Boge S 60-2, SF 60-2, S 61-2, S 75-2, S 100-2 Operating Instructions Manual

...
Operating instructions
Belt-driven screw compressors S 40-2 ... S 341 SF 40-2 ...SF 220 series
Before installation or starting the compressor for the first time, this manual should be studied carefully to obtain a clear knowledge of the unit and of the duties to be performed while operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the air compressor at all times.
separate manuals: compressor control / frequency converter
Index
Operating instructions for the belt-driven screw compressors
– S 40-2 / SF 40-2 ( 40 Hp) – S 50-2 ( 50 Hp) – S 60-2 / SF 60-2 ( 60 Hp) – S 61-2 ( 60 Hp) – S 75-2 ( 75 Hp) – S 100-2 / SF 100-2 (100 Hp) – S 101 (100 Hp) – S 125 (125 Hp) – S 150
-2 / SF 150 (150 Hp)
– S 151 (150 Hp) – S 180 (180 Hp) – S 220 – S 271 – S 341
BOGE KOMPRESSOREN P.O. Box 10 07 13 D-33507 Bielefeld Germany
Otto-Boge-Straße 1–7 D-33739 Bielefeld
Phone: ++49 / 52 06-6 01-0 Fax: ++49 / 52 06-6 01-2 00 Mail: info@boge.com Net: www.boge.com
-2 / SF 220 (200 Hp)
(270 Hp) (340 Hp)
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Inhalt.pm6.5 - USA
As of 04 / 2010
No. 596.0935.18
Nominal price: US $ 5.00
Page I
Index
Page II BOGE Operating instructions for S 40-2... S 341 / SF 40-2... SF 220 series screw compressors
Inhalt.pm6.5 - USA
Index
Index
Part 1: General
Part 2: Product description
1.1 General safety instructions ......................................................... 1.1
Safety instructions for compressor operation .................................1.1
Safety instructions for maintenance and repair of the compressor. 1.2
Accident prevention regulations ..................................................... 1.2
1.2 Introduction ..................................................................................1.4
Symbols used................................................................................. 1.4
Symbols on the compressor ........................................................... 1.5
Intended use .................................................................................. 1.7
Inadmissible use ............................................................................1.7
Transportation damage ..................................................................1.8
Data on the type plate ....................................................................1.8
Service ...........................................................................................1.8
2.1 Technical data ..............................................................................2.1
Technical data S 40-2 to S 100-2, part 1 ........................................ 2.1
Technical data S 101 to S 341, part 1............................................. 2.2
Technical data S 40-2 to S 100-2, part 2 ........................................ 2.3
Technical data S 101 to S 341, part 2............................................. 2.4
Technical data SF 40-2 to SF 220, part 1 .......................................2.5
Technical data SF 40-2 to SF 220, part 2 .......................................2.6
2.2 Function description.................................................................... 2.7
Function principle of the air end ..................................................... 2.7
Air circuit ........................................................................................ 2.7
Oil circuit ........................................................................................ 2.8
2.3 Compressor control ..................................................................... 2.9
Supply pressure ............................................................................. 2.9
Operating states ............................................................................. 2.9
Operating modes............................................................................ 2.9
Short operating times .....................................................................2.9
2.4 Control devices ..........................................................................2.10
Operating pressure transmitter..................................................... 2.10
Proportional controller (option for S-series) .................................. 2.10
2.5 Safety and monitoring devices ................................................. 2.11
General ........................................................................................ 2.11
Safety temperature limiting device ............................................... 2.11
Safety valve ..................................................................................2.11
Monitoring the drive and fan motor............................................... 2.11
Rotational direction monitoring ..................................................... 2.11
Safety pressure switch (option) .................................................... 2.11
System pressure build-up (option) ...............................................2.11
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Inhalt.pm6.5 - USA
Page III
Index
2.6 Water cooling .............................................................................. 2.12
Serial connection.......................................................................... 2.12
Parallel connection ....................................................................... 2.12
2.7 Cooling water ............................................................................. 2.13
Water connection (for water cooling) ............................................ 2.13
Cooling water quality .................................................................... 2.13
Part 3: Installation
3.1 Transport ....................................................................................... 3.1
General .......................................................................................... 3.1
Transport possibilities .....................................................................3.1
3.2 Compressor room ........................................................................3.2
Installation surface ......................................................................... 3.2
Fire protection ................................................................................ 3.2
Admissible environmental influences ............................................. 3.2
Frost protection .............................................................................. 3.2
Ventilation ....................................................................................... 3.2
Cooling air requirement ..................................................................3.3
Ventilation possibilities ...................................................................3.4
Condensate disposal ...................................................................... 3.4
3.3 Installation ....................................................................................3.5
General .......................................................................................... 3.5
Checking the delivery scope .......................................................... 3.5
Installing the compressor ............................................................... 3.5
Connecting the compressor to the compressed air network ..........3.5
Connecting the cooling water (option) ............................................ 3.6
Removing the transport securing bolts ........................................... 3.6
Activating the belt tensioning device .............................................. 3.7
Checking the oil level ...................................................................... 3.7
3.4 Electrical connection ................................................................... 3.8
3.5 Commissioning ..........................................................................3.10
Checking the rotational direction ..................................................3.10
Opening the stop valves ............................................................... 3.10
Checking for leaks........................................................................ 3.10
Conduct trail run ........................................................................... 3.10
Commissioning following extended stoppages .............................3.11
Part 4:
4.1 General.......................................................................................... 4.1
Faults
4.2 General faults ...............................................................................4.2
Part 5: Maintenance
Page IV BOGE Operating instructions for S 40-2... S 341 / SF 40-2... SF 220 series screw compressors
5.1 Safety instructions .......................................................................5.1
5.2 General.......................................................................................... 5.2
Maintenance through BOGE service .............................................. 5.2
Review of regular maintenance work ............................................. 5.2
Inhalt.pm6.5 - USA
Index
Maintenance intervals .................................................................... 5.3
General information concerning the lubricants used ...................... 5.4
Disposal of used operating material ...............................................5.5
Spare and wearing parts ................................................................5.5
5.3 Regular maintenance work ..........................................................5.6
Clean or change intake filter........................................................... 5.6
Cleaning the filter cartridge ............................................................ 5.6
Changing the supply air filter mats (option) ....................................5.7
Lubricating the drive motor bearings ..............................................5.7
Drive motors with permanent lubrication ........................................5.7
Drive motors with lubrication device ............................................... 5.8
Servicing drive motor .....................................................................5.9
Changing the V-belt ......................................................................5.10
Setting GM – Belt tensioning device S 40-2 – S 341 /
SF 40-2 – SF 220 ......................................................................... 5.11
Checking the oil level, topping up oil ............................................5.11
Changing the oil filter ...................................................................5.13
Changing the oil separator ........................................................... 5.14
Oil change ....................................................................................5.16
Flushing the oil circuit ................................................................... 5.18
Cleaning the compressed air / oil cooling unit (air cooling)........... 5.18
Proportional controller (option for S-series) .................................. 5.19
Checking the safety valve ............................................................. 5.20
Part 6: Appendix
5.4 Spare parts and optional equipment ........................................5.21
List of spare and wearing parts (for maintenance) ....................... 5.21
6.1 Flow chart ..................................................................................... 6.1
Air cooled version, standard ........................................................... 6.1
Water cooled version, serial connection .........................................6.2
Water cooled version, parallel connection ......................................6.2
Air cooled version, frequency-controlled ........................................ 6.3
6.2 List of maintenance and service work ........................................ 6.4
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Inhalt.pm6.5 - USA
Page V
Index
Page VI BOGE Operating instructions for S 40-2... S 341 / SF 40-2... SF 220 series screw compressors
Inhalt.pm6.5 - USA
General
1.1 General safety instructions
WARNING! Nonobservance of the following safety instructions may lead to injuries
and damage to the compressor.
Also observe the generally valid safety and accident prevention regu­lations in addition to the information in these operating instructions!
Safety instructions for compressor operation
1. Ensure that no commissioning or maintenance work on the compressor be undertaken until these operating instructions are understood.
2. Only use the compressor for its intended use, as described in these op­erating instructions.
3. The owner must ensure: – That only appropriately trained and authorized personnel work on this
compressor.
– That the operating, maintenance and repair personnel has been made
fully familiar with all safety instructions, and that they are being obser ved
– That the compressor is only operated in a safe operating condition.
4. Avoid any operating method which may impair the safety of the com­pressor.
5. Do not exceed the limit value for the final compression pressure specified on the type plate.
6. Do not operate the compressor without the attendant protection and safety devices. Do not dismantle any built-in safety devices or put them out of operation. Ensure that all cladding and doors are closed prior to commissioning/ starting up the compressor and are not opened during operation.
7. Place the compressor out of operation as described in these operating instructions, when dismantling the cladding or safety devices for repair or maintenance work. Reattach all cladding and safety devices immedi­ately upon completion of the repair or maintenance work.
8 Only operate the compressor using the additional equipment (options)
recommended or authorized by the manufacturer.
9. Undertake conversions and modifications of the compressor only in agreement with BOGE, taking all relevant safety regulations into consid­eration. The manufacturer is not liable for damages resulting from independent modifications on the compressor.
10. Never start compressor when one or serveral parts (e.g. cable, plug) are damaged, when not in perfect working order or when damage is detected or suspected.
11. Observe all safety and danger signs directly attached on the compressor!
12. The compressed air-oil pressure receiver has to be inspected in pre­determined intervals according to the local authorities responsible for pressure receivers.
13. To avoid damages, special precautions have to be taken during (re-) operation of compressors with frequency control, if the frequency con­verter was cut off from the power supply for a longer period of time (> 12 months). In this case please contact the BOGE-Service.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Page 1.1
General
1.1 General safety instructions
Safety instructions for maintenance and repair of the compressor
1. Ensure that maintenance work is only carried out by appropriately trained persons.
2. Ensure that setting work, malfunction rectification and repair are only carried out by specialists or appropriately trained persons.
3. Prior to maintenance or repair work:
Switch off main switch.Secure main switch against unintentional switch-on.Check to ensure that all parts have been isolated.Disconnect compressor from compressed air network (relieve or block
pressurized lines).
4. Exercise extreme caution during repair or maintenance work requiring compressor to be operational. Ensure that no persons are located in the hazardous area.
5. Ensure that work on the electrical equipment is only undertaken by quali­fied electricians.
6. Work on voltage carrying parts and devices are not permitted. Exceptions are governed by the appropriate regulations.
CAUTION
7. Only use original spare parts, compressor oils and operating materials released by BOGE during repair or maintenance.
8. The operator is required to check the compressor daily for externally vis­ible damage and defects, and to immediately report any changes (includ­ing operational behavior).
9. When the automatic restart (Auto-Restart) is activated, the compressor restarts automatically following a voltage loss. Prerequisite: The net pressure is lower than the switch-on pressure.
Accident prevention regulations
The owner of a compressor plant is required to ensure that it is properly in­stalled, operated and maintained.
For operation of the compressor plant, the accident prevention regulations of the owner country must be observed in addition to the data contained in these operating instructions. In the event that measures are required above and beyond the legal regu­lations or the data contained in these operating instructions, then it is of utmost importance that these be carried out prior to commissioning the compressor plant.
Page 1.2
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General
1.1 General safety instructions
WARNING!
Failure to adhere to these recommendations can result in mechanical failure, property damange and serious injury or death. All air and water inlet, and air and water discharge pipework to and from the inlet and discharge port connections must take into account vibration, pul­sations, temperature, maximum pressure applied, corrosion and chemical resistance. In addition, it should be noted that lubricated compressors will discharge some oil into the air stream; therefore, compatibilty between dis­charge piping, system accessories and software must be assured. For the foregoing reasons, the use of plastic piping, and soldered copper fittings as discharge piping is not recommended. In addition, flexible joints and/or flex lines can only be considered for such purposes if their specifi­cations fit the operating parameters of the system. It is the responsibility of the installer and owner to provide the appropriate service pipework to and from the machine.
