BONFIGLIOLI Vectron User Manual

Page 1
ACTIVE CUBE
Expansion Module EM-RES-03 Frequency Inverter 230 V / 400 V
Page 2
Page 3
g
g
r
General points on the documentation
The present supplement of the documentation is valid for the frequency inverter se­ries ACU 201 and ACU 401. The information necessary for the assembly and applica­tion of the EM-RES-03 expansion module is documented in this guidance.
For better clarity, the user documentation is structured according to the customer-
specific demands made of the frequency inverter.
Brief instructions The brief instructions describe the fundamental steps for mechanical and electrical
installation of the frequency inverter. The
uided commissioning supports you in the selection of necessary parameters and the software configuration of the frequency inverter.
Operating instructions The operating instructions document the complete functionality of the frequency in-
verter. The parameters necessary for specific applications for adaptation to the ap­plication and the extensive additional functions are described in detail.
Application manual The application manual supplements the documentation for purposeful installation and
commissioning of the frequency inverter. Information on various subjects connected with the use of the frequency inverter is described specific to the application.
Installation instructions
The installation instructions describe the mechanical installation and use of devices which differ from those described in the brief instructions and the operating instruc­tions.
The documentation and additional information can be requested via your local repre-
sentation of the company BONFIGLIOLI.
The following pictograms and signal words are used in the documentation:
Danger!
means a directly threatening danger. Death, serious damage to persons and consider­able damage to property will occur if the precautionary measure is not taken.
Warning!
marks a possible threat. Death, serious damage to persons and considerable damage to property can be the consequence if attention is not paid to the text.
Caution!
refers to an indirect threat. Damage to people or property can be the result.
Attention!
refers to a possible operational behavior or an undesired condition, which can occur in accordance with the reference text.
Note
marks information, which facilitates handling for you and supplements the corre­sponding part of the documentation.
Warning! In installation and commissionin
, comply with the information in the documentation. You as a qualified person must have read the documenta­tion carefully and understood it. Comply with the safety instructions. Fo the purposes of the instructions, "qualified person" designates a person acquainted with the erection, assembly, commissioning and operation of the frequency inverters and possessing the qualification corresponding to the activity.
EM-RES-03 110/07
Page 4
TABLE OF CONTENTS
1 General safety and application information .................................................................. 4
1.1 General information................................................................................................. 4
1.2 Proper use................................................................................................................ 5
1.3 Transport and storage ............................................................................................. 5
1.4 Handling and positioning......................................................................................... 5
1.5 Electrical connection................................................................................................ 6
1.6 Operation information ............................................................................................. 6
1.7 Maintenance and service ......................................................................................... 6
2 Introduction ................................................................................................................... 7
3 Technical data of the expansion module EM-RES-03 .................................................... 8
4 Installation of the EM-RES-03 expansion module ......................................................... 9
4.1 General .................................................................................................................... 9
4.2 Mechanical installation ............................................................................................ 9
4.3 Electrical installation ............................................................................................. 11
4.3.1 Circuit diagram...................................................................................................... 11
4.3.2 Control terminals ................................................................................................... 12
5 System bus interface.................................................................................................... 14
5.1 Bus termination ..................................................................................................... 14
5.2 Cables .................................................................................................................... 15
5.3 Socket X410B......................................................................................................... 15
5.4 Baud rate setting/line length ................................................................................ 16
5.5 Setting node address ............................................................................................. 16
5.6 Functional overview .............................................................................................. 17
5.7 Network management ........................................................................................... 17
5.7.1 SDO channels (parameter data).............................................................................. 18
5.7.2 PDO channels (process data).................................................................................. 18
5.8 Master functionality............................................................................................... 19
5.8.1 Control boot-up sequence, network management..................................................... 19
5.8.2 SYNC telegram, generation..................................................................................... 21
5.8.3 Emergency message, reaction................................................................................. 22
5.8.4 Client SDO (system bus master).............................................................................. 23
5.9 Slave functionality ................................................................................................. 24
5.9.1 Implement boot-up sequence, network management................................................ 24
5.9.1.1 Boot-up message ............................................................................................ 24
5.9.1.2 Status control ................................................................................................. 24
5.9.2 Process SYNC telegram .......................................................................................... 25
5.9.3 Emergency message, fault switch-off....................................................................... 26
5.9.4 Server SDO1/SDO2................................................................................................ 27
5.10 Communication channels, SDO1/SDO2.............................................................. 29
5.10.1 SDO telegrams (SDO1/SDO2) .................................................................................29
5.10.2 Communication via field bus connection (SDO1)....................................................... 31
5.10.2.1 Profibus-DP .................................................................................................... 31
5.10.2.2 RS232/RS485 with VECTRON bus protocol ........................................................ 31
EM-RES-03 10/072
Page 5
5.11 Process data channels, PDO ............................................................................... 33
5.11.1 Identifier assignment process data channel.............................................................. 33
5.11.2 Operation modes process data channel.................................................................... 34
5.11.3 Timeout monitoring process data channel................................................................ 35
5.11.4 Communication relationships of the process data channel ......................................... 36
5.11.5 Virtual links ........................................................................................................... 37
5.11.5.1 Input parameters of the TxPDO’s for data to be transmitted ............................... 40
5.11.5.2 Source numbers of the RxPDO’s for received data.............................................. 42
5.11.5.3 Examples of virtual links .................................................................................. 43
5.12 Control parameters............................................................................................. 44
5.13 Handling of the parameters of the system bus .................................................. 45
5.14 Ancillaries ........................................................................................................... 47
5.14.1 Definition of the communication relationships........................................................... 48
5.14.2 Production of the virtual links.................................................................................. 49
5.14.3 Capacity planning of the system bus........................................................................ 50
6 Control inputs and outputs .......................................................................................... 52
6.1 Analog input EM-S1INA ......................................................................................... 52
6.1.1 General................................................................................................................. 52
6.1.2 Characteristic ........................................................................................................ 52
6.1.3 Operation modes ................................................................................................... 53
6.1.3.1 Examples........................................................................................................ 53
6.1.4 Scaling..................................................................................................................56
6.1.5 Tolerance band and hysteresis................................................................................ 57
6.1.6 Error and warning behavior .................................................................................... 58
6.1.7 Adjustment ........................................................................................................... 59
6.1.8 Filter time constant................................................................................................ 59
6.2 Digital outputs EM-S1OUTD and EM-S2OUTD ....................................................... 60
6.2.1 General................................................................................................................. 60
6.2.2 Operation modes ................................................................................................... 60
6.2.3 Fixed reference values and fixed value switch-over................................................... 60
6.3 Digital inputs EM-SxIND ........................................................................................ 61
6.4 Resolver input EM-RES .......................................................................................... 62
6.4.1 Offset ...................................................................................................................62
6.4.2 Actual speed source............................................................................................... 65
6.4.3 Evaluation mode.................................................................................................... 65
6.5 Frequency and percentage reference channel ...................................................... 65
6.6 Actual value display ............................................................................................... 65
6.7 Status of the digital signals ................................................................................... 66
6.8 Motor temperature ................................................................................................ 67
7 Parameter list............................................................................................................... 68
7.1 Actual value menu (VAL) ....................................................................................... 68
7.2 Parameter menu (PARA) ....................................................................................... 68
8 Annex ........................................................................................................................... 70
8.1 Error messages ...................................................................................................... 70
EM-RES-03 310/07
Page 6
T
t
g
1 General safety and application information
This documentation has been created with greatest care and has been extensively and repeatedly checked. For reasons of clarity, we have not been able to take all detailed information on all the types of the products and also not every ima positioning, operation or maintenance into account. If you require further information or if particular problems not treated extensively enough in the operating instructions occur, you can obtain the necessary information via the local representation of the company BONFIGLIOLI. In addition, we would point out that the contents of these operatin not part of an earlier or existing agreement, assurance or legal relationship, nor are they intended to amend them. All the manufacturer's obligations result from the pur­chase contract in question, which also contains the completely and solely valid war­ranty regulation. These contractual warranty provisions are neither extended nor lim­ited by the implementation of these operating instructions.
he manufacturer reserves the right to correct or amend the contents and produc information as well as omissions without specific announcement and assumes no kind of liability for damage, injuries or expenditure to be put down to the aforementioned reasons.
1.1 General information
Warning! BONFIGLIOLI VECTRON frequency inverters have high voltage levels dur-
in have hot surfaces. In the event of inadmissible removal of the necessary covers, improper use, wron persons or property. To avoid the damage, only qualified staff may carry out the transport, installation, setup or maintenance work required. Comply with the stan­dards EN 50178, IEC 60364 (Cenelec HD 384 or DIN VDE 0100), IEC 60664-1 (Cenelec HD 625 or VDE 0110-1), BGV A2 (VBG 4) and na­tional provisions. Qualified persons within the meaning of this principal safety information are people acquainted with the erection, fitting, com­missionin and in possession of qualifications matching their activities.
ginable case of
g instructions are
operating, depending on their protection class, drive moving parts and
g installation or operation, there is the risk of serious damage to
g and operating of frequency inverters and the possible hazards
EM-RES-03 10/074
Page 7
g
g of
T
j
g
g
g
g
r
1.2 Proper use
Warning! The frequency inverters are electrical drive components intended for in-
stallation in industrial plant or machines. Commissioning and start of in­tended operation are not allowed until it has been established that the machine corresponds to the provisions of the EC machine directive 98/37/EEC and EN 60204. According to the CE sign, the frequency invert­ers additionally fulfill the requirements of the low-volta 73/23/EEC and the standards EN 50178 / DIN VDE 0160 and EN 61800-2. Responsibility for compliance with the EMC directive 89/336/EEC is with the user. Frequency inverters are available in a limited way and as com­ponents exclusively intended for professional use within the meanin the standard EN 61000-3-2. With the issue of the UL certificate according to UL508c, the requirements of the CSA Standard C22.2-No. 14-95 have also been fulfilled. The technical data and the information on connection and ambient condi­tions stated on the ratin
g plate and the documentation must be complied with. The instructions must have been read and understood before start­ing work at the device.
1.3 Transport and storage
ransport and storage are to be done appropriate in the original packing. Store the
units only in dry rooms, which are protected against dust and moisture and are sub-
ected to little temperature deviations only. Observe the climatic conditions accordin to standard EN 50178 and to the information on the label of the original packing. The duration of storage without connection to the admissible reference volta exceed one year.
1.4 Handling and positioning
Warning! Damaged or destroyed components may not be put into operation be-
cause they may be a health hazard.
The frequency inverters are to be used accordin
and the standards. Handle carefully and avoid mechanical overload. Do not bend the components or chan
e the isolation distances. Do not touch electronic components o contacts. The devices contain construction elements with a risk of electrostatic, which can easily be damaged by improper handling. Any use of damaged or destroyed com­ponents shall be considered as a non-compliance with the applicable standards. Do not remove any warning signs from the device.
e directive
e may not
to the documentation, the directives
EM-RES-03 510/07
Page 8
T
g
j
1.5 Electrical connection
Warning! Before any assembly or connection work, de-energize the frequency in-
verter. Make sure that the frequency inverter is de-energized.
While working on the frequency inverters, obey the applicable standards BGV A2 (VBG
Do not touch the sockets, because the capacitors may still be charged. Comply with the information
given in the operating instructions and on
the frequency inverter label.
4), VDE 0100 and other national directives. Comply with the information in the docu­mentation on electrical installation and the relevant directives. Responsibility for com­pliance with and examination of the limit values of the EMC product standard EN 61800-3 for variable-speed electrical drive mechanisms is with the manufacturer o the industrial plant or machine.
he documentation contains information on installation correct for EMC. The cables connected to the frequency inverters may not be subjected to an isolation test with a high test voltage without previous circuit measures.
1.6 Operation information
Warning! Before commissioning and the start of the intended operation, attach all
the covers and check the sockets. Check additional monitoring and pro­tective devices pursuant to EN 60204 and the safety directives applicable in each case (e.
g. Working Machines Act, Accident Prevention Directives etc.). No connection work may be performed, while the system is in operation.
1.7 Maintenance and service
Warning! Unauthorized openin
ury or damage to property. Repairs on the frequency inverters may
in only be done by the manufacturer or persons authorized by the latter.
and improper interventions can lead to physical
f
EM-RES-03 10/076
Page 9
2 Introduction
f
This document describes the possibilities and the properties of the EM-RES-03 expan-
sion module for the frequency inverters of the ACU device series.
Note: This document exclusively describes the EM-RES-03 expansion module. It
Note: The expansion module EM-RES-03 can be used only with frequency in-
The EM-RES-03 expansion module is an optional hardware component to extend the
functionality of the frequency inverter. It enables the data exchange within the net­work between the components which have been directly connected, for example con­trol and regulation elements.
The EM-RES-03 module extends the functionality of the frequency inverters of the
ACU device series by the following additional functions:
CAN system bus
(CAN interface ISO-DIS 11898; CAN High Speed; max. 1 MBaud)
Analog input (second bipolar analog input)
Resolver input including PTC evaluation via SubD-9 connection
Three digital inputs
is not to be understood as fundamental information for the operation o the frequency inverters of the ACU device series.
verters of the ACU series. It is not applicable for frequency inverters o the ACT series.
f
Two digital outputs
Voltage output DC 24V
Note: The EM-RES-03 expansion module has been enclosed with the frequency
inverter as a separate component and must be fitted by the user. This is described in detail in the chapter "Mechanical Installation".
To assemble the expansion module it can be simply plugged into the frequency in-
verter of the ACU device series.
Warning! The assembly is done before the frequency inverter is put into operation,
and only in a voltage-free state.
The pluggable sockets of the expansion module enable economical overall fitting with
a safe function.
Note: The EM-RES-03 expansion module differs in the resolver evaluation from
the expansion modules EM-RES-01 and EM-RES-02. The frequency of the excitation signal is set to the fixed value 8 Hz. This module is applicable for BONFIGLIOLI motor types BCR and BTD.
EM-RES-03 710/07
Page 10
3 Technical data of the expansion module EM-RES-03
For usage of the expansion module comply with the technical data of the basic de-
vice.
X410A.1 DC-24 V output
(max. 180 mA) X410A.2 Ground 24 V X410B.2 Digital input EM-S1IND 2) X410A.3 Digital output EM-S1OUTD 2) X410B.3 Digital input EM-S2IND 2) X410A.4 Digital output EM-S2OUTD 2) X410B.4 Digital input EM-S3IND 2) X410A.5 Not connected. X410B.5 System bus, CAN-Low X410A.6 Analog input EM-S1INA 2) X410B.6 System bus, CAN-High X410A.7 Ground 10 V X410B.7 Ground 10 V
1)
The power supply at terminal X410A.1 may be loaded with a maximum current of
= 180 mA. Relative to the application, the maximum current available will be
I
max
reduced by the further control outputs of the frequency inverter and expansion module.
