Bolid Security Systems RIP-12 02 Instruction Manual

RIP-12 SHUTTING OFF
1) Shut off the mains power supply 220 V.
2) Detach the battery.
3) Remove the fuse F1.
4) Disconnect the load circuit.
MAINTENANCE
The maintenance of RIP-12 is to be carried out annually. The maintaining operations include:
2) Measuring the power output parameters and checking them to be in conformance with items of SPECIFICATION.
3) LED and sound indication testing to meet the requirements of Table above.
4) Proper RIP-12 firmly attaching, and contact tightening, and wire integrity inspection.
WARRANTY
Manufacturer warrants RIP-12 Uninterrupted Power Supply to be free from defects and to operate in conformance with specification under normal transportation, mounting and maintenance for 18 months since putting it into operation, but no more than for 24 month since acceptance date (see below).
In the event of in-warranty failure the failed RIP-12 should be brought back to the manufacturer supplied with its damage certificate describing the defect and its acceptance certificate to validate the warranty status. Send your complaints to the manufacturer at the following address:
ZAO NVP BOLID
#4, Pionerskaya street, Korolyov, Moscow Region, Russia, 141070
Tel./fax +7 495 777-40-20, +7 495 516-93-72.
E-mail: info@bolid.ru
, Web-site: www.bolid.com
ACCEPTANCE CERTIFICATE
RIP-12 Uninterrupted Power Supply model 02
Product Designation Serial Number
Produced, tested by quality control department in compliance with state standards and specifications, packed by NVP BOLID Company and qualified as deliverable.
Q.C.
STAMP _____________________ ____________________________
Name Date of Acceptance
UNINTERRUPTED POWER SUPPLY
RIP-12 model 02
INSTRUCTION MANUAL
GENERAL
Uninterrupted Power Supply RIP-12 model 02 (referred to as RIP-12 below) is designed to provide the electric power to various fire and intruder detectors, as long as control and indication equipment suited for uninterrupted 12 VDC.
RIP-12 is round-the-clock operating device with defined output parameters, sealed backup battery being tested and ch arged a utomat icall y. PIR-12 provides battery shutting off from load circuit in order to avoid its unacceptable discharge.
RIP-12 is equipped with light and audible indication of its current status, i.e. normal or no voltage, battery charge, output short failure or overload, battery missing or shutting down when discharged.
When operated, RIP-12 should be protected against atmospheric fallout and mechanical damage.
SPECIFICATION
AC Input Voltage Range – from 187 to 242 VAC @ 50 Hz
Backup Power Supply – battery «Delta» DTM1207 12 V @ 7 Ahr or analogous
Output Voltage Range
– 13.6 ± 0.6 VDC at both AC and charged battery powering;
– 11.0 ± 0.5 VDC min provided the battery is discharged Load Current Rating – 2.0 А Maximum Load Current – 3.0 А within 10 minutes or 5 А within 2 minutes at both mains
and battery powering, once an hour minimum Input Current Consumption – 0.3 А maximum for ra ting lo ad Ripple (mVp-p)×2 – 20 mV maximum at rating load current Battery Low Shutdown
– 10.2±0.6 VDC
On Battery Run-Time – at least 5 hours for 1 A load current, increasing proportionally to
load reduction Ingress Protection Rating – IP20 Power-Up Operation Readiness – 6 seconds maximum Operating Temperature Range
– from –10°C to +40°C Overall Dimensions – 255х310х95 mm RIP With Battery Weight – 6.5 kg maximum Typica l Lifetime – 8 years, the battery being to be replaced once every 5 year
RIP-12 provides protection against short circuit failure along with automatically recovering of output voltage
after short failure disappearing while powered from mains and backup battery.
RIP-12 is equipped with open collector transistor output functioning as contact closure device. It is opened
when AC line fails and RIP-12 is operating in battery mode, or in case of a short load circuit failure, so it can be used for remote signaling of RIP electric troubles. The maximum output permissible voltage and commutation current are 30 V and 100 mA respectively.
DELIVERY SET
Uninterrupted Power Supply RIP-12 model 02 - 1 Instruction Manual - 1 Fuse 0.5А - 1 pc Screw-nail - 3 pcs Dowel - 3 pcs Plastic Bushing - 2 pcs Front Cover Lock Key - 2 pcs Package - 1 pc
ISO 9001
RIP-12 ХТ 3
12V Output"
1
3
+ОC Output
5
+12V Output
+
To the device power supply leads
R 4,7 k
+loop
loop
To the device loop
R
is the Loop End-Of-Line Terminator provided along with a device; it is to be installed within RIP-12 enclosure
SAFETY PRECAUTIONS
Current-carrying RIP-12 circuits at 220 V are dangerous and can bring human injure. Do periodically inspect proper RIP-12 grounding and fuse proper operability. Never open RIP-12 unless AC line shut off. Do shut off AC line power before mounting, installing or maintaining of RIP-12. Only skilled personnel trained in electric codes and work safety rules should service the device.
