Operation enabled” again, while the dri ve is de celera ting. I n this wa y, t he drive a ccele
has dropped below the set Switch-Off Threshold (equivalent to the behavior in the case of a quick stop). In this co
Switch-Off Threshold stop function 637 (percentage of parameter
58
Agile
VABus/TCP 12/13
The controller (PLC) can define the reference frequency for the frequency inverter via
e-
Actual speed
In the reference frequency channel, via parameter Reference frequency source 1 475 or
Reference frequency source 2
l-
ue”.
Actual values
Parameters
Contents
Format
Internal reference fre­quency
Internal reference value from the reference
xxx.xx Hz
Bus reference frequency
282
Reference line value from Field bus
xxx.xx Hz
Ramp reference frequency
283
= sum of internal reference frequency +
xxx.xx Hz
The reference value for the frequency inverter from parameter Reference frequency RAM
[Hz]
is connected to the reference line value. This reference value will be combined with the internal reference value from the reference frequency channel and directed to the ramp. For information on the reference frequency channel, refer to the operating instructions of the frequency inverter.
internal set point
refer to note
frequency ramp
fmax
fmin
0
1
+
line set point
operation mode 434
ramp set point
The internal reference value from the reference frequency channel and the reference line value can be led to the ramp individually or as an add ed variable. The ope ration mode of the ramp function is set via the data set switchable parameter
Reference percentage 524 can be used for regular changing of reference percentages,
e.g. as a reference value for technology controllers or as a reference torque.
Parameters
Settings
No.
Description
Min.
Max.
Factory set-
ting
434
Ramp Setpoint
1 3 3
484
Reference frequency RAM [Hz]
-999.99
999.99
0.00
524
Reference percentage RAM [%]
-300.00
300.00
0.00
Operation mode 434
Function
-
Internal reference frequen­cy
The internal reference frequency is determined from the reference frequency channel.
2 -
Reference line value
The reference value is supplied externally via the bus
3 -
Internal reference frequen­cy + reference line value
Addition (consider ing the sign) of internal reference frequency and reference line value

11.3.2 Refere nce value /actual value

parameter Reference frequency RAM [Hz] 484 and receive the actual value via param ter
240.
492, you can select sett ing “20 – Field bus reference va
228
frequency channe l
reference line value
484
1
12/13
Agile
VABus/TCP 59
Reference ramp 434.

11.3.3 Example sequence

1
Control word =
0x0000
Disable voltage
2
Control word =
0x0006
Shut down
3
Control word =
0x0007
Switch On
4
Control word =
0x000F
Enable operation
OR
1
Control word =
0x0000
Disable voltage
2
Control word =
0x000F
Enable operation
60
Agile
VABus/TCP 12/13
Actual values
Modbus or VABus error register. See chapter 8.2 “Telegram check”.
Status word. See chapter 11.1 “Control via contacts/remote contacts”.

12 Actual values

No. Description Function
11 VABus SST error register
282 Bus reference frequency Reference value from serial interface. 283 Ramp reference frequency Reference value from reference frequency channel.
411 Status word
12/13
Agile
VABus/TCP 61
The parameter list is sorted numerically. For better overview, the parameters are marked with pictograms:
The parameter is available in the four data sets.
The parameter value is set by the SET-UP routine
This parameter cannot be written when the frequency inverter is in operation.
Actual value parameter
No.
Description
Unit
Indication range
Chapter
RS485/RS232
Actual values of frequency inverter
228
Internal reference frequency
Hz
-1000,00 ... 1000.00
11.3.2
240
Actual speed
min-1
-60000 … 60000
11.3.2
260
Current error
-
0 ... 0xFFFF
14.5
270
Warnings
-
0 ... 0xFFFF
14.3
282
Bus reference frequency
Hz
-999,99 … 999,99
Bus control
411
Status word
-
0 ... 0xFFFF
11.2
VABus/TCP
Parameters Current error 260, Warnings 270 and Application warnings 274 are only accessible via Field Bus. They cannot be addressed via the V Plus control software or the control unit.