2)
The control electronics can be freely parameterized.
Resolver: PTC input 2)
Number of pole pairs: 1 … 7 Tripping resistance = 2.4 kΩ acc. DIN 44081 Input voltage 7 V Input frequency 8 kHz Input current <= 60 mA PTC thermistor respectively U
= 0.5 bimetallic temperature sensor (normally closed
in/Uref
Warning! The PTC input is not insulated. Only PTC thermistors with safe insulation
Note: BONFIGLIOLI servomotors of types BCR and BTD are designed with safe
Digital inputs (X410B.2) … (X210B.4): Low signal: 0 V … 3 V, High signal: 12 V … 30 V, Input resistance: 2.3 k, Response time: 4 ms, PLC compatible Frequency signal: 0 ... 30 V, 10 mA at 24 V, fmax Digital outputs (X410A.3), (X410A.4): Low signal: 0 V … 3 V, High signal: 12 V … 30 V, output current: 40 mA, PLC compatible Analog input (X410A.6): Analog signal: input voltage: -10 V … 10 V / 0 V … 10 V (R Resolution 10 Bit DC-24 V output (X410A.1):
= 180 mA. This value can be lower dependent on the load at the digital outputs
I
max
of the basic device and expansion module. Conductor cross section: Suitable cross sections of the control terminals are: With wire end ferrule: 0.25…1.0 mm² Without wire end ferrule: 0.14…1.5 mm²
Terminal X410A Terminal X410B
1)
X410B.1 Not connected.
Resolver- and PTC-input X412 (SubD-9)
RMS
Hysteresis = 1.3 k
contact)
from the motor winding acc. to EN61800-5-1 may be connected.
insulation from the motor winding.
Technical data of the control terminals
= 150 kHz
= 100 k),
i
EM-RES-03 10/078
Page 11
4 Installation of the EM-RES-03 expansion module
g
t
g
The mechanical and electrical installation of the EM-RES-03 expansion module is to be
The frequency inverters are designed according to the requirements and limit values
For further information, refer to the operating instructions of the frequency inverter.
4.1 General
carried out by qualified personnel according to the general and regional safety and installation directives. Safe operation of the frequency inverter requires that the documentation and the device specification be complied with durin start of operation. For specific areas of application further provisions and guidelines must be complied with where applicable.
of product standard EN 61800-3 with an interference immunity factor (EMI) for opera­tion in industrial applications. The electroma expert installation and observation of the specific product information.
Warning! All connection sockets where dan
g installation and
gnetic interference is to be avoided by
erous voltage levels may be presen (e.g. motor connection sockets, mains sockets, fuse connection sockets, etc.) must be protected against direct contact.
4.2 Mechanical installation
Danger! If the followin
with possible consequences of death or severe injury by electrical current. To disregard the instructions can lead to destruction of the frequency inverter and/or of the expansion module.
Before assembly or disassembly of the EM-RES-03 expansion module, the fre­quency inverter must be de-energized. Take appropriate measures to make sure it is not energized unintentionally.
Make sure that the frequency inverter is de-energized.
Danger! The mains, direct voltage and motor terminals can be live with dangerous
voltage after disconnection of the frequency inverter. Work may only be done on the device after a waitin link capacitors have been discharged.
instructions are not complied with, there is direct danger
g period of some minutes until the DC
EM-RES-03 910/07
Page 12
The EM-RES-03 expansion module is supplied in a housing for assembly on the lower
Remove the lower cover (1) of the frequency inverter.
slot of the frequency inverter.
The slot for the EM-RES-03 expansion module becomes accessible.
1
Caution! The EM-RES-03 expansion module (2) is pre-fitted in a housing. Do NOT
touch the PCB visible on the back, as modules may be damaged.
Plug the EM-RES-03 expansion module (2) onto the slot (3).
3
2
Re-install the lower cover (1).
This completes the assembly procedure.
When the supply voltage of the frequency inverter is switched on, the EM-RES-03
expansion module is ready for operation.
1
EM-RES-03 10/0710
Page 13
g
t
g
X
4.3 Electrical installation
Danger! If the following instructions are not complied with, there is direct danger
Before electrical installation of the EM-RES-03 expansion module, the frequency inverter must be de-ener energized unintentionally.
Make sure that the frequency inverter is de-energized.
with the possible consequences of death or severe injury by electrical current. Further, failure to comply can lead to destruction of the frequency inverter and/or of the expansion module.
ized. Take appropriate measures to make sure it is no
Danger! The mains, direct voltage and motor sockets can have dangerous voltages
even after disconnection of the frequency inverter. Work may only be done on the device after a waitin link capacitors have been discharged.
4.3.1 Circuit diagram
410A
1
+24 V / 180 mA GND 24 V
2
EM-S1OUTD
3
A
EM-S2OUTD
4
N.C.
5
EM-S 1I NA
6
B
GND 10 V
7
period of some minutes until the DC
A
D
X410B
N.C.
1
EM-S1IND
2
C
D
E
Digital outputs EM-S1OUTD, EM-S2OUTD
A
Digital signal, DC-24 V, I
Analog input EM-S1INA
B
max
Analog signal, resolution 10 Bit, U
Digital inputs EM-S1IND … EM-S3IND
C
EM-S2IND
3
EM-S3IND
4
CAN-L ow
5
CAN-H igh
6
7
GND
X412
Resolver
PTC
= 40 mA, PLC compatible, overload and short-circuit proof
= ±10 V (Ri = 100 kΩ)
max
Digital signal, , response time approx. 16 ms, U
PLC compatible, Frequency signal, 0 ... 30 V, 10 mA at 24 V, f
max
SYS
= 30 V, 10 mA at 24 V,
max
= 150 kHz
EM-RES-03 1110/07
Page 14
T
CAN actuation of the system bus according to ISO-DIS 11898 (CAN High Speed)
Communication interface system bus
D
Resolver- and PTC thermistor input (SubD9)
E
he resolver interface is suitable for the connection of standard resolvers with the following specifications: Input impedance > 95 Ω at 8 kHz, number of pole pairs up to 7, 30 000 rpm at number of pole pairs = 1
Excitation voltage U Input voltage U Phase shift (at excitation frequency): 7° (5 kHz), 14° (10 kHz), 26° (20 kHz)
Tripping resistance > 2.4 kΩ (PTC) acc. DIN 44081,
min rms
= 3.5 V, I
REF rms
= 1.8 V, voltage proof up to 30 V
= 60 mA
max
PTC thermistor or bimetal temperature sensor (normally closed contact)
Use PTC thermistors with safe insulation from the motor winding acc. to EN 61800 5-1.
4.3.2 Control terminals
The control and software functionality can be freely configured for economical opera-
tion with a safe function.
Expansion module EM-RES-03
Wieland DST85 / RM3,5
0.14 … 1.5 mm
2
AWG 30 … 16
0.14 … 1.5 mm
2
AWG 30 … 16
0.25 … 1.0 mm
2
AWG 22 … 18
0.25 … 0.75 mm
0.2 … 0.3 Nm
AWG 22 … 20
1.8 … 2.7 lb-in
2
Caution! The control inputs and outputs must be connected and disconnected free
of electrical power. Otherwise components may be damaged.
Attention! In order to minimize electromagnetic interference and to obtain a good
signal quality, the line screen is to be connected to PE on a plane at both ends.
EM-RES-03 10/0712
Page 15
Control terminal X410A
Ter. Description 1 DC-24 V output (max. 180 mA) 1) 2 Ground 24 V 3 Digital output EM-S1OUTD 2) 4 Digital output EM-S2OUTD 2) 5 Not connected 6 Analog input EM-S1INA 2) 7 Ground 10 V
Control terminal X410B Ter. Description 1 Not connected 2 Digital input EM-S1IND 2) 3 Digital input EM-S2IND 2) 4 Digital input EM-S3IND 2) 5 System bus, CAN-Low 6 System bus, CAN-High 7 Ground
1)
The power supply at terminal X410A.1 may be loaded with a maximum current of
= 180 mA. Relative to the application, the maximum current available will be
I
max
reduced by the further control outputs of the frequency inverter and expansion module.
2)
The control electronics is freely programmable.
Resolver- and PTC input (SubD-9) Pin Designation Function socket shielding Connected with PE 1 PE Protective earth conductor 2 PTC+ PTC thermistor connection
5
3 COS+ Cosinus track
9
4 SIN+ Sinus track 5 +UE Excitation voltage 6 7
PTC­COS-
PTC thermistor connection Cosinus track
6
1
8 SIN- Sinus track 9
Note: If a synchronous motor should be connected to the resolver input which is
-UE
Excitation voltage
not from BONFIGLIOLI it can be necessary to change the sign of the sinus track. This can be set via parameter
Evaluation Mode 492. Refer to chapter
6.4.3.
Use PTC thermistors with safe insulation from the motor winding acc. to EN 61800-5-1.
Use shielded twisted pair.
The resolver cable must be kept physically separate from the motor cable.
Place the cable shield of the resolver cable on both sides with large area contact.
BONFIGLIOLI VECTRON recommends ready-made cable for the connection of
synchronous motors of types BCR and BTD.
EM-RES-03 1310/07
Page 16
5 System bus interface
)
D
The CAN connection of the system bus is physically designed according to ISO-DIS
11898 (CAN High Speed). The bus topology is the line structure.
The frequency inverter supports a CAN protocol controller, which may exist in either the
CM-CAN communication module with CANopen interface OR in an extension module for the system bus, such as the EM-RES-03 extension module.
Attention: Installation of two optional components with CAN-Protocol controller
5.1 Bus termination
The necessary bus termination at the physically first and last node can be activated via
the DIP switch S1 on the EM-RES-03 expansion module.
S1 built the normal passive termination.
Switch S1 to ON for a passive termination. This is necessary for the first and last node.
results in a deactivation of the system bus interface in the EM-RES-03 extension module.
S1
Attention: The factory setting for the bus termination is OFF (switch in
lower position).
ata line
CAN high (X410B.6
120
Data line
CAN low (X410B.5)
passive
EM-RES-03 10/0714
Page 17
X
X
5.2 Cables
For the bus line, use twisted a cable with harness shield (no foil shield).
Attention: The control and communication lines are to be laid physically separate
from the power lines. The harness screen of the data lines is to be con­nected to ground (PE) on both sides on a large area and with good con­ductivity.
The system bus is connected via three sockets of the plug X410B on the EM-RES-03
5.3 Socket X410B
expansion module.
X410A
410B
2
2
4
4
6
6
3
3
5
1
1
5
410B
7
7
Socket X410B Socket Input/Output Description X410B.1 Not connected X410B.2 Digital input S1IND X410B.3 Digital input S2IND
Chapter
„Control inputs and outputs“ X410B.4 Digital input S3IND X410B.5 CAN-Low CAN-Low (System bus) X410B.6 CAN-High CAN-High (System bus) X410B.7 GND CAN-GND (System bus)
EM-RES-03 1510/07
Page 18
5.4 Baud rate setting/line length
The setting of the baud rate must be identical in all subscribers on the system bus.
The maximum possible baud rate is based on the necessary overall line length of the system bus. The baud rate is set via the parameter
Baud-Rate 903 and thus defines
the possible line length.
Operation mode Function max. line length 3 - 50 kBaud Transmission rate 50 kBaud 1000 meters
4 - 100 kBaud Transmission rate 100 kBaud 800 meters 5 - 125 kBaud Transmission rate 125 kBaud 500 meters 6 - 250 kBaud Transmission rate 250 kBaud 250 meters 7 - 500 kBaud Transmission rate 500 kBaud 100 meters 8 - 1000 kBaud Transmission rate 1000 kBaud 25 meters
A baud rate under 50 kBaud, as defined according to CANopen, is not sensible for the
system bus as the data throughput is too low.
The maximum line lengths stated are guidelines. If they are made complete use of,
the admissible length is to be calculated on the basis of the line parameters and the bus driver (PCA82C250T)
5.5 Setting node address
A maximum of 63 slaves or frequency inverters with system bus can be operated on
the system bus. Each frequency inverter is given a node ID, which may only exist once in the system, for its unambiguous identification. The setting of the system bus node ID is done via the parameter
Node-ID 900.
Parameter Setting No. Description Min. Max. Factory setting
900 Node-ID -1 63 -1
Thus, the system bus possesses a maximum number of 63 subscribers (Network
nodes), plus one frequency inverter as a master.
Note:
With the factory setting of parameter
Node-ID 900 = -1, the system bus
is deactivated for this frequency inverter. If the
Node-ID 900 = 0 is set, the frequency inverter is defined as a
master. Only one frequency inverter on the system bus may be defined as a master.
EM-RES-03 10/0716
Page 19
The system bus produces the physical connection between the frequency inverters.
5.6 Functional overview
Logical communication channels are produced via this physical medium. These chan­nels are defined via the identifiers. As CAN does not possess a subscriber-oriented, but a message-oriented addressing via the identifiers, the logical channels can be displayed via it.
In the basic state (factory setting) the identifiers are set according to the Predefined
Connection Set of CANopen. These settings are aimed at one master serving all the channels. In order to be able to build up process data movement via the PDO chan­nels between individual or a number of inverters (transverse movement), the setting of the identifiers in the subscribers has to be adapted.
Note: The exchange of data is done message-oriented. An frequency inverter
can transmit and receive a number of messages, identified via various identifiers.
As a special feature, the properties of the CAN bus mean that the messages transmit-
ted by one subscriber can be received by a number of subscribers simultaneously. The error monitoring methods of the CAN bus result in the message being rejected by all recipients and automatically transmitted again if there is a faulty reception in one receiver.
5.7 Network management
The network management controls the start of all the subscribers on the system bus.
Subscribers can be started or stopped individually or together. For subscriber recogni­tion in a CAL or CAN open system, the slaves on the system bus generate a starting telegram (boot-up report). In the event of a fault. the slaves automatically transmit a fault report (emergency message).
For the functions of the network management, the methods and NMT telegrams
(network management telegrams) defined according to CAN open (CiA DS 301) are used.
PLC
Field bus
System bus Master
Parameter Function
SDO 2 SDO 1 PDO
System bus
Controller / PC
System bus Slave
Parameter Function
SDO 2 SDO 1 PDO
System bus
System bus
EM-RES-03 1710/07
Page 20
5.7.1 SDO channels (parameter data)
Each frequency inverter possesses two SDO channels for the exchange of parameter
data. In a slave device, these are two server SDO's, in a device defined as a master a client SDO and a server SDO. Attention must be paid to the fact that only one master for each SDO channel may exist in a system.
