BOC Edwards EXT555H Instruction Manual

NRA-266-880 Issue A Original
98/37/EC 89/336/EEC 73/023/EEC
Instruction Manual
EXT555H
Jun 01 Issue A
PAGE
i
i
1 INTRODUCTION 1
1.1 Scope and definitions 1
2TECHNICAL DATA 3
2.1 General 3
2.2 Pumping media 3
2.2.1 Pumps without gas purge 4
2.2.2 Pumps with gas purge 4
2.3 Vent gas specification and vent control data 4
2.4 Purge gas specification 5
2.5 Water cooling 5
2.6 Materials exposed to gases pumped 6
3 INSTALLATION 9
3.1 Unpack and inspect 9
3.2 Typical installation 9
3.3 Connection to the vacuum system 9
3.3.1 Inlet screens (supplied fitted) 9
3.3.2 Inlet connection 11
3.3.3 Backing connection 11
3.3.4 Interstage connection (Hi pump variants only) 13
3.4 Vent options, vent valve connection and control 13
3.5 Purge gas connection 15
3.5.1 Connect the purge gas 15
3.5.2 Recommended purge gas flow 15
3.6 Electrical installation 15
3.7 Cooling 15
3.7.1 Introduction 15
3.7.2 Forced air cooling 17
3.7.3 Water cooling 17
4 OPERATION 19
4.1 Start up 19
4.2 Stand-by 19
4.3 Shut-down 19
4.4 Safety interlocks and control system 19
4.5 Bakeout (conflat only) 20
5MAINTENANCE 21
5.1 Introduction 21
5.2 Bearing maintenance 21
5.3 Clean the pump 21
5.4 Fault finding 21
6 STORAGE AND DISPOSAL 25
CONTENTS
Section Title Page
dcs/0112
Issue A Jun 01
EXT555H
ii
PAGE
ii
6.1 Storage 25
6.2 Disposal 25
7 SERVICE, SPARES AND ACCESSORIES 27
7.1 Introduction 27
7.2 Service 27
7.3 Spares 27
7.3.1 ISX inlet-screen 27
7.3.2 Inlet-strainer (EXT555Hi pump only) 28
7.3.3 Inlet-flange seals 28
7.4 Accessories 28
7.4.1 Installation 28
7.4.2 EXC controller 28
7.4.3 Pump-to-controller cable 30
7.4.4 EXDC drive modules 30
7.4.5 BX bakeout band (conflat only) 30
7.4.6 FL20K foreline trap 31
7.4.7 TAV vent-valve and vent-port adaptor 31
7.4.8 ACX air-cooler 31
7.4.9 WCX water-cooler 32
7.4.10 Vibration isolators 32
7.4.11 PRX purge-restrictor 32
7.4.12 VRX vent-restrictor 33
ILLUSTRATIONS
Figure Title Page
1 Typical pumping system 10 2 Diagram of inlet screen - remove screws 'A' in order
to remove the inlet screen. Do not remove screws 'B' 12 3 Maximum rate of pressure rise when venting 14 4 Dimensions and features of EXT555H pumps 16 5 Installation of EXT555H optional accessories and spares 29
CONTENTS (continued)
Section Title Page
Jun 01 Issue A
PAGE
iii
iii
1 General information 3 2 Vent gas and vent control data 4 3 Purge gas specification 5 4 Cooling water specification 5 5Technical data 6 6 List of items supplied 9 7 Vent restrictor orifice diameter (with atmospheric
pressure at the inlet) 13 8 Fault finding 22 9ISX inlet-screen 27 10 Inlet-strainer (EXT555Hi pump only) 28 11 Inlet-flange seals 28 12 EXC controller 28 13 Pump-to-controller cable 30 14 EXDC drive modules 30 15 BX bakeout band 30 16 FL20K foreline trap 31 17 TAV vent-valve and vent-port adaptor 31 18 ACX air-cooler 31 19 WCX water-cooler 32 20 Vibration isolators 32 21 PRX purge-restrictor 32 22 VRX vent-restrictor 33
ASSOCIATED PUBLICATIONS
Publication Title Publication Number
EXC120/120E/300/300M Turbomolecular Pump Controllers D396-14-880G EXC250E/250L Turbomolecular Pump Controllers D396-36-880A EXDC Turbomolecular Pump Drive Modules D396-40-880E
TABLES
Table Title Page
Issue A Jun 01
EXT555H
PAGE
iv
iv
This page intentionally blank.
