Features & Benets ...............................................................................................................................................................................................
Performance Data & Specications
Air Defrost ....................................................................................................................................................................................................4-5
Electric Defrost ...........................................................................................................................................................................................6-7
Hot Gas Defrost .......................................................................................................................................................................................... 8-9
Physical Data .................................................................................................................................................................................................. 10-11
Dimensional Data ................................................................................................................................................................................................12
Hot Gas Reverse Cycle Kits ........................................................................................................................................................................ 13-14
3-Pipe Hot Gas Defrost ......................................................................................................................................................................................15
Replacement Parts by InterLink™ ..................................................................................................................................................................16
Standard Nozzle Selection ...............................................................................................................................................................................
We have made a commitment to customer needs, innovation and environmental stewardship and have dedicated
ourselves to delivering energy-ecient choices. PSC and EC motors will reduce costs, improve the bottom line and
enhance equipment performance and service life.
3
17
Choose the most energy-ecient motor available for evaporators.
Nomenclature
ADT120AK
Model SeriesCapacityElectrical CodeDesign Revision
ADT = Air defrost
LET = Electric defrost, 6 FPI
LLE = Electric defrost, 4 FPI
HGT = Hot gas defrost
2
# x 100 = BTUHA = 115/1/60
The EC motor is an Energy Solutions® option on new Bohn Low Prole
evaporators. Available on all new equipment or as an easy-to-install,
drop-in replacement aftermarket part from InterLink™ Commercial
Refrigeration Parts. Because they’re a drop-in replacement for existing
shaded pole and PSC motors, installation is quick and easy. It’s a high impact, quick payback solution for reducing costs and achieving green
initiatives without replacing the entire system.
EC motors by InterLink are up to 75% ecient - that’s a 51-59% increase
over shaded pole motors and a 30-35% increase over permanent-split
capacitor (PSC) motors. With all of this added eciency, you can count
on more energy savings and lower operational costs while taking a
step in the right direction toward conserving our planet’s resources.
To learn more about EC motors, visit www.interlinkparts.com/ec.
B = 208-230/1/60
C = 208-230/3/60
M = 460/1/60
AH = 115/1/60 (PSC)
BH = 208-230/1/60 (PSC)
AE = 115/1/60 (EC)
BE = 208-230/1/60 (EC)
CE = 208-230/3/60 (EC)
Minimal height of the low profile series makes it ideal for low ceiling coolers
•
Cabinet design features front access panels on each side for easy access to electrical and refrigeration components
•
All electrical components factory wired to terminal board and identified, making it easy to field wire the unit
•
Sweat connections to reduce potential for leaks
•
Internal panels are isolated for quiet operation
•
Liquid line solenoid wire harness is factory-installed for quick installation
•
Pre-drilled holes on the back of the unit for room thermostat
•
Coil
Internally enhanced tubing and fin design for higher efficiency
•
Coil heater slots have been enlarged for easier installation and replacement
•
Reduced heater wattages
•
Hot gas loop on bottom of coil for easier access is standard for hot gas defrost models
•
Fixed defrost termination for electric, adjustable defrost termination for hot gas
•
Drain Pan
Large diameter drain hole (3/4" ID) is located on the back of the unit
•
Extended drain pan heaters for more uniform defrost throughout the drain pan and additional heat in
•
end compartments
On 4-6 fan models, drain pan has a lanyard for easy and safe access
•
Motors
Motors plug into wiring harness for easier servicing
•
EC motors available factory-installed or as a drop-in replacement through InterLink™ Commercial Refrigeration Parts in
•
115/1/60, 208-230/1/60 and 208-230/3/60 unit voltages
PSC and PSC (Totally Enclosed) motors for 115/1/60, 208-230/1/60 and 460/1/60 unit voltages
•
PSC motors or EC motors required for 50 Hz operation
•
Options
Unit Configurations: mounted components, pre-assembled, pre-charged and Beacon II™
•
- Units available with mounted TXV and mounted TXV / solenoid valve
- Pre-assembled units come with mounted TXV, liquid line solenoid valve and room thermostat. Available in a master
liquid line configuration
- Pre-charged units come with mounted TXV, liquid line solenoid valve, room thermostat and quick connect fittings
- Various room thermostat variations including rear mount and front access versions
- Beacon II units come with electronic expansion valves, pressure transducer, temperature sensors and Beacon
control board
Most models available with glycol circuiting (see glycol product brochure)
•
Units available with stainless steel housing and drain pan
•
Units available with copper fins. Air defrost units also available with polyester coated fins or various coil coatings options
The standard design for the Bohn Low Prole Evaporator incorporates a hot gas loop in the drain pan. Utilizing a hot gas
loop is ideal for hot gas defrost applications where high temperature gas can be maintained to defrost both the evaporator
drain pan and coil.
For applications where cooler (lower) temperature hot gas is used for defrosting, Bohn oers optional electric heater
elements in the drain pan to ensure quick and ecient defrost of the drain pan allowing condensate to drain quickly, saving
the hot gas for ecient evaporator coil defrost.