WARNING! Statement concerning the inadvertent breathing of compressed air
exhaust.
The purchaser/user shall ensure that adequate ventilation and make up air are provided if a non-BAP designated compressor supplies air in a confined area to air consuming devices such as air motors, air tools, solenoids, air cylinders, air guns, nozzles, etc. The compressed air discharge stream may contain residual coolants/lubricants/carbon monoxide and condensable hydrocarbons or other materials which may be hazardous to health with pro­longed inhalation.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Page 1.3
General
1. 2 Introduction
The purpose of these operating instructions is to familiarize the user with the function and all application possibilities of the compressor.
These operating instructions contain important information on how to operate the compressor safely, economically and according to its intended use. Ob­serving these operating instructions will assist in avoiding danger, to reduce repair costs and downtimes and to increase the reliability and service life of the compressor. It contains important information concerning the required maintenance and repair measures, assists in case of malfunctions and con­tains data concerning spare and wearing parts.
The operating instructions must at all times be made available to the com­pressor operating personnel at the place of operation. The operating instructions must be carefully read and applied by all persons engaged to undertake the following work on the compressor:
Operation, including fault rectification and daily careMaintenance (service, inspection, repair)CommissioningTransportation
The compressor and its additional equipment must not be installed and commissioned until the operating instructions are understood.
Symbols used
These operating instructions can be supplemented with instructions on the basis of existing national regulations concerning accident prevention and environmental protection.
In the illustrations, the compressor is shown in part without cladding or safety devices for better visualization. However, operation without these compo­nents is prohibited!
DANGER! Risk of injury! Danger is used to indicate the presence of a hazard which
will cause severe personal injury, death, or substatial property damage if the warning is ignored.
WARNING!
Warning is used to indicate the presence of a hazard which can cause se­vere personal injury, death, or substantial property damage if the warning is ignored.
CAUTION!
Caution is used to indicate the presence of a hazard which will or can cause minor personal injury or property damage if the warning is ignored.
Page 1.4
DANGER: Voltage! This symbol indicates information warning of life threat­ening electrical voltage levels. It indicates work which must be exclusively performed by skilled electricians.
NOTICE!
Notice is used to notify people of installation, operation, or maintenance in­formation which is important but not hazard-related.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General
1. 2 Introduction
DANGER
Discharge air. Can contain carbon monoxide or other contaminants. Will cause severe injury or death.
Do not breathe this air.
NOTICE
Electrical power inlet.
Before working at the compressor:
disconnect all current-cyarrying parts!check if all parts actually voltage-free!secure the compressor against switching-on!reduce the pressure in all areas!
If you neglect these rules, your health will be endangered!
Before putting into service:
read the instructionscheck electric connectionscheck oil-level (not for oil-free)if applicable, remove the transport safety devicecheck the direction of rotation of compressoroperate only with a belt protective grating
or a sound protection bonnet.
– do not close the cooling air inlets and outlets air
during operation!
Warning:
The unit is operated by remote control, and might start without warning.
Regular maintenance:
Observe the operating instructions! – check suction filter weekly, if necessary clean
or replace it
check cooler for dirt, if necessary clean itcheck oil-level weekly (not for oil-free)drain condensation water from pressure tank
at least once a week
– check operativeness of automatic steam trap
NOTICE
Air discharge.
Prohibited:
Never open the valve before the air hose (connection to the compressed air network) is connected.
NOTICE
Reler to the Instruction/ Operators Manual before performing any maintenance.
NOTICE
Do not operate without enclosure panels & forklift covers in place.
Refer to the Instruction/ Operators Manual before performing any maintenance.
NOTICE
Motors must be greased periodically. See Operators Manual for procedure.
WARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect power before servicing. Lockout/Tagout machine.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Page 1.5
General
1. 2 Introduction
Motor lubrication
See motor rating plate for relubrication interval, kind and quantity of grease. Always lubricate with motor running.
CAUTION
Improper coolant filter replace­ment will cause compressor damage.
Replace filter element after first 500 hours of operation and every 3000 hours thereafter or when coolant is changed.
WARNING
Exposed fan blade. Can cause severe injury.
Do not operate with covers removed. Disconnect power. Lock and tag.
NOTICE
Lift here.
WARNING
Moving parts. Can cause severe injury.
Do not operate with covers removed. Service only with machine blocked to prevent turn over.
NOTICE
Rotation.
Use of incorrect coolant can cause system contamination.
Use only BOGE Syprem 8000 S.
CAUTION
WARNING
Hot surface. Can cause severe injury.
Do not touch. Allow to cool bevore servicing.
WARNING
High pressure air. Can cause severe injury or death.
Relieve pressure before removing filter plugs/caps. fittings or covers.
Page 1.6
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
General
1. 2 Introduction
Intended use
Inadmissible use
BOGE S series screw compressor, including its additional equipment, is exclusively intended for the compression of air. The air taken in must not contain any explosive or chemically instable gases or vapors. Do not exceed specified final compression temperature.
BOGE screw compressors are designed for stationary operation. Ensure that they are only installed and operated in dry and clean rooms.
Operation, control and maintenance are designed to be executed by trained and authorized operators.
Never direct the produced compressed air towards persons. Danger to life!
WARNING! Statement concerning the use of this equipment for breathing air and/
or aqua lung service. If the model number on this air compressor contains
the letters "BAP", the compressor is suitable for use in breathing air services. In the absence of such a designation, the compressor is NOT considered as capable of producing air of breathing quality. For a compressor to be capable of use in breathing air services it must be fitted with additional specialized equipment to properly filter and/or purify the air to meet all applicable federal, state and local laws, rules, regulations and codes, such as, but not limited to, OSHA 29 CFR 1910.134, Compressed Gas Association Commodity Specification G-7, 1-1966, Grade D Breathing Air and/or Canadian Standards Association. Should the Purchaser and/or User fail to add such specialized equipment and proceeds to use the compressor for breathing air service, the Purchaser/User assumes all liability resulting therefrom without any re­sponsibility or liability being assumed by BOGE COMPRESSORS. The Purchaser is urged to include the above provision in any agreement for any resale of this compressor.
This BOGE screw compressor is not explosion protected. Do not operate in explosive areas!
Do not operate compressor in rooms in which extreme dust, toxic or flam­mable vapors and gases may occur.
The following is not permitted:
Exceeding the final compression pressure indicated on the type plate.Altering the safety devices and cladding or placing them out of operation.Removing or painting over signs and symbols on the compressor.Operation of the compressor by unauthorized or untrained persons.Operation of the compressor with removed cladding or safety devices.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Page 1.7
General
1. 2 Introduction
Transportation damage
Data on the type plate
BOGE does not accept any liability for breakage or transportation damage. Please inspect the compressor immediately after delivery and direct dam­age claims to the last carrier – even when the packing is not damaged! To safeguard claims against the carrier we recommend leaving the machine, devices and packing material in the same condition as they were in when the damage was detected.
In the event of any other complaints, please inform us within six days after arrival of the delivery.
Enter the data of your compressor from the type plate or enclosed data sheet in the illustration below. This will ensure that in the event of enquiries, you will always have the most important data at hand.
Service
Fig. 1.1: Data on the type plate
Please do not hesitate to contact BOGE service if you have any questions. Please call:
770 - 8 74 -1570
In the event of inquiries, always specify the following data of your compressor to prevent any delays:
TypeYear of manufactureMachine number
NOTICE!
Only BOGE service technicians or persons authorized by BOGE in writing may repair or alter the compressor during the warranty period. Otherwise all warranty claims will expire!
Page 1.8
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Allgemeines.pm6.5 - USA
Product description
2.1
Technical data
Technical data for S 40-2 to S 100-2, part 1
Type S 40-2 S 50-2 S 60-2 S 61-2 S 75-2 S 100-2
Dimensions – Height (silenced) [inch] 57 57 57 57 57 57 – Height (super silenced) [inch] 77 77 77 77 77 77 – Depth [inch] 64 64 64 79 79 79 – Width (silenced / super silenced) [inch] 38 38 38 42 42 42
Weight – silenced [lbs.] 1790 1830 1855 2570 2680 3135 – super silenced [lbs.] 1860 1900 1915 2670 2790 3245
Max. sound pressure level [±3 dB(A)] accord. to DIN 45635, part 13 76/71 78/72 78/73 79/73 79/73 80/73 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / super silenced [dB(A)]
Air cooling
Sound capacity level – silenced / super silenced [dB(A)]
Max. sound pressure level [±3 dB(A)] accord. to DIN 45635, part 13 75/70 77/71 77/72 78/72 78/72 79/72 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / super silenced [dB(A)]
Water cooling
Sound pressure capacity – silenced / super silenced [dB(A)]
Compressor
max. final compression temperature [°F] + 230 + 230 + 230 + 230 + 230 + 230 Volume flow according to ISO 1217 Part C
= 100 psig [cfm] 195.3 234.8 257.6 285.5 345.9 448.6
– p
max
– p
= 115 psig [cfm] 182.6 224.2 247.2 271.9 329.4 427.3
max
– p
= 125 psig [cfm] 182.6 224.2 247.2 271.9 329.4 427.3
max
– p
= 150 psig [cfm] 163.5 204.1 223.9 244.4 293.1 370.8
max
– p
= 190 psig [cfm] 134.9 174.8 189.3 207.3 251.1 324.9
max
Drive motor
Rated power [hp] 40 50 60 60 75 100 Rated speed – 60 Hz [min
Protection type TEFC TEFC TEFC TEFC TEFC TEFC ISO class F F F F F F
Electrical connection
1
Mains voltage Frequency Recommended fuse protection
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.
) [V]
1
) [Hz] 60 60 60 60 60 60
2
) [A]
15/16 15/16 15/16 16/17 16/17 16/17
91/87 93/88 93/98 95/90 95/90 96/90
15/16 15/16 15/16 16/17 16/17 16/17
90/86 92/87 92/88 94/89 94/89 95/89
-1
] 3600 3600 3600 3600 3600 3600
200/208/230 230 230 230 230 230
460/575 460/575 460/575 460/575 460/575 460/575
150/150/125 175/70 175/90 175/90 225/125 300/150
60/50 60 70 70 90 125
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.1
Product description
2.1 Technical data
Technical data for S 101 to S 341, part 1
Type S 101 S 125 S 150 S 151 S 180 S 220 S 271 S 341
Dimensions – Height (silenced) [inch] 69 69 69 79 79 79 84.4 84.4 – Height (super silenced) [inch] 89 89 89 99 99 99 104.1 104.1 – Width (silenced / super silenced) [inch] 93 93 93 89/101 89/101 89/101 122 122 – Depth [inch] 53 53 53 63 63 63 75.2 75.2
Weight – silenced [lbs.] 4080 4190 4565 5090 5400 5735 9921 11023 – super silenced [lbs.] 4210 4315 4700 5315 5620 5955 10141 11244
Max. sound pressure level [±3 dB(A)] accord. to DIN 45635, part 13 76/72 79/74 79/74 85/77 85/77 83/74 84/77 87/80 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / super silenced [dB(A)]
Air coolingWater cooling
Sound capacity level – silenced / super silenced [dB(A)]
Max. sound pressure level [±3 dB(A)] accord. to DIN 45635, part 13 72/70 73/71 73/71 79/71 79/71 79/71 86/79 86/79 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / ssuper silenced [dB(A)
Sound pressure capacity – silenced / super silenced [dB(A)]
Compressor
max. final compression temperature [°F] + 230 + 230 + 230 + 230 + 230 + 230 + 230 + 230 Volume flow according to ISO 1217 part C
= 100 psig [cfm] 480 580 685 706 861 1024 1208 1498
– p
max
– p
= 115 psig [cfm] 463 555 650 685 823 985 1080 1439
max
– p
= 125 psig [cfm] 463 685 823 950 1080 1439
max
– p
= 150 psig [cfm] 403 484 576 600 735 886 – 1310
max
– p
= 190 psig [cfm] 346 424 501 508 629 766 – 1119
max
Drive motor
Rated power [Hp] 100 125 150 150 180 200 250 350 Rated speed – 60 Hz [min
Protection type TEFC TEFC TEFC TEFC TEFC TEFC TEFC TEFC ISO class FFFFFFFF
Electrical connection
1
Mains voltage Frequency Recommended fuse protection
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.