Note: Only one master can initiate by the system bus an exchange of data via
The identifier assignment for the SDO channels (Rx/Tx) is done according to the Pre-
defined Connection Set. This assignment can be amended by parameterization, in order to solve identifier con­flicts in a larger system in which further devices are on the CAN bus alongside the frequency inverters.
Attention: If a system in which an frequency inverter works as a master is pro-
Parameters are read/written via the SDO channels. With the limitation to the SDO
Segment Protocol Expedited, which minimizes the requirements of the parameter ex­change, the transmittable data are limited to the uint / int / long types. This permits complete parameterization of the frequency inverters via the system bus, as all the settings and practically all the actual values are displayed via these data types.
5.7.2 PDO channels (process data)
Each frequency inverter possesses three PDO channels (Rx/Tx) for the exchange of
process data.
The identifier assignment for the PDO channel (Rx/Tx) is done by default according to
the Predefined Connection Set. This assignment corresponds to an alignment to a central master control. In order to produce the logical channels between the devices (transverse movement) on the system bus, the amendment of the PDO identifiers for Rx/Tx is necessary.
Each PDO channel can be operated with time or SYNC control. In this way, the opera-
tion behavior can be set for each PDO channel:
The setting of the operation mode is done via the following parameters:
TxPDO1 Function 930, TxPDO2 Function 932 und TxPDO3 Function 934 RxPDO1 Function 936, RxPDO2 Function 937 und RxPDO3 Function 938
Operation mode Function 0 - deactivated no exchange of data via the PDO channel (Rx and/or Tx) 1 - time-controlled Tx-PDO’s cyclically transmit according to the time specifi-
2 - SYNC controlled Tx-PDO’s transmit the data from the application that are
For synchronous PDO’s, the master (PC, PLC or frequency inverter) generates the
SYNC telegram. The identifier assignment for the SYNC telegram is done by default according to the Predefined Connection Set. This assignment can be altered by parameterization.
its client SDO.
duced, the identifier allocations for the SDO channel may not be altered. In this way, an addressing of individual subscribers via the field bus/system bus path of the master frequency inverter is possible.
cation Rx-PDO‘s are read in with Ta = 1 ms and forward the data received to the application
then current after the arrival of the SYNC telegram. Rx-PDO’s forward the last data received to the application after the arrival of the SYNC telegram.
EM-RES-03 10/0718
Page 21
5.8 Master functionality
An external control or an frequency inverter defined as a master (node ID = 0) can
be used as a master. The fundamental tasks of the master are controlling the start of the network (boot-up sequence), generating the SYNC telegram and evaluating the emergency messages of the slaves. Further, there can be access to the parameterization of all the frequency inverters on the system bus by means of a field bus connection via the client SDO of the master frequency inverter.
5.8.1 Control boot-up sequence, network management
The Minimum Capability Boot-Up method defined according to CANopen is used for
the state control of the subscribers (nodes). This method knows the pre-operational, operational and stopped states.
After the initialization phase, all the subscribers are in the pre-operational state. The
system bus master transmits the NMT command Start-Remote-Node. With this command, individual nodes or all the nodes can be started together. An frequency inverter defined as a master starts all the nodes with one command. After receipt of the Start Remote Node command, the subscribers change into the Operational state. From this time on, process data exchange via the PDO channels is activated. A master in the form of a PLC/PC can start the subscribers on the system bus indi­vidually and also stop them again.
As the slaves on the system bus need different lengths of time to conclude their ini-
tialization phases (especially if external components exist alongside the frequency inverters), an adjustable delay for the change to Operational is necessary. The set­ting is done in an frequency inverter defined as a system bus master via
Delay
904.
Parameter Setting No. Description Min. Max. Factory setting 904 Boot-Up Delay 3500 ms 50000 ms 3500 ms
Properties of the states:
State Properties
Pre-Operational Parameterization via SDO channel possible
Operational Parameterization via SDO channel possible
Stopped Parameterization via SDO channel not possible
Note: Start-Remote-Node is cyclically transmitted with the set delay time by an
Boot-Up
Exchange of process data via PDO channel not possible
Exchange of process data via PDO channel possible
Exchange of process data via PDO channel not possible
frequency inverter defined as a system bus master, in order to put slaves added with a delay or temporarily separated from the network back into the Operational state.
EM-RES-03 1910/07
Page 22
Power on
(1)
Initialization
any state
Pre-Operational
(2)
(4)
(7)
(5)
Stopped
(3)
(6)
(8)
Operational
After Power On and the initialization, the slaves are in the Pre-Operational state.
The transition (2) is automatic. The system bus master (frequency inverter or PLC/PC) triggers the transition (3) to Operational state. The transitions are controlled via NMT telegrams.
The identifier used for the NMT telegrams is "0" and may only be used by the system
bus master for NMT telegrams. The telegram contains two data bytes.
Byte 0 Byte 1 CS (Command Specifier) Node-ID
Identifier = 0
With the statement of the node ID 0, the NMT command acts on the subscriber selected via the node ID. If node ID = 0, all the subscribers are addressed. If Node­ID = 0, all nodes are addressed.
Transition Command Command Specifier (3) , (6) Start Remote Node 1 (4) , (7) Enter Pre-Operational 128 (5) , (8) Stop Remote Node 2
- Reset Node 129
- Reset Communication 130
Note: A frequency inverter defined as a system bus master only transmits the
command "Start Remote Node” with node ID = 0 (for all subscribers). Transmission of the command is done after completion of the initializa­tion phase and the time delay
Boot-Up Delay 904 following it.
EM-RES-03 10/0720
Page 23
5.8.2 SYNC telegram, generation
If synchronous PDO’s have been created on the system bus, the master must send the
SYNC telegram cyclically. If an frequency inverter has been defined as a system bus master, the latter must generate the SYNC telegram. The interval for the SYNC tele­gram of an frequency inverter defined as the system bus master is adjustable. The SYNC telegram is a telegram without data.
The default identifier = 128 according to the Predefined Connection Set.
If a PC or PLC is used as a master, the identifier of the SYNC telegrams can be
adapted by parameterization on the frequency inverter. The identifier of the SYNC telegram must be set identically in all subscribers on the system bus.
Parameter Setting No. Description Min. Max. Fact. sett.
The setting of the identifier of the SYNC telegram is done via the parameter
Identifier
918.
918 SYNC-Identifier 0 2047 0
The setting "0” results in identifier assignment according to the Predefined Connection
Set.
Attention: The identifier range 129...191 may not be used as the emergency tele-
The temporal cycle for the SYNC is set on an frequency inverter defined as a system
bus master via the parameter
Note:
grams can be found there.
SYNC-Time 919.
A setting of 0 ms for the parameter telegram”.
SYNC-
SYNC-Time 919 means "no SYNC
EM-RES-03 2110/07
Page 24
5.8.3 Emergency message, reaction
If a slave on the system bus suffers a fault, it transmits the emergency telegram. The
emergency telegram marks the node ID for the identification of the failed node via its identifier and the existing fault message via its data contents (8 bytes).
After a fault has been acknowledged on the slave, the latter again transmits an emer-
gency telegram with the data content zero.
The emergency telegram has the identifier 128 + node ID ( = 129 ... 191)
The system bus master evaluates the emergency telegrams of the slaves. Its reaction
to an emergency telegram can be set with
Operation mode Function 0 - Error The system bus master receives the emergency
1 - No Error Das Emergency Telegram is displayed as a warn-
Operation mode - parameter 989 = 0 – Error
Behavior of the system bus master in
As soon as the system bus master receives an emergency telegram, it also switches
to failure mode and reports the failed subscriber on the basis of its ID via the kind of error. Only the subscriber is reported, not the cause of the error.
The fault message on the system bus master via = node ID (hexadecimal) of the slave in which a fault switch-off exists. In addition, the system bus master reports the warning Sysbus (0x2000) via the pa­rameter
Warnings 270 Bit 13.
If a fault switch-off occurs on a number of slaves, the first slave to transmit its emer-
gency telegram is displayed on the system bus master.
Operation mode - parameter 989 = 1 – No Error
Behavior of system bus master in the case of Error:
As soon as the system bus master receives an emergency telegram, it reports the
warning Sysbus (0x2000) via the parameter
Note: In both cases, the Boolean variable SysbusEmergency with source num-
Emergency Reaction 989.
telegram and switches-off
ing
Emergency Reaction 989 = 0 / Error:
Current error 260 is 21nn with nn
Emergency Reaction 989 = 1 / No
Warnings 270 Bit 13.
ber 730 is set to TRUE in the system bus master. It can be used in the system bus master and (in transmission via a TxPDO) in the slaves for a defined shutdown. SysbusEmergency is also set if the system bus master breaks down. Resetting of SysbusEmergency is done with the fault acknowledgment.
EM-RES-03 10/0722
Page 25
5.8.4 Client SDO (system bus master)
Each subscriber on the system bus can be addressed via the SDO channels. In this
way, each subscriber can be addressed and parameterized by one master via its cli­ent SDO1. All the parameters of the data types uint/int/long are accessible. String parameters can not be processed. If an frequency inverter has been defined as a system bus master, each subscriber on the system bus in this frequency inverter can
Note: The second SDO channel SDO2 of the frequency inverters is planned for
The service used is SDO Segment Protocol Expedited according to CANopen. An fre-
be addressed by means of a field bus connection (RS232, RS485, Profibus-DP) via its client SDO1.
quency inverter defined as a system bus master automatically generates the correct telegrams. If the SDO channel is operated via a PLC/PC on the system bus, the tele­grams must be generated according to the specification.
PLC
Field bus
the parameterization of the frequency inverters via a visualization tool on the system bus.
Inv.1 Inverter 2 Inverter 2
Field bus
Client-SDO 1
Inverter 1
Server-SDO 2
Client-SDO 2
Visualizationtool
Server-SDO 1
Server-SDO 1
Inverter 2 Inverter 2
Server-SDO 2
Server-SDO 2
System bus
System bus
EM-RES-03 2310/07
Page 26
After the initialization, each slave on the system bus transmits its boot-up message
5.9 Slave functionality
5.9.1 Implement boot-up sequence, network management
5.9.1.1 Boot-up message
(heartbeat message).
Note: The boot-up telegram has the identifier 1792 + node ID and a data byte
with contents = 0x00.
This telegram is of importance if a PLC/PC with CANopen functionality is used as a
master. An frequency inverter defined as a system bus master does not evaluate the boot-up message.
5.9.1.2 Status control
The identifier used for the NMT telegrams is "0" and may only be used by the system
bus master for NMT telegrams. The telegram contains two data bytes.
Byte 0 Byte 1 CS (Command Specifier) Node-ID
Identifier = 0
With the statement of the node ID 0, the NMT command acts on the subscriber se­lected via the node ID. If node ID = 0, all the subscribers are addressed. If Node-ID = 0, all nodes are addressed.
Transition Command Command Specifier (3),(6) Start Remote Node 1 (4),(7) Enter Pre-Operational 128 (5),(8) Stop Remote Node 2
- Reset Node 129
- Reset Communication 130
Attention: The reset node and reset communication command specified according
to DS 301 lead to a change to Pre-Operational via Initialization in the frequency inverters. There is a new boot-up message.
After a slave has received the command "Start Remote Node”, it activates the PDO
channels and is ready for the exchange of process data.
EM-RES-03 10/0724
Page 27
5.9.2 Process SYNC telegram
If synchronous PDO’s have been created in an frequency inverter, their processing is
synchronized with the SYNC telegram. The SYNC telegram is generated by the system bus master and is a telegram without data.
The identifier is 128 according to the Predefined Connection Set.
If a PC or PLC is used as a master, the identifier of the SYNC telegrams can be
adapted by parameterization on the frequency inverter. The identifier of the SYNC telegram must be set identically in all subscribers on the system bus.
Attention: The identifier range 129 ... 191 may not be used as the emergency tele-
grams can be found there.
The setting of the identifier of the SYNC telegram is done via the parameter
Identifier
918.
SYNC-
Parameter Setting No. Description Min. Max. Factory setting 918 SYNC-Identifier 0 2047 0
The setting "0” results in identifier assignment according to the Predefined Connection
Set.
The data of the Rx-PDO’s are forwarded to the application after the arrival of the SYNC
telegram. At the same time, the Tx-PDO’s with the currently available data from the application are sent.
SYNC
SYNC
RxPDO's RxPDO'sTxPDO's TxPDO's
Zeit
This method enables pre-occupancy of set points in the system bus subscribers and a
synchronous / parallel take-over of the data.
EM-RES-03 2510/07
Page 28
5.9.3 Emergency message, fault switch-off
As soon as a fault switch-off occurs in a slave frequency inverter, the emergency
telegram is transmitted. The emergency telegram marks the node ID for the identifi­cation of the failed node via its identifier and the existing fault message via its data contents (8 bytes).
The emergency telegram has the identifier 128 + node ID.
After a fault acknowledgment, another emergency telegram is transmitted, with the
data content (Byte 0 ...7) being set to "0" this time. This identifies the subscriber's repeated readiness for operation. If a further fault occurs subsequently, it is transmit­ted in a new emergency telegram.
The acknowledgment sequence is based on the definitions according to CANopen.
Data contents of the emergency telegram:
Emergency telegram Byte Value Meaning 0 0x00 low-byte Error-Code 1 0x10 high-byte Error-Code 2 0x80 Error-Register 3 0x00 - 4 0x00 - 5 0x00 - 6 0xnn internal Error-Code, low-byte 7 0xmm internal Error-Code, high-byte
Bytes 0, 1 and 2 are firmly defined and compatible with CANopen.
Bytes 6/7 contain the product specific VECTRON error code.
Error-Code = 0x1000 = general error Error-Register = 0x80 = manufacturer-specific error
The explanation and description of the product-specific VECTRON error code can be
found in the annex "Error messages".
EM-RES-03 10/0726
Page 29
The communication channel for the exchange of parameter data is the SDO channel.
5.9.4 Server SDO1/SDO2
Communication works according to the client/server model. The server is the sub­scriber holding the data (here the frequency inverter), the client the subscriber re­questing or wanting to alter the data (PLC, PC or frequency inverter as system bus master).
For the frequency inverter, two server SDO channels have been implemented.
The first SDO channel SDO1 is used for the parameterization of the PLC/PC as a mas­ter or frequency inverter with field bus connection as a system bus master. The second SDO channel SDO2 is reserved for a visualization tool for parameteriza­tion. An exchange of data can only be implemented by the master via a client SDO.
The SDO channels are stipulated for the server SDO’s via identifiers according to the
Predefined Connection Set to CANopen. As CANopen only provides for and defines one SDO channel in the Predefined Connection Set, the second SDO channel can be deac­tivated. In addition, the number of system bus subscribers ad and the adjustable node ID are limited to 63.
Identifier assignment according to the Predefined Connection Set:
Identifier Rx-SDO = 1536 + Node-ID (Node-ID = 1 ... 127, Identifier = 1537 ...