Jun 01 Issue A
INTRODUCTION
PAGE
1
1
1INTRODUCTION
1.1 Scope and definitions
This manual provides installation, operation, maintenance and storage instructions for the BOC Edwards EXT555H compound turbo-molecular pumps. Please read and follow all the instructions in this manual.
The EXT555H pump is designed for use with a BOC Edwards EXC or EXDC controller. Read this manual and the instruction manual supplied with your controller before you attempt to install or operate the equipment. The controller manual contains details of electrical installation.
Important safety information in this manual is highlighted as WARNING and CAUTION instructions. Please obey these instructions. The use of warnings and cautions is defined below.
In accordance with the recommendations of EN61010, the following warning symbols may appear on the pump or its accessories:
Warning - refer to accompanying documentation.
Warning - risk of electric shock.
WARNING
Warnings are given where failure to observe the instruction could result
in injury or death to people.
CAUTION
Cautions are given where failure to observe the
instruction could result in damage to the
equipment, associated equipment or process.
Warning - hot surfaces.
The units used throughout this manual conform to the SI system of units of measurement. Also, throughout this manual, wherever flow rates are specified, the abbreviation 'sccm' is used to mean standard cm
3
min-1: this is a flow of 1cm3 min-1 at an ambient temperature of 0 °C and a pressure of 1013 mbar (1.013 x 10
5
Pa).
Issue A Jun 01
EXT555H
PAGE
2
2
This page intentionally blank.
Jun 01 Issue A
TECHNICAL DATA
PAGE
3
3
2TECHNICAL DATA
2.1 General
General items Reference data
Performance See Table 5
Dimensions and features See Figure 4
Maximum inlet flange temperature 80 °C
Maximum magnetic field
EXT555H DN160CF 3 mT horizontal, 5 mT vertical
EXT555H ISO160 2.5 mT horizontal, 5 mT vertical
Installation category EN61010 part 1, category 1
Pollution degree EN61010 part 1, category 2
Equipment type Fixed equipment, for indoor use only
Operating altitude up to 3000 m
Ambient temperature 5 °C - 35 °C (air cooled)
5 °C - 40 °C (water cooled)
Relative humidity 10 - 95% non condensing
Table 1 - General information
2.2 Pumping media
WARNING
Vent dangerous gases and gas
mixtures safely. Do not expose
people to these gases.
WARNING
Do not use EXT555H pumps to
pump explosive gas mixtures as the
pumps are not suitable for this
purpose.
WARNING
On an Hi variant, gas pumped
through the interstage port will mix
with gas pumped through the pump
inlet. Ensure that the gases will not
react or combine to form dangerous
gases and substances.
Note: Concentrations of gases may be modified by
the compression of the pump.
CAUTION
Do not use an EXT555H pump to pump gases containing more than 20% oxygen unless a bearing purge is applied as stated in Section 2. If you do the
lubricant will be damaged and the pump will fail
prematurely.
CAUTION
Do not use the EXT555H pump to pump mercury
vapour, and do not allow mercury to come into contact with the pump. If you do, the rotor may
corrode and fail.
Issue A Jun 01
PAGE
4
EXT555H
TECHNICAL DATA
4
2.2.1 Pumps without gas purge
The pumps are designed to pump the following residual gases normally used in high vacuum systems:
air
nitrogen
carbon dioxide
carbon monoxide
krypton
helium
neon
argon
hydrogen
ethane
propane
butane
methane
You can use the pumps to pump oxygen and water vapour subject to the following conditions:
Oxygen
The oxygen concentration must be less than 20% by volume unless a bearing purge is applied as detailed in Section 2.2.2.
Water vapour
You must ensure that vapour does not condense inside the pump - refer to Section 3.7.3.
If you wish to pump a gas not previously listed, contact your supplier for advice. If you do not contact your supplier you may invalidate the warranty on the pump.
The pumps are not suitable for pumping aggressive or corrosive gases.
