bolid S2000-SP4/220 Instruction Manual

Page 1
ADDRESSABLE EXECUTIVE MODULE
S2000-SP4/220 Ver 1.04
INSTRUCTION MANUAL
1 TECHNICAL DATA
1.1 General
1.1.1 This Instruction Manual describes S2000-SP4/220 Addressable Executive Module along
1.1.2 The module is used as part of a multipart executive device in fire and intrusion alarm
systems under control of an S2000-KDL ver.2.01+ or S2000-KDL-2I ver.1.00+ controller and an S2000M console.
1.1.3 Meeting requirements for sound and light indication of control and indicating equipment
is provided together with the S2000-KDL and S2000M.
1.1.4 The module is designed to monitor and control fire dampers, smoke control dampers,
deluge valves, and other executive devices powered by mains power 220 V.
1.1.5 The module is to be attached at a suitable place (on a wall, above a suspended ceiling, or
on another constructions near the connected executive device) protected against atmospheric fallouts, mechanical damage, and unauthorized access. The module is designed for round-the-clock operation.
1.1.6 The module must not be used in aggressive medium or dust condition, or in explosion-
hazardous premises.
1.1 Specifications
1) Input Voltage Communication Part – 8 V to 12 V via the polling loop
Executive Part
2) Insulating Voltage of the Polling Loop
and Executive Part
3) Consumed Current: Communication Part – 1.5 mА max
Executive Part – 50 mА max(without regard to output’s current)
4) Outputs – 2
5) Max Switching Current per an Output
6) Switching Voltage – 220 V
7) Circuit Control Current – 0.5 mА max
8) Monitored Limit Switches
9) Pre-Operation Time – 15 s max
10) Operating Temperatures – Minus 30°C to +55°С
11) Humidity – 93 % at +40°С
12) Overall Dimensions – 156 mm × 107 mm × 39 mm
13) Weight – 0.2 kg max
14) Ingress Protection Rating
– An external power supply, 220 V ac – Up to 500 V
– 3 А
– 2
– IP20 – IP30, if wall mounted
Table 1. Specifications
1
Page 2
1.2 Standard Delivery
Circuit
Table 2. Standard Delivery
Item Q-ty
S2000-SP4/220 Addressable Executive Module 1 Instruction Manual 1 Woodscrews 3 Wall Plugs 6×30 3 Flat Head Tapping Screw 2.2х6.5 1 MF 1/4W-8k2-5% Resistor 6 Fuse 3.15 A (the spare part) 1 Fuse 0.25 А (the spare part) 1 Package 1
2 OPERATION
2.1 Outputs
2.1.1 The module provides control of their outputs in accordance with a given executive
program under receiving commands sent via the polling loop from the connected S2000-KDL controller. The module also provides monitoring the connected executive circuits for open / short circuit failures.
2.1.2 The module executes commands to switch the outputs on and off for a programmed
time.
Note: In state of an open or short circuit failure at the moment of receiving a command to switch
on, an output will not be switched on.
2.1.3 States of an output are defined by the voltage on the terminals of the output relative to
the ‘N‘ terminal of the power input:
Table 3. States of an Output
Condition
Norm
Open Failure
Short Failure
Output State L [R] Terminal N [R] Terminal
On Input Voltage Value 0.3 V to 0.9 V
Off 0.35 V to 4.5 V 0.3 V to 0.6 V
On Input Voltage Value 0 V to 0.3 V
Off 4.5 V to 5 V 0 V to 0.3 V
On Input Voltage Value Input Voltage Value
Off 0.3 V to 0.6 V 0.3 V to 0.6 V
Note: If an output is switched off, a short circuit failure is defined by a voltage between the
output’s terminals which must not exceed 60 mV.
2.1.4 If executive devices with the effective resistance of 250 Ohm to 50 kOhm are to be
connected to the module, they should be connected directly without any additional units (see Figure 1).
2.1.5 If the effective resistance of an executive device is less than 250 Ohm (the voltage
between output terminals is less than 0.06 V while the control current is 0.5 mA), the device must be connected in series with two back-to-back diodes with relevant wattage and backward voltage 400 V and more (for example, a 1N4007 diode if the operational current does not exceed 1А or a
2
Page 3
1N5406 diode if the operational current exceeds 1А). The diodes must be brought closely to the
Circuit
Circuit Resistance
executive device (see Figure 1).
