OFF ON
After recovering
mains power test the
battery charge-
discharge cycle *
AC line failed, the battery
voltage is below 10.2 V
(after two hours)
OFF
Flashes once
every 10 s
OFF ON
After recovering
mains power test the
battery charge-
discharge cycle *
Note:
• After detaching the battery from the load circuit and recovering utility power it is necessary to check the
battery charge-discharge cycle. If the CHARGE LED has been still lit after 24 hours since having
restored power then the battery operability has to be checked. If extra batteries are connected the charge
time will be increased.
RIP-12 SHUTTING OFF
1. Shut off the mains power supply 220 V.
2. Remove the fuse F1.
3. Detach the battery.
4. Disconnect the load circuit.
MAINTENANCE
The maintenance of RIP-12 is to be carried out annually. The maintaining operations include:
1) RIP-12 visual inspection to discover mechanical injures and to clean any dirt or dust if presented.
2) Measuring the power output parameters and checking them to be in conformance with items of
SPECIFICATION.
3) LED and sound indication testing to meet the requirements of Table above.
4) Proper RIP-12 attaching and contact tightening and wire integrity inspection.
TROUBLESHOOTING
Symptom Reason Human Action
The RIP-12, being powered by
mains power, is not turned on
The F1 fuse has blown or wiring
is faulty
Measure the voltage across XT1 contacts
before the F1 fuse and after this one,
replace the F1 fuse, repair wiring
The RIP-12, being powered by
the battery, is not turned on
The output voltage of the battery
has dropped below 10 V
Measure the battery output voltage and
charge or replace the battery, if necessary
MANUFACTURER
ZAO NVP BOLID
#4, Pionerskaya street, Korolev, Moscow Region, Russia, 141070
Tel./fax +7 495 775-71-55
E-mail: info@bolid.ru, overseas@bolid.com Web-site: www.bolid.com
BATTERY BACKED POWER SUPPLY
RIP-12 model 01
INSTRUCTION MANUAL
GENERAL
Battery Backed Power Supply RIP-12 model 01 (referred to as RIP-12 below) is designed to provide electric power
to various fire and intrusion detectors as well as control and indication equipment suited for uninterrupted 12 VDC.
The RIP-12 is round-the-clock operating device with defined output parameters, sealed backup battery being tested
and charged automatically. PIR-12 provides shutting off the battery from load circuit to avoid its unacceptable discharge.
The RIP-12 is equipped with light and audible indication of its current status, i.e. normal or no voltage, battery
charge, output short failure or overload, battery missing or shutting down when discharged.
Being powered by AC power, the RIP-12 provides its outputs against short circuit failures with automatic
recovering output voltage after repairing short circuit failures. Also the RIP-12 protects its outputs against
overvoltage.
Being powered by the backup battery, the RIP-12 provides its outputs against short circuit failures with automatic
recovering output voltage after repairing short circuit failures.
When operated, the RIP-12 should be protected against atmospheric fallout and mechanical damage.
SPECIFICATION
AC Input Voltage Range: from 150 to 250 VAC @ 50 Hz
Backup Power Supply: a battery «Delta» DTM1217 12 V @ 17 Ah or analogous
Output Voltage Range:
13.6 ± 0.6 VDC at both AC and charged battery powering;
11.0 VDC min provided the battery is discharged
Load Current Rating: 3.0 А
Maximum Load Current: 4.0 А for 10 min, once an hour, at both mains and battery pow.
Input Power: 100 W max at rating voltage
Input Current Consumption: 0.5 A max at rating load
RIP-12 Consumption From the Battery: 40 mA max
Ripple (mVp-p)×2: 120 mV maximum at rating load current
Battery Low Shutdown:
10.2±0.6 VDC
On Battery Run-Time:
at least 4 hours for 3 A load current at 25°C
Pre-Operation Time: 6 seconds maximum
Operating Temperature Range:
from –10°C to +40°C
Overall Dimensions: 255 mm х 310 mm х 95 mm
RIP With Battery Weight: 8.5 kg maximum
Software Version 7.1
Typical Lifetime: 10 years, the battery being to be replaced once every 5 year
The RIP-12 provides outputting a signal to the NPN output in case of switching to powering by the backup battery
(in state of no mains power) or a short failure in the load circuit. It is opened when AC line fails and the RIP-12 is
operating in battery mode or in case of a short load circuit failure, and it is closed when the RIP-12 is powered by
mains power, so it can be used for remote signaling RIP electric troubles. The maximum NPN output permissible
voltage and commutation current are 30 V and 100 mA respectively.
The RIP-12 is equipped with a tamper switch which terminals are closed in state of the closed RIP-12 door and are
open in state of opening the RIP-12 door. Tamper switch terminals are coupled to the XT2 terminal block.
RIP-12 provides connecting two extra 12 V batteries of 17 Ah each placed in a special Box 2x17Ah to increase the time
of operation from the battery (with total capacity of all RIP-12 batteries being of 51 Ah).
STANDARD DELIVERY
Battery Backed Power Supply RIP-12 mod.01 1
Instruction Manual 1
Fuse 2А 1
Woodscrews 3
Wallplugs 3
Plastic Bushing 2
Lock Key 2