13 Parameter List

13.1 Actual values (Menu “Actual”)

11 VABusSST-Error-Register - 0 ... 15 8.2
249 Active dataset - 0 … 4 11
274 Warning application - 0 ... 0xFFF F 14.4
283 Ramp reference frequency Hz -999.99 … 999.99
12
1431 M odule Info - String 7.4.2.1
62
Agile
VABus/TCP 12/13
Parameters
VABus/TCP
Bus Error Behaviour
Bus control
392
State Transition 5
-
Selection
11.3.1
410
Control word
-
0 … 0xFFFF
11.2
412
Local/Remote
-
Selection
11
Data set switching
414
Data set selection
-
0 … 4
11
Frequency ramps
434
Ramp Setpoint
-
Selection
11.3.2
Fixed frequency values
484
Reference frequency RAM
Hz
-999.99 … 999.99
11.3.2
Fixed percentages
524
Reference percentage RAM
%
-300,00 ... 300.00
11.3.2
Digital outputs
549
Max. control deviation
%
0.01 … 20.00
11
Stopping behavior
637
Switch-Off Thre shold
%
0.0 … 100.0
638
Holding Time
s
0.0 … 200.0
System Bus
900
Node-ID
-
Selection
8.1.4
VABus/TCP
1432
IP address
-
-
1435
DNS Server
-
-
1436
DHCP Option
-
Selection
1437
IP command
-
Selection
1440
Email Function
-
Selection
1441
Email Text (Body)
-
Text

13.2 Parameters (Menu “Para”)

No. Description Unit Setting range Chapter
388
- 0 … 5 7.5
11.3, 11.3.1
1433 Netmask - ­ 1434 Gateway - -
7.2
12/13
Agile
VABus/TCP 63

14 Appendix

Bit
Standard (no posi-
tioning)
Quick Stop (low active)
Halt
Bit
Standard (no posi-
tioning)
Quick Stop (low active)

14.1 List of control words

The tables on this page provide an overview of the functions of the control word bits.
0 Switch On 1 Enable Voltage
2 3 Enable Operation
4 5 6 7 Fault reset 8 9 10 11 12 13 14 15

14.2 List of status words

The tables on this page provide an overview of the functions of the status word bits.
Ready to Switch On
0 1 Switched On
Operation enabled
2 3 Fault 4 Voltage enabled
5
Switch On Disabled
6 7 Warning 8 9 Remote
10 Target reached
Internal limit active
11 12 13 14 15 Warning 2
64
Agile
VABus/TCP 12/13
Warning messages
Bit no.
Warning
code
Description
0 0x0001
Warning Ixt
1 0x0002
Warning short-time Ixt
2 0x0004
Warning long-time Ixt
3 0x0008
Warning heat sink temperature Tk
4 0x0010
Warning inside temperature Ti
5 0x0020
Warning Limit
6 0x0040
Warning Init
7 0x0080
Motor temperature warning
8 0x0100
Warning mains failure
9 0x0200
Warning motor circuit breaker
10
0x0400
Warning Fmax
11
0x0800
Warning analog input MFI1A
12
0x1000
Warning analog input A2
13
0x2000
Warning System Bus
14
0x4000
Warning Udc
15
0x8000
Warning Application warning status 273
The meanings of the individual warnings are described in detail in the frequency in-

14.3 Warning messages

The different control methods and the hardware of the frequency inverter include functions for con­tinuous monitoring of the application. In addition to the messages documented in the frequency in­verter user manual, further warning messages are activated by the Field Bus module. The bit-coded warning reports are issued via parameter ter
Warnings 270 is provided for read-out via a PLC, Parameter Warnings 269 provides the infor-
mation, including a brief description in VPlus and the control panel.
Warnings 270 according to the following pattern: Parame-
verter Operating Instructions.
12/13
Agile
VABus/TCP 65