1663)
Identifier Tx-SDO = 1408 + Node-ID (Node-ID = 1 ... 127, Identifier = 1409 ...
1535)
Identifier assignment for SDO1/SDO2 compatible with the Predefined Con-
nection Set:
Identifier Rx-SDO1 = 1536 + Node-ID (Node-ID = 1 ... 63, Identifier = 1537 ...
1599)
Identifier Tx-SDO1 = 1408 + Node-ID (Node-ID = 1 ... 63, Identifier = 1409 ...
1471)
Identifier Rx-SDO2 = 1600 + Node-ID (Node-ID = 0 ... 63, Identifier = 1600 ...
1663)
Identifier Tx-SDO2 = 1472 + Node-ID (Node-ID = 0 ... 63, Identifier = 1472 ...
1535)
This corresponds to the factory settings of the frequency inverters for the SDO‘s.
The node ID = 0 for SDO2 is the system bus master.
Attention: The SDO2 must be deactivated in a CANopen system in order not to
generate any compatibility problems.
If an frequency inverter has been defined as the system bus master, the above set-
tings for the SDO1 must be maintained in all the frequency inverters. In this way, ac­cess to the parameterization of the frequency inverters via a field bus connection on the master frequency inverter is possible. The client SDO1 in the master frequency inverter addresses the server SDO1 of the slaves via the above identifiers.
Attention: The identifiers for a visualization tool on the second SDO channel SDO2
cannot be changed.
EM-RES-03 2710/07
Page 30
If a PC or a PLC is used as a master, the identifiers of the Rx/Tx-SDO1 can be
adapted by parameterization on the frequency inverter.
Attention: In free assignment of identifiers, there may not be any double occu-
pancy !
The identifier range 129...191 may not be used as the emergency tele­grams can be found there.
The setting of the identifiers of the RxSDO1 is done via the parameter
Identifier
921.
RxSDO1-
Parameter Setting No. Description Min. Max. Fact. sett. 921 RxSDO1-Identifier 0 2047 0
The setting of the identifiers of the TxSDO1 is done via parameter number 922.
Parameter Setting No. Description Min. Max. Fact. sett. 922 TxSDO1-Identifier 0 2047 0
The setting "0” results in identifier assignment according to the Predefined Connec-
tion Set.
The second SDO channel can be deactivated via the
SDO2 Set Active 923.
Operation mode Function 0 - SDO2 deactivated Communication channel deactivated 1 - SDO2 activated Communication channel activated for the visuali-
zation tool
The identifier assignment for the second SDO channel is always to the
specification:
Identifier Rx-SDO2 = 1600 + Node-ID Identifier Tx-SDO2 = 1472 + Node-ID
Note: In this way, firm identifiers via which communication takes place are
available for the visualization tool.
EM-RES-03 10/0728
Page 31
5.10 Communication channels, SDO1/SDO2
The service used for the exchange of parameter data is SDO Segment Protocol
Access to the parameters in the frequency inverters with a statement of parameter
The data to be transmitted have a length of 2 bytes for uint/int and 4 bytes for long.
The data are on bytes 4...7 of the SDO telegram.
- uint/int variables are transmitted in bytes 4 and 5
- long variables are transmitted in bytes 4...7.
Writing parameters:
0x22 LSB MSB 0xnn LSB MSB
0x60 LSB MSB 0xnn 0
0x80 LSB MSB 0xnn Code 0 0 0
The error code is stated in byte 4 in a faulty reading process.
Attention: Control byte 0x22 for the identification "SDO Download expedited” does
5.10.1 SDO telegrams (SDO1/SDO2)
Expedited. The data (type uint, int, long) are exchanged in a telegram.
number and data set is displayed via the addressing defined for object access pursu­ant to the specifications of CANopen via Index/Sub-Index. Index = parameter number / Sub index = data set.
As standardization and simplification, 4 bytes are always transmitted.
with bytes 6 und 7 = 0.
Client Î Server
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
uint/int LSB MSB 0x00 0x00
long LSB ... ... MSB
Server Î Client Download Response Î Writing process free of errors
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
Server Î Client Abort SDO Transfer Î Writing process faulty
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
(see Table, failure codes).
SDO Download (expedited)
not consider the bits "s” (data size indicated) and "n” (number of bytes not containing data). If set, they are ignored. The user is responsible for the number of bytes matching the type of data.
EM-RES-03 2910/07
Page 32
Reading parameters:
Client Î Server
SDO Upload (expedited)
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
0x40 LSB MSB 0xnn 0
Server Î Client Upload Response Î Reading process free of errors
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
0x42 LSB MSB 0xnn LSB MSB
uint/int LSB MSB 0x00 0x00
long LSB ... ... MSB
Server Î Client Abort SDO Transfer Î Reading process faulty
0 1 2 3 4 5 6 7
Ctrl. byte Parameter number Data set Data
0x80 LSB MSB 0xnn Code 0 0 0
The error code is stated in byte 4 in a faulty reading process.
(see Table, failure codes).
failure codes Code Description 1 inadmissible parameter figure 2 inadmissible data set 3 parameter not readable 4 parameter not writable 5 reading error EEPROM 6 writing error EEPROM 7 checksum error EEPROM 8 parameter cannot be written during running drive 9 values of the data sets differ 10 parameter of wrong type 11 unknown parameter 12 BCC error in VECTRON bus protocol 15 unknown error 20 system bus subscriber not available only in access via
field bus connection
21 string parameter not admissible only in access via VEC-
TRON bus protocol
Errors marked in the table are generated by the field bus side, not in the Abort SDO
Transfer of the system bus.
EM-RES-03 10/0730
Page 33
5.10.2 Communication via field bus connection (SDO1)
If an frequency inverter has been defined as the system bus master and equipped with
a field bus interface, access to the parameterization of all the subscribers in existence on the system bus is possible by means of this field bus interface via the first SDO channel (SDO1). An extension has been created in the protocol frame of the field buses for this purpose.
Attention: The prerequisite for this mechanism is that the identifier setting for the
first SDO channel (SDO1) corresponds to the Predefined Connection Set. The parameter addressed must also be existent in the system bus mas­ter.
5.10.2.1 Profibus-DP
If an object with communication channel (PKW) is used in Profibus-DP, access to all
the other subscribers on the system bus can be done via it. The structure of the com­munication channel permits an additional addressing of a system bus subscriber. This is done by the use of an unused byte in the communication channel.
Communication channel PKW
0 1 2 3 4 5 6 7
PKE Index - Data
AK/SPM Parameter
number
Data set Node-ID
system bus
Byte 3 is used to transmit the node ID of the required subscriber on the system bus. If
byte 3 = 0, the master inverter of the system bus is addressed. The display is binary (0...63).
5.10.2.2 RS232/RS485 with VECTRON bus protocol
In the VECTRON bus protocol, there is a byte in the telegram header that is always
transmitted with 0 as a standard feature.
ENQUIRY
0 1 2 3 4 5 6 Address 0 p n n n ENQ
Node-ID
Data set Parameter number
system bus
SELECT
0 1 2 3 4 Address STX 0 p n n n ... Node-ID
Data set Parameter number
System bus
Byte 1 in the enquiry and byte 2 in the select telegram are not defined and are used to
transmit the node ID of the required subscriber on the system bus. If this byte = 0, the master inverter of the system bus is addressed. The display is ASCII corresponding to the conventions for the display of the address in the VECTRON bus protocol.
Note: If there is an NAK fault message, the error is to be read out from the
system bus master with node ID = 0 via parameter 11.
EM-RES-03 3110/07
Page 34
Display of node ID system bus in the VECTRON bus protocol:
System bus Node-ID System bus
address
(ASCII-)
character
HEX value System bus
address
(ASCII-)
character
HEX value
1 A 41 31 _ 5F 2 B 42 32 ` 60 3 C 43 33 a 61 4 D 44 34 b 62 5 E 45 35 c 63 6 F 46 36 d 64 7 G 47 37 e 65 8 H 48 38 f 66 9 I 49 39 g 67 10 J 4A 40 h 68 11 K 4B 41 i 69 12 L 4C 42 j 6A 13 M 4D 43 k 6B 14 N 4E 44 l 6C 15 O 4F 45 m 6D 16 P 50 46 n 6E 17 Q 51 47 o 6F 18 R 52 48 p 70 19 S 53 49 q 71 20 T 54 50 r 72 21 U 55 51 s 73 22 V 56 52 t 74 23 W 57 53 u 75 24 X 58 54 v 76 25 Y 59 55 w 77 26 Z 5A 56 x 78 27 [ 5B 57 y 79 28 \ 5C 58 z 7A 29 ] 5D 59 { 7B 30 ^ 5E 60 | 7C 61 } 7D 62 ~ 7E 63
7F
EM-RES-03 10/0732
Page 35
5.11 Process data channels, PDO
5.11.1 Identifier assignment process data channel
The process channel for the exchange of process data under CANopen is the PDO
channel. Up to three PDO channels with differing properties can be used in one device.
The PDO channels are defined via identifiers according to the Predefined Connection
Set to CANopen:
Identifier 1. Rx-PDO = 512 + Node-ID Identifier 1. Tx-PDO = 384 + Node-ID
Identifier 2. Rx-PDO = 768 + Node-ID Identifier 2. Tx-PDO = 640 + Node-ID
Identifier 3. Rx-PDO = 1024 + Node-ID Identifier 3. Tx-PDO = 896 + Node-ID
This corresponds to the factory settings of the frequency inverters for the Rx/Tx-
PDO‘s. This occupancy is aligned to an external master (PLC/PC) serving all the chan­nels. If the PDO channels are used for a connection of the frequency inverters amongst one another, the identifiers are to be set accordingly by parameterization.
Attention: In free assignment of identifiers, there may not be any double occu-
pancy!
The identifier range 129...191 may not be used as the emergency tele­grams can be found there.
Setting of the identifiers of the Rx/TxPDO’s:
Parameter Setting No. Description Min. Max. Fact. sett. 924 RxPDO1 Identifier 0 2047 0 925 TxPDO1 Identifier 0 2047 0 926 RxPDO2 Identifier 0 2047 0 927 TxPDO2 Identifier 0 2047 0 928 RxPDO3 Identifier 0 2047 0 929 TxPDO3 Identifier 0 2047 0
The setting "0” results in identifier assignment according to the Predefined Connection
Set.
EM-RES-03 3310/07
Page 36
5.11.2 Operation modes process data channel
The transmit/receive behavior can be time controlled or controlled via a SYNC tele-
gram. The behavior can be parameterized for each PDO channel.
Tx-PDO’s can work time controlled or SYNC controlled. A time controlled TxPDO
transmits its data at the interval of time set. A SYNC controlled TxPDO transmits its data after the arrival of a SYNC telegram.
RxPDO’s in the time controlled setting forward the received data to the application
immediately. If an RxPDO has been defined as SYNC controlled, its forwards its re­ceived data to the application after the arrival of a SYNC telegram.
Settings TxPDO1/2/3
Parameter Setting No. Description Min. Max. Fact. sett. 931 TxPDO1 Time 1 ms 50000 ms 8 ms 933 TxPDO2 Time 1 ms 50000 ms 8 ms 935 TxPDO3 Time 1 ms 50000 ms 8 ms
The setting of the operation mode is done via the following parameters:
TxPDO1 Function 930, TxPDO2 Function 932 und TxPDO3 Function 934
Operation mode Function 0 - Not Active No data are sent. 1 - Controlled by time In the cycle of the adjusted time interval the data
are sent.
2 - Controlled by SYNC To arrival of a SYNC telegram the data are sent.
Settings RxPDO1/2/3
The setting of the operation mode is done via the following parameters:
RxPDO1 Function 936, RxPDO2 Function 937 und RxPDO3 Function 938
Operation mode Function 0 - Controlled by time The received data are passed on immediately. 1 - Controlled by SYNC After arrival of a SYNC telegram the received
data are passed on.
Note: In the "controlled by time” operation mode, there is a polling of the re-
ceived data with the trigger cycle of Ta = 1 ms.
EM-RES-03 10/0734
Page 37
5.11.3 Timeout monitoring process data channel
Each frequency inverter monitors its received data for whether they are updated
within a defined time window. The monitoring is done onto the SYNC telegram and the RxPDO channels.
Monitoring SYNC / RxPDO‘s
Parameter Setting No. Description Min. Max. Fact. sett. 939 SYNC Timeout 0 ms 60000 ms 0 ms 941 RxPDO1 Timeout 0 ms 60000 ms 0 ms 942 RxPDO2 Timeout 0 ms 60000 ms 0 ms 945 RxPDO3 Timeout 0 ms 60000 ms 0 ms
Setting "0" means no timeout monitoring.
Attention: There is only monitoring for the SYNC telegram if at least one RxPDO or
one TxPDO channel is defined as SYNC controlled.
If a timeout period is exceeded, the frequency inverter switches to failure mode and reports one of the faults:
F2200 System bus Timeout SYNC
F2201 System bus Timeout RxPDO1 F2202 System bus Timeout RxPDO2 F2203 System bus Timeout RxPDO3
EM-RES-03 3510/07
Page 38
5.11.4 Communication relationships of the process data channel
Regardless of the process data to be transmitted, the communication relationships of
the process data channels must be defined. The connection of PDO channels is done via the assignment of the identifiers. The identifiers of Rx-/Tx-PDO must match in each case.
There are two principal possibilities:
- one Rx-PDO to one Tx-PDO (one to one)
This process is documented in a tabular form via a communication relationship
- connect several Rx-PDO’s to one TxPDO (one to many)
list.
Example:
Frequency inverter 1 Frequency inverter 2 Frequency inverter 3 PDO Identifier PDO Identifier PDO Identifier TxPDO1 385 TxPDO1 TxPDO1 RxPDO1 RxPDO1 385 RxPDO1 385 TxPDO2 641 TxPDO2 TxPDO2 642 RxPDO2 RxPDO2 641 RxPDO2 TxPDO3 TxPDO3 TxPDO3 RxPDO3 RxPDO3 642 RxPDO3
Attention: All the TxPDO’s used must have different identifiers !!!
Frequency inverter 1
The Identifier must be clear in the system bus network.
Frequency inverter 2
Frequency inverter 3
PDO1
Rx
Tx
385
PDO2
Rx
641
Tx
PDO3
Rx
Tx
PDO1
Rx
Tx
PDO2
Rx Tx
385 641
EM-RES-03 10/0736
PDO3
Rx Tx
PDO1
Rx
385642
Tx
PDO2
Rx Tx
642
PDO3
Rx Tx
Page 39
5.11.5 Virtual links
A PDO telegram contains 0 ...8 data bytes according to CANopen. A mapping for any
kind of objects can be done in these data bytes.