2.2.2 Pumps with gas purge
When purged with an inert gas the pumps can be used to pump oxygen in concentrations above 20% by volume.
2.3 Vent gas specification and vent
control data
Although the pump may be vented to atmosphere, relatively high air humidity may greatly increase the subsequent pump-down time. To reduce pump­down times you should vent the pump with dry, clean gases.
Vent gas system items Reference data
Vent gas Dry air, nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure -22 °C
Maximum size of particulate 1 micron
Maximum concentration of oil 0.1 parts per million
Time for rotational speed to reach 50% >15 seconds
Maximum allowed rate of pressure rise see Figure 3
Table 2 - Vent gas and vent control data
Jun 01 Issue A
TECHNICAL DATA
PAGE
5
5
2.4 Purge gas specification
Purge gas system items Reference data
Purge gas Dry nitrogen, argon or other inert gases
Maximum dew point at atmospheric pressure -22 °C
Maximum size of particulates 1 micron
Maximum concentration of oil 0.1 parts per million
Allowable purge gas flow (when required) 20 to 150 sccm (0.33 to 2.48 mbar l s-1, 33 to 248
Pa l s-1)
Recommended purge gas flow 25 sccm (0.42 mbar l s-1, 42 Pa l s-1)
Maximum allowable purge gas supply pressure 2 bar gauge (29 psig, 3 x 10
5
Pa)
Table 3 - Purge gas specification
2.5 Water cooling
The following water cooling specification corresponds to a typical high quality drinking water specification. Check with your water supply authority if you are in doubt about the quality of your supply.
Cooling water system items Reference data
Quality Mechanically clean and optically with no deposits
or turbidity
pH value 6.0 to 8.0
Maximum calcium carbonate concentration 75 parts per million
Maximum chloride concentration 100 parts per million
Minimum oxygen concentration 4 parts per million
Recommended water cooling flow rate (at 15 °C) 15 l hr
-1
Water temperature See Table 5
Maximum water pressure 5 bar (gauge), 73.5 psig, 6 x 10
5
Pa
Materials exposed to cooling water Copper, brass, braise
Table 4 - Cooling water specification
Issue A Jun 01
PAGE
6
EXT555H
TECHNICAL DATA
6
2.6 Materials exposed to gases pumped
The following materials and component types are exposed to the gases pumped: aluminium alloys, stainless steels, fluoroelastomer and nitrile 'O' rings, hydrocarbon lubricant, rare earth magnets, silicon nitride, phenolic resin and carbon fibre epoxy resin.
Parameter EXT555H Notes
Mass EXT555H ISO160 13.4 kg
Mass EXT555H DN160CF 21.2 kg
Main inlet flange DN160ISO-K/DN160CF
Outlet flange DN25NW
Interstage port (Hi variants) DN25NW
Vent port 1/8 inch BSP
Purge port 1/8 inch BSP
Inlet pumping speed *
N2 540 l s
-1
He 580 l s
-1
H2 500 l s
-1
Ar 510 l s
-1
Interstage pumping speed *
N2 8 l s
-1
He 6 l s
-1
H2 8 l s
-1
Ar 10 l s
-1
Inlet compression ratio **
N2 >10
10
Pb < 20 mbar
He 10
8
Pb < 12 mbar
H2 10
6
Pb < 7 mbar
Ar >10
10
Pb < 20 mbar
Critical backing pressure
N2 > 20 mbar
H2 9 mbar
He 20 mbar
Ar > 20 mbar
Table 5 - Technical data
Jun 01 Issue A
TECHNICAL DATA
PAGE
7
7
Ultimate pressure CF ISO
<10
-10
mbar
<2 x 10
-9
mbar
Minimum backing pump displacement
12 m
3 h-1
Recommended backing pump RV12
Maximum continuous inlet pressure (light gas pumping)
††
Forced air cooled, 30 °C ambient 1 x 10-3 mbar
Forced air cooled, 35 °C ambient 5 x 10
-4
mbar
Water cooling at 15 °C2 x 10
-3
mbar
Maximum continuous inlet pressure (argon pumping)
††
Forced air cooled, 30 °C ambient 2 x 10-4 mbar
Forced air cooled, 35 °C ambient 2 x 10
-4
mbar
Water cooling at 15 °C3 x 10
-4
mbar Water cooling while pumping high
concentrations of argon is not recommended
Maximum continuous backing pressure (light gas pumping)
††
Forced air cooled, 30 °C ambient 12 mbar
Forced air cooled, 35 °C ambient 7.5 mbar
Water cooling at 15 °C15 mbar
Maximum continuous backing pressure (argon)
††
Forced air cooled, 30 °C ambient 5 mbar
Forced air cooled, 35 °C ambient 3.5 mbar