14.4 Application warning messages

When the highest bit of the warning message is set, an “Application warni ng message” is present.
indicates the warnings as plain text in
Use parameter Application warnings 274 in order to read the warning messages via Field Bus.
Application warning messages
Bit no.
Warning
code
Description
0 0x0001
BELT
- V-belt 1
0x0002
(reserved)
2 0x0004
(reserved)
3 0x0008
(reserved)
4 0x0010
(reserved)
5 0x0020
(reserved)
6 0x0040
SERVICE
– Service Warning
7 0x0080
User 1
– User Warning 1
8 0x0100
User 2
– User Warning 2
9 0x0200
(reserved)
10
0x0400
(reserved)
11
0x0800
(reserved)
12
0x1000
(reserved)
13
0x2000
(reserved)
14
0x4000
(reserved)
15
0x8000
(reserved)
For details on the warnings, refer to the frequency inverter Operating Instructions.
The application warning messages are bit-encoded as per the following pattern via parameter Appli-
cation warnings
the control panel and the VPlus PC control software.
274. Parameter Application warnings 273
66
Agile
VABus/TCP 12/13
The error code stored following a fault comprises the error group FXX (hig h-byte, hexa-
Communication error
Key
Meaning
Ethernet
F27
14
Communication loss to PLC
The current error can be read via parameter Current error 260.
In addition to the errors listed, there are other error messages. However, they are used
ss fault messages
which are not listed here, please do not hesitate t o call us.
Speed [1/min] in
Frequency [Hz]
See Chapter 14.6.1
Frequency [Hz] into
speed [1/min]
See Chapter 14.6.2

14.5 Error messages

decimal) and the code YY (low-byte, hexadecimal).
Parameter Current error 259 indicates the current error as plain text in the control panel and the VPlus PC control software.
for internal purpose s only and are not listed her e. If you come acro

14.6 Conversions

The speeds/frequencies can be converted to other speed formats using the formulas in this chapter:

14.6.1 Speed [1/min] into frequency [Hz]

𝑓 [Hz]=
𝑛[min
-1
]
× 𝑁𝑜. 𝑜𝑓 𝑝𝑜𝑙𝑒 𝑝𝑎𝑖𝑟𝑠 (𝑃. 373)
60

14.6.2 Frequency [Hz] into speed [1/min]

[
]
𝑛
rpm
=
𝑁𝑜. 𝑜𝑓 𝑝𝑜𝑙𝑒 𝑝𝑎𝑖𝑟𝑠 (𝑃. 373)
𝑓 [Hz]× 60
12/13
Agile
VABus/TCP 67
Dec.
Hex.
Char.
Dec.
Hex.
Char.
Dec.
Hex.
Char. 0
00
NUL 43
2B +
86
56
V
1
01
44
2C ,
87
57 W
2
02
STX 45
2D -
88
58 X
3
03
ETX 46
2E .
89
59
Y
4
04
EOT 47
2F /
90
5A Z
5
05
ENQ 48
30 0
91
5B [
6
06
ACK 49
31 1
92
5C
\
7
07
BEL 50
32 2
93
5D ]
8
08
BS 51
33 3
94
5E ^
9
09
TAB 52
34 4
95
5F
_
10
0A
LF 53
35 5
96
60 `
11
0B
VT 54
36 6
97
61 a
12
0C
FF 55
37 7
98
62
b
13
0D
CR 56
38 8
99
63 c
14
0E
57
39 9
100
64 d
15
0F
58
3A :
101
65
e
16
10
59
3B ;
102
66 f
17
11
60
3C <
103
67 g
18
12
61
3D =
104
68
h
19
13
62
3E >
105
69 i
20
14
63
3F ?
106
6A
j 21
15
NAK 64
40 @
107
6B
k
22
16
65
41 A
108
6C l
23
17
66
42 W
109
6D m
24
18
67
43 C
110
6E
n
25
19
68
44 D
111
6F o
26
1A
69
45 E
112
70 p
27
1B
ESC 70
46 F
113
71
q
28
1C
71
47 G
114
72 r
29
1D
72
48 H
115
73 s
20
1E
73
49 I
116
74 t
31
1F
74
4A J
117
75
u
32
20
SPACE
75
4B K
118
76 v
33
21 !
76
4C L
119
77
w
34
22 „
77
4D M
120
78 x
35
23 #
78
4E N
121
79 y
36
24 $
79
4F O
122
7A z
37
25 %
80
50 P
123
7B
{
38
26 &
81
51 Q
124
7C |
39
27 '
82
52 R
125
7D
}
40
28 (
83
53 S
126
7E ~
41
29 )
84
54 D
127
7F
DEL 42
2A *
85
55 U
Frequently used values are marked.