If the optional electric heating element drain pan is preferred, please specify when ordering, there is no additional charge.
NOTE: Hanger brackets will accept 3/8” / 9.5 mm hanger rods.
Electric and
Hot Gas
Defrost Model
No.
of
Fans
Dimensions
ABCD
12
Hot Gas Reverse Cycle Kits
Shipped-looseFactory-installed
TXV Bypass Assembly KitsTXV Bypass Assembly Kits
HGT 6 FPISQE/SBFEGHFESCSQE/SBFEGHFESC
035-075
090-160
180-280
HGT 4 FPI
041-080
102-204
235
HGT 6 FPI
035-065
075-140
160-280
HGT 4 FPI
041
068-102
136-235
Recommendation is that both check valve kits are ordered: (For hot gas models with the hot gas loop drain
pan ONLY)
NOTE: The drain pan check valve kit can be ordered as an independent item. But the suction line check valve kit
must be ordered with the drain pan check valve kit in order to complete the piping.
NOTE: When using the hot gas units with a hot gas loop drain pan on 0°F applications and below, an insulated
drain pan is required.
50169210
50169211
50169212
50169210
50169211
50169212
Shipped-looseFactory-installed
Drain Pan Loop
Check Valve Kit
50169304
50169305
50169306
50169304
50169305
50169306
50169213
50169214
50169215
50169213
50169214
50169215
50169216
50169217
50169218
50169216
50169217
50169218
Suction Line
Check Valve Kit
50169604
50169605
50169606
50169604
50169605
50169606
52733701
52733702
52733703
52733701
52733702
52733703
Drain Pan Loop
Check Valve Kit
52733601
52733602
52733603
52733601
52733602
52733603
52733704
52733705
52733706
52733704
52733705
52733706
52733707
52733708
52733709
52733707
52733708
52733709
Suction Line
Check Valve Kit
52733801
52733802
52733803
52733801
52733802
52733803
The hot gas unit coolers can be used in reverse cycle hot gas defrost systems using multiple evaporators connected to one
condensing unit. Generally, not more than one-third of the system defrosts at one time.
During the reverse cycle defrost, the reversing valve;
located in the compressor discharge line, diverts hot
gas through the suction line to the evaporator. See
piping view in Figure 1. The suction line check valve
directs the hot gas through the drain pan loop which
prevents condensate in the pan from freezing. The
hot gas exits the loop at the pan loop outlet header
and enters the evaporator through the check valve
assembly. As the hot gas defrosts the coil, heat is
removed from the hot gas and eventually it condenses
into a liquid and exits the coil at the distributor
sideport. The liquid then ows through the check
valve of the thermostatic expansion valve bypass
assembly, around the thermostatic expansion valve,
and into the system liquid line. The liquid refrigerant
then feeds other evaporators on the cooling cycle,
evaporates, and returns to the compressor through
their suction lines.
13
Hot Gas Reverse Cycle Kits (cont.)
In the refrigeration cycle, the thermostatic expansion
valve bypass assembly check valve only allows refrigerant
ow through the thermostatic expansion valve and into the
evaporator coil. As the refrigerant vapor exits the coil at the
suction line, the check valve of the drain pan loop check valve
assembly prevents the refrigerant vapor ow through the drain
pan loop.
Factory engineered assemblies (kits) are available for both
shipped-loose and factory-installed at an additional cost to
complete the reverse cycle piping and components. The suction
line check valve assembly includes the suction line check valve
and the piping for both the suction line and the connection
to the drain pan loop inlet header. In order for the suction line
check valve assembly to be mounted, the drain pan loop check
valve assembly must be used. The drain pan loop check valve
assembly includes the check valve, suction line tee and a bent
pipe. The thermostatic expansion valve bypass assembly option
includes the check valve, tee and necessary piping. In order for
the thermostatic expansion valve bypass assembly option to
be complete, a thermostatic expansion valve must be selected
by the sales engineer. The thermostatic expansion valve
bypass assembly option is dependent on the body style of the
thermostatic expansion valves which includes the Sporlan SQE,
SBF, EG and the Alco HFESC body styles. The factory-installed
thermostatic expansion valve bypass assembly option must
have the thermostatic expansion valve selection included on
the order for the hot gas unit cooler.
To increase the eciency, higher performance and greater system protection, a heat exchanger may be benecial to the
system. In order to use a heat exchanger, the thermostatic expansion valve bypass assembly option must be modied. See
the piping view in Figure 2. The modication includes rerouting the pipe from the thermostatic expansion valve bypass
check valve to the inlet connection of the liquid line to the heat exchanger. A pipe needs to be routed from the liquid line
outlet connection of the heat exchanger to the inlet connection of the thermostatic expansion valve.
The electrical control option includes an adjustable defrost termination and fan delay control (DTFD) which is standard.
For an additional cost, an optional (2) control electrical system is available with one adjustable control for defrost
termination (DT) and one xed control for the fan delay (FD). For both the DTFD and DT adjustable controls, the remote
bulb position is with the bulb strapped to the piping of the thermostatic expansion valve bypass assembly option between
the distributor sideport and the check valve. When the thermostatic expansion valve bypass assembly is shipped-loose, the
installer will need to position the remote bulb. When the thermostatic expansion valve bypass assembly is factory-installed,
the remote bulb should already be properly installed.