Water cooling at 15 °C 8 mbar Water cooling while pumping high
concentrations of argon is not recommended
Operating attitude Any
Nominal rotational speed 50000 rpm
Start time to 90% speed:
EXC250 < 8 minutes
EXC300 < 8 minutes
EXDC160 < 8 minutes
Parameter EXT555H Notes
Table 5 - Technical data (continued)
Issue A Jun 01
PAGE
8
EXT555H
TECHNICAL DATA
8
Cooling method forced air / water
Ambient air temperature for forced air cooling
0 °C - 35 °C
Minimum cooling water flow rate (water at 15 °C)
15 l h
-1
Water temperature 10 °C - 20 °C
Noise level at 1 metre <60 dBA
Recommended controllers EXC250, EXC300, EXDC160
Quiescent power consumption 35 W
* Pumping speeds are without inlet screen or inlet strainer (EXT555Hi)
Inlet screens and inlet strainers reduce pumping speed by about 20%
** Pb = backing pressure
Pumping speed has dropped by 10%
††
Above this pressure the rotational speed of the pump drops below nominal
Parameter EXT555H Notes
Table 5 - Technical data (continued)
Jun 01 Issue A
INSTALLATION
PAGE
9
9
3 INSTALLATION
3.1 Unpack and inspect
Take care when you unpack the pump to avoid excessive shocks which could damage the bearings and reduce the life of the pump. The pump is supplied with the inlet and the outlet sealed to prevent entry of dust and vapour. Do not remove these seals until you are ready to install the pump on your vacuum system.
Remove all the outer cardboard packaging and check the pump. If the pump is damaged, notify your supplier and carrier in writing within three days; state the item number of the pump together with your order number and your supplier's invoice number. Retain all the packing materials for inspection. Do not use the pump if it is damaged.
Check that your package contains the items listed in Table 6. If any of these items is missing, notify your supplier in writing within three days.
If the pump is not to be used immediately, store the pump in suitable conditions as described in Section 6.1.
It is advised that you retain all packing materials for use should you return the pump for service.
WARNING
The EXT555H DN160CF pump
variant weighs 21 kg. Take care when
handling the pump and ensure that you grip it firmly by the inlet flange
when manoeuvring it.
3.2 Typical installation
A typical pump system with an EXT555H pump is shown in Figure 1.
The accessories available for the EXT555H pump are detailed in Section 7.4. The accessories are shown in Figure 5.
3.3 Connection to the vacuum system
Carefully remove the pump from packaging media and connect to the vacuum system
.
3.3.1 Inlet screens (supplied fitted)
WARNING
Install the pump on the vacuum system before you connect the
controller to the power supply. This
will ensure that the pump cannot
operate and injure people during
installation.
WARNING
Removal of inlet screens will expose
people to the risk of injury from
sharp edges.
CAUTION
Removal of inlet screens could allow debris to fall into the pump, which could cause serious damage
to the pump.
Qty Description
1 EXT555H turbomolecular pump
1 Inlet screen (fitted)
1 Inlet seal (trapped 'O' ring, co-seal or copper compression gasket)
1 Inlet strainer (EXT555Hi only, fitted in the interstage port)
Table 6 - List of items supplied
Issue A Jun 01
PAGE
10
EXT555H
INSTALLATION
10
Figure 1 - Typical pumping system
1. Alternative position for vent-valve
2. Vacuum system
3. High-vacuum gauge
4. Inlet-screen
5. EXT pump
6. Backing valve
7. Vacuum gauge
8. Flexible bellows
9. Foreline trap
10. Rotary backing pump
11. Mist filter
12. Cooling water connectors
13. EXC controller
14. Air cooler
15. PRX10 purge restrictor
16. Regulated purge gas supply
17. Vent-valve
Jun 01 Issue A
INSTALLATION
PAGE
11
11
Do not remove inlet screens unless you can be sure that there is no danger that debris can fall into the pump. If the inlet screens are removed, the pumping speed through the inlet will increase by approximately 20%.