14.7 ASCII table (0x00 – 0x7F)

68
Agile
VABus/TCP 12/13

Index

A
Acknowledging error messages ................... 41
Actual values .............................................. 61
Application warning messages ..................... 66
Application warnings ................................... 66
Assembly
Communication module ........................... 22
B
Bus Error behavior ................................ 33, 41
Bus reference frequency ............................. 61
C
Control
Contacts ................................................. 50
Remote contacts ..................................... 50
Copyright ..................................................... 7
D
Decommissioning ....................................... 16
Designated use ............................................ 9
Disassembly
Communication module ........................... 23
E
Electrical connections ................................. 14
Error messages .......................................... 67
Example telegrams ..................................... 45
G
General Information about the Documentation
................................................................ 6
I
Index parameters
Read ...................................................... 44
Write ...................................................... 43
Installation ................................................ 14
L
Local/Remote ............................................ 49
M
Maintenance .............................................. 15
P
Parameter access
Index parameters
Read .................................................. 44
Write index parameter ............................ 43
R
Ramp reference frequency ......................... 61
Remote contacts ........................................ 50
S
Safety
General .................................................... 8
State machine
Device control ........................................ 53
Statemachine ............................................ 53
Storage ..................................................... 14
T
TCP/IP address .......................................... 26
Transition 5 of state machine ..................... 58
Transport .................................................. 14
U
USB .......................................................... 21
V
VPlus ........................................................ 21
W
Warning messages ..................................... 65
Warranty and liability ................................... 7
12/13
Agile
VABus/TCP 69
Bonfiglioli worldwide network.
Bonfiglioli New Zealand
88 Hastie Avenue, Mangere Bridge, Auckland 2022, New Zealand - PO Box 11795, Ellerslie Tel. (+64) 09 634 6441 - Fax (+64) 09 634 6445 npollington@bonfiglioli.com.au
Bonfiglioli Österreich
Molkereistr 4 - A-2700 Wiener Neustadt Tel. (+43) 02622 22400 - Fax (+43) 02622 22386 www.bonfiglioli.at info@bonfiglioli.at
Bonfiglioli South East Asia
No 21 Woodlands indusrial park E1 #02-03 Singapore 757720 Tel. (+65) 6893 6346/7 - Fax (+65) 6893 6342 www.bonfiglioli.com.au sales@bonfiglioli.com.sg
Bonfiglioli South Africa
