bolid S2000-APA User Manual

Page 1
ISO 9001
Standalone Addressable Device Programmer
S2000-APA
User’s Manual
Page 2
This User’s Manual is intended to help for studying operability principles and maintenance
of S2000-APA Standalone Addressable Device Programmer.
Please read the instructions completely before connecting, operating, adjusting, or
maintaining this programmer.
Page 3
S2000-APA
http://bolid.ru 3
CONTENTS
1
General ........................................................................................................................................ 4
1.1 Specifications ......................................................................................................................... 4
1.2 Standard Delivery .................................................................................................................. 4
1.3 Safety Precautions .................................................................................................................. 4
2
Description.................................................................................................................................. 5
2.1 Main Menu ............................................................................................................................. 6
2.2 Adjusting the Programmer ..................................................................................................... 7
2.2.1 Adjusting the Data Communication Protocol ................................................................ 7
2.2.2 Adjusting the Backlight Brightness ............................................................................... 8
2.2.3 Adjusting LCD Contrast ................................................................................................ 9
2.2.4 Adjusting the Time Before the Backlight Turns Off .................................................... 10
2.2.5 Adjusting Auto-shutdown Settings .............................................................................. 11
2.2.6 Adjusting Sound Settings ............................................................................................. 12
2.2.7 Battery Voltage ............................................................................................................. 13
2.3 Changing Address ................................................................................................................ 14
2.3.1 Changing Address of an Addressable Device Using the DPLS Protocol .................... 14
2.3.2 Changing Address of an Addressable Device Using the PA Protocol .......................... 17
2.4 Setting Addresses ................................................................................................................. 20
2.5 Reading Data ........................................................................................................................ 22
2.5.1 Reading Parameters of an Addressable Device Using the DPLS Protocol .................. 22
2.5.2 Reading the Status of an Addresable Device Using the PA Protocol ........................... 24
2.6 Information .......................................................................................................................... 26
2.6.1 Programmer Data ......................................................................................................... 26
2.6.2 Manufacturer Data ....................................................................................................... 26
2.6.3 Manufacturer Address .................................................................................................. 26
2.6.4 Company Phone/Fax .................................................................................................... 27
2.6.5 Manufacturer Site and E-Mail...................................................................................... 27
3
Connecting to the Charger ........................................................................................................ 28
4
Updating Programmer Firmware .............................................................................................. 29
5
Troubleshooting ........................................................................................................................ 31
6
Maintenance .............................................................................................................................. 32
7
Storage ...................................................................................................................................... 32
8
Transporting .............................................................................................................................. 32
9
Manufacturer Data .................................................................................................................... 32
10 Certificates ................................................................................................................................ 32
11 Product Acceptance Certificate ................................................................................................ 32
Page 4
ISO 9001
4
http://bolid.ru
1 General
S2000-APA Standalone Addressable Device Programmer (hereinafter referred to as the APA) is designed to assign addresses to addressable devices connected into the polling loops of S2000-KDL controllers and addressable devices connected into the Fire Threshold Addressable alarm loops of Signal-10 control units with PA data communication protocol. Also APA provides reading parameters and states of the addressable devices.
1.1 Specifications
1.2 Standard Delivery
1.3 Safety Precautions
WARNING: The programmer is intended to operate at ambient temperatures 0 to 50ºC.
The programmer is powered by lithium-ion batteries, so do not expose the programmer to high and low ambient temperatures in order to avoid battery failures.
The programmer is designed for operation in premises with regulated and unregulated climatic conditions. The design of the programmer does not provide operating under the influence of aggressive environment.
Parameter Value
Power Voltage
3.6 V (from built-in batteries)
Battery Capacity
800 mAh × 2 pcs
Max Consumed Current
70 mA
Current Consumption in Quiescent Mode
10 mA
Current Consumption in Turned Off Mode
100 µA
Dimensions
105 mm × 279 mm × 58 mm
Weight
500 gram
Operating Temperatures
0 to +50°С
Ingress Protection Rating IP30
Item Q-ty
Standalone Addressable Device Programmer
1pcs. S2000-APA Datasheet 1 pcs. Base Adapter (to accommodate various detector types)
1 pcs. 220V AC to 5V DC Power Adapter (1A) 1 pcs. USB Type-A to USB Type-B Connection Cable
1 pcs. Coffer with Belts
1 set Packing
1 pcs.