) [V]
1
) [Hz] 60 60 60 60 60 60 60 60
2
) [A]
17/18 17/18 17/18 18/19 18/19 18/19 18/19 19/20
93/90 96/92 96/92 101/93 101/93 101/93 105/99 105/99
17/18 17/18 17/18 18/19 18/19 18/19 18/19 18/19
89/88 90/89 90/89 79/90 79/90 97/90 104/98 104/98
-1
] 3600 3600 3600 3600 3600 1800 1800 1800
230/460 460/575 460/575 460/575 460/575 460/575 460/575 460/575
575
300/150 175/150 200/175 200/175 300/225 300/250 400 500
125
Page 2.2
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
2.1 Technical data
Technical data for S 40-2 to S 100-2, part 2
Type S 40-2 S 50-2 S 60-2 S 61-2 S 75-2 S 100-2 Oil filling quantity
Oil receiver volume [gallon] 11 11 11 17 17 17 Total oil filling quantity [gallon] 6 6 6 10 10 10 Oil topping up quantity between min. + max. [gallon] 1.5 1.5 1.5 2 2 2
Intake air temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 – max. [°F] + 113 + 113 + 113 + 113 + 113 + 104
Cooling air requirement – free-standing installation [cfm] 6600 7700 7700 7700 9400 10800 – with supply and exhaust [cfm] 3300 3800 3800 3800 4700 5400
(air duct)
Air cooling
– free ventilator pressure [inch/H2O] 0.24 0.24 0.24 0.24 0.24 0.24 Cooling air requirement
– free-standing installation [cfm] 1200 1200 1200 1200 1200 1200 – with supply and exhaust [cfm] 600 600 600 600 600 600
Required cooling water quantity – delta t = 15 K [cfm] 0.958 1.182 1.440 1.440 1.764 2.404 – delta t = 30 K [cfm] 0.479 0.591 0.720 0.720 0.882 1.202 Max. cooling water quantity [cfm] 2.05 2.1 2.05 2.05 2.5 2.5
Cooling water inlet temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 – max. [°F] + 86 + 86 + 86 + 86 + 86 + 86
Water cooling
Cooling water outlet temperature – max. [°F] + 113 + 113 + 113 + 113 + 113 + 113
Cooling water pressure – min. [psig] 30 30 30 30 30 30 – max. [psig] 146 146 146 146 146 146
1
Operating pressure switch
(factory settings) – p
= 100 psig: Switch-off press. p
max
Switch-on press. p
– p
= 115 psig: Switch-off press. p
max
Switch-on press. p
– p
= 125 psig: Switch-off press. p
max
Switch-on press. p
– p
= 150 psig: Switch-off press. p
max
Switch-on press. p
– p
= 190 psig: Switch-off press. p
max
Switch-on press. p
Safety valve
Activation pressure at:
= 100 psig [psig] 160 160 160 160 160 160
– p
max
– p
= 115 psig [psig] 160 160 160 160 160 160
max
– p
= 150 psig [psig] 160 160 160 160 160 160
max
– p
= 190 psig [psig] 203 203 203 203 203 203
max
1
) Compressors for other operating pressures P
)
max
min
max
min
max
min
max
min
max
min
[psig] 100 100 100 100 100 100 [psig] 87 87 87 87 87 87 [psig] 115 115 115 115 115 115 [psig] 100 100 100 100 100 100 [psig] 125 125 125 125 125 125 [psig] 110 110 110 110 110 110
[psig] 150 150 150 150 150 150 [psig] 130 130 130 130 130 130
[psig] 190 190 190 190 190 190 [psig] 174 174 174 174 174 174
= P
min
minus (–) 14.5 psig.
max
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.3
Product description
Technical data2.1
Technical data for S 101 to S 341, part 2
Type S 101 S 125 S 150 S 151 S 180 S 220 S 271 S 341 Oil filling quantity
Oil receiver volume [gallon] 29 29 29 46 46 46 61 61 Total oil filling quantity [gallon] 16 16 16 24 24 24 34 34 Oil topping up quantity between min. + max. [gallon] 2.4 2.4 2.4 4.0 4.0 4 4.8 4.8
Intake air temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 + 41 + 41 – max. [°F] + 113 + 113 + 113 + 113 + 113 + 113 + 113 + 113
Cooling air requirement – free-standing installation [cfm] 11800 18900 18900 18900 28700 28700 32960 38846 – with supply and exhaust [cfm] 5900 9400 9400 9400 14350 14350 16480 19423
(air duct)
Air cooling
– free ventilator pressure [inch/H2O] 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 Cooling air requirement
– free-standing installation [cfm] 2000 2000 2000 2000 5880 5880 5880 5880 – with supply and exhaust [cfm] 1000 1000 1000 1000 2940 2940 2940 2940
Required cooling water quantity – delta t = 15 K [cfm] 2.41 2.881 3.528 7.997 4.23 5.127 6.409 7.997 – delta t = 30 K [cfm] 1.20 1.440 1.764 3.998 2.11 2.564 3.205 3.998 Max. cooling water quantity [cfm] 5.30 5.3 5.3 8.0 7.1 7.1 8.0 8.0
Cooling water inlet temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 + 41 + 41 + 41 – max. [°F] + 86 + 86 + 86 + 86 + 86 + 86 + 86 + 86
Water cooling
Cooling water outlet temperature – max. [°F] + 113 + 113 + 113 + 113 + 113 + 113 + 113 + 113
Cooling water pressure – min. [psig] 30 30 30 30 30 30 30 30 – max. [psig] 146 146 146 146 146 146 146 146
1
Operating pressure switch
(factory settings) – p
= 100 psig: Switch-off press. p
max
Switch-on press. p
– p
= 115 psig: Switch-off press. p
max
Switch-on press. p
– p
= 125 psig: Switch-off press. p
max
Switch-on press. p
– p
= 150 psig: Switch-off press. p
max
Switch-on press. p
– p
= 190 psig: Switch-off press. p
max
Switch-on press. p
Safety valve
Activation pressure at:
= 100 psig [psig] 160 160 160 160 160 160 160 160
– p
max
– p
= 115 psig [psig] 160 160 160 160 160 160 160 160
max
– p
= 150 psig [psig] 160 160 160 160 160 160 160 160
max
– p
= 190 psig [psig] 203 203 203 203 203 203 203 203
max
1
) Compressors for other operating pressures P
)
[psig] 100 100 100 100 100 100 100 100
max
[psig]87878787878787
min
[psig] 115 115 115 115 115 115 115 115
max
[psig] 100 100 100 100 100 100 100 100
min
[psig] 125 125 125 125 125 125 125 125
max
[psig] 110 110 110 110 110 110 110 110
min
[psig] 150 150 150 150 150 150 150
max
[psig] 130 130 130 130 130 130 130
min
[psig] 190 190 190 190 190 190 190
max
[psig] 174 174 174 174 174 174 174
min
= P
min
minus (–) 14.5 psig.
max
87
Page 2.4
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
Technical data2.1
Technical data for SF 40-2 – SF 220, part 1
Type SF40-2 SF60-2 SF100-2 SF150 SF220
Dimensions – Height (silenced) [inch] 57 57 57 69 79 – Height (super silenced) [inch] 77 77 77 89 99 – Width (silenced / super silenced) [inch] 64 64 79 93 89/101 – Depth [inch] 38 38 42 53 63
Weight – silenced [lbs] 1470 1850 3377 4720 5735 – super silenced [lbs] 1540 1920 3487 4850 5955
Max. sound pressure level [± 3 dB(A)] accord. to DIN 45635, part 13 76/71 78/73 80/73 79/74 83/74 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / super silenced [dB(A)]
Air coolingWater cooling
Sound capacity level – silenced / super silenced [dB(A)]
15/16 15/16 16/17 17/18
91/87 93/89 96/90 96/92 101/93
Max. sound pressure level [± 3 dB(A)] accord. to DIN 45635, part 13 75/70 77/72 79/72 73/71 79/71 – silenced / super silenced [dB(A)]
Measuring surface dimension – silenced / super silenced [dB(A)]
Sound pressure capacity – silenced / super silenced [dB(A)]
15/16 15/16 16/17 17/18 18/19
90/86 92/88 95/89 90/89 97/90
Compressor
max. final compression temperature [°F] 230 230 230 230 230 Volume flow according to ISO 1217 Part C
= 100 psig [cfm] 48,7 – 195,3 64,4 – 257,6 114,1 – 448,6 171,3 – 685 256 – 1024
–p
max
–p
= 115 psig [cfm] 45,6 – 182,6 61,8 – 247,2 106,6 – 427,3 162,4 – 650 246 – 985
max
–p
= 125 psig [cfm] 45,6 – 182,6 61,8 – 247,2 106,6 – 427,3 162,4 – 650 246 – 985
max
–p
= 150 psig [cfm] 41,0 – 163,5 55,8 – 223,9 92,7 – 370,8 144,1 – 576 222 – 886
max
–p
= 190 psig [cfm] 33,9 – 134,9 47,3 – 189,3 81,2 – 324,9 125,3 – 501 192 – 766
max
Drive motor
Rated power [hp] 40 60 100 150 200 Rated speed – 60 Hz [min
-1
] 3600 3600 3600 3600 3600
Protection type TEFC TEFC TEFC TEFC TEFC ISO class F FFFF
Electrical connection
Mains voltage
1) 3
) [V] 460/575 460/575 460/575 460/575 460/575 Frequency 1) [Hz] 60 60 60 60 60 Recommended fuse protection 2) [A] 60/50 90/70 150/125 200/175 300/250
1
) Standard equipment. Mains voltages and frequencies are specified on a plate in the switch cabinet.
2
) Only for 460 V / 60 Hz. The fuse values change in the case of other mains voltages and frequencies.
3
) For the refrigeration compressed air dryer 230 V / 60 Hz are required.