14
3-Pipe Hot Gas Defrost
The hot gas defrost unit coolers conforms to
the standard 3-pipe hot gas system using a check
valve assembly, an electrical control to terminate
the defrost, and a hot gas solenoid valve. The
check valve assembly transports the hot gas
between the drain pan loop and the sideport
distributor of the coil. The check valve assembly kit
is available for shipped-loose or factory-installed
for an additional cost.
The electrical control option includes an
adjustable defrost termination and fan delay
control (DTFD) which is standard. An optional
(2) control electrical system is available with one
adjustable control for defrost termination (DT)
and one xed control for the fan delay (FD) for
an additional cost. For both the DTFD and DT
adjustable controls, the remote bulb position is
with the bulb strapped to the suction line to insure
a complete defrost. The remote bulb is positioned
by the installer. The hot gas solenoid valve must be
ordered separately and will be shipped-loose. The thermostatic expansion valve could be ordered separately and shippedloose or the thermostatic expansion valve could be factory-installed with a liquid line for an additional cost.
The liquid line is designed for the body styles of the Sporlan SQE, SBF, EG and the Alco HFESC thermostatic expansion
valves. The thermostatic expansion valve needs to be selected by the sales engineer. In a typical 3-pipe, multiple evaporator
system, the compressor discharge defrosts the evaporator. The liquid/vapor mixture of refrigerant after defrost, however,
returns to the common suction line of the system. In order to provide sucient re-evaporation of the liquid vapor mixture
and sucient heat for defrost, no more than one-third of the system should be defrosted at one time. Some means of
control in the 3-pipe hot gas system should be supplied to regulate the large amount of liquid returning to the compressor,
refrigerant slugging can otherwise damage the compressor.
Shipped-looseFactory-installed
TXV Liquid LineTXV Liquid Line
HGT 6 FPISQE/SBFEGHFESCSQE/SBFEGHFESC
035-075
090-160
180-280
50169410
50169411
50169412
50169413
50169414
50169415
50169416
50169417
50169418
52733901
52733902
52733903
52733904
52733905
52733906
52733907
52733908
52733909
HGT 4 FPI
041-080
102-204
235
For hot gas models with the
hot gas loop drain pan only
When using the hot
gas units with a hot
gas loop drain pan on
0°F applications and
below, an insulated
drain pan is required.
50169410
50169411
50169412
HGT 6 FPI
035-075
090-160
180-280
50169413
50169414
50169415
50169416
50169417
50169418
52733901
52733902
52733903
52733904
52733905
52733906
52733907
52733908
52733909
Shipped-looseFactory-installed
Drain Pan Loop Check Valve KitDrain Pan Loop Check Valve Kit
50169504
50169505
50169506
52739601
52739602
52739603
HGT 4 FPI
041-080
102-204
235
50169504
50169505
50169506
52739601
52739602
52739603
15
Replacement Parts
Commercial Refrigeration Parts
Right source. Right parts. Right now.
InterLink™ is your link to a complete line of dependable and certied
commercial refrigeration parts, accessories and innovative electronic
controls for all Bohn equipment. At InterLink, we provide our wholesalers
with a comprehensive selection of product solutions and innovative
technologies for the installed customer base. And every product is built
to ensure the same high performance standards with which all Heatcraft
Refrigeration Products (HRP) brands are built — backed by a dedicated
team to serve every customer need, delivering at the best lead times in
the industry.
Dependable. Versatile. Courteous.
Finally, one simple source for all your replacement needs from a name
you can trust.
For parts, please contact (800) 686-7278 or visit www.interlinkparts.com.
5140CFan Blade1 - 6
37000701Fan Guard - Molded1 - 6
37000601Fan Guard - Wire1 - 6
23104901Motor Mount used with 115 & 230V motors1 - 6
23103301Motor Mount used with 460V motors1 - 6
Cabinet Components
Part #DescriptionNo. Fans
40480101Drain Pan Air & Hot Gas Defrost1
40480201Drain Pan Air & Hot Gas Defrost2
40480301Drain Pan Air & Hot Gas Defrost3
40480401Drain Pan Air & Hot Gas Defrost4
40480501Drain Pan Air & Hot Gas Defrost5
40480601Drain Pan Air & Hot Gas Defrost6
40480103Drain Pan Electric Defrost1
40480205Drain Pan Electric Defrost2
40480305Drain Pan Electric Defrost3
40480403Drain Pan Electric Defrost4
40480503Drain Pan Electric Defrost5
40480603Drain Pan Electric Defrost6
40880801Access Panel - Elect.1 - 6
40880701Access Panel - Refrig.1 - 6
40880901Back Panel - Refrig.1 - 6
40881001Back Panel - Elect.1 - 6
40881201End Panel - Hot Gas Refrig.1 - 6
Hot Gas Defrost - Electric Drain Pan
Option Drain Pan Heater (1 per unit)