Page 5
S2000-APA
http://bolid.ru 5
2 Description
To program smoke, heat, and gas detectors with addresses, APA is equipped with a DIP-34A-03
base . To program other addressable devices, install the base adapter provided into the base. Figure 1 shows the view and the control buttons of the APA.
Figure 1. Appearance and Controls of the Programmer
1 – Base for inserting an analog addressable detector 2 – Display 3 – Keypad 4 – Base adapter (with red wire for +PL and blue wire for −PL”) 5 – Base adapter cover 6 – USB port
1 4
1
2
3
4
5
6
Page 6
ISO 9001
6
http://bolid.ru
2.1 Main Menu
1 – Name of the selected menu option 2 – Icon of the current menu option 3 – Battery indicator 4 – Indicator of the selected data communication protocol (DPLS/PA)
Switch the programmer on/off (hold the button pushed for 3 seconds).
Move between menu options.
Enter the selected menu option.
Cancel/Quit to the main menu.
The options of the main menu are as follows.
Change Address
Set Addresses
Read Parameters
Settings
Info
1
2
3
4
Page 7
S2000-APA
http://bolid.ru 7
2.2 Adjusting the Programmer
2.2.1 Adjusting the Data Communication Protocol
Select Settings in the main menu by means of the buttons:
Then press :
The first menu option provides selecting the data communication protocol for the programmer to operate with an addressable device:
The DPLS protocol (S2000-KDL)
The PA protocol (Signal-10)
By means of the buttons select the required protocol. The selected protocol will be indicated by the icon at the upper right corner of the display:
For the DPLS protocol, and For the PA protocol
To save changes and to return to the main menu, press .
To return to the main menu without saving changes, press .
Page 8
ISO 9001
8
http://bolid.ru
2.2.2 Adjusting the Backlight Brightness
Select Settings in the main menu with the help of the buttons:
Then press .
Use the buttons in the Settings menu to select the option BL Brightness:
By the buttons adjust brightness level of the backlight.
To save changes and to return to the main menu, press .
To return to the main menu without saving changes, press .
Page 9
S2000-APA
http://bolid.ru 9
2.2.3 Adjusting LCD Contrast
Select Settings in the main menu by means of the buttons:
Then press .
Select the LCD Contrast option ( ) of the Settings menu by the buttons.
Adjust the contrast level of the display by means of the buttons.
To save settings and return to the main menu, press .
To return to the main menu without saving changes, press .
Page 10
ISO 9001
10
http://bolid.ru
2.2.4 Adjusting the Time Before the Backlight Turns Off
Select Settings in the main menu by means of the buttons:
Then press .
Use the buttons in the Settings menu to select the option Backlight Off:
Select the timeout value using the buttons .
To save changes and to return to the main menu, press .
To return to the main menu without saving changes, press .
Page 11
S2000-APA
http://bolid.ru 11
2.2.5 Adjusting Auto-shutdown Settings
Select Settings in the main menu by means of the buttons:
Then press .
In the Settings menu use the buttons to select the option Auto Power-Off:
Using the buttons select the time for the programmer to shutdown automatically.
To save changes and to return to the main menu, press .
To return to the main menu without saving changes, press .
Page 12
ISO 9001
12
http://bolid.ru
2.2.6 Adjusting Sound Settings
Select Settings in the main menu by means of the buttons:
Then press .
Select the Sound option in the Settings menu by means of the buttons:
Then select the required setting by the buttons :
Sound effects are available, or
Sound effects are disabled.
To save changes and to return to the main menu, press .
To return to the main menu without saving changes, press .
Page 13
S2000-APA
http://bolid.ru 13
2.2.7 Battery Voltage
Select Settings in the main menu by means of the buttons:
Then press .
In the Settings menu by means of the buttons select the option Battery Voltage:
In the information area of the display the current battery percentage of capacity and battery voltage shall be indicated.
To quit to the main menu, press or .