18/19
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.5
Product description
Technical data2.1
Technical data for SF 40-2 – SF 220, part 2
Type SF40-2 SF60-2 SF100-2 SF150 SF 220 Oil filling quantity
Oil receiver volume [gallon] 11 11 17 29 46 Total oil filling quantity [gallon] 6 6 10 16 24 Oil topping up quantity between min. + max. [gallon] 1.5 1.5 2 2.4 4
Intake air temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 – max. [°F] + 104 + 119 + 104 + 119 + 113
Cooling air requirement – free-standing installation [cfm] 6600 7600 10800 18900 28700 – with supply and exhaust [cfm] 3300 3800 5400 9400 14350
(air duct)
Air cooling
– free ventilator pressure [psig/H Cooling air requirement
– free-standing installation [cfm] 1200 1200 1200 2000 5880 – with supply and exhaust [cfm] 600 600 600 1000 2940
Required cooling water quantity – delta t = 15 K [cfm] 0.959 1.440 1.764 3.528 5.127 – delta t = 30 K [cfm] 0.479 0.720 0.882 1.764 2.564 Max. cooling water quantity [cfm] 2.4 2.1 2.5 5.3 7.1
Cooling water inlet temperature – min. [°F] + 41 + 41 + 41 + 41 + 41 – max. [°F] + 86 + 86 + 86 + 86 + 86
Water cooling
Cooling water outlet temperature – max. [°F] + 113 + 113 + 113 + 113 + 113
Cooling water pressure – min. [psig] 30 30 30 30 30 – max. [psig] 146 146 146 146 146
1
Operating pressure switch
)
(factory settings) –p
= 100 psig: Switch-off press. p
max
Switch-on press. p
–p
= 115 psig: Switch-off press. p
max
Switch-on press. p
–p
= 125 psig: Switch-off press. p
max
Switch-on press. p
–p
= 150 psig: Switch-off press. p
max
Switch-on press. p
–p
= 190 psig: Switch-off press. p
max
Switch-on press. p
max
min
max
min
max
min
max
min
max
min
Safety valve
Activation pressure at:
= 100 psig [psig] 160 160 160 160 160
–p
max
–p
= 115 psig [psig] 160 160 160 160 160
max
–p
= 150 psig [psig] 160 160 160 160 160
max
–p
= 190 psig [psig] 203 203 203 203 203
max
1
) Compressors for other operating pressures P
O] 0.24 0.24 0.24 0.24 0.24
2
[psig] 100 100 100 100 100 [psig] 87 87 87 87 87
[psig] 115 115 115 115 115 [psig] 100 100 100 100 100
[psig] 125 125 125 125 125 [psig] 110 110 110 110 110
[psig] 150 150 150 150 150 [psig] 130 130 130 130 130
[psig] 190 190 190 190 190 [psig] 174 174 174 174 174
= P
min
minus (–) 14.5 psig.
max
Page 2.6
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
2.2 Function description
Function principle of the air end
Air circuit
The air end operates according to the displacement principle. In the housing, the main and secondary screws are driven by means of an electric motor and V-belt. Both screws have screw-shaped profiles, intermeshing without contact. Together with the housing wall, these screws form chambers which gradually reduce in size, seen in air flow direction. Rotation of the rotors causes the air taken in to be compressed to the final pressure in the chambers. During compression oil is continuously injected into the air end. This having a cooling, sealing and lubricating function.
1
543
2
Fig. 2.1:
78
6
Components of the air circuit
1 = Intake filter
The intake filter cleans the air suctioned by the air end.
2 = Intake regulator
The intake regulator opens (load operation) or closes (idling operation or standstill) the intake line depending on the operating condition of the com­pressor.
3 = Air end
The air end compresses the intake air.
4 = Compressed air/oil receiver
The compressed air separates from the oil under the force of gravity in the compressed air/oil receiver.
5 = Oil separator
The oil separator separates the residual oil contained in the compressed air.
6 = Minimum pressure check valve
The minimum pressure check valve does not open until the system pressure has increased to 3.5 bar (51 psig). This causes a rapid build-up of the system pressure and ensures lubrication in the starting phase. Once the compressor has been switched off, the check valve prevents the compressed air from flowing back out of the mains line.
7 = Compressed air after-cooler (air and water cooled) The compressed air is cooled in the compressed air after-cooler, causing the water contained in the air to condensate.
8 = Stop valve
The screw compressor may be isolated from the mains by means of the stop valve.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.7
Product description
2.2 Function description
Oil circuit
The oil injected into the air end has the following function:
It dissipates the compression heat (cooling).It seals the gaps between the screws and between the screws and housing.It lubricates the bearings.
56
1
2
4
3
Fig. 2.2: Components of the oil circuit
1 = Compressed air/oil receiver
The oil separated from the compressed air through the force of gravity collects in the compressed air/oil receiver. The system pressure forces it out of the receiver into the air end.
2 = Thermostatic oil control valve
Depending on the oil temperature, the thermostatic oil control valve either allows the oil to pass through the oil cooler or through a bypass (e.g. in the starting phase). Thus the oil constantly maintains its optimum operating temperature.
3 = Oil cooler (air or water cooled) The oil cooler cools down the hot oil to operating temperature.
4 = Oil filter
The oil filter traps impurities in the oil.
5 = Air end
The injected oil returns to the compressed air/oil receiver together with the compressed air. There, it is separated through the force of gravity.
6 = Drainage line
The collectet oil from the oil-separator is drained back to the air end into the oil circuit via the drainage line.
Page 2.8
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
2.3 Compressor control
Supply pressure
Operating states
For the compressor, the pressure downstream of the check valve is termed the supply pressure. The control system switches the compressor on and off during operation depending on the supply pressure.
All screw compressor controls are based on three basic operating states:
1. Load operation
The compressor delivers its maximum amount of compressed air.It consumes its maximum energy.
2. Idling operation
The compressor runs but does not deliver any compressed air.It consumes approx. 75% less energy than in load operation.When compressed air is required, it switches to load operation with-
out delay.
– Idling operation reduces switching frequencies which can damage the
drive motor, and reduces wear of the system.
3. Standstill ready for operation
The compressor is standing still but ready for operation.When compressed air is required, it switches automatically to load
operation.
Operating modes
Short operating times
The two most important operating modes are achieved by combining the three operating states:
1. Intermittent operation
In intermittent operation the energy balance is perfect.
The compressor operates in load operation.Upon reaching the switch-off pressure p
the compressor switches
max
to standstill. It does not consume any energy.
– Once the pressure has dropped to the switch-on pressure p
min
the
compressor switches back to load operation.
2. Continuous operation
Continuous operation limits the drive motor switching cycles and reduces wear to the system.
The compressor operates in load operation.Upon reaching the switch-off pressure p
the compressor switches
max
to idling operation.
– Once the pressure has dropped to the switch-on pressure p
min
the
compressor switches from idling operation back to load operation.
CAUTION!
During short operating times, the compressor does not reach its operating temperature. It operates below the dew point. The generated condensate mixes with the oil. The lubricating ability of the oil is reduced. This leads to damage on the air end. It is of utmost importance to consult BOGE, if you operate your system with short operating times.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.9
Product description
2.4 Control devices
Operating pressure transmitter
Proportional controller (option for S-series)
The operating pressure transmitter controls the operation of the compres­sor within the set switching limits.
Switch-on pressure p
If the network pressure drops to the set switch-on pressure p sor switches on.
1
Switch-off pressure p
If the network pressure increases to the switch-off pressure p
min
min
max
max
sor either switches off (intermittent operation) or switches to idling operation (continuous operation).
The proportional controller is an additional control device intervening in the sequences of the intake regulator.
The intake regulator only opens as far as necessary to supply the current compressed air requirement. Thus the compressor saves compression energy.
A compressor with proportional controller is able to supply its delivered quantity variable between 0% and 100%. However, the energy consumption does not reduce accordingly. Therefore, a control is only practical between 50% and 100% of the delivered quantity.
The proportional controller is factory set to a delivered quantity between 50% and 100% of the compressor capacity.
The proportional controller closes when the desired delivered quantity has dropped below 50% of the compressor capacity. The compressor then oper­ates in idling operation (continuous operation) or switches off (intermittent operation).
, the compres-
, the compres-
Page 2.10
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
2.5 Safety and monitoring devices
General
Safety temperature limiting device
Safety valve
The safety devices guarantee a high degree of operational safety, in connec­tion with the BOGE monitoring system.
When one of the safety devices responds, the control system reacts as follows:
The compressor is immediately switched off.A flashing fault number in the left field of the display indicates the cause
of the fault.
DANGER!
Do not operate the compressor without built-in safety devices. Do not dismantle the safety devices or put them out of operation.
Safety temperature limiting device switches off the compressor once the maximum admissible final compression temperature has been reached. The compressor does not switch on when dropping below the minimum temperature.
Switch off the compressor (OFF button). Fault is acknowledged.Rectify the fault.Switch on the compressor (ON button).
Safety valve  on the compressed air/oil receiver prevents the maximum admissible pressure being exceeded. When the maximum pressure is ex­ceeded (e.g. incorrect setting of the operating pressure switch), the entire delivery volume of the compressor is ejected.
1
Monitoring the drive and fan motor
Rotational direction monitoring
Safety pressure switch (option)
System pressure build-up (option)
The following monitoring devices are standard for BOGE control systems: The drive motor is monitored by PTC resistors. The fan motor is monitored by overcurrent/overload release units.
The pressure switch checks the rotational direction of the drive motor each time the system starts up. The pressure switch for the rotational direction is placed next to the operat­ing pressure switch.
The safety pressure switch prevents the maximum admissible system pres­sure being exceeded. The switch-off pressure is below the response pres­sure of the safety valve.
The system pressure build-up unit monitors the system pressure build-up when the compressor starts up.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.11
Product description
2.6 Water cooling
Water cooling
Serial connection
Parallel connection
BOGE screw compressors are available in water or air-cooled design. In the standard version, the oil and compressed air after-coolers are con­nected in series on the water side. A parallel connection is possible as an option.
45
Fig. 2.3: Serial connection
23 1
4
5
Page 2.12
Fig. 2.4: Parallel connection
23 1
1 = Cooling water solenoid valve
The cooling water solenoid valve closed the cooling water supply when the compressor switches off.
2 = Cooling water stop valve
The compressor may be separated from the cooling water supply by means of the stop valve (e.g. for maintenance or repair work).
3 = Dirt trap (provided by customer)
The dirt trap protects the cooling unit against sedimenting. Pore size: max. 0.6 mm
4 = Oil cooling unit
5 = Compressed air after-cooler
The water cooling units are designed for specific standard cooling water quantities, temperatures and pressures (see "Technical data"). For individually fluctuating values, they are designed according to the speci­fied order data.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Product description
2.7 Cooling water
Water connection (for water cooling)
Cooling water quality
The cooling water must have the following properties:
Electrical conductivity: >50 µS/cm at pH value 7– 9: Carbonatehardness CaCo
3
<16°dH
Cooling water pressure – max. [psig] 146
– min. [psig] 30
Cooling water inlet temperature – min. [°F] 41
– max. [°F] 86
Max. cooling water quantity – refer to technical data.
The cooling units are fitted with nonferrous heat exchangers, as standard. To avoid damage to these components and to guarantee a long term function, ensure that the substances contained in the cooling water used do not exceed the following values:
Substances Symbol max. admissible concentration [mg/l]
Ammonia NH
3
2 Chloride <70°C Ci 100 Sulphite, free chlorides Ci 5 Iron Fe 2 Free carbon dioxide Co
2
20 Manganese Mn 1 Nitrate NO Oxygen O
2
Silicon oxide SiO Sulphate SO
4
100
3
2
8
2
60 Total dissolved substances TD-S 600
Table: Maximum admissible concentration of the substances
If the specified limit values are exceeded, use cooling units made of other materials. Please consult BOGE service.
ATTENTION! If the cooling water data changes, the cooling units may have to be redesigned. Incorrectly designed cooling units may cause malfunctions and the compressor to switch off! Please consult BOGE.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Page 2.13
Product description
Page 2.14
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Produkt.pm6.5 - USA
Installation
3.1 Transport
General
Transport possibilities
Please observe the generally accepted safety and accident prevention regu­lations when transporting the compressor. BOGE accepts no liability for damage caused by improper transport!!
CAUTION!
The compressor is delivered filled with oil. Do not tilt during transport!
Forklift truck or lifting carriage transport
Ensure that the forks grip underneath the base frame of the compressor.
Crane transport
Only use suitable transport slings having a minimum length of approx. 315 in. Position the slings at the ends underneath the base frame of the compressor.