For the system bus, the PDO telegrams are firmly defined with 8 data bytes. The
mapping is not done via mapping parameters as with CANopen, but via the method of sources and links.
Each function provides its output data via a source. These sources are defined via
source numbers. The input data of functions are defined via parameters. The link of a data input to a data output is done via the assignment of parameters to source num­bers.
Example 1:
Function A
Source
No. 27
Function C
Parameter 125
Function B
Parameter 187
Source--
In example 1, the two inputs of function C are connected to the outputs of functions
A and B. The parameterization for this connection is thus:
Function C Parameter 125 = Source-No. 27 Parameter 187 = Source-No. 5
Example of a virtual connection in VPlus:
No. 5
Parameter
(Softwarefunction)
Source-No.
(Operation mode)
e.g.
Start-clockwise
068
e.g. 71-S2IND
Digital input
The assignment of the operation modes to the software functions available can be
adapted to the application in question.
EM-RES-03 3710/07
Page 40
For the system bus, the input data of the TxPDO’s are also displayed as input pa-
rameters and the output data of the RxPDO’s as sources.
Example 2:
Function A Inverter 1
TxPDO Inverter 1
Source-No. 27
Parameter 977
system bus Function B Inverter 1
Source-No. 5
RxPDO Inverter 2
Source-No. 727
Parameter 972
Function C Inverter 2
Parameter 125
system bus
Source-No. 724
Parameter 187
Example 2 displays the same situation as Example 1. But now, the functions A and B
are in frequency inverter 1 and function C in frequency inverter 2. The connection is done via a TxPDO in frequency inverter 1 and a RxPDO in frequency inverter 2. Thus, the parameterization for this connection is:
Frequency inverter 1 Parameter 977 = Source-No. 27 Parameter 972 = Source-No. 5
Frequency inverter 2 Parameter 125 = Source-No. 727 Parameter 187 = Source-No. 724
As the links with the system used exceed the device limits, they are termed "virtual
links".
EM-RES-03 10/0738
Page 41
The virtual links with the possible sources are related to the Rx/TxPDO channels. For
this purpose, the eight bytes of the Rx-/TxPDO’s are defined structured as inputs and sources. This exists for each of the three PDO channels.
Each transmit PDO and receive PDO can be occupied as follows:
4 Boolean variables
or
4 uint/int variables
or
2 long variables
or
a mixture paying attention to the eight bytes available
Assignment data type / number of bytes:
Assignment Data type Length Boolean 2 Bytes uint/int 2 Bytes long 4 Bytes
EM-RES-03 3910/07
Page 42
5.11.5.1 Input parameters of the TxPDO’s for data to be transmitted
The listed parameters can be used to stipulate the data that are to be transported
there for each position in the TxPDO telegrams. The setting is done in such a way that a source number is entered for the required data in the parameters.
TxPDO1
Byte
0 0 0
1
2 2 2
3 4 4 4 5 6 6 6
7
TxPDO2
Byte
0 0 0
1 2 2 2
3 4 4 4 5 6 6 6 7
TxPDO3
Byte
0 0 0
1 2 2 2
3 4 4 4 5 6 6 6
7
Note: Depending on the selected data information the percentages values are
P. No.
TxPDO1
Boolean
input
Byte
946
Boolean1
1
947
Boolean2
3
948
Boolean3
5
949
Boolean4
P. No.
7
TxPDO2
Boolean
input
Byte
956
Boolean1
1
957
Boolean2
3
958
Boolean3
5
959
Boolean4
P. No.
7
TxPDO3
Boolean
input
Byte
966
Boolean1
1
967
Boolean2
3
968
Boolean3
5
969
Boolean4
7
displayed via the uint/int inputs.
P. No.
uint/int
input
950
Word1
951
Word2
952
Word3
953
Word4
P. No.
uint/int
input
960
Word1
961
Word2
962
Word3
963
Word4
P. No.
uint/int
input
972
Word1
973
Word2
974
Word3
975
Word4
TxPDO1
Byte
1
3
5
7
TxPDO2
Byte
1
3
5
7
TxPDO3
Byte
1
3
5
7
P. No.
long input
954
Long1
955
Long2
P. No.
long input
964
Long1
965
Long2
P. No.
long input
976
Long1
977
Long2
EM-RES-03 10/0740
Page 43
With this method, there are up to three possibilities for a meaning of the contents of
the individual bytes. Each byte may only be used for one possibility.
To ensure this, the processing of the input links is derived from the setting.
If an input link has been set to the fixed value of zero, it is not processed.
The settings for the fixed value zero are:
Source = 7 (FALSE) for Boolean variables Source = 9 (0) for uint, int, long variables
This is simultaneously the factory setting.
Examples Boolean source
Boolean source
Source Data
6 TRUE 7 FALSE 70 Contact input 1 71 Contact input 2 72 Contact input 3 161 Running message 163 Nominal figure reached 164 Set frequency reached (P. 510)
Examples uint/int source
unit/int source
Source Data
9 0 63 Reference percentage 1 64 Reference percentage 2 52 Percentage MFI1 133 Output percentage ramp 137 Output reference percentage
channel
138 Output actual percentage chan-
nel 740 Control word 741 State word
Examples long source
long source
Source Data
9 0 0 Output frequency ramp 1 Fixed frequency 1 5 Reference line value 62 Output frequency reference
value channel
50 Reference frequency MFI1
EM-RES-03 4110/07
Page 44
5.11.5.2 Source numbers of the RxPDO’s for received data
Equivalent to the input links of the TxPDO’s, the received data of the RxPDO’s are
displayed via sources or source numbers. The sources existing in this way can be used in the frequency inverter via the local input links for the data targets.
RxPDO1
Byte
0 0 0
1
2 2 2
3 4 4 4 5 6 6 6
7
RxPDO2
Byte
0 0 0
1 2 2 2
3 4 4 4 5 6 6 6
7
RxPDO3
Byte
0 0 0
1 2 2 2
3 4 4 4 5 6 6 6
7
Source No.
Boolean
value
700
Boolean1
701
Boolean2
702
Boolean3
703
Boolean4
Source No.
Boolean
value
710
Boolean1
711
Boolean2
712
Boolean3
713
Boolean4
Source No.
Boolean
value
720
Boolean1
721
Boolean2
722
Boolean3
723
Boolean4
RxPDO1
Byte
1
3
5
7
RxPDO2
Byte
1
3
5
7
RxPDO3
Byte
1
3
5
7
Source No.
uint/int
value
704
Word1
705
Word2
706
Word3
707
Word4
Source No.
uint/int
value
714
Word1
715
Word2
716
Word3
717
Word4
Source No.
uint/int
value
724
Word1
725
Word2
726
Word3
727
Word4
RxPDO1
Byte
1
3
5
7
RxPDO2
Byte
1
3
5
7
RxPDO3
Byte
1
3
5
7
Source No.
long-
Value
708
Long1
709
Long2
Source No.
long
value
718
Long1
719
Long2
Source No.
long
value
728
Long1
729
Long2
With this method, there are up to three possibilities for a meaning of the contents of
the individual bytes. Each byte may only be used for one possibility.
Note: Depending on the selected data information the percentages values are
displayed via the uint/int inputs.
EM-RES-03 10/0742
Page 45
5.11.5.3 Examples of virtual links
Frequency inverter 1 Frequency inverter 2 Source
Example 1:
- No.
word
740
2 2 3 3 4 4 5 5 6 6
Output reference frequency channel 62
Parameter 950 = Source-No. 740 Parameter 99 = Source-No. 704 Parameter 955 = Source-No. 62 Parameter 137 = Source-No. 709
The control word of frequency inverter 1 is linked with the control word of frequency
inverter 2. In this way, both frequency inverters can be operated synchronously via the remote control. The output of the reference value channel of frequency inverter 1 is laid onto the output of the ramp of frequency inverter 2. In this way, both fre­quency inverters have a joint source of reference values and are given reference values in the internal notation.
As an extension, a number of frequency inverters can also exist on the receive side
(Rx), these then being supplied with data parallel and simultaneously.
The input link not used in the TxPDO1 of frequency inverter 1 is on ZERO and is thus
not served.
Example 2:
Example of a virtual link with transmission via the system bus:
Input link TxPDO1
Byte
950
0 0 Control 1
955
7
TxPDO1 Identifier
925
Parameter
RxPDO1
Byte
1
7
385
Identifier
Source
- No.
704 Control in-
put, Control word 99
709 Ramp input,
Line set value 137
Inverter 1
Target
system bus
TxPDO1 Boolean1
Parameter
RxPDO1 Identifier
Parameter
Start-clockwise
Parameter
EM-RES-03 4310/07
924
068
946
71-S2IND
Source-No.
385
Inverter 2
Identifier
700-RxPDO1 Boolean
Source-No.
Page 46
5.12 Control parameters
For the monitoring of the system bus and the display of the internal states, two con-
trol parameters are provided. There is a report of the system bus state and a report of the CAN state via two actual value parameters.
The parameter tional, Stopped state. A PDO transfer is only possible in the Operational state. The state is controlled by the system bus master (PLC / PC / frequency inverter) via NMT telegrams.
The parameter layer. If there are transmission errors, the state changes from OKAY to WARNING until the cancellation of the communication with BUS-OFF. After BUS-OFF, the CAN controller is automatically re-initialized and the system bus started again.
Note: If the BUS-OFF state occurs, the frequency inverter breaks down with
After Bus-OFF, the system bus in the frequency inverter is completely reinitialized.
There is a new boot-up message from the subscriber and an emergency telegram with the Bus-OFF message is transmitted. The change of state of the subscriber to Operational is done by the Start-Remote-Node telegram cyclically sent by the system bus master.
Actual values of the system bus No. Description Display 978 Node-State 1 - Pre-Operational
979 CAN-State 1 - OKAY
Node-State 978 gives information about the Pre-Operational, Opera-
CAN-State 979 gives information about the state of the physical
"F2210 BUS-OFF".
2 - Operational 3 - Stopped
2 - WARNING 3 - BUS-OFF
EM-RES-03 10/0744
Page 47
5.13 Handling of the parameters of the system bus
As soon as the system bus expansion module EM-SYS exists in an frequency inverter,
the actual value parameters for system state and bus state are activated and can be observed in the actual value menu VAL of the control unit KP500 or with the VPlus PC program in the menu Actual values \ Systembus.
Note: The actual value parameters are on control level 3 and are thus available
for the user at any time.
All the setting parameters for the configuration of the system bus are not directly ac-
cessible for the user. For defined customer applications, pre-defined XPI files can be generated by VECTRON for the VPlus PC program, with which the necessary parame­ters are visible for the user. The application-relevant variables are then available in these XPI files.
Note: XPI files can be read in addition to the loaded parameter information of
The method of working via an XPI file has its reasoning in the fact that deep interven-
tions in the system are possible via the system bus and can lead to serious problems in the application with an untrained user. Via the XPI files, a user is given a selection list pre-defined by VECTRON.
Attention: The configuration of the necessary parameters for the system bus is
Experienced users have complete access to all the existing sources and possible input
links with the XPI file of the active functions. The selection depends on the selected configuration and control procedure.
the frequency inverter into the VPlus PC program. In the menu of the software under the point "Edit" you find the com­mand "Read in XPI file".
accessible by a XPI file with the help of the VPlus PC program. The control unit KP500 does not support this functionality. If the extension module system bus EM-SYS is installed additionally to a communication module for the field bus connection (CM-232, CM-485 or CM-PDP) in the frequency inverter, the parameterization can be made with the interface adapter KP232.
EM-RES-03 4510/07
Page 48
The display of the parameters when using the XPI file is according to the following
structure:
System bus Basic Settings 900 Node-ID 903 Baud-Rate
Master Functions 904 Boot-Up Delay 919 SYNC-Time
SYNC-Identifier 918 SYNC-Identifier
SDO1-Identifier 921 RxSDO1-Identifier 922 TxSDO1-Identifier
SDO2 Set Active 923 SDO2 Set Active
PDO-Identifier 924 RxPDO1-Identifier 925 TxPDO1-Identifier 926 RxPDO2-Identifier 927 TxPDO2-Identifier 928 RxPDO3-Identifier 929 TxPDO3-Identifier
TxPDO-Function 930 TxPDO1 Function 931 TxPDO1 Time 932 TxPDO2 Function 933 TxPDO2 Tome 934 TxPDO3 Function 935 TxPDO3 Time
RxPDO-Function 936 RxPDO1 Function 937 RxPDO2 Function 938 RxPDO3 Function
Timeout 939 SYNC Timeout 941 RxPDO1 Timeout 942 RxPDO2 Timeout 945 RxPDO3 Timeout
TxPDO1 Objects 946 TxPDO1 Boolean1 947 TxPDO1 Boolean2 948 TxPDO1 Boolean3 949 TxPDO1 Boolean4 950 TxPDO1 Word1 951 TxPDO1 Word2 952 TxPDO1 Word3 953 TxPDO1 Word4 954 TxPDO1 Long1 955 TxPDO1 Long2
TxPDO2 Objects 956 TxPDO2 Boolean1 957 TxPDO2 Boolean2 958 TxPDO2 Boolean3 959 TxPDO2 Boolean4 960 TxPDO2 Word1 961 TxPDO2 Word2 962 TxPDO2 Word3 963 TxPDO2 Word4 964 TxPDO2 Long1 965 TxPDO2 Long2
TxPDO3 Objects 966 TxPDO3 Boolean1 967 TxPDO3 Boolean2 968 TxPDO3 Boolean3 969 TxPDO3 Boolean4 972 TxPDO3 Word1 973 TxPDO3 Word2 974 TxPDO3 Word3 975 TxPDO3 Word4 976 TxPDO3 Long1 977 TxPDO3 Long2
Actual values System bus 978 Node-State 979 CAN-State
EM-RES-03 10/0746
Page 49
5.14 Ancillaries
For the planning of the system bus according to the drive tasks in question, there are
ancillaries in the form of tables.
The planning of the system bus is done in three steps:
1. Definition of the communication relationships
2. Production of the virtual links
3. Capacity planning of the system bus
The priority assignment of the identifiers is relevant for the definition of the commu-
nication relationships. Data that are to be transmitted with a higher priority must be given low identifiers. This results in the message with the higher priority being trans­mitted first with a simultaneous access of two subscribers to the bus.
Note: The recommended identifier range for the communication relationships
via the PDO channels is 385 ...
The identifiers below 385 are used for the NMT telegrams (boot-up se-
quence, SYNC telegram) and emergency message.
The identifiers above 1407 are used for the SDO channel for parameteri-
zation.
EM-RES-03 4710/07
Page 50
5.14.1 Definition of the communication relationships
The communication relationships are planned and documented with the help of the table. The table is available as a Microsoft Word document "kbl.doc" on the VECTRON product CD or upon request.