2.1.6 If the control voltage is 5 V and the load effective resistance exceeds 50 kOhm (the
voltage between terminals of the output exceeds 4 V), a resistor with resistance less than 50 kOhm and the relevant wattage (47 kOhm & 2 W is recommended) should be brought in the circuit closely to the executive device, in parallel with it (see Figure 1).
2.1.7 The module provides responding with the current output circuit condition on a request
from the connected S2000-KDL.
2.1.8 States of the executive outputs and the controlled circuits connected to them are
indicated in the quiescent mode by means of ‘1’ and ‘2’ LEDs on the module’s faceplate as shown in Table 4.
Table 4. Indication of Output Status
Condition
Norm
Open Failure
Output Status Indicator Behavior
On Lit steady in green Off Off On Off
Double-flashes in yellow once per two seconds
On
Short Failure
Off
Flashes in yellow once per two seconds
2.2 Limit Switches
2.2.1 The module can monitor states of two connected limit switches (LS).
2.2.2 Limit switches are used to monitor current position of the damper’s blades
(open / closed).
2.2.3 A limit switch circuit can be in one of the four states which are defined by the circuit
resistance. Table 5 shows the ranges of resistance values for relative states of the limit switch circuits.
2.3 TEST Button
2.3.1 The module provides connecting an external button TEST.
2.3.2 The TEST button is designed to test damper operation conditions manually.
2.3.3 To avoid unauthorized actions with the damper, the TEST button is active only if the
module is switched to a special test mode.
2.3.4 To switch the module to the test mode, send the relevant command from the network
controller specifying the address of the module and the time the module will be being tested for.
2.3.5 The electric circuit of the TEST button can be in one of four available states which are
defined by the circuit resistance. Table 5 shows ranges of the resistance values for these four states of the TEST button circuit.
2.3.6 Any electric button – either a push button or a sticky button, with switched or closed
contacts can be used as the TEST button.
Table 5. Circuit Conditions of TEST Button and Limit Switches
Min Max Min Max TEST Button Limit Switch
0 2 2 6 6 20
20
[kOhm]
ADC Values Circuit Condition
0 85
86 139
140 200
∞∞∞∞
201 255
Short Failure Short Failure
Pushed in Closed
Released Open
Open Failure Open Failure
3
Page 4
2.4 Power Inputs
Second
2.4.1 The module monitors input power voltage at the power inputs during operation.
2.4.2 Status of powering the module is indicated by READY LED.
2.4.3 If power voltage at both power inputs is between 150 V and 280 V, the module enters in
the Power Norm mode and the READY LED is lit steady.
2.4.4 When the voltage at any power input comes out of the normal range 150 V to 280 V, the
module enters the Power Failed mode.
Table 6. Power Status Indication
First Power
Input Status
Power Input
Status
Indicator Behavior
Failed Norm Flashes in green once per four seconds Norm Failed Double-flashes in green once per four seconds Failed Failed Flashes triply in green once per four seconds Norm Norm Lit steady in green
3 INSTRUCTIONS
3.1 Safety Precautions
3.1.1 There are circuits under a hazardous voltage within the module, the terminals of the
circuits being covered by a protective electric insulated housing.
3.1.2 Do SHUT OFF the device power before mounting, wiring, or maintaining the module.
3.1.3 Mounting and maintaining the module MUST be performed by qualified engineers.
3.2 Preparation for Using
3.2.1 If necessary, change the module’s addresses within the polling loop of the connected
S2000-KDL. The addresses of the module must not be the same as addresses of any devices connected to the same polling loop.
3.2.2 If you are going to use the module with a single power supply, the power supply should
be connected to both power inputs of the module.
WARNING: Connecting an alternating current power supply to the module, be sure the Neutral wire is connected only to the N terminals of the module. These terminals are combined in a block, so both power inputs must be fed from the same phase of the mains.
3.2.3 Attach the module at a suitable location (on the wall, or above a suspended ceiling, or on
another construction closely to executive devices at places protected against atmospheric fallouts, mechanical damage, and unauthorized access).
3.2.4 Wire the module as shown in Figure 1.
3.2.5 If it is necessary to control an executive device which requires a single control signal
(and uses only one module’s relay output), the unused module’s output is shunted by a resistor of less than 50 kOhm and relevant wattage (47 kOhm & 2 W is recommended).