CAUTION!
Do not subject the safety cladding to force during transport. Protect the compressor using wooden spacers (see arrows). Remove the transport timbers.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.1
Installation
3.2 Compressor room
Installation surface
Fire protection
Admissible environmental influences
A level industrial floor without foundation is adequate for the installation of the compressor. No special fastening elements are required.
WARNING! Requirements of fire protected compressor rooms:
Flammable liquids must never be stored in the compressor room.The floor around the compressor must be made of non-flammable material.Leaking oil must not spread out over the floor.No inflammable materials must be located within a radius of at least
3 metres around the compressor.
– No inflammable machine parts, such as cable ducts, may run overhead
of the compressor.
The compressor room must be clean, dry, cool and free of dust.
Admissible ambient temperatures (see "Technical data") Maximum ambient temperature (for air cooling): + 104 / 113°F Minimum ambient temperature: +
CAUTION! Nonobservance of the admissible ambient temperature may lead to the following problems:
– The compressor will switch off when the admissible final compres-
sion temperature is exceeded or gone below.
Pipe lines and valves will freeze up at low temperatures.Damage due to reduced lubricating ability of the compressor oil.
141°F
Frost protection
Ventilation
Measures to be taken to ensure that admissible ambient temperatures are observed:
– Avoid any pipe lines or units radiating heat in the vicinity of the compres-
sor, or insulate them well.
Never install the compressor in the cooling air flow of other machines.Provide the supply air openings with adjustable louvres to ensure that
the minimum temperature is not gone below in winter.
– Use the BOGE frost protection device.
The compressor must be installed frost-protected.
If the following instructions are not observed, the admissible final compression temperature may be exceeded. In this case, the compressor will switch off automatically.
CAUTION!
Arrange the compressor intake openings or ducts such, that dangerous admixtures (e.g. explosive or chemically unstable materials) cannot be drawn in.
Page 3.2
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation
3.2 Compressor room
Ventilation openings (free-standing installation)
Arrange supply air openings close to the floor.Arrange exhaust air openings in the ceiling or at the top of the wall.The required cross sections for the supply openings (as well as for the
flaps and weather protection grids) are indicated in the table.
Supply and exhaust air ducts
Ensure that the flow rates in the ducts do not exceed 9 mph.Never position cooling air ducts directly on the compressor.
Always use a compensator to avoid distortion and the transfer of vibrations.
Fans
Ensure that the heated exhaust air is not taken in again. If necessary, the heated air must be extracted by exhaust fans. To ensure perfect cooling even at higher temperatures in the summer, the fans must be designed as follows: – The fan capacity must be rated approx. 10 – 15% higher than the sum of the
cooling air quantity required for all machines operated in the room.
– For free-standing installation, the cooling air requirement specified in the
table corresponds to the required fan capacity.
Supply air filter
– Equip the compressor with supply air filter mats if the compressor room
is contaminated with dust (option).
Cooling air requirement
Please refer to the following table for the cooling air requirement and size of the supply air openings for your compressor. Ensure that flaps and weather protection grids have the necessary free cross section. We generally recom­mend contacting a specialist company for performing the duct construction work and planning.
Type Drive
rating Cooling air Necessary Cooling air Necessary Cooling air Necessary
requirement inlet opening requirement free duct requirement inlet opening
for free for free for installation cross section for free for free
standing unit standing unit with ducting standing unit standing unit
[Hp] [cfm] [sq. ft.] [cfm] [sq. ft.] [cfm] [sq. ft.] S 40-2 40 6600 17.0 3300 4.5 1200 2.7 S 50-2 50 7700 17.0 3800 5.2 1200 2.7 S 60-2 60 7700 15.0 3800 5.2 1200 2.7 S 61-2 60 7700 15.0 3800 5.2 1200 2.7 S 75-2 75 9400 22.0 4700 6.3 1200 2.7 S 100-2 100 10800 24.0 5400 7.3 1200 2.7 S 101 100 11800 27.0 5900 8.0 2000 4.8 S 125 125 18900 43.0 9400 13.1 2000 4.8 S 150 /S 151 150 18900 43.0 9400 16.2 2000 4.8 S 180 180 28700 66.0 11800 18.7 5880 13.5 S 220/SF 220 200 28700 66.0 14350 22.7 5880 13.5 S 271 270 32960 75.0 16430 26.9 5880 13.5 S 341 340 38846 89.0 19423 26.9 5880 13.5 SF 40-2 40 6600 18.5 3300 4.5 1200 2.7 SF 60-2 60 7700 17.0 3800 5.2 1200 2.7 SF 100-2 100 10800 24.0 5400 7.3 1200 2.7 SF 150 150 18900 43.0 9400 16.2 2000 4.8 SF 220 200 28700 66.0 14350 22.7 5880 13.5
Table 1: cooling air requirement, necessary cross sections for openings and ducts.
* For the cooling air requirements the basis is a 7°F temperature difference between room and outside temperature.
Air cooling Water cooling*
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.3
Installation
BA
D
C
E
Ventilation possibilities
3.2 Compressor room
Condensate disposal
A: Supply and exhaust air openings in the outside walls (free-standing
installation)
B: Supported by exhaust air fan
C: Exhaust air duct into the open
D: Exhaust air duct with recirculation flap
Hot exhaust air is mixed with the cold ambient air, as required, preventing the plant from freezing up at temperatures below freezing.
E: Using the hot exhaust air for heating
In the winter, the hot exhaust air is used for room heating. In summer it is directed into the open.
The air taken in contains water in form of vapour, which turns into condensat during compression.
WARNING!
The condensate contains oil. Never lead it into the public sewage system without prior treatment. Strictly observe the effluent disposal laws of your local authorities.
Page 3.4
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation
3.3 Installation
General
BOGE screw compressor units are supplied ready for connection. Only the work described in the following paragraphs needs to be carried out during the installation.
CAUTION!
Only have the installation work carried out by appropriately trained persons or specialists.
Prior to delivery, each compressor is subjected to a trail run at the factory. It is carefully tested and set. However, possible transport damage cannot be excluded.
– Please inspect the compressor immediately after delivery and direct dam-
age claims to the last haulier – even when the packing is not damaged! To safeguard claims against the haulier we recommend leaving the machine, devices and packing material in the same condition as they were in when the damage was detected.
Prior to commissioning, check the compressor for external damage.Observe the compressor very closely during commissioning and the
following trial run.
– If malfunctions occur, switch off the compressor immediately and inform
the BOGE-Service.
Checking the delivery scope
Installing the compressor
Connecting the compressor to the compressed air network
The delivery scope depends on your order. Prior to commissioning, please check whether all required parts have been provided. Please check the order confirmation for any possible accessory equipment.
The delivery scope includes the following component parts:
Operating instructionsKeysElectric circuit diagram (in the compartment of the switch cabinet)List of electrical equipment (in the compartment of the switch cabinet)
Remove the packing material on and in the compressor.Install compressor and align horizontally.
The compressor must stand firmly on the ground on all feet.
– Connect the compressor to the compressed air network or a compressed
air receiver. For this, use a BOGE high pressure hose.
NOTICE! Do not install a check valve in the pressure line.
The compressor is already equipped with a check valve.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.5
Installation
3.3 Installation
Connecting the cooling water (option)
Removing the transport securing bolts
The pipework for the cooling water circuit in the compressor is completely installed at the factory. Only the following work must be performed during installation:
– Check, whether the water supply has the required data and whether the
cooling water quality is adequate (see page 2.10).
– Connect the cooling water supply and discharge line to the water supply.
The following component parts must be provided by the customer for cooling water installation:
Dirt traps
The dirt trap at the cooling water inlet protects the cooling units against sediment collecting. Pore width: max. 0.6 mm
– Expansion vessel and safety valve
ATTENTION!
If the stop valves in the supply and discharge lines are simultaneously closed in a closed cooling system, an enclosed room will result. If the water heats up in this room, it will expand and the pressure will increase. Install an expansion vessel and a safety valve to prevent damage to the cooling units.
The frame of the drive unit is bolted to the base frame for transport. Remove the four red marked screws  and  (each two on the longitudinal side) together with the space collars.
Page 3.6
1
2
Fig. 3.1: Removing the transport securing bolts Note:
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation
3.3 Installation
Activating the belt tensioning device
The V-belts are slackened for transport. Activate the GM belt tensioning device prior to commissioning by lowering the motor plate.
Secure bolt head against turning by means of a spanner (NW 27).Turn locknut upwards by turning counterclockwise until it locks against
the bolt head.
The belt tensioning device is activated. It automatically sets the correct V-belt tension in every operating mode.
1
2
Checking the oil level
Fig. 3.2: Activating the belt tensioning device Note
BOGE compressors are supplied with a complete oil filling. Prior to commissioning/start up, check the oil level as described in chapter
"Maintenance".
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.7
Installation
3.4 Electrical connection
Electrical connection
DANGER: Voltage!
Ensure that work on the electrical equipment of the compressor is only carried out by authorized electricians.
When connecting to the power supply, observe the valid regulations or the local safety regulations.
Also observe the regulations of your local power supply company regarding the load rating of your power supply.
Main switch
The customer is responsible to provide the following safety measures: Compressor plants having a drive motor larger than 3 kW and current inten-
sities larger than 16 amperes must be equipped with a lockable main switch and series fuses.
Please refer to the technical data for the design and fuse rating.
Rated voltage
The data of your mains (operating voltage, control voltage, type of current, frequency, ...) must coincide with the data on the type plate on the switch cabinet.
In the event of deviations, please contact the BOGE service or your supplier.
Connecting the leads
– Check to ensure that all terminals in the switch cabinet are firmly tightened.
If necessary, retighten the screw connections.
Guide the lead cable through the PG screw connection.Connect the leads L1, L2, L3, N, Pe (PEN) firmly to the power supply
terminal. A clockwise rotational field must be created.
– Tighten the electrical connections after the first operating hours.
Drive with frequency converter
According to operational conditions electrical drive systems with frequency converter may have an earth leakage current above 10 mA. Therefore the required precautions according to EN 60204-1:2006 and EN 50178:1997 have to be applied as soon as the compressor is electrically connected. A permanently installed connection is required. One or several of the following qualifications for the protective-conductor system have to be fulfilled:
2
1. The protective conductor must have a minimum cross section of 10 mm
Cu
along its total length.
2. If the protective conductor has a minimum cross section of less than
2
10 mm
Cu, a second conductor with at least the same cross section has
to be provided up to the point from where the protective conductor has a
2
minimum cross section of more than 10 mm
.
3. Automatic interruption of the supply if the continuity of the protective con­ductor is lost.
Please observe any additional national rules and regulations.
Page 3.8
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation
3.4 Electrical connection
DANGER: Risk of injury!
Prior to any work on the compressor:
Switch off the main switch and secure against unintentional switching-on.Check to ensure that all machine parts are voltage free.Depressurize all areas under pressure.
Never omit a single safety step! Otherwise, you will risk injuries due to restarting, electric shock or self-releasing parts.
DANGER!
When the automatic restart (Auto-Restart) is activated, the compressor will automatically restart following a power failure. Prerequisite: The net pressure is lower than the switch-on pressure.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.9
Installation
3.5 Commissioning
Checking the rotational direction
Opening the stop valves
CAUTION!
Always check the rotational direction of the drive motor prior to commission­ing/initial start up. Even brief operation in the wrong direction of rotation (more than approx. 5 seconds) may cause total destruction of the air end!
Ensure that the rotational direction coincides with the rotational direction arrow on the air end.
Switch on the main switch.Switch the compressor on and immediately off again to check the rota-
tional direction.
Changing the rotational direction:
DANGER: Risk of injury!