________
________
________
________
Node-ID:
________
Node-ID:
________
PDO Identifier
PDO Identifier
TxPDO1
RxPDO1
TxPDO2
RxPDO2
TxPDO3
RxPDO3
TxPDO1
RxPDO1
TxPDO2
RxPDO2
TxPDO3
RxPDO3
________
________
Inverter: Inverter: Inverter:Inverter:Inverter:
Node-ID:
________
Node-ID:
________
Node-ID:
PDO Identifier
TxPDO1
RxPDO1
TxPDO2
RxPDO2
TxPDO3
RxPDO3
PDO Identifier
TxPDO1
RxPDO1
TxPDO2
RxPDO2
TxPDO3
RxPDO3
PDO Identifier
TxPDO1
RxPDO1
TxPDO2
RxPDO2
TxPDO3
RxPDO3
EM-RES-03 10/0748
Page 51
The virtual links are planned and documented with the help of the table. The table is
5.14.2 Production of the virtual links
available as a Microsoft Word document "vvk.doc" on the VECTRON product CD or upon request.
No.
Source-
________
: ___________________________
Inverter
Node-ID: ________
Identifier: ___________
Input Link/Parameter-No.
RxPDO-No.:
(Tx/RxPDO)
Boolean uint/int long
: ___________________________
Inverter
Node-ID: ________
________
Boolean uint/int long
Input Link/Parameter-No.
No.
TxPDO-No.:
Source-
EM-RES-03 4910/07
Page 52
5.14.3 Capacity planning of the system bus
Each PDO telegram possesses a constant useful data content of 8 Bytes. According to
worst case, this results in a maximum telegram length of 140 bits. The maximum tele­gram run time of the PDO’s is thus stipulated via the set baud rate.
Capacity planning Baud rate /
kBaud
1000 140 500 280 250 560 125 1120 100 1400 50 2800
As a function of the set baud rate and the transmission interval of the TxPDO’s se-
lected, the following bus loads results:
Capacity of the system bus
Baud rate
/ kBaud
Bus load as a function of the transmission for one TxPDO in %
1ms 2ms 3ms 4ms 5ms 6ms 7ms 8ms 9ms 10ms
1.000 14 7 4,7 3,5 2,8 2,3 2 1,8 1,6 1,4 500 28 14 9,3 7 5,6 4,7 4 3,5 3,1 2,8 250 56 28 18,7 14 11,2 9,3 8 7 6,2 5,6 125 112 56 37,3 28 22,4 18,7 16 14 12,4 11,2 100 140 70 46,7 35 28 23,3 20 17,5 15,6 14 50 280 140 93,3 70 56 46,7 40 35 31,1 28
Attention: A bus load >100% means that a telegram cannot be dispatched com-
pletely between two transmission times.
This observation must be done for each TxPDO. The sum of all the TxPDO’s decides
on the entire bus load. The bus load must be designed in such a way that any tele­gram repetitions for transmission errors are possible without exceeding the bus capac­ity.
Note: To facilitate capacity planning, a Microsoft Excel file with the name
"Load_Systembus.xls” is available.
Telegram run time /
μ
s
Such a setting is not admissible!
EM-RES-03 10/0750
Page 53
The capacity planning are planned and documented with the help of the table. The
work sheet is available as a Microsoft Excel document "Load_Systembus.xls" on the
Load system bus
VECTRON product CD or by request.
Baud rate [kBaud]:
50, 100, 125, 250, 500, 1000
1000
Frequency
inverter
1 0 0
1
TxPDO
Number
Ta
[ms]
Workload
[%]
2 0 0
1 0 0
2
3 0 0
2 0 0
1 0 0
3
3 0 0
2 0 0
1 0 0
4
3 0 0
2 0 0
1 0 0
5
3 0 0
2 0 0
1 0 0
6
3 0 0
2 0 0
1 0 0
7
3 0 0
2 0 0
1 1 14
8
3 0 0
2 1 14
1 1 14
9
3 1 14
2 1 14
1 0 0
10
3 0 0
2 0 0
3 0 0
Total workload [%] 70
In the table, the set baud rate is entered from the parameter kBaud. For each frequency inverter, the set time for the transmission interval (e. g.
TxPDO1 Time 931) in ms is entered for the TxPDO being used at the time. In the
column Load the bus load caused by the individual TxPDO appears, under Total Load the entire bus load.
For the bus load (Total load) the following limits have been defined:
Î
80 %
80 ... 90
% > 90 %
OKAY CRITICAL
Î
Î NOT POSSIBLE
Baud-Rate 903 in
EM-RES-03 5110/07
Page 54
6 Control inputs and outputs
E
g
The analog input of the EM-RES-03 expansion module can optionally be configured as
The mapping of the analog input signals onto a frequency or percentage reference
6.1 Analog input EM-S1INA
6.1.1 General
a voltage or a current input. Parameterization of the input signal is done by the defini­tion of a linear characteristic and assignment as a
reference value source (can be selected via the parameter
reference percentage source (can be selected via the parameter
actual percentage source (can be selected via the parameter tion x11) or
limit value sources (can be selected via the parameters 734737).
Reference frequency source 475),
Reference percentage source 476),
Actual percentage source 478, in configura-
6.1.2 Characteristic
value is possible for various demands. The parameterization is to be done via two points of the linear characteristic of the reference channel. The characteristic point 1, with the coordinates X1 and Y1, and the characteristic point 2, with the coordinates X2 and Y2, can be set in four parameters. The characteristic points X1 and X2 are stated as percentages, as the analog input can be switched as a current or voltage input via switch S3.
No. Description Min. Max. Fact. sett. 564 Characteristic point X1 -100.00 % 100.00 % -98.00 % 565 Characteristic point Y1 -100.00 % 100.00 % -100.00 % 566 Characteristic point X2 -100.00 % 100.00 % 98.00 % 567 Characteristic point Y2 -100.00 % 100.00 % 100.00 %
The coordinates of the characteristic points are related as a percentage to the analog
signal, with 10 V or 20 mA, and the parameter ter
Maximum reference percentage 519. The change of direction of rotation can be
done via the digital inputs of the frequency inverter and/or by selecting the character­istic points.
The definition of the analog input characteristic can be calculated via the two-point
form of the straight-line equation. The speed Y of the drive mechanism is controlled according to the analog control signal X.
Parameter Setting
Maximum Frequency 419 or parame-
Y1-Y2
Y + ⋅=
()
Y1X1X
X1-X2
Attention!
Monitoring of the analog input signal via the parameter
Behavior
use is only possible if the range.
563 demands a check of the characteristic parameters. Sensible
Characteristic point X1 564 is in the positive
rror/Warnin
EM-RES-03 10/0752
Page 55
6.1.3 Operation modes
g
f
g
The operation modes of the analog input characteristic enable application-related scal-
as a supplement to the characteristic points stated. One of the four linear types o
in characteristic is selected for adaptation of the signal for the analog input signal via the parameter
Operation mode 562.
If the characteristic points are not suited for the type of characteristic selected, the characteristic points are corrected internally.
Operation mode Function
1 - bipolar The analog input signal is mapped onto the reference
figure according to the characteristic points (X1/Y1) and (X2/Y2).
11 - unipolar With a negative parameter value of the characteristic
points X1 or X2, they are mapped to the reference value zero.
21 - unipolar
2…10 V / 4…20 mA
If the characteristic points X1 or X2 have been set with a negative parameter figure or smaller than 0%, the input characteristic is mapped to the reference value 20%.
101 - bipolar absolute value Negative parameter values of the characteristic points
Y1 or Y2 are mapped as a positive reference value in the characteristic.
Further information on the operation modes stated in the table can be found in the
following chapter "Examples“.
6.1.3.1 Examples
The analog input signal is mapped onto a reference value as a function of the charac-
teristic. The following examples show the operation modes for an analog voltage sig­nal. The parameter teristic point 100% for the Y-axis corresponds to the parameter 419 of 50.00 Hz in the examples.
Minimum Frequency 418 is set to the value 0.00 Hz. The charac-
Maximum Frequency
Attention! The various operation modes change the input characteristic as a function
of the parameterized characteristic points. In the following examples, the areas of the coordinate system from which a characteristic point is dis­placed are marked.
Operation mode "1 – bipolar"
In operation mode "1 – bipolar“, the characteristic of the analog input can be freely
set by stating two characteristic points.
42.50Hz
Y
(X2=80% / Y2=85%)
Characteristic point 1:
X1 = -70.00% · 10 V = -7.00 V Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Characteristic point 2:
X2 = 80.00% · 10 V = 8.00 V Y2 = 85.00% · 50.00 Hz = 42.50 Hz
8V
X
Tolerance band:
-7V
ΔX = 2.00% · 10 V = 0.20 V
-25Hz
(X1=-70% / Y1=-50%)
The change of direction of rotation is done in the example at an analo
input signal of -1.44 V, with a tolerance band of ±0.20 V.
EM-RES-03 5310/07
Page 56
Operation mode "11 – unipolar"
In operation mode "11 – unipolar“, the characteristic points are displaced to the origin
of the characteristics with a negative value for the X-axis.
42.50Hz
-7V
Y
(X2=80% / Y2=85%)
8V
Characteristic point 1:
X1 = -70.00% · 10 V = -7.00 V Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Characteristic point 2:
X2 = 80.00% · 10 V = 8.00 V Y2 = 85.00% · 50.00 Hz = 42.50 Hz
X
Tolerance band:
ΔX = 2.00% · 10 V = 0.20 V
-25Hz
(X1=-70% / Y1=-50%)
The characteristic point 1 has been dis­placed to the origin. The parameter
erance band
560 is not taken into ac-
count in this example, as no chan
Tol-
ge of sign of the reference frequency value takes place.
42.50Hz
Y
(X2=80% / Y2=85%)
Characteristic point 1:
X1 = 30.00 % · 10 V = 3.00 V Y1 = -50.00 % · 50.00 Hz = -25.00 Hz
Characteristic point 2:
X2 = 80.00 % · 10 V = 8.00 V Y2 = 85.00 % · 50.00 Hz = 42.50 Hz
X
3.00V
8.00V
Tolerance band:
ΔX = 2.00 % · 10 V = 0.20 V
-25.00Hz (X1=30% / Y1=-50%)
The change of direction of rotation is done in the example at an analog input signal of
4.85 V, with a tolerance band of ±0.20 V.
EM-RES-03 10/0754
Page 57
=
g
Operation mode "21 – unipolar 2…10 V / 4…20 mA"
This operation mode limits the input characteristic to the ran
ge between 20% and 100% of the analog signal. If the value for a characteristic point of the X-axis is out­side 0%, it is mapped to the characteristic point (2 V / 0 Hz).
The characteristic point on the X-axis is calculated according to the following formula:
42.50Hz
Y
(X2=80% / Y2=85%)
20.00%20.00%)-(100.00%X valueparameterXpoint sticcharacteri +
Characteristic point 1:
X1 = [-70.00% · (100.00% - 20.00%) + 20.00% ] · 10 V = -7.60 V Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Characteristic point 2:
-7.60V
8.40V
-25.00Hz
(X1=-70% / Y1=-50%)
X2 = [80.00% · (100.00% - 20.00%)
X
+ 20.00% ] · 10 V = 8.40 V Y2 = 85.00% · 50.00 Hz = 42.50 Hz
Tolerance band:
ΔX = [2.00% · (100.00% - 20.00%)
· 10 V] = 0.16 V
The characteristic point 1 has been dis­placed to the point (2.00 V / 0.00 Hz). The parameter used in this example, as no chan
Tolerance band 560 is not
ge of sign of the reference frequency value takes place.
42.50Hz
Y
(X2=80% / Y2=85%)
Characteristic point 1:
X1 = [30.00% · (100.00% - 20.00%) + 20.00% ] · 10 V = 4.40 V Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Characteristic point 2:
X2 = [80.00% · (100.00% - 20.00%) + 20.00% ] · 10 V = 8.40 V
4.40V
8.40V
X
Y2 = 85.00% · 50.00 Hz = 42.50 Hz
Tolerance band:
-25.00Hz (X1=30% / Y1=-50%)
ΔX = [2.00% · (100.00% - 20.00%)
· 10 V] = 0.16 V
The change of direction of rotation is done in the example at an analo
input signal of
5.88 V, with a tolerance band of ±0.16 V.
EM-RES-03 5510/07
Page 58
g
f
g
g
g
Operation mode "101 – bipolar absolute value"
The operation mode "101 – bipolar absolute value“ maps the bipolar analog signal
onto a unipolar input characteristic. The formation of the absolute amount takes the characteristic into account comparable to the "bipolar" operation mode, but the char­acteristic points are reflected on the X-axis with a negative value for the Y-axis.
42.50Hz
25.00Hz
Y
(X2=80% / Y2=85%)
Characteristic point 1:
X1 = -70.00% · 10 V = -7.00 V Y1 = -50.00% · 50.00 Hz = -25.00 Hz
Characteristic point 2:
X2 = 80.00% · 10 V = 8.00 V Y2 = 85.00% · 50.00 Hz = 42.50 Hz
X
-7V
8V
Tolerance band:
ΔX = 2.00% · 10 V = 0.20 V
-25.00Hz
(X1=-70% / Y1=-50%)
In this example, the reference value is
ain increased from an analog input
a signal of -1.44 V with a tolerance band o ±0.20 V. The theoretical chan
e of sign of the reference value is used and leads to the tolerance band stated. There is no change of the direction of rotation.
6.1.4 Scaling
The analog input signal is mapped to the freely configurable characteristic. The maxi-
mum admissible settin
uration selected via the frequency limits or the percentage value limits. In the
confi
range of the drive mechanism is to be set according to the
parameterization of a bipolar characteristic, the minimum and maximum limit for both directions of rotation are taken over. The percenta
ge values of the characteristic
points are relative to the maximum limits selected.
Parameter Setting No. Description Min. Max. Fact. sett. 418 Minimum Frequency 0.00 Hz 999.99 Hz 3.50 Hz 419 Maximum Frequency 0.00 Hz 999.99 Hz 50.00 Hz
The controls use the maximum value of the output frequency, which is calculated from
maximum frequency 419 and the compensated slip of the drive mechanism. The
the frequency limits define the speed ran
ge of the drive mechanism and the reference percentage values supplement the scaling of the input characteristic according to the configured functions.