3.2.6 Table 7 describes how to connect actuators.
4
Page 5
Figure 1. Connection Diagram.
Table 7. How to Connect an Actuator to the S2000-SP4/220
Manufacturer Article How to Connect
Belimo BLF-230
Directly to the required output, the unused output is shunted
by a 47 kOhm @ 2 W resistance Belimo BE-230 Directly, without additional elements Belimo BLE-230 Directly, without additional elements
5
Page 6
3.3 Assigning an Address
The module occupies five addresses within the polling loop of the S2000-KDL and provides storing the addresses in the module’s non-volatile memory. The addresses are adjacent, that is the module occupies five addresses in a row, for example (factory values):
Damper address: 123
R1 (Output 1) address: 124
R2 (Output 2) address: 125
LS1 (Limit Switch 1) address: 126
LS2 (Limit Switch 2) address: 127
To assign the addresses, send from the S2000M console or the PC one of the following commands for the S2000-KDL:
Program the Device Address;
Change the Device Address.
Program the Device Address command is used when the currant module addresses are unknown or the same addresses are incorrectly assigned to two or more devices. To program the module addresses from the console or the PC, issue the relevant command specifying the required address which is to be assign with the module. In such case the LOOP LED of the module flashes four times periodically. Within 5 minutes since issuing the command press the tamper switch of the module three times long (>1 s) and once short (<0.5 s). The pause between pressings should be no more than
0.5 s. If a mistake was taken during pressing the combination, nest time try to press the tamper switch after 5 s or more. The console or PC will display the events about disconnecting devices with old addresses and finding devices with new programmed addresses. If the devices did have the same addresses, no messages about disconnecting devices with old addresses are displayed.
If you need to change module’s addresses which have been already known, you should send a Change the Device Address command from the console or PC specifying the old address (the first of the five old addresses) and the new address (the first of the five new addresses) of the module. In such case the console or PC will display events about disconnecting the devices with the old addresses and finding the devices with the newly given addresses.
3.4 Using
The module operates under the connected S2000-KDL controller; all operation conditions (executive program, activation time, activation delay) are specified in the S2000-KDL configuration using Uprog software. To use the module, by means of the UProg program set the Device Type in the ‘S2000-SP4/220’ value for the first of the five addresses which are to be used for the S2000­SP4/220 and, if necessary, associate S2000-KDL zones with outputs on the Dampers tab. The algorithms of setting types of addressable devices and configuration parameters are described at the exploitative documents for S2000-KDL, S2000M, and Orion Pro software.
3.5 Inspecting Module’s Operability
3.5.1 Wire the module as described in Clause 3.2.
3.5.2 After supplying power to the PL terminals, the LOOP indicator is lit steady until the
S2000-KDL polls the programmed address. Then the LOOP LED flashes with long pauses.
3.5.3 Assign a required address range for the module.
3.5.4 By means the UProg program, in the configuration of the S2000-KDL assign the first
module’s address with the S2000-SP4-24 Device Type.
3.5.5 Open the module cover and ensure that a tamper alarm message has been received by
the S2000M console or Orion Pro software (a message about tamper recovery should come within 15 seconds after closing the cover).
3.5.6 Further inspection of the module is to be carried out in cooperation with other system
components, by issuing damper control commands to the module and logging messages about states
6
Page 7
of monitored circuits. The system should comprise an S2000M console or a personal computer with installed Orion Pro software and the connected S2000-KDL controller.
3.5.7 Test the damper manually by using the TEST button connected to the S2000-SP4/220 (if
connected). To do so, switch the module to the Test Mode, issuing the relevant command from the network controller. Pushing the TEST button (for at least a half of second) will invert the current damper state. For example, if the damper is in the operating state, pushing the TEST button will run the mechanism of switching the damper to the safety state.
4 MAINTENANCE
Please inspect the module annually by doing the following:
1. Check the S2000-SP4/220 visually for contaminations and mechanical damage
2. Test the S2000-SP4/220 operability as said above
3. Verify the S2000-SP4/220 for secure mounting and wire connection conditions
5 OVERALL AND MOUNTING DIMENSIONS
ZAO NVP Bolid, 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia
Phone/fax: +7 495 775-7155 Email:
info@bolid.ru, overseas@bolid.com
www.bolid.com
7
Loading...