Switch off the main switch and secure against unintentional switching-on. – Interchange two phases (L1, L2 or L3) in the power cable.
Open ball valve on the compressor outlet.
Checking for leaks
Conduct trail run
Undertake the following to prevent leaks:
Check screw connection of the lines and retighten, if necessary.Check to ensure that the oil filter and oil separator are hand tight seated.
Switch on the main switch.
Switch on the compressor using the ON key. The compressor starts.The compressor switches off automatically once the switch-off pressure,
factory set on the operating pressure switch, has been reached.
– Check the supply pressure on the supply pressure gauge.
If necessary, reset operating pressure switch.
– The compressor is ready for operation.
Page 3.10
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Installation
3.5 Commissioning
Commissioning following extended stoppages
If an extended stoppage is scheduled, you should contact BOGE-Service beforehand.
Following an extended stoppage of more than 2 months, fill a small amount of oil in the suction controller prior to starting the compressor.
CAUTION!
Only fill the suction controller with the grade of oil used to operate the com­pressor. Never mix different oil grades and brands.
DANGER: Risk of injury!
Switch off main switch and secure against unintentional switching-on.
Unscrew the plug on the suction controller .The following quantities of compressor oil have to be filled into the intake
regulator: approx. 0.13 gallon for models S 31-2 – S 60-2 approx. 0.65 gallon for models S 61-2 – S 100-2 approx. 1.30 gallon for models S 101 – S 150 approx. 2.10 gallon for models S 151 – S 220 / SF 220 approx. 2.65 gallon for models S 271 – S 341 approx. 0.13 gallon for models SF 40-2 – SF 60-2 approx. 0.65 gallon for models SF 100-2 approx. 1.30 gallon for models SF 150
Reclose the controller using the plug.Turn the air end by hand 5 to 10 times to distribute the oil evenly.
Fig. 3.3: Suction controller
1
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
Page 3.11
Installation
Page 3.12
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Aufstellung.pm6.5 - USA
4.1 GeneralFaults
General
The tables on the following pages give information on the possible causes of operating faults and measures for their rectification (please also refer to operating instructions of the compressor control).
ATTENTION!
Ensure that any work required to rectify faults is only carried out by trained personnel or specialists. Ensure that components which have a safety function are only set, repaired or exchanged by BOGE Service!
Please contact BOGE-Service at the following telephone number, if you have any questions.
770 - 874 -1570
Stoerung.pm6.5 - USA
Page 4.1BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
4.2 General faultsFaults
Fault RectificationPossible cause
No quantity delivered, no pressure build-up, max. pressure 0.5 bar
System components in the compressor are leaking
Minimum pressure valve is defective
Electromagnetic venting valve does not close
Suction controller does not open
V-belts are torn
Check oil and compressed air lines inside the com­pressor; tighten and/or reseal screw connections, if necessary
Close ball valve and check whether pressure builds up; if so, open ball valve again immediately; replace minimum pressure valve
Check solenoid valve and replace, if necessary
Suction controller or solenoid valve is defective; check and replace, if necessary
Fit new V-belts
Compressor does not start up
Oil in suction filter
Excessive oil consumption
No electric power to com­pressor
Fuses are defective
Machine has not vented perfectly
Voltage fluctuations in the electrical mains power
Compressor oil is very viscous due to low ambient temperature
Minimum pressure non­return valve is leaking
Suction controller is leaking
Cut-out performed by emergency-off switch
Drain line is blocked Defective oil separator
element Excessive oil filling
Check electrical connection
Check the mains and control fuses, replace if necessary
Check venting valve and replace, if necessary
Ensure constant voltage in accordance with IEC 38
Heat up the compressor (additional heater available as as option)
Check the minimum pressure check valve and replace, if necessary
Check the suction controller and replace, if necessary
Cut-out normally via O key
Dismantle and clean drain line Check oil separator and replace, if necessary
Drain off oil
Safety valve blows Set operating pressure to the maximum
System pressure
Operating pressure switch has been misadjusted
Defective safety valve
Venting valve does not open
permissible pressure of the screw compressor Replace safety valve
Check venting valve and replace, if necessary
does not decrease
when switch-
ing off
Page 4.2 BOGE Operating instructions for S 40-2 ... S 341 / SF 40-2 ... SF 220 series screw compressors
Check valve is leaking
Check the check valve and replace, if necessary
Stoerung.pm6.5 - USA
Maintenance
5.1 Safety instructions
DANGER!
Ensure that maintenance work is only carried out by specialists or appro­priately trained person.
– Prior to starting any maintenance work, always stop the compressor as
described in these operating instructions prior to removing any cladding or safety devices. Refit the cladding or safety devices immediately upon completion of the maintenance work.
– Only use original spare parts, compressor oils and operating materials
released by BOGE for the maintenance work.
– When the automatic restart (Auto-Restart) is activated, the compressor
restart automatically following a voltage loss. Prerequisite: The net pressure is lower than the switch-on pressure.
Safety precautions
DANGER: Risk of injury!
Always adhere to the specified operating method described below for all maintenance work. Never omit a single safety step! Otherwise you will risk injury from restarting, electric shock or parts which may fly off.
Prior to all maintenance work:
1. Switch off the compressor using the OFF button.
2. Switch off the main switch and secure it against unintentional switch­on.
3. Check to ensure that all machine elements are definitely isolated.
4. Separate the compressor from the compressed air network by closing the ball valve at the compressed air outlet.
5. Vent the compressor. To this effect open the safety valve on the combined compressed air­oil receiver as follows:
– Turn the knurled nut counterclockwise until you can feel a resilient
resistance.
– Tun the knurled nut a little further.
Any possibly existing air will escape. The system pressure gauge will indicate a pressure of 0 bar.
– Once the residual air has completely escaped from the system,
firmly retighten the knurled nut.
6. Remove all safety cladding necessary to perform the maintenance work.
Once the maintenance work has been concluded:
7. Reattach all removed safety cladding.
8. Open the ball valve at the compressed air outlet.
9. Prior to switching on again, check whether anyone else is working on the compressor!
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.1
Maintenance
5.2 General
Maintenance through BOGE service
Have BOGE service check your compressor every 3000 operating hours or annually.
NOTICE: Maintenance agreement
Enter into a maintenance agreement with BOGE. BOGE service will carry out the proper maintenance on your compres­sor at regular intervals. This guarantees maximum safety and realiability of your compressed air supply.
Review of regular maintenance work
Check intake filter with S 100-2 on the back sid
of the compressors Check / set pressure switch
Clean filter and cartridge
Change filter cartridge
Change oil filter
Clean compressed air / oil cooler externally
Top up oil in the suction controller after an extended down time
Change supply air filter
(option)
Change oil separator
Check oil levelTop up oil
Change oil (Lubricate motor bearings)
Fig. 5.1: Review of regular maintenance work Note:
Check V-belts (S 60-2 air-cooled)
Page 5.2
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.2 General
Maintenance intervals
The maintenance intervals specified in the table are based on average oper­ating and ambient conditions. Extreme conditions may require shorter maintenance intervals.
NOTICE: Note down any maintenance work in the table on the last page. This will facilitate trouble shooting for BOGE service.
CAUTION! Oil change
Please change oil and replace oil filter and nozzle with dirt catch after the first 500 operating hours!
Maintenance work Maintenance intervals in operating hours
1)
Page
weekly/ 1000 1500 3000 8000 monthly annually annually annually annually
General maintenance work
Check final compression temperature (set point value: 160 – 212°F)
w Control
Check compressor for leaks X – Check system relief on system pressure gauge
(set point value 0 – 21 psig)
w Control
Check function of EMERGENCY STOP button m Control Check and if necessary change supply air filter (option) w 5.7 Clean oil cooler X 5.18 Check if electr. connections are firmly tightened X
Air circuit
Check and if necessary change intake filter m 5.6 Change intake filter cartridge X 5.6 Replace suction controller (wearing parts set) X – Check / reset operating pressure X Control Replace minimum pressure valve (wearing parts set) X – Replace solenoid valve X – Check safety valve X 5.20
Oil circuit
Check oil level and top up as required
2)
X 5.11 Replace oil regulator (wearing parts set) X – Replace nozzle with dirt catch X – Change oil separator Change oil filter Change oil
2)
2)
2)
X 5.14 X 5.13
X 5.16
Drive
Check / change V-belt X X 5.10 Lubricate drive motor bearings for details please see nameplate or enclosed operating instructions
for drive motor from 45 kW and up
Replace grease in motor bearings Depending on mains frequency: 50 Hz 10.000 operating hours
60 Hz 8.000 operating hours
1)
If the compressor is not often used, undertake the maintenance according to the specified intervals (weekly/monthly/annually) depending on the number of operating hours.
2)
The specified intervals only apply when BOGE compressor oil Syprem 8000 S is used! The service life may differ depending on the ambient temperature. In this case have the oil analyzed by your BOGE service!
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.3
Maintenance
5.2 General
General information concerning the lubricants used
DANGER: Risk of injury!
Oil presents a potential danger to health and environment due to their additives.
– Avoid contact with skin and eyes.
Wear protective gloves made of resistant synthetic material. Wash yourself thoroughly after contact with oils.
Do not inhale the fumes or mist.Protect your environment.
Ensure that no oil is spilt.
– Fire, naked flames and smoking is stricltly prohibited when handling
oil.
We recommend using only oil according to following specification:
Viscosity range of 55 mmMinimum viscosity at 100°C of 8 mm
2
/s at 40°C.
2
/s.
Maximum viscosity at 0°C of 1.000 mm²/s.Failure load stage 10, FZG-Test, DIN 51 354-02/ ISO DIS 14 635-1.Test Method A/8,3/90 10.Excellent oxidation stability: Meets requirements of Pneurop oxidation test.Antifoam – additives.Additives to prevent residue formation.Compatibility with all materials which are resistant to mineral hydrocar-
bons, e.g. Neoprene, NBR, FPM, PTFE, acrylic and epoxy resin pains, nylon (polyamide) and PVC.
Flash point (DIN ISO 2592) > 230°C.Excellent demulsifying properties.Additives for corrosion protection of metallic surfaces.Excellent oxidation stability: Rotating bomb oxidation Test (ASTM D 2272)
higher than 2,400 minutes.
Meets VDL requirements DIN 51 506 (including Pneurop test).Or you use BOGE compressor oil Syprem 8000 S.
The stated maintenance intervals refer to the use of Syprem 8000 S only.
Syprem 8000 S can be purchased from BOGE retailers.Never mix different oil types and brands. The additives may be incompat-
ible. It may lead to foam formation, premature aging or loss of lubricating ability.
Page 5.4
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.2 General
Disposal of used operating material
Spare and wearing parts
WARNING!
The handling and disposal of mineral oils is subject to legal regulations. It is an offense not to ensure correct and safe disposal of old oil!
Please instruct one of the known service companies to dispose of used operating materials or deliver them to an authorized disposal point.
Observe the following points when disposing of old oil:
Never mix the oil with other material or liquids.Used oil filters and oil separator cartridges require special waste treat-
ment and must be kept separate from normal waste!
CAUTION!
Only use original spare parts, compressor oils and operating materials released by BOGE for repair and maintenance work.
BOGE is not liable for any damage resulting from the use of other spare parts or operating materials.
ATTENTION!
If the nozzle with dirt catch is soiled the oil consumption may increase sig­nificantly!
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.5
Maintenance
5.3 Regular maintenance work
Clean or change intake filter
Cleaning the filter cartridge
Cleaning: 1x monthly,
however, at least every 500 operating hours.
– Correspondingly earlier if the air taken in is heavily soiled.
Change: In the event of damage.
After the second cleaning.
Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Removing the filter cartridge
Remove cladding on the maintenance side.Remove lid of the filter housing.Loosen nut and remove filter cartridge .
CAUTION! Do not clean filter cartridges in liquids. Do not use any hard objects when cleaning to avoid damaging the filter paper.
Refit a new filter cartridge in the event of damage or once it has been cleaned twice.
– Hit on the filter cartridge using the palm of your hand to knock out coarse
dust.
– Blow out fine dust from the inside to the outside using dry compressed
air (maximum pressure 70 psig).
– Clean the sealing surface of the filter cartridge.
Note: Demonstration example. Com-
pressor may only be operated with the switch cabinet closed and all panels fitted.
Fitting a filter cartridge
Insert filter cartridge into the filter housing.Tighten nut.Attach lid of the filter housing.Attach cladding on the maintenance side.
2
3
1
Fig. 5.2: Changing the intake filter Note:
Page 5.6
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
Changing the supply air filter mats (option)
Check: 1x weekly,
however, at least every 500 operating hours.
– Correspondingly earlier if the air taken in is heavily soiled.
Change: When a crust of dirt has accumulated on the filter mat.
When the final compression temperature has exceeded
its set point value by 7 to 9°F. The crust of dirt on the filter mat prevents an adequate cooling air supply.
– Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
CAUTION!
Pull filter mat out of its holder from above.Insert new filter mat into the holder.
Lubricating the drive motor bearings
Drive motors with permanent lubrication
1
Fig. 5.3: Changing the supply air filter Note:
As a rule, the bearings of the drive motors are provided with a maintenance free permanent lubrication. The drive motor of some series are equipped
with a post-lubricating unit. These motors can be easily recognised by the two grease nipples on the upper side of the housing. In addition, plates on the compressor indicate the type of motor lubrication.
Under normal operating conditions (coolant temperature max. 105°F, continous operation) the bearings are maintenance free for the service life.
Bearing service life: Mains frequency Operating hours
60 8,000
The service life decreases or increases as thermal stress increases or decreases (due to increased or reduced coolant temperature).
NOTICE: ATTENTION!
Have BOGE service dismantle the bearings and install new bearings once the specified service life has expired!
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.7
Maintenance
5.3 Regular maintenance work
Drive motors with lubrication device
Motors with lubrication devices are easily recognised by the two grease nip­ples on the top of the cover. Please check which motor is installed in your compressor and service it according to the respective instructions.
Lubricate the bearings of the drive motor at the prescribed intervals so as not to sustain damage due to lack of lubricant.
The motors with lubrication device can be recognised by the two grease nip­ples on the top of the cover. Adhesive plates on the compressor also indicate the motor lubrication. On motors with lubrication devices, regular greasing belongs to the scope of maintenance.
The lubrication intervals, quantity and type of grease are given on the type plate or a separate plate. For lubrication, the required quantity is pressed through the nipple into the bearing with a grease gun while the compressor is running.
DANGER: Risk of injury!
Always exercise great caution when lubricating the bearings with the com­pressor running and observe all safety precautions! Never put your hand in the area of the V-belt and the fan wheel. Fitted safety devices and cladding may not be removed.
CAUTION!
Always use the same type of grease for lubrication. The lubricating ability can be sharply reduced if different types of greases are mixed.
If you intend to use a different type of grease: – have the bearings removed and thoroughly cleaned prior to filling with
new grease.
Please always observe the specified lubrication intervals and quantities of grease.
Even over-greasing and an excess of lubricant can the bearings to be de­stroyed.
Page 5.8
Lubricating nipple
Fig. 5.4: Grease nipples of the lubricating device on the cabinet corner post for external greasing
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
Servicing drive motor
The drive motors have an automatic lubricating device (see figure). There is a lubricating nipple on the A bearing and B bearing side of the motor. The lubricating nipple is connected with the automatic lubricating device via a tube. The tubes are already filled with grease. When the tubes are replaced, they must be filled with grease. The type of grease is indicated on the lubrication unit of the compressor (see Fig. 5.5 below).
Voltage is supplied from the switch cabinet.
Both LC units (LC = lubrication canister) are designed for 1 year in three­shift operation. After one year, the canisters must be replaced because of lubricant ageing, no matter how much lubricant they have.
So as to comply with the necessary lubricating deadlines, the coding switches "VOL" and "TIME" of the drives are preset in the factory according to table
7.2 of the Operating Instructions for CONTROL TIME.
Set values: – LC unit S250 for A bearing: 2.89 cm³/ per 100 operating hours
For information regarding operating and maintenance to CONTROL TIME, please read enclosed operating instructions.
Fig. 5.5: Automatic lubricating device CONTROL TIME
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.9
Maintenance
5.3 Regular maintenance work
Changing the V-belt
Check: 1x per year for damage. Change: At visible damage.
The BOGE GM drive system automatically adjusts the V-belt to the correct V-belt tension in any operating mode. Maintenance of the V-belt drive is limited to the above mentioned work.
– Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Slacken the V-belts:
Remove cladding on the maintenance side as well as the belt protection.Secure screw head of the tensioning device with NW 27 spanner to
prevent it from turning.
– Turn locknut clockwise. Raise the motor in arrow direction  until the
V-belts are fully slackened.
Change the V-belts:
Remove the slackened belts from the belt pulleys.Fit new V-belts on the belt pulleys on the motor and compressor.
CAUTION!
The new V-belts must be of precisely the same length. Only change the V-belts as a complete set!
Tensioning the V-belts:
– Lower the motor again. For this purpose, secure screw head  against
turning, then turn locknut  counterclockwise and lock by means of the screw head. The V-belts are automatically correctly tensioned by the BOGE GM drive system.
Fit belt protection.Reattach cladding on the maintenance side.
3
4
5
Page 5.10
Fig. 5.6: The BOGE GM drive system
Note:
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
Setting GM – Belt tensioning device S 40-2 – S 341 SF 40-2 – SF 220
blue
inch
Setting
sealed
Model Pressure Setting
+0/– 0.04
psig inch S 40-2 / SF 40-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 50-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 60-2 / SF 60-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 61-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 75-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 100-2 / SF 100-2 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 101 100 / 115 / 125 / 150 / 190 4.4 / 4.4 / 4.4 / 4.4 / 4.4 S 125 100 / 115 / 125 / 150 / 190 3.6 / 3.8 / 3.8 / 3.7 / 3.9 S 150 / SF 150 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.0 S 151 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.0 S 180 100 / 115 / 125 / 150 / 190 3.6 / 3.4 / 3.4 / 3.4 / 3.5 S 220 / SF 220 100 / 115 / 125 / 150 / 190 3.5 / 3.3 / 3.3 / 3.4 / 3.5 S 271 100 / 115 / 125 / 150 / 190 4.0 / 4.0 / 3.8 / 3.8 / 4.8 S 341 100 / 115 / 125 / 150 / 190 3.5 / 3.5 / 3.2 / 3.2 / 4.6
The settings shown in the table are fixed by the manufacturer and may not be changed. Slight deviations are allowed and compensated by the GM drive system. The current settings are also shown on the GM drive system. With special versions the settings on the sticker may deviate from the standard values. If the spring is not pre-tensioned at the set measure, the measure must be reduced until the spring is slightly pretensioned (to prevent the spring clap­ping).
Checking the oil level, topping up oil
Check: Prior to commissioning/start-up of the compressor.
– Then every 1000 operating hours,
however at least once a year.
Topping up: – When the oil level has dropped below the "min" mark
(see sketch).
CAUTION!
Always use the same oil type when topping up. Never mix different oil types and brands.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.11
Maintenance
5.3 Regular maintenance work
Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Close ball valve at the compressed air outlet.Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
Wait approx. 3 minutes to permit the oil to settle.Remove cladding on the maintenance side.
DANGER: Risk of injury!
Danger of burning due to hot oil!
Remove plug of oil filling socket .Check oil level.
The oil level must not drop below the "min" mark (see sketch).
– If necessary, top up with oil to the lower edge of the thread ("max." mark)
on the oil filling socket.
Screw plug with viton seal back in.Reattach clading on the maintenance side.Open ball valve at the compressed air outlet.
Page 5.12
1
2
Fig. 5.7: Checking the oil level, topping up with oil Note:
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
Changing the oil filter
Change: After 3000 operating hours,
however, no later than after one year.
With each oil change!
Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Close ball valve at the compressed air outlet.Take off safety warm air hood and open safety sound insulation hood.Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
Wait approx. 3 minutes to permit the oil to settle.Remove cladding on the maintenance side.
DANGER: Risk of injury!
Danger of burning due to hot oil! – Unscrew soiled oil filter  by hand or use a strap wrench, turning counter-
clockwise. Catch the draining oil and dispose of properly according to environmental regulations.
Fill the new oil filter with compressor oil.Lightly oil the sealing ring of the new oil filter.Screw in new oil filter by hand, turning clockwise.Close safety sound insulation hood.
CAUTION!
Do not use tools to screw in the new oil filter! You might damage the oil filter or its sealing ring. A hand tight seating of the oil filter is sufficient.
– Close safety sound insulation hood and reattach cladding on the mainte-
nance side.
Open ball valve at the compressed air outlet.Switch on the compressor and heat up to operating temperature.Subsequently, check the oil filter for leaks once again and tighten by hand,
if necessary (Procedure as described above).
DANGER: Risk of injury!
Switch off the main switch and secure against unintentional switch-on.
Check the oil filter for leaks and tighten by hand, if necessary.Check oil level.
Top up oil losses, if any.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.13
Maintenance
5.3 Regular maintenance work
3
Fig. 5.8: Changing the oil filter Note:
Changing the oil separator
Change: When the difference between supply and system pressure
exceeds 12 psig.
– When warning message "8" appears on the control system
display (if option is installed).
– After 3000 operating hours,
however, no later than after one year.
NOTICE: If the specified maintenance intervals are not observed, the oil separa­tors might become blocked. In this case, the differential pressure will increase until the safety valve blows.
Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Close ball valve at the compressed air outlet.Open safety sound insulation hood.Vent the compressor (as described in the beginning of the chapter).
The system pressure gauge must indicate a pressure of 0 psig.
– Wait approx. 3 minutes to permit the oil to settle.
Note: Demonstration example. Com-
pressor may only be operated with the switch cabinet closed and all panels fitted.
Page 5.14
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
DANGER: Risk of injury!
Danger of burning due to hot oil!
Remove cladding on the maintenance side.Unscrew soiled oil separators by hand or use a strap wrench, turning
counterclockwise.
– Catch the draining oil and dispose of properly according to environmental
regulations.
Lightly oil the sealing rings of the new oil separator.Screw in new oil separators by hand, turning clockwise.
CAUTION!
Do not use tools to screw in the new oil separators! You might damage the oil separators or their sealing rings. A hand tight seating of the oil separators is sufficient.
Close safety sound insulation hood.Reattach cladding on the maintenance side.Open ball valve at the compressed air outlet.Switch on the compressor and heat up to operating temperature.Check the oil filter for leaks once again (Procedure as described above).
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on. – Check the oil separators for leaks and tighten by hand, if necessary.
4
Fig. 5.9: Changing the oil separators Note:
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.15
Maintenance
5.3 Regular maintenance work
Oil change
Change: After 9000 operating hours,
however, at the latest after two years.
– For other types of oil the appropriate oil change intervals
must be complied with.
NOTICE:
The service life of the oil, the oil filter and oil separators is reduced under the following conditions:
When the compressor is operated at extreme ambient temperatures.When the intake air is extremely soiled.
Building up a pressure cushion
The combined compressed air / oil receiver is located at the lowest point of the system. Therefore, a light pressure cushion (approx. 30 psig system pressure) must be applied to drain the oil. This pressure cushion forces the oil through the drain hose into a suitable collecting basin.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on. – Screw cap nut  onto the vent hole of the solenoid valve on the suction
controller by hand. The cap nut (M8) is located in the storage compartment of the switch cabinet.