Parameter Setting No. Description Min. Max. Fact. sett. 518 Minimum reference percentage 0.00 % 300.00 % 0.00 % 519 Maximum reference percentage 0.00 % 300.00 % 100.00 %
EM-RES-03 10/0756
Page 59
6.1.5 Tolerance band and hysteresis
T
g
g
Parameter Setting No. Description Min. Max. Fact. sett. 560 Tolerance band 0.00 % 25.00 % 2.00 %
he analog input characteristic with change of sign of the reference value can be adapted by the parameter to be defined extends the zero crossin signal. The percenta
Tolerance band 560 of the application. The tolerance band
g of the speed relative to the analog control
e parameter value is relative to the maximum current or voltage
signal.
pos. max. value
(X2/Y2)
pos. max. value
(X2 / Y2)
-10V
(-20mA)
(X1 / Y1)
Without tolerance band
Minimum Frequency 418 or the Minimum reference percentage 518 set in the
The
neg. max. value
+10V
(+20mA)
-10V
(-20mA)
(X1/Y1)
With tolerance band
+10V
Tolerance band
neg. max. value
factory extends the parameterized tolerance band to the hysteresis.
pos. max. value
pos. min. value
neg. min. value
(X1 / Y1)
(X2/Y2)
Tolerance band
neg. max. value
With tolerance band and minimum value
For example, the output variable resulting from the positive input signals is kept at the
positive minimum value until the input si
nal is below the value for the tolerance band
in a negative direction. After that proceed on the set characteristic.
EM-RES-03 5710/07
Page 60
6.1.6 Error and warning behavior
T
g
E
g
The monitoring of the analog input signal necessary according to the application is to
be configured via the parameter
Operation mode Function
0 - Off The input signal is not monitored.
1 - Warning < 1 V / 2 mA
2 - Shutdown < 1 V / 2 mA
Fault switch-off
3 -
< 1 V / 2 mA
he monitoring of the analog input signal is active independent of the release of the
frequency inverter according to the operation mode selected.
In operation mode 2, the drive mechanism is decelerated independent of the stopping
behavior set (Parameter (shutdown and switch-off). If the set holding time has expired, there is a fault mes­sage. A repeat start of the drive mechanism is possible by switching the start signal on and off if the fault has been cleared.
Operation mode 3 defines the free stoppage of the drive mechanism, independent of
the stopping behavior selected, which is stipulated with the parameter
tion
630.
Attention!
Monitoring of the analog input signal via the parameter
Behavior
563 demands a check of the characteristic parameters.
Error/Warning behavior 563.
If the input signal is less than 1 V or 2 mA, there is a warning message. If the input signal is less than 1 V or 2 mA, there is a warning message, the drive mechanism is decelerated according to stopping behavior 1. If the input signal is less than 1 V or 2 mA, there is a warning and fault message and the drive me­chanism stops freely.
Operation mode 630) accordin
to stopping behavior 1
Stop func-
rror/Warnin
EM-RES-03 10/0758
Page 61
g
6.1.7 Adjustment
As a result of component tolerances, it can be necessary to adjust the analog input.
Parameter
Operation mode Function
0 - no adjustment Normal operation
1 - Adjustment 0 V / 0 mA
2 - Adjustment 10 V / 20 mA
Adjustment 568 is used for this purpose.
Adjustment of the measurement with an analog signal of 0 V or 0 mA. Adjustment of the measurement with an analog signal of 10 V or 20 mA.
Example of the adjustment of the analog input with a voltage signal:
Note: The measurements for the adjustment are to be done with a suitable
measuring instrument and the correct polarity. If not, faulty measurements can result.
Apply 0 V to the analog input; e.g. with a wired link from the socket of the analo input X410A.6 to socket X210B.7 (earth/GND) of the frequency inverter.
Select operation mode "1 - Adjustment 0 V / 0 mA“.
Apply 10 V to the analog input, e.g. with a wired link from the socket of the analog input to socket X210B.5 (reference output 10 V) of the frequency inverter.
Select operation mode "2 - Adjustment 10 V / 20 mA“.
6.1.8 Filter time constant
The time constant of the filter for the reference analog value can be set via the pa-
rameter The time constant states the time for which the input signal is averaged by means of a low pass filter, e.g. in order to eliminate fault effects.
The setting range is a range of values between 0 ms and 5000 ms in 15 steps.
Operation mode Function
2 - Time constant 2 ms 4 - Time constant 4 ms 8 - Time constant 8 ms 16 - Time constant 16 ms 32 - Time constant 32 ms 64 - Time constant 64 ms 128 - Time constant 128 ms 256 - Time constant 256 ms 512 - Time constant 512 ms 1000 - Time constant 1000 ms 2000 - Time constant 2000 ms 3000 - Time constant 3000 ms 4000 - Time constant 4000 ms 5000 - Time constant 5000 ms
Filter time constant 561.
0 - Time constant 0 ms
Filter deactivated – analog reference value is for­warded unfiltered Filter activated – averaging of the input signal via the set value of the filter time constants
EM-RES-03 5910/07
Page 62
6.2 Digital outputs EM-S1OUTD and EM-S2OUTD
g
F
d
f
F
F
F
Parameterization of this digital output permits a linking to a variety of functions. The
6.2.1 General
selection of functions depends on the parameterized configuration.
The operation mode of the digital output EM-S1OUTD (terminal X410A.3) is selected
The operation mode of the digital output EM-S2OUTD (terminal X410A.4) is selected
The operation modes to be selected correspond to the table shown in the operatin
6.2.2 Operation modes
via the parameter
via the parameter
instructions of the frequency inverter in the chapter "Digital outputs“.
Operation Mode EM-S1OUTD 533.
Operation Mode EM-S2OUTD 534.
6.2.3 Fixed reference values and fixed value switch-over
Depending on the Reference Frequency Source 475 selected, fixed frequencies can be used as reference values. The expansion module extends the functionality described in the operating instructions of the frequency inverter (parameter
change-over 1
66 and Fixed frequency change-over 2 67) by the parameter
Fixed frequency
ixe
requency change-over 3 131 and the matching parameters Fixed frequency 5 485,
Fixed frequency 6 486, Fixed frequency 7 487, Fixed frequency 8 488.
Fixed frequency 1 480 Fixed frequency 2 481 Fixed frequency 3 482 Fixed frequency 4 483 Fixed frequency 5 485 Fixed frequency 6 486 Fixed frequency 7 487 Fixed frequency 8 488
ixed frequency
change-over 1
0 0 0 1 0 0 1 1 0 0 1 0 0 1 1 1 1 1 1 0 1 0 0 1
66
ixed frequency
change-over 2
67
change-over 3
ixed frequency
131
EM-RES-03 10/0760
Page 63
6.3 Digital inputs EM-SxIND
The EM-RES-03 expansion module has three digital inputs. The assignment of the
control signals to the available software functions can be adapted to the application in question. As a function of the selected and the selection of the operation mode differ. In addition to the di
Configuration 30, the factory-set assignment
gital control inputs
available, further internal logistic signals are also available as sources.
The individual software functions are assi
gned to the various signal sources via parameterization-capable inputs. This enables a flexible and varied use of the digital control signals.
Operation mode Function
320 - EM-S1IND Signal on digital input 1 (X410B.2) 321 - EM-S2IND Signal on digital input 2 (X410B.3) 322 - EM-S3IND Signal on digital input 3 (X410B.4) 520 - EM-S1IND inverted Inverted signal on digital input 1 (X410B.2) 521 - EM-S2IND inverted Inverted signal on digital input 2 (X410B.3) 522 - EM-S3IND inverted Inverted signal on digital input 3 (X410B.4)
Alongside the operation modes listed, those stated in the operating instructions of the
frequency inverter in the chapter "Digital inputs" also apply.
EM-RES-03 6110/07
Page 64
6.4 Resolver input EM-RES
g
N
j
The resolver input is used for evaluating the position information from the resolver.
Parameter Function
Parameter Function
The frequency of the field signal for the resolver is set to the fixed value of 8 kHz.
If the no. of resolver pole pairs > 1, the measured electric angle runs through the range of 0°...360° several times during one mechanical revolution. For the detection of the position an
le of the rotor at a synchronous motor, the ratio of the no. of motor pole pairs to the no. of resolver pole pairs must be an integer. The no. of pole pairs of the resolver can be adjusted via parameter
Pairs
381.
o. of Pole
No. Description Min. Max. Fact. sett.
381 No. of pole pairs 1 7 1
6.4.1 Offset
In order to enable the start of a synchronous machine, the absolute position of the rotor must be known. This information is required in order to actuate the stator wind­ings in the right order depending on the position of the rotor. The position of the ro­tary field in the synchronous machine must be controlled in order to obtain a continu­ous movement of the rotor. During first commissioning, the position of the rotor wind­ing of the resolver is adjusted to the rotor displacement angle of the synchronous mo­tor by adjusting the offset. For operating a synchronous machine with resolver, the offset must be ad torque. The correct
Offset 382 is adjusted when the flux-forming voltage 235 reaches the
value 0 (approximately) while the motor is turning.
No. Description Min. Max. Fact. sett.
382 Offset -360.0° 360.0° 0.0°
The offset can be determined and adjusted as follows:
During first commissioning "SEtUP" will be displayed in the control unit. Press ESC
to stop this operation. The guided commissioning („SETUP“) is performed after ad­justing the offset.
Open the parameter menu "PARA" and enter the machine data indicated on the
type plate or the data sheet of the motor.
Adjust parameter No. of Pole Pairs 381 to the number of pole pairs of the re-
solver.
usted in order to obtain perfectly true running and a maximum
EM-RES-03 10/0762
Page 65
g
y
f
t
g
r
t
Before adjusting the offset, take the following safety precautions:
Disable the frequency inverter via the digital inputs for controller release.
If possible, uncouple the motor from the load so that the motor shaft turns freely.
If installed, release the mechanical brake. If uncoupling is not possible, make sure that the motor is loaded as little as possi­ble.
Warning! In certain circumstances, the motor speed may reach high values. If the
Set the max. permissible output frequency of the frequency inverter to a low fre­quency value via parameter that uncontrolled acceleration of the motor ("overspeedin stage. This limitation is necessary in order to avoid personal and material damage.
Set parameter Current Limit 728 of the speed controller to a low current value (e.
g. 10% of the rated motor current). In this way it is made sure that there are no
excessive currents of the offset is set incorrectly.
Turn motor shaft manually. Check the sense of rotation of the resolver via the ac­tual value of parameter rotation of the motor shaft, positive values are displayed for the actual frequency value. If the displayed sense of rotation does not correspond to the actual sense of rotation, change the connections SIN+ and SIN- at socket X410A of the frequency inverter.
The Offset 382 must be between 0° and 360°, divided by the number of motor pole pairs. If the number of resolver pole pairs is higher than 1, the possible range is be­tween 0° and the max. offset.
OffsetMax.
=
If the adjusted value is changed by the max. offset, this does not affect the flux-
orming voltage 235.
Adjust a low reference speed value (approx. 10% lower than the Switch-off Limi
Frequency 417), and enable the frequency inverter via controller release and
S2IND (start clock-wise operation) in order to accelerate the motor.
If an overcurrent is detected or a fault message is issued due to an overload, the guided commissionin data. After completion of the guided commissioning, adjust the parameter Limi
Current 728 to a low value again because this value was overwritten during the
guided commissioning.
motor is not uncoupled from the load, personal and material damage may result. To avoid such damage, make the following settings in any case.
Switch-Off Limit 417. Select the frequency value such
") is detected at an earl
Frequency Speed Sensor 2 219. In the case of a clock-wise
°
360
number of motor pole pairs / number of resolver pole pairs
(setup) will start first. Confirm the machine and resolve
EM-RES-03 6310/07
Page 66
f
r
g
t
Depending on the behavior of the motor after start, carry out the following steps:
Motor does not turn, or the motor shaft only turns to a new position and
stops again:
Check if the parameters No. of Pole Pairs 373 for the motor and No. of Pole
Pairs
If these values are adjusted correctly, take the following measures complying with the safety instructions.
Warning! The mains, direct voltage and motor sockets can be live with dangerous
Before electrical installation work, de-energize the frequency inverter and take appropriate precautions to make sure it is not re-energized unintentionally. Make sure that the frequency inverter is de-energized.
Exchange two motor phases (e.g. U and V) at the frequency inverter sockets because the senses of rotation of the motor and the resolver do not corre­spond to each other.
Switch on the power supply again.
As described above, adjust a low speed reference value and start the motor.
If the motor does not start despite the phase exchange:
Increase the parameter value for Offset 382 by 90°, divided by the no. of mo­tor pole pairs.
If the motor still does not turn, exchange the two motor phases (e.g. U and V) again.
The motor turns and accelerates until it reaches the Frequency Switch-Of
Limit 417:
Check the resolver lines and check the resolver connection contacts.
In the case of fault message "Overfrequency" F1100: increase the paramete
value for Offset 382 by 180°, divided by the no. of motor pole pairs.
If the motor turns at the adjusted speed and in the right direction, carry out the fine adjustment of the offset:
Adjust the parameter value for Offset 382 in small steps (e.g. 2.5°) until the
flux-forming voltage 235 is approximately 0.
In case the flux-forming voltage deviates from 0 si
in bigger steps.
In the case of a positive flux-forming voltage, increase the offset.
In the case of a negative flux-forming voltage, reduce the offset.
Adjust parameters Frequency Switch-Off Limit 417 and Current Limit 728 to
the required values.
Repeat the fine adjustment of the offset at 50% of the rated frequency.
This completes the offset adjustment.
Start the guided commissioning. This is required for optimum current control.
381 for the resolver are set correctly.
voltage after disconnection of the frequency inverter. Work only on the device after a waiting period of some minutes until the DC link capacitors have discharged.
nificantly, adjust the offse
EM-RES-03 10/0764
Page 67
6.4.2 Actual speed source
g
s
d
Switch-over is effected via Actual Speed Source 766. If the resolver delivers the actual value si
gnal for the speed controller, speed sensor 2 must be selected as the source In
the basic setting, speed sensor 1 is used as the actual value source.
Operation mode Function
1 - Speed sensor 1
2 - Speed sensor 2
The actual speed source is speed sensor 1 of the basic device (factory setting). The actual speed source is speed sensor 2 of the EM­RES-03 expansion module.
6.4.3 Evaluation mode
If a synchronous motor which is not from BONFIGLIOLI should be connected to the resolver input it can be necessary to chan via parameter
Evaluation Mode 492.
Evaluation Mode 492
e the sign of the sinus track. This can be set
Function
0 - Bonfiglioli Factory setting. For Bonfiglioli synchronous motors. 1 - inverted The sign of the sinus track is changed.
6.5 Frequency and percentage reference channel
The varied functions for the specification of the reference values are connected in the various configurations by the frequency or percentage reference channel. The
ence frequency source
475, and the Reference percentage source 476 determine the additive connection of the available reference sources as a function of the installed hardware.