Page 14
ISO 9001
14
http://bolid.ru
2.3 Changing Address
2.3.1 Changing Address of an Addressable Device Using the DPLS Protocol
In the main menu use the buttons to select the option Address Change:
Select DPLS as the protocol type (see Section Adjusting the Data Communication Protocol). Connect the addressable device to the programmer via the DIP-34A-03 base or via the base adapter
observing polarity and press . In case of incorrect polarity or a short circuit failure a warning shall be issued:
To quit to the main menu, press or .
Repair the failure and press .
To stop searching and quit to the main menu, press .
To stop searching as soon as the required device has been found, press or wait until the search is completed.
On completing the operation the result can be seen on the display:
– If no addressable device is found then the display will be as follows:
To quit to the main menu, press or .
Page 15
S2000-APA
http://bolid.ru 15
– If the addressable device is found then its name, address and the firmware version will be shown on the display:
1: The name of the addressable device; 2: The device picture; 3: The device address; 4: The firmware version of the addressable device.
If several addresses are assigned to the addressable device then use the buttons to select the address to be changed:
Then press .
By means of the buttons select the position of the digit to be changed;
By means of the buttons change the digit values of the address. If the new address has been already occupied then the programmer displays a warning:
To cancel operation and return to the address selecting menu press .
To confirm changing the address, press . If the address has already been in use then the programmer will request a confirmation:
To cancel, press .
To continue, press .
2
1
3
4
Page 16
ISO 9001
16
http://bolid.ru
When the change address operation is completed the procedure of addressable device search will be started:
On completing the search the display will show the information about the addressable device:
To quit to the main menu, press . If the addressable device has not responded the display indicates an error:
To quit to the main menu, press or .
Page 17
S2000-APA
http://bolid.ru 17
2.3.2 Changing Address of an Addressable Device Using the PA Protocol The PA address can be changed only for addressable devices which have already been
assigned with addresses.
In the main menu use the buttons to select the option Address Change:
Select PA as the protocol type (see Section Adjusting the Data Communication Protocol). Connect the addressable device to the programmer via the DIP-34A-03 base or via the base adapter
observing polarity and press . In case of incorrect polarity or a short circuit failure a warning shall be issued:
To quit to the main menu, press or .
Repair the failure and press .
To stop searching and quit to the main menu, press .
To stop searching as soon as the required device has been found, press or wait until the search is completed.
On completing the operation the result can be seen on the display:
– If no addressable device is found then the display shows the message as follows:
To quit to the main menu, press or .
– If the addressable device is found then the display shows its address:
Page 18
ISO 9001
18
http://bolid.ru
To quit to the main menu, press .
To change the address, press .
By means of the buttons select the position of the digit to be changed;
By means of the buttons change the digit values of the address.
To cancel, press . To change address for a DIP-34PA or S2000-IP-PA:
Press and hold the LED button on the addressable device.
Holding the button pressed, press .
Wait until the LED of the addressable device starts illuminating.
Release the button when the LED of the addressable device has turned off.
If the address change operation has succeeded then a search procedure shall be started:
On completing the search the display will show the information about the addressable device with the new address:
To quit to the main menu, press .
Page 19
S2000-APA
http://bolid.ru 19
If the addressable device has not responded to the command to change address then the display indicates an error:
To quit to the main menu, press or .
WARNING: Addressable detectors operating with a Signal-10 come with indefinite factory addresses. To assign addresses to them do the following:
For DIP-34PA and S2000-IP-PA detectors it is necessary to:
Press the LED button on the addressable device and holding it pressed start the operation of
changing address.
Wait until the detector LED starts illuminating.
Release the button when the LED has turned off. It means that the first address is assigned to
the addressable device.
Start the operation of changing address to assign a required address.
For an IPR 513-3PAM an address is assigned as discussed in its Instruction Manual. For DIP-34PA and S2000-IP-PA addresses also can be assigned as discussed in their Instruction Manuals.
Page 20
ISO 9001
20
http://bolid.ru
2.4 Setting Addresses
The mode of setting addresses is available only for the DPLS protocol. Select DPLS as the protocol type (see Section Adjusting the Data Communication Protocol).
In the main menu use the buttons to select the option Addr Settings:
Then press .
Use the buttons and to select an initial value of an address range:
To quit to the main menu, press .
To proceed to setting of the last address of the range, press .
Use the buttons and to define a last address value provided that this value should be more or equal to the first address value:
To return to the previous step, press .
To start the procedure of setting addresses, press .