To remove the inlet screen, undo the three screws ('A') which hold it down (Figure 2). If you need to replace the inlet screen, do so by undoing these screws, changing the inlet screen, and replacing the screws. Ensure that screws are firmly tightened.
3.3.2 Inlet connection
Ensure that the EXT555H pump is securely fixed to the vacuum system following the instructions below.
Make sure that the pump inlet and all components fitted to the pump inlet are clean and dust free. If the pump inlet is not kept clean the pump down time may be increased.
Use the vacuum seal provided with the pump.
If you are using an EXT555H ISO160 pump, connect it to the vacuum system using an ISO160 rotatable flange with a full complement of bolts. Alternatively use at least 8 claw clamps.
If you are using an EXT555H DN160CF, use a full complement of 20 M8 bolts to attach the pump to your vacuum system.
CAUTION
Do not remove the three screws which retain the locking plate ('B' in Figure 3). If you do so the pump
settings may change and the pump may cease to
operate or have a shortened life.
WARNING
Ensure that the EXT555H pump is
securely fixed to the vacuum system
following the instructions below. If you do not, and the pump seizes, the stored energy of the rotor can cause
rapid movement of the pump, which
may cause injury to people and
further damage to equipment.
If the inlet flange of the EXT555H is not connected to a rigid, firmly fixed vacuum system, ensure that the base of the pump is fixed to a firm support. Remove the four feet and secure the pump using eight M8 screws through the tapped fixing holes in the base of the pump. If you are using a WCX555 water cooling accessory, mount through the cooling plate into the tapped holes on the base of the pump.
If the pump inlet is connected to the vacuum system using a vibration isolator, use the tapped fixing holes in the base of the pump to secure the pump to a firm support as described above. Alternatively, fit suitable restraints to prevent movement of the pump and fracture of the vibration isolator in the unlikely event of a seizure of the pump rotor.
The pump can be mounted in any orientation. If it is mounted off-vertical, ensure that the backing port points downwards to reduce the risk of contamination from backing pump oil.
3.3.3 Backing connection
Use suitable vacuum tubing and connectors to connect the NW flange of the backing port to your backing pump. If necessary use flexible pipe or bellows to reduce the transmission of vibration from the backing pump to the EXT555H pump.
We recommend that you use a BOC Edwards RV backing pump. The minimum size of the backing pump required is given in Table 5. You may have to use a larger backing pump if you run the pump at a high inlet pressure or high throughput, or if you purge the pump.
CAUTION
If you back the EXT555H pump with the interstage
of another turbomolecular pump, make sure that the backing pressure does not fall below 5 x 10
-4
mbar (5 x 10
-2
Pa). Lower backing pressures will
increase the evaporation rate of the lubricant and
so will reduce the life of the bearings.
Issue A Jun 01
PAGE
12
EXT555H
INSTALLATION
12
Figure 2 - Diagram of inlet screen - remove screws 'A' in order to remove the inlet screen. Do not remove
screws 'B'
Jun 01 Issue A
INSTALLATION
PAGE
13
13
3.3.4 Interstage connection (Hi pump
variants only)
Use suitable vacuum tube and connectors to connect the interstage port to your vacuum system or to the outlet flange of another turbomolecular pump. Leave the inlet strainer in the interstage port unless you are sure that debris cannot be drawn into the interstage port.
3.4 Vent options, vent valve connection
and control
To maintain the cleanliness of your vacuum system we recommend that, whenever you switch the pump off, you vent the pump or the vacuum system when the speed of the EXT555H pump is between full rotational speed and 50% of full rotational speed. At and above 50% of full rotational speed the rotor spins fast enough to suppress any hydrocarbon oil from your backing pump. Venting may be accomplished by one of the following methods:
Use a TAV5 or TAV6 solenoid vent valve accessory (see Section 7) in place of the manual vent valve.
Use a TAV5 or TAV6 solenoid vent valve connected to a convenient flange on your vacuum system.