Operation mode Function
2 - EM-S1INA, absolute value Reference source is the analog input EM-S1INA
MFI1A + EM-S1INA, abso-
4 -
lute value
MFI1A + EM-S1INA + FF,
14 -
absolute value
MFI1A + EM-S1INA + MP,
24 -
absolute value
Reference sources are the multifunctional input MFI1A and the analog input EM-S1INA Reference sources are the multifunctional input MFI1A, analog input EM-S1INA and fixed frequency FF Reference sources are the multifunctional input MFI1A, analog input EM-S1INA and the motor po­tentiometer function MP
102 to 124 Operation modes with signs (+/-)
Additional to the operation modes listed, those stated in the operating instructions of the frequency inverter in the chapter "Frequency reference channel“, and in the chap­ter "Percentage reference channel“ also apply.
6.6 Actual value display
The actual value of speed sensor 2 can be read via the parameters Frequency
sensor 2 219 and Speed, speed sensor 2 220.
The analog input signal on analog input EM-S1INA is displayed via the actual value parameter
Analog input EM-S1INA 253.
Refer-
pee
EM-RES-03 6510/07
Page 68
6.7 Status of the digital signals
The status of the digital signals can be read in decimal coding via the parameters
tal inputs
checkin
250 and Digital outputs 254. The display of the digital input signals enables
g the various control signals and their connections with the software functions
in question, in particular in commissioning.
Coding of the status of the digital signals
Example:
After conversion of the decimal figure into the binary system, bits 8, 9 and 10 displa the states of the inputs EM-S1IND, EM-S2IND and EM-S3IND.
151413 control signal 16 (decimal value 32768)
control signal 15 ( 16384)decimal value
control signal 14 ( 8192)decimal value
control signal 13 ( 4096)decimal value
control signal 12 ( 2048)decimal value
control signal 11 ( 1024)decimal value
control signal 10 ( 512)decimal value
control signal 9 ( 256)decimal value
The actual value parameter
Bit
12 11109
7
8
Digital inputs 250 displays the decimal value 640. After
5 432
6
Bit
0
1
control signal 1 ( 1)decimal value
control signal 2 ( 2)decimal value
control signal 3 (4)decimal value
control signal 4 ( 8)decimal value
control signal 5 ( 16)decimal value
control signal 6 ( 32)decimal value
control signal 7 ( 64)decimal value
control signal 8 ( 128)decimal value
conversion into the binary system, the following combination results:
Binary system:
control signal 10 (decimal value 512)
12 11109
000 000 01
7
8
1 0 0 0 0 0 0
5 432
6
BitBit
015 14 13
1
0
control signal 8 (decimal value 128)
The following status of the digital input signals of the expansion module has been dis-
played:
Digital input EM-S1IND = 1 – control signal 8
Digital input EM-S2IND = 0 – control signal 9
Digital input EM-S3IND = 1 – control signal 10
Digi-
y
EM-RES-03 10/0766
Page 69
f
6.8 Motor temperature
Temperature monitoring forms part of the configurable error- and warning behavior.
The connected load can be monitored by connecting a measuring resistor (motor PTC) with temperature characteristics according to DIN 44081 or by means of a bimetal tem­perature sensor (break contact). The operation mode of the motor ptc port can be selected via parameter
Mode Motor Temp.
ture" of the frequency inverter operating instructions are complemented by the follow-
Operation
570 The operation modes described in chapter "Motor Tempera-
ing operation modes with the expansion module:
Operation mode Function
EM-MPTC:
11 -
warning only
EM-MPTC:
12 -
Error-switch-off
EM-MPTC:
13 -
Error-switch-off,
The critical operating point is displayed by the control unit and parameter
Warnings 269.
Error-switch-off is displayed by message F0400. Error­switch-off can be acknowledged via the control unit or the digital input. Error-switch-off according to operation mode 2, delayed
by one minute. 1 min. delay EM-MPTC:
14 -
Error-switch-off,
Error-switch-off according to operation mode 2, delayed
by five minutes. 5 min. delay EM-MPTC:
15 -
Error-switch-off,
Error-switch-off according to operation mode 2, delayed
by ten minutes. 10 min. delay
The function to be adjusted by parameter
Operation Mode Motor Temp. 570 results in
signaling the overtemperature by the red LED of the frequency inverter, irrespective o the selected operation modes of the control inputs and outputs. The operation modes with error-switch-off result in the fault messa
ge "FAULT" with fault number "F0400" being displayed on the control unit KP500. The fault message can be acknowledged via parameter linked with parameter
Error Acknowledgement 103.
Program 34 or the logic signal
EM-RES-03 6710/07
Page 70
7 Parameter list
System bus No. Description Unit Display range Chapter 923 SDO2 Set Active - Selection 5.9.4 924 RxPDO1-Identifier - 0 ... 2047 5.11.1 925 TxPDO1-Identifier - 0 ... 2047 5.11.1 926 RxPDO2-Identifier - 0 ... 2047 5.11.1 927 TxPDO2-Identifier - 0 ... 2047 5.11.1 928 RxPDO3-Identifier - 0 ... 2047 5.11.1 929 TxPDO3-Identifier - 0 ... 2047 5.11.1 930 TxPDO1 Function - Selection 5.11.2 931 TxPDO1 Time ms 0 ... 50000 5.11.2 932 TxPDO2 Function - Selection 5.11.2 933 TxPDO2 Time ms 0 ... 50000 5.11.2 934 TxPDO3 Function - Selection 5.11.2 935 TxPDO3 Time ms 0 ... 50000 5.11.2 936 RxPDO1 Function - Selection 5.11.2 937 RxPDO2 Function - Selection 5.11.2 938 RxPDO3 Function - Selection 5.11.2 939 SYNC Timeout ms 0 ... 60000 5.11.3 941 RxPDO1 Timeout ms 0 ... 60000 5.11.3 942 RxPDO2 Timeout ms 0 ... 60000 5.11.3 945 RxPDO3 Timeout ms 0 ... 60000 5.11.3 946 TxPDO1 Boolean1 - Selection 5.11.5.1 947 TxPDO1 Boolean2 - Selection 5.11.5.1 948 TxPDO1 Boolean3 - Selection 5.11.5.1 949 TxPDO1 Boolean4 - Selection 5.11.5.1 950 TxPDO1 Word1 - Selection 5.11.5.1 951 TxPDO1 Word2 - Selection 5.11.5.1 952 TxPDO1 Word3 - Selection 5.11.5.1 953 TxPDO1 Word4 - Selection 5.11.5.1 954 TxPDO1 Long1 - Selection 5.11.5.1 955 TxPDO1 Long2 - Selection 5.11.5.1 956 TxPDO2 Boolean1 - Selection 5.11.5.1 957 TxPDO2 Boolean2 - Selection 5.11.5.1 958 TxPDO2 Boolean3 - Selection 5.11.5.1 959 TxPDO2 Boolean4 - Selection 5.11.5.1 960 TxPDO2 Word1 - Selection 5.11.5.1 961 TxPDO2 Word2 - Selection 5.11.5.1 962 TxPDO2 Word3 - Selection 5.11.5.1 963 TxPDO2 Word4 - Selection 5.11.5.1 964 TxPDO2 Long1 - Selection 5.11.5.1 965 TxPDO2 Long2 - Selection 5.11.5.1 966 TxPDO3 Boolean1 - Selection 5.11.5.1 967 TxPDO3 Boolean2 - Selection 5.11.5.1 968 TxPDO3 Boolean3 - Selection 5.11.5.1 969 TxPDO3 Boolean4 - Selection 5.11.5.1 972 TxPDO3 Word1 - Selection 5.11.5.1 973 TxPDO3 Word2 - Selection 5.11.5.1 974 TxPDO3 Word3 - Selection 5.11.5.1 975 TxPDO3 Word4 - Selection 5.11.5.1 976 TxPDO3 Long1 - Selection 5.11.5.1 977 TxPDO3 Long2 - Selection 5.11.5.1 989 Emergency Reaction - Selection 5.8.3
The parameter list is structured according to the menu branches of the control unit.
Actual values of the machine No. Description Unit Display range Chapter 219 Frequency speed sensor 2 Hz 0.0 ... 999.99 6.6 220 Speed, speed sensor 2 rpm 0 ... 60000 6.6 Actual values of the frequency inverter 253 Analog input EM-S1INA V -10 ... +10 6.6
Resolver No. Description Unit Setting range Chapter
492 Evaluation Mode - Selection 6.4.3 Digital outputs 533 Op. Mode EM-S1OUTD - Selection 6.2.2 534 Op. Mode EM-S2OUTD - Selection 6.2.2
System bus 900 Node-ID - -1 ... 63 5.5 903 Baud-Rate - Selection 5.4 904 Boot-Up Delay ms 3500 ... 50000 5.8.4 918 SYNC-Identifier - 0 ... 2047 5.8.2 919 SYNC-Time ms 0 ... 50000 5.9.2 921 RxSDO1-Identifier - 0 ... 2047 5.9.4 922 TxSDO1-Identifier - 0 ... 2047 5.9.4
Analog input
561 Filter time constant - Selection 6.1.8 562 Operation mode - Selection 6.1.3 563 Error/warning behavior - Selection 6.1.6
568 Adjustment - Selection 6.1.7 Speed controller
For better clarity, the parameters are marked with pictograms:
The parameter is available in the four data sets
The parameter value is adjusted by the SETUP routine if a control method for a synchronous machine is selected for parameter C
This parameter cannot be written in the operation of the frequency inverter
7.1 Actual value menu (VAL)
7.2 Parameter menu (PARA)
381 No. of pole pairs - 1 ... 7 6.4 382 Offset ° -360.0 ... 360.0 6.4.1
560 Tolerance band % 0.00 ... 25.00 6.1.5
564 Characteristic point X1 % -100.00 ... 100.00 6.1.2 565 Characteristic point Y1 % -100.00 ... 100.00 6.1.2 566 Characteristic point X2 % -100.00 ... 100.00 6.1.2 567 Characteristic point Y2 % -100.00 ... 100.00 6.1.2
766 Actual speed source - Selection 6.4.2
onfiguration 30.
EM-RES-03 10/0768
Page 71
No. Description Unit Display range Chapter 923 SDO2 Set Active - Selection 5.9.4 924 RxPDO1-Identifier - 0 ... 2047 5.11.1
System bus
925 TxPDO1-Identifier - 0 ... 2047 5.11.1 926 RxPDO2-Identifier - 0 ... 2047 5.11.1 927 TxPDO2-Identifier - 0 ... 2047 5.11.1 928 RxPDO3-Identifier - 0 ... 2047 5.11.1 929 TxPDO3-Identifier - 0 ... 2047 5.11.1 930 TxPDO1 Function - Selection 5.11.2 931 TxPDO1 Time ms 0 ... 50000 5.11.2 932 TxPDO2 Function - Selection 5.11.2 933 TxPDO2 Time ms 0 ... 50000 5.11.2 934 TxPDO3 Function - Selection 5.11.2 935 TxPDO3 Time ms 0 ... 50000 5.11.2 936 RxPDO1 Function - Selection 5.11.2 937 RxPDO2 Function - Selection 5.11.2 938 RxPDO3 Function - Selection 5.11.2 939 SYNC Timeout ms 0 ... 60000 5.11.3 941 RxPDO1 Timeout ms 0 ... 60000 5.11.3 942 RxPDO2 Timeout ms 0 ... 60000 5.11.3 945 RxPDO3 Timeout ms 0 ... 60000 5.11.3 946 TxPDO1 Boolean1 - Selection 5.11.5.1 947 TxPDO1 Boolean2 - Selection 5.11.5.1 948 TxPDO1 Boolean3 - Selection 5.11.5.1 949 TxPDO1 Boolean4 - Selection 5.11.5.1 950 TxPDO1 Word1 - Selection 5.11.5.1 951 TxPDO1 Word2 - Selection 5.11.5.1 952 TxPDO1 Word3 - Selection 5.11.5.1 953 TxPDO1 Word4 - Selection 5.11.5.1 954 TxPDO1 Long1 - Selection 5.11.5.1 955 TxPDO1 Long2 - Selection 5.11.5.1 956 TxPDO2 Boolean1 - Selection 5.11.5.1 957 TxPDO2 Boolean2 - Selection 5.11.5.1 958 TxPDO2 Boolean3 - Selection 5.11.5.1 959 TxPDO2 Boolean4 - Selection 5.11.5.1 960 TxPDO2 Word1 - Selection 5.11.5.1 961 TxPDO2 Word2 - Selection 5.11.5.1 962 TxPDO2 Word3 - Selection 5.11.5.1 963 TxPDO2 Word4 - Selection 5.11.5.1 964 TxPDO2 Long1 - Selection 5.11.5.1 965 TxPDO2 Long2 - Selection 5.11.5.1 966 TxPDO3 Boolean1 - Selection 5.11.5.1 967 TxPDO3 Boolean2 - Selection 5.11.5.1 968 TxPDO3 Boolean3 - Selection 5.11.5.1 969 TxPDO3 Boolean4 - Selection 5.11.5.1 972 TxPDO3 Word1 - Selection 5.11.5.1 973 TxPDO3 Word2 - Selection 5.11.5.1 974 TxPDO3 Word3 - Selection 5.11.5.1 975 TxPDO3 Word4 - Selection 5.11.5.1 976 TxPDO3 Long1 - Selection 5.11.5.1 977 TxPDO3 Long2 - Selection 5.11.5.1 989 Emergency Reaction - Selection 5.8.3
EM-RES-03 6910/07
Page 72
8 Annex
g
g
The various control functions and methods and the hardware of the frequency inverter
Control connections 21 Resolver synchronization not successful. Check resolver signal for inter-
22 Resolver counting error: Check resolver signal for interferences. 23 Resolver pole pair number is invalid. The ratio of the no. of pole pairs to
Additional to the listed fault messages, there are further fault messages for internal
8.1 Error messages
contain functions which continuously monitor the application. As a supplement to the messages documented in these operating instructions, the followin activated by the EM-RES-03 expansion module.
F14
ferences.
the no. of resolver pole pairs must be an integer number. Check pa­rameters
Pairs
No. of Pole Pairs 373 for the motor and und No. of Pole
381 for the resolver, correct if necessary.
24 Open circuit: check resolver connections and lines.
purposes and not listed here. If you receive fault messa
es, which are not listed here,
please contact us by phone.
failure keys are
EM-RES-03 10/0770
Page 73
Page 74
Bonfiglioli has been designing and developing innovative and reliable power transmission and control solutions for industry, mobile machinery and renewable energy applications since 1956.
www.bonfiglioli.com
Bonfiglioli Riduttori S.p.A.
Via Giovanni XXIII, 7/A 40012 Lippo di Calderara di Reno Bologna, Italy
tel: +39 051 647 3111 fax: +39 051 647 3126 bonfiglioli@bonfiglioli.com www.bonfiglioli.com
VEC 546 R0
Loading...