Connect an addressable device to the programmer via the DIP-34A-03 base or via the base adapter observing polarity.
The programmer will automatically find the addressable device and change its address for a next address of the given range.
Page 21
S2000-APA
http://bolid.ru 21
When an addressable device is responding to programmer commands the display indicates the procedure of changing address:
If the addressable device with the new address has not responded the display indicates an error:
To cancel operation and quit to the main menu, press .
To continue programming address, press .
If the command of changing address has succeeded then the address indicated on the display will be a new one:
For an addressable device with several addresses the programmer checks whether the device responds from the new addresses, automatically takes into account the range of occupied addresses, and changes the number for a next one from a given sequence. To continue, remove the addressable device from the programmer and connect the next addressable device. The procedure of setting address shall start automatically for a new address.
The mode of setting addresses terminates when the last given address has been assigned:
To quit to the main menu, press .
To continue, press .
To continue, define a new range of addresses.
To quit to the main menu, press .
Page 22
ISO 9001
22
http://bolid.ru
2.5 Reading Data
2.5.1 Reading Parameters of an Addressable Device Using the DPLS Protocol
Select Read Parameters (the icon ) in the main menu by the buttons:
Select DPLS as the protocol type (see Section Adjusting the Data Communication Protocol). Connect the addressable device to the programmer via the DIP-34A-03 base or via the base adapter
observing polarity and press .
To stop searching and quit to the main menu, press .
To stop searching as soon as the required device has been found, press or wait until the search is completed.
On completing the operation the result can be seen on the display:
– If no addressable device is found then the display shows the message as follows:
– If the addressable device is found then the display shows its name, address(es) and firmware version:
If the addressable device is assigned to several addresses then select the required address by the
buttons and press
1 – The name of the selected addressable device; 2 – The icon of the parameter; 3 – The value of the parameter; 4 – The description of the parameter or the units of measurement.
2
3
4
1
Page 23
S2000-APA
http://bolid.ru 23
The parameter icons can be:
- Request for analog-to-digital converter value
- Request for dustiness value
- Request for voltage value
Parameters and units of measurement:
- Analog-to-digital converter units
- Dustiness of the smoke chamber of the detector
- Parts-per-million (10-6)
- Degrees Centigrade
- Percentage
- Volts
Page 24
ISO 9001
24
http://bolid.ru
2.5.2 Reading the Status of an Addresable Device Using the PA Protocol
In the main menu use the buttons to select the option Read Parameters:
Select PA as the protocol type (see Section Adjusting the Data Communication Protocol). Connect the addressable device to the programmer via the DIP-34A-03 base or via the base adapter
observing polarity and press .
To stop searching and quit to the main menu, press .
To stop searching as soon as the required device has been found, press or wait until the search is completed.
On completing the operation the result can be seen on the display:
– If no addressable device is found then the display will be as follows:
– If the addressable device is found then its address will be shown on the display:
To quit to the main menu, press .
To read the status of the addressable device, press .
1: Addressable device picture; 2: The code of the status of the addressable device; 3: The short description of the status type.
1
2
3
Page 25
S2000-APA
http://bolid.ru 25
The status can be one of the following:
- The smoke alarm is dusted and requires service
- Norm
- Fault
- Tested
- Fire Alarm (for a smoke or heat detector)
- Manual Fire Alarm (for a manual call point)
Page 26
ISO 9001
26
http://bolid.ru
2.6 Information
In the main menu use the buttons to select the option Info:
Then press .
Move between menu options
or Quit to the main menu
2.6.1 Programmer Data
Device Type: S2000-APA Firmware version: V1.00 Model: 0 Revision: 5 Date: 05.2017 ID: 01234567
2.6.2 Manufacturer Data
Manufacturer: Bolid CJSC
2.6.3 Manufacturer Address
Manufacturer address: 4 Pionerskaya Str., Korolev, Moscow Region, Russia.
Page 27
S2000-APA
http://bolid.ru 27
2.6.4 Company Phone/Fax
Company phone/fax: (495) 775-71-55 (multi-channel), 777-40-20
2.6.5 Manufacturer Site and E-Mail
E-mail: info@bolid.ru
The last version of the firmware along with additional information about operating the programmer are available in Internet at the address of:
www.bolid.ru.