ATTENTION! Connecting RIP-12 to the mains utility power supply KEEP UP the correct coupling
of LINE and NEUTRAL TERMINALS in agreement with the picture located inside the enclosure close to power terminal block.
MOUNTING AND WIRING
8
3
1 2 7
1 9 0
1 5 0
3 1 0
2 5 5
Note: Load current rating is 2 A. The maximum current consumption from RIP-12 can reach up to 3 A within 10 minutes or up to 5 A within 2 minutes provided RIP-12 is powered both from AC line and backup battery. Such a short time increase of current consumption is necessary for sound alarms, executive devices and automated fire extinguishing systems powering on. The intervals between heavy consumption periods must be at least one hour.
4) In order to transmit RIP-12 trouble messages about mains power failed or load circuit shorted connect RIP-12 open collector transistor output (XT3) to an alarm loop of powered control and indication equipment, e.g. S2000-4, Signal-20, Signal-20P SMD and so on. The example of such a wiring is demonstrated below:
STARTING UP
Before the first turning on ensure the RIP-12 mounting has accomplished correctly. Then, insert the fuse F1. Next, connect the RIP-12 backup battery to the battery leads keeping in mind proper polarity with red wire to be
coupled with positive battery terminal.
Finally, turn on a mains power supply 220 V@50 Hz.
OPERATING
а) When AC line is powering on the device LEDs POWER, CHARGE and 12 V will be lit while RIP-12
sounder will remain in silence.
Note: The battery being completely charged and its voltage being over 13 V, CHARGE LED will not be lit.
б) After RIP-12 powering up the battery is tested. If the battery is not connected or its voltage is below 10 volt then sound and CHARGE indicator goes off in interrupted mode within 8-10 seconds. After that the sounder silences, but CHARGE indicator flashed unless the battery is connected. Battery testing procedure is carried out periodically (at least once every 8 hours). If the battery is found to be missed, then CHARGE indicator flashes.
в) In the events of short load circuit failure and overload (in AC line operating mode) POWER and sound indicators after 3 seconds begin to flash once every 1-2 seconds until the trouble disappearing. 12 V and CHARGE indicators are off. After load trouble having been repaired RIP-12 automatically continues normal operating.
г) When mains power supply fails the battery is switched to the load circuit, 12 V indicator being turned on and sounder going off periodically.
д) If the battery voltage has dropped to 11 V the sounder switches on and off five to ten times more rapidly. It is necessary to take measures to restore mains power line.
When the battery voltage has dropped below 10 V it is shut off from a load in order to avoid deep discharge. In such a case POWER and 12 V indicators will be off, CHARGE indicator will be flashing, and audible alarm will sound. In 2 hours RIP-12 will be transferred to low battery powering mode, CHARGE and sound indicator flashes once every 8-10 seconds until line power having restored.
LEDs and sound indicator behavior along with human actions required are shown in Table below.
RIP Current Status POWER LED CHARGE LED 12V LED Sounder Human Actions
Mains power is starting up, the battery is not connected
ON
Flashes once
every 1-2 s
ON
Sounds for 8-10
seconds in
interrupted mode
Connect the battery
Normal AC line voltage, the battery is not charged
ON ON ON OFF -
Normal AC line voltage, the battery is charged
ON OFF ON OFF -
Normal AC line voltage, output short failure or overload at least 3 s
Flashes once
every 1-2 s
OFF OFF
Flashes twice
every 1-2 s
Repair the circuit
load
AC line failed, output short failure or overload
OFF OFF OFF
Short time
interrupted with
4-5 s period tone
Repair the circuit
load
AC line failed, battery voltage is above 11 V
OFF OFF ON
Short time
interrupted with
4-5 s period tone
Inspect fuse F1 operability and
r
ecover the mains line
AC line failed, battery voltage is below 11 V
OFF OFF ON
Short time
interrupted with
0.5-1 s period tone
Repair AC line
AC line failed, battery voltage is below 10.2 V
OFF
Flashes once
every 1-2 s
OFF ON
After AC line
recovering test the
battery charge-
discharge cycle *
Note:
* After detaching the battery from its load circuit and utility power recovering it is necessary to check the battery charge-discharge cycle. If CHARGE LED has been still lit after 24 hours since power having restored then the battery operability has to be checked.
RIP-12 is to be mounted on the wall or other construction on premises protected against atmospheric fallout, mechanical damage and unauthorized access. RIP-12 mounting dimensions are shown in figure at left. Attach the RIP-12 at a selected location. Then, in accordance with wiring diagram fixed on internal side of RIP-12 front cover do the following:
1) Ground RIP-12 coupling the contact "
" located on the input terminal
block with an earthing network;
2) Having removed F1 (0.5 А) fuse, connect mains power supply wires to the input block terminals;
3) Connect load circuits to the output terminal block keeping the proper polarity (ХТ3/1,2 to "
+" and ХТ3/3,4 to "")