55 Galaxy Avenue, Linbro Business Park - Sandton Tel. (+27) 11 608 2030 OR - Fax (+27) 11 608 2631 www.bonfiglioli.co.za bonfigsales@bonfiglioli.co.za
Bonfiglioli Türkiye
Atatürk Organíze Sanayi Bölgesi, 10015 Sk. No: 17, Çigli - Izmir T
el. +90 (0) 232 328 22 77 (pbx) Fax +90 (0) 232 328 04 14 www.bonfiglioli.com.tr info@bonfiglioli.com.tr
Bonfiglioli United Kingdom
Industrial Solutions
Unit 7, Colemeadow Road North Moons Moat - Redditch, Worcestershire B98 9PB Tel. (+44) 1527 65022 - Fax (+44) 1527 61995 www.bonfiglioli.com uksales@bonfiglioli.com
Mobile Solutions
3 - 7 Grosvenor Grange, Woolston Warrington - Cheshire WA1 4SF Tel. (+44) 1925 852667 - Fax (+44) 1925 852668 www.bonfiglioli.co.uk mobilesales@bonfiglioli.co.uk
Bonfiglioli USA
3541 Hargrave Drive Hebron, Kentucky 41048 Tel. (+1) 859 334 3333 - Fax (+1) 859 334 8888 www.bonfiglioliusa.com
Bonfiglioli Vietnam
Lot C-9D-CN My Phuoc Industrial Park 3 Ben Cat - Binh Duong Province Tel. (+84) 650 3577411 - Fax (+84) 650 3577422 www
.bonfiglioli.vn
salesvn@bonfiglioli.com
Bonfiglioli Australia
2, Cox Place Glendenning NSW 2761 Locked Bag 1000 Plumpton NSW 2761 Tel. (+ 61) 2 8811 8000 - Fax (+ 61) 2 9675 6605 www.bonfiglioli.com.au - sales@bonfiglioli.com.au
Bonfiglioli Brazil
Travessa Cláudio Armando 171 - Bloco 3 CEP 09861-730 - Bairro Assunção São Bernardo do Campo - São Paulo T
el. (+55) 11 4344 1900 - Fax (+55) 11 4344 1906 www.bonfigliolidobrasil.com.br bonfigliolidobrasil@bonfiglioli.com
Bonfiglioli Canada
2-7941 Jane Street - Concord, Ontario L4K 4L6 Tel. (+1) 905 7384466 - Fax (+1) 905 7389833 www.bonfigliolicanada.com sales@bonfigliolicanada.com
Bonfiglioli China
19D, No. 360 Pu Dong Nan Road New Shanghai International Tower 200120 Shanghai Tel. (+86) 21 5054 3357 - Fax (+86) 21 5970 2957 www.bonfiglioli.cn - bdssales@bonfiglioli.com.cn
Bonfiglioli Deutschland
Sperberweg 12 - 41468 Neuss T
el. (+49) 02131 2988-0 Fax (+49) 02131 2988-100 www.bonfiglioli.de - info@bonfiglioli.de
Bonfiglioli España
TECNOTRANS BONFIGLIOLI S.A. Pol. Ind. Zona Franca sector C, calle F, n°6 08040 Barcelona Tel. (+34) 93 4478400 - Fax (+34) 93 3360402 www.tecnotrans.com - tecnotrans@tecnotrans.com
Bonfiglioli France
14 Rue Eugène Pottier BP 19 Zone Industrielle de Moimont II 95670 Marly la Ville Tel. (+33) 1 34474510 - Fax (+33) 1 34688800 www.bonfiglioli.fr - btf@bonfiglioli.fr
Bonfiglioli India
PLOT AC7-AC11 Sidco Industrial Estate Thirumudivakkam - Chennai 600 044 Tel. +91(0) 44 24781035 - 24781036 - 24781037 Fax +91(0) 44 24780091 - 24781904 www.bonfiglioliindia.com - bonfig@vsnl.com
Bonfiglioli Italia
V
ia Sandro Pertini lotto 7b 20080 Carpiano (Milano) Tel. (+39) 02 985081 - Fax (+39) 02 985085817 www.bonfiglioli.it customerservice.italia@bonfiglioli.it
Bonfiglioli has been designing and developing innovative and reliable power transmission and control solutions for industry, mobile machinery and renewable energy applicacations since 1956.
Bonfiglioli Riduttori S.p.A.
Via Giovanni XXIII, 7/A 40012 Lippo di Calderara di Reno Bologna (Italy)
tel: +39 051 647 3111 fax: +39 051 647 3126 bonfiglioli@bonfiglioli.com www.bonfiglioli.com
COD. VEC 1022 R0
Loading...