Use an alternative valve connected to your vacuum system.
The maximum rate of pressure rise is given in Figure 3.
When using the manual vent valve supplied you must only open the vent valve when the rotational speed of the EXT555H pump has fallen to 50% of full rotational speed.
If you use a TAV vent valve or other solenoid vent valve, you should only use the vent valve to vent the pump from full speed if the vacuum system has a volume of 20 litres or more. If the system has a volume of less than 20 litres you should incorporate a suitable restrictor (see below and Table 7). Alternatively, if you are using an EXC controller to operate the vent valve, you can configure the valve so that it opens once the pump has reached 50% of full rotational speed.
Do not vent from the backing line as this may lead to contamination. If you vent into your vacuum system, select a point upstream of the pump to prevent oil backstreaming from the backing line.
CAUTION
You must ensure that your vacuum system cannot suddenly be vented to atmosphere when the pump is running a t full r otational s p e e d - if it does so t hen
the EXT555H pump may suffer a catastrophic
failure. As the inlet screen is not designed to
contain pump components in the event of a
catastrophic failure, subsequent damage may result
to the connected vacuum system.
CAUTION
If you vent the pump when it is at full rotational
speed and the rate of pressure rise is too high the
pump bearing life may be reduced.
Vacuum system volume (litres) Orifice diameter (mm)
< 20 < 1.0
< 10 < 0.7
< 5 < 0.5
< 2 < 0.35
Table 7 - Vent restrictor orifice diameter (with atmospheric pressure at the inlet)
Issue A Jun 01
PAGE
14
EXT555H
INSTALLATION
14
Figure 3 - Maximum rate of pressure rise when venting
Jun 01 Issue A
INSTALLATION
PAGE
15
15
If you use the TAV5 or TAV6 vent valve you can control it using an EXC controller or by other methods. Table 7 gives an indication of the appropriate size of orifice to be fitted to the vent valve for given vacuum system volumes in order that the vent rate is kept within the limits given in Figure 3.
Refer to Section 2 for information on vent gas specification.
3.5 Purge gas connection
3.5.1 Connect the purge gas
If you want to supply a purge gas to the pump, fit a vent port adapter (see Section 7) in place of the blank plug (item 6, Figure 4). Connect your gas supply to the purge port. Your purge gas must comply with the specification given in Section 2.
You must limit the purge gas flow rate to the allowed range, also specified in Section 2. To limit the flow rate use a flow controller or a pressure regulator and calibrated flow restrictor. The PRX10 purge restrictor accessory (see Section 7) is suitable for this purpose. Adjust the PRX10 as described in the instruction manual supplied with the accessory.
3.5.2 Recommended purge gas flow
The recommended purge gas flow for typical applications is 25 sccm (0.42 mbar l s
-1
, 42 Pa l s-1). This flow will protect the pump when you pump oxygen in concentrations above 20% by volume.
3.6 Electrical installation
Note: You must electrically bond the EXT555H
pump to earth (ground) using the earth
(ground) screw provided on the pump (item 5,
Figure4) to ensure that the pump complies
with EN61010.
Always make the electrical connections to the pump after the pump has been installed on the vacuum system.
The EXC controller provides the electrical supply to the EXT555H pump through the pump-to­controller cable. Connect and lock the bayonet connectors at the ends of the cable to the mating connectors on the pump and the EXC controller (if applicable). If the cable is disconnected at either end while the pump is operating, the EXC controller output is switched off, which makes the cable safe.
The EXC controller is designed to allow a pumping system to be configured in a variety of ways, from a basic manually operated system to a fully automatic system with remote control. Refer to the instruction manual supplied with the controller to complete the electrical installation.
3.7 Cooling
3.7.1 Introduction
You must use water cooling in any of the following operating conditions:
When backing pressure is high (see Table 5).
When you bake the EXT pump or the vacuum
system close to the pump.
When the ambient temperature is above 35 °C.
When there is high continuous gas throughput (see Table 5).
In all other operating conditions, you can use forced air cooling. If you use forced air cooling you must ensure that there is an adequate supply of cooling air to the pump.
CAUTION
You must cool the pump by forced-air or water
cooling to prevent damage to the bearing.