CAUTION!
Never use any tools to screw on the cap nut! Damage af the solenoid valve might result.
– Switch on the compressor again and allow it to start up.
If necessary, let out some air from the compressed air receiver until the switch-on pressure of the compressor is reached.
– Switch off the compressor at approx. 30 – 44 psig system pressure using
the EMERGENCY-OFF-button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Slowly loosen cap nut until compressed air escapes.Let off compressed air until the system pressure gauge shows a residual
pressure of approx. 30 psig.
– Tighten cap nut  by hand.
DANGER: Risk of injury!
Danger of burning due to hot oil!
Draining old oil
Place the oil drain hose into a suitable container .Slowly open the stop valve.
The pressure cushion forces the oil into the container.
– Once the compressed air/oil receiver has been completely drained, close
the stop valve.
– Remove the cap nut from the solenoid valve.
Page 5.16
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
– Remove oil filler screw  on the compressed air/oil cooler and drain the
residual oil (max. 5 litres) into a suitable container.
Reinsert the oil filler screw together with a new copper sealing ring.Change oil filter (Procedure as described above).Change oil separators (Procedure as described above).
Filling with new oil:
– Fill up to the edge of the thread of the filling socket (max.).
(Procedure as described above).
CAUTION! After each oil change you have to fill a small quantity of oil into the suction
controller before starting the compressor. For oil quantity and procedure see chapter "Commissioning following extended stoppages".
CAUTION!
Always fill with the same oil type as previously used. Never mix different oil types and brands.
The oil circuit must be flushed prior to changing the oil type.
Close safety sound insulation hood.Open ball valve at the compressed air outlet.Reattach cladding on the maintenance side.Conduct trial run.
5
Fig. 5.10: Solenoid valve Note: on the intake controller with the cap nut screwed on
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on. – Check the oil filters and oil separators for leaks and tighten by hand,
if necessary (procedure as described above).
– Check oil level (procedure as described above).
Top up oil losses, if any.
7
6
Fig. 5.11: Note: Drain off old oil from air/oil separator vessel
Fig. 5.12: Note: Drain off residual oil from oil cooler
Note: Demonstration example. Compressor may only be operated with the switch cabinet closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.17
Maintenance
5.3 Regular maintenance work
Flushing the oil circuit
Cleaning the compressed air / oil cooling unit (air cooling)
Flushing the oil circuit with clean oil becomes necessary:
When the oil is excessively soiled.Prior to changing the oil type.
CAUTION!
Detailed information as to the flushing with BOGE oils you can obtain from the following service number.
770 - 874 -1570
Cleaning: – After 1500 operating hours,
however, at the latest after one year.
The service life of the compressed air/oil cooling unit depends on the degree of soiling (dust, oil vapour) of the suctioned cooling air. Extreme external soiling of the cooling unit leads to an increased temperature in the oil circuit.
Switch off the compressor using the OFF button.
DANGER: Risk of injury!
Switch off the main switch and secure it against unintentional switch-on.
Remove cladding on the maintenance side.Unscrew the maintenance flap on the air guidance box.Remove accumulated soiling with a fibre brush.
CAUTION!
Do not use any sharp objects for cleaning! These could damage the cooling unit!
– Blow down the dirt with compressed air  in the opposite direction to the
normal cooling air flow. Clean out the dirt using an industrial vacuum cleaner (see Fig.).
If the cooling unit is excessively soiled (cleaning is no longer possible with compressed air), have it disassembled and cleaned by BOGE service.
Page 5.18
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.3 Regular maintenance work
1
Proportional controller (option for S-series)
1
2
For water-cooled versions a cleaning is not necessary
Fig. 5.13: Cleaning the compressed air/oil cooling unit Note:
Check: – After approx. 3000 operating hours,
however, at least once a year.
1. Setting the operating pressure sensor
Switch-on pressure: P Switch-off pressure: P
= Final compression pressure – 14 psig.
min
= Final compression pressure.
max
2. Setting the proportional controller
Displace the control range of the proportional controller by turning cap . – Increase pressure level:
Turn cap clockwise.
– Reduce pressure level:
Turn cap counterclockwise.
Always set the proportional controller higher than the bottom operat­ing pressure value (P
min
)!
3. Pressure switch for infinitely variable capacity control
The low pressure switch for the infinitely variable capacity control limits the reduction of the delivered quantity and switches the compressor in the event of less than 50 % delivered quantity into idling operation or off.
Note: Demonstration example. Compressor may only be operated with the switch cabinet
closed and all panels fitted.
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.19
Maintenance
5.3 Regular maintenance work
Checking the safety valve
DANGER: Risk of injury!
Because a hot air-oil mixture will escape when checking the safety valve with running compressor only trained personnel or specialists should carry out this work!
Check: – After approx. 3000 operating hours,
however, at least once a year.
Check safety valve by opening the screw plug .
DANGER: Risk of injury!
Danger of burning due to hot oil! Take extreme care when checking the safety valve with the compressor
running taking all safety measures into consideration. Wear eye protection. A hot air-oil mixture escapes when opening! – Open the threaded plug  counterclockwise.
The compressed air escapes.
– Tighten the threaded plug by turning clockwise.
Fig. 5.14: check safety valve
1
Page 5.20
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Maintenance
5.4 Spare parts and optional equipment
List of spare and wearing parts (for maintenance)
Designation
Filter mat for supply air filter
Compressor oil Syprem 8000 S
Set of V-belts
Lubrication for drive motor bearings
Maintenance kit consisting of: oil filter, oil separator, suction filter cartridge, gaskets, nozzle with dirt catch
Wearing part kit consisting of: oil regulator, intake regulator, minimum pressure valve
Solenoid valve
NOTICE: When ordering, please specify the data on the type plate:
TypeYear of manufactureMachine number
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Page 5.21
Maintenance
Page 5.22
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Wartung.pm6.5 - USA
Appendix
Air cooled version, standard
6.1 Flow chart
Air IN
1 = Suction filter 2 = Maintenance display (from 30 kW) 3 = Vacuum switch
(for suction filter monitoring) * 4 = Suction controller 5 = Ventilation and regulation control valve 7 = Drive motor 8 = Compressor air end 9 = Sensor for final compression temperature
10 = Combined compressed air/oil receiver 11 = Oil separator 12 = Safety valve 16 = Thermostatic oil control valve 17 = Oil cooler 18 = Oil filter 19 = Differential pressure switch
(for oil filter monitoring) *
20 = Oil throttle 21 = Minimum pressure check valve 22 = Compressed air after-cooler
Compressed air
OUT
23 = Pressure sensor system pressure 24 = Pressure sensor network pressure 25 = Stop valve, compressed air outlet 27 = Stop valve, oil drainage 28 = Check valve drainage line (up to 75 kW) 29 = Proportional controller * 30 = Diff. pressure switch for prop. controller * 31 = 3/2-way solenoid valve for prop. contr. *
(with standard control passage here) 37 = Display of F.a.d. for prop. controller * 42 = 3/2-way solenoid valve for suction control
regulation * 43 = Double check valve*
(Pos. 42 + 43 = rapid-start valve) 44 = Double check valve *
(Monitoring of rotational direction)
* = Option
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Page 6.1
Appendix
6.1 Flow chart
Water cooled version, serial connection – parallel connection
Air IN
Water OUT
Water IN
* Parallel connection Serial connection
1 = Suction filter 2 = Maintenance display (from 30 kW) 3 = Vacuum switch
(for suction filter monitoring) * 4 = Suction controller 5 = Air relief and regulation control valve 7 = Drive motor 8 = Compressor air end 9 = Sensor for final compression temperature
10 = Combined compressed air/oil receiver 11 = Oil separator 12 = Safety valve 16 = Thermostatic oil control valve 17 = Oil cooler 18 = Oil filter 19 = Differential pressure switch
(for oil filter monitoring) *
20 = Oil throttle 21 = Minimum pressure check valve 22 = Compressed air after-cooler 23 = Pressure sensor system pressure 24 = Pressure sensor network pressure 25 = Stop valve, compressed air outlet
Compressed
air OUT
Water OUT
Water IN
Compressed
air OUT
27 = Stop valve, oil drainage 28 = Check valve drainage line (up to 75 kW) 29 = Proportional controller* 30 = Diff. pressure switch for prop. controller * 31 = 3/2-way solenoid valve for prop. contr. *
(with standard control passage here) 32 = 2/2-way solenoid valve 33 = Control valve water supply (preadjusted) 34 = Control valve water supply (preadjusted) 37 = Display of F.a.d. for prop. controller * 42 = 3/2-way solenoid valve for suction control
regulation * 43 = Double check valve*
(Pos. 42 + 43 = rapid-start valve) 44 = Double check valve *
(Monitoring of rotational direction)
To be provided by customer: 35 = Dirt trap 36 = Stop valve
* = Option
Page 6.2
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Appendix
6.1 Flow chart
Air cooled version, frequency-controlled
Air IN
1 = Suction filter 2 = Maintenance display 3 = Vacuum switch (for suction filter monitoring) * 4 = Suction controller 5 = Air relief and regulation control valve 6 = Pressure switch (for rotational direction,
system relief and V-belt monitoring) 7 = Drive motor 8 = Air end 9 = Final compression temperature display and switch
10 = Combined compressed air/oil receiver 11 = Oil separator 12 = Safety valve 13 = Differential pressure switch
(for oil separator monitoring) *
14 = System pressure switch
(for system pressure build-up and monitoring) *
15 = Safety pressure switch (for pressure limitation) * 16 = Thermostatic oil control valve
Compressed
air OUT
17 = Oil cooler 18 = Oil filter 19 = Differential pressure switch
(for oil filter monitoring) * 20 = Oil throttle 21 = Minimum pressure check valve 22 = Compressed air after-cooler 23 = Operating pressure switch 24 = Pressure gauge (line pressue)
24.1= Pressure gauge (system pressure) 25 = Stop valve, compressed air outlet 27 = Stop valve, oil drainage
27.1= Stop valve, oil drainage
(oil cooler, 75 – 250 kW) 28 = Check valve drainage line
(to 75 kW)
* = Option
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Page 6.3
Appendix
Motor
mainte-
6.2 List of maintenance and service work
nance
unit
Cooling
cleaning
Oil
separator
**
Oil-
level
Oil-
filter
*
filter
Intake
ture
Tempera-
Please note the completed maintenance work in the respective columns
System
pressure
Ch = Change
** C = Check
Page 6.4
Line
pressure
hours
Operating
Date Remarks
Ch = Change
* Cl = Cleaning
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Appendix
Motor
mainte-
6.2 List of maintenance and service work
nance
unit
Cooling
cleaning
Oil
separator
**
Oil-
level
Oil-
filter
*
filter
Intake
ture
Tempera-
Please note the completed maintenance work in the respective columns
System
pressure
Ch = Change
** C = Check
Line
pressure
hours
Operating
Date Remarks
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Ch = Change
* Cl = Cleaning
Page 6.5
Appendix
Motor
mainte-
6.2 List of maintenance and service work
nance
unit
Cooling
cleaning
Oil
separator
**
Oil-
level
Oil-
filter
*
filter
Intake
ture
Tempera-
Please note the completed maintenance work in the respective columns
System
pressure
Ch = Change
** C = Check
Page 6.6
Line
pressure
hours
Operating
Date Remarks
Ch = Change
* Cl = Cleaning
BOGE Operating instructions for S 40-2...S 341 / SF 40-2...SF 220 series screw compressors
Fliess.pm6.5 - USA
Loading...