Page 28
ISO 9001
28
http://bolid.ru
3 Connecting to the Charger
To recharge batteries, use the AC/DC power adapter supplied. Connect the programmer to the power adapter via the USB port.
If the programmer is turned off then the display shall indicate the charging mode:
This display indicates charging in progress
This display indicates that charging has been completed
If the programmer is turned on then charging mode is indicated by the blinking battery icon in the top right corner of the display:
When charging is completed the programmer issues a sound and the battery icon stops blinking.
– The icon shows the level of battery charge.
– The icon shows that the programmer is connected to the charger.
WARNING: While the batteries are being charged the programmer doesn’t turn off
automatically. To switch the programmer off, press and hold the button .
Page 29
S2000-APA
http://bolid.ru 29
4 Updating Programmer Firmware
Prior to connecting the programmer to a personal computer for the first time it is necessary to install its driver. For doing so:
1. Go to
http://bolid.ru/production/orion/support-hardware/apa.html#download
(PRODUCTS Integrated security system “Orion” AUXILIARY EQUIPMENT S2000-APA Download). In the section Distributives select the driver zipfile.
2. Download the file usb_rs_exar.zip and unpack it.
3. Run the driver installation file xrusbser_ver2200_installer.exe from the EXE folder.
4. Follow the installation instructions.
To switch the programmer to the firmware update mode (BootLoader), connect the programmer to the PC by means of the USB cable. If the programmer is turned on, turn it off. Then press both the
buttons and simultaneously and hold them pressed for at least 3 seconds.
If the programmer is connected for the first time then a new hardware installation wizard software will be run. Wait until installation has been completed.
The file with update firmware can be found at the address of
(PRODUCTS Integrated
http://bolid.ru/production/orion/support-hardware/apa.html#download
security system “Orion” AUXILIARY EQUIPMENT S2000-APA Download) in the section Firmware.
Run the update file UpdateS2000_APA-En_Vx_xx.exe.
To cancel updating and quit the program, click Close. To start updating, click Next.
Page 30
ISO 9001
30
http://bolid.ru
Wait until updating is completed:
When updating is completed the programmer will proceed to the operating mode and turns on. To quit the program, click Close.
Page 31
S2000-APA
http://bolid.ru 31
5 Troubleshooting
The table below shows common problems and ways for their repairing.
Problem Possible Cause Remedy
The programmer doesn’t turn on
Low battery
Connect the programmer to the charger and recharge the batteries
An error while writing or reading the address of a device
Faulty programmed device or the device is not properly connected to the programmer (no contact)
Connect an operative addressable device (repair the contact)
Page 32
ISO 9001
32
http://bolid.ru
6 Maintenance
When using the programmer it is necessary to monitor the level of battery charge and recharge the batteries in time.
Visit the Bolid site periodically to know whether a new version of programmer firmware has been published and update the firmware.
7 Storage
Programmers should be stored packed at an ambient temperature of 0 to 50°C. Programmers should be stored on the shelves. The distances between the walls or the floor of the storage room and packages with programmers
should be at least 0.1 m. The distances between the heating devices and packages with programmers should be at least 0.5 m. There should be no vapors of aggressive substances and conductive dust in the room.
8 Transporting
Packed programmers can be transported by all kinds of transport in covered vehicles and in sealed aircraft compartments.
9 Manufacturer Data
The Bolid Company, Russia Address: 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia Tel./fax: +7 (495) 775-71-55 (multi-channel), +7 (495) 777-40-20, +7 (495) 516-93-72 E-mail: info@bolid.ru; Technical Support: support@bolid.ru; http://bolid.ru
10 Certificates
Production of Standalone Addressable Device Programmer is certified according to ГОСТ ISO 9001-2011 by a conformity certificate No.РОСС RU.ИК32.К00153.
Conformity Certificate ЕАЭС RU Д-RU.МЕ61.В.00699 certifies that S2000-APA Standalone Addressable Device Programmer meets the requirements of Technical Reglament of Custom Union TR CU 020/2011.
11 Product Acceptance Certificate
Standalone Addressable Device Programmer with Serial No._________________ is accepted in accordance with mandatory requirements of state standards and current technical documentation, qualified as proper for operation and packaged by CJSC NVP “Bolid”.