Issue A Jun 01
PAGE
16
EXT555H
INSTALLATION
16
Figure 4 - Dimensions and features of EXT555H pumps
1. Backing port (NW25)
2. Interstage port - Hi variants (NW25)
3. Electrical supply connector
4. Vent valve
5. Earth bond point
6. Purge plug
Jun 01 Issue A
INSTALLATION
PAGE
17
17
3.7.2 Forced air cooling
An air cooler accessory is available for the EXT555H pump (see Section 7). Fit the air cooler as described in the instructions supplied with it. If you wish to use alternative air cooling, ensure that the flow rate is above 280 m
3 h-1
(80 l s -1, 160 cfm).
3.7.3 Water cooling
A water cooling accessory is available for the EXT555H pump (see Section 7). Fit the water cooler as described in the instructions supplied with it. It is not necessary to use thermal contact grease with this water cooling accessory.
The cooling water must comply with the specification given in Section 2.5. Pipes in the water cooling circuit may become blocked if the cooling water contains too much calcium carbonate or if it contains particulates which are too large. Corrosion of the water cooling circuit may occur if there is too little calcium carbonate or oxygen in the water. Good quality drinking water is usually suitable for water cooling. If in doubt you must check the quality of your cooling water supply and, if necessary, provide treatment and filtration.
CAUTION
To prevent excessive thermal gradients from
developing across the bearing, do not use thermal
transfer paste between the water-cooling
accessory and the turbo-pump body.
CAUTION
Where possible, if you need to pump argon you
should avoid water cooling the pump, in order to
avoid excessive thermal gradients from developing
across the bearing.
If you must water cool while pumping argon (for
example if you are required to bake the pump)
then you must ensure that you limit the inlet
pressure and backing pressure according to the
values given in Table 5.
Connect the cooling water supply to the water cooler as described below. Either of the riffled connectors can be used for the water supply or return connections.
1. Push reinforced hose (approximately 6 mm internal diameter) over the ends of the riffled hose connectors on the water cooler.
2. Attach the hose with strong hose clips and make sure that they are tightened securely.
3. If the pump is mounted off the vertical, ensure that the water cooling plate connectors are positioned below the electrical connector so that any leaking water does not drip onto it.
You must turn off the cooling water supply when you switch off the pump to prevent condensation of vapours inside the pump. EXC controllers can operate a solenoid valve for this purpose. Refer to the controller manual for details.
If you want to remove the pump for maintenance but do not want to break the cooling water circuit, unscrew the fixing screws and remove the water cooler from the pump.
Issue A Jun 01
EXT555H
PAGE
18
18
This page intentionally blank.
Jun 01 Issue A
OPERATION
PAGE
19
19
4OPERATION
4.1 Start up
Use the following procedure to start up a basic manually controlled pumping system with a manual vent valve and an EXC250 or EXC300 controller. Refer to the controller instruction manual.
1. Turn the manual vent valve clockwise to close it.
2. Turn on the cooling water supply (if cooling water is used) or switch on the power supply to the air cooler.
3. Start the backing pump.
4. When the vacuum system pressure is 10 mbar or less, use the controller start/stop button or the appropriate signal command to the controller to start the pump.
5. The pump will accelerate to full operating speed. When this has been reached the 'normal' indicator LED on the controller will light up.
4.2 Stand-by
The EXC250 controller has a 95% speed standby option - this can be used to stop 'beating' between two EXT555H pumps on a system. Refer to the controller manual for details.
WARNING
Do not operate the EXT555H pump unless it is connected to your vacuum system. If you do the pump rotor can cause injury. The pump rotor rotates
at very high speeds and the rotating
blades might not be visible.
The EXC300 also has a standby option, operated using the standby button on the front of the controller. This runs the pump at 70% rotational speed. This can be used to allow system pressure to increase where this suits a particular process. However, you should not run the pump in this mode for long periods of time, as the pump is not designed to be run at this speed for its lifetime.
4.3 Shut-down
Use the procedure below to shut down a basic, manually controlled pumping system with a manual vent valve and an EXC controller. Refer to the EXC controller instruction manual if the backing pump and accessories are controlled by the EXC controller.
1. Close the valve in the backing line connecting the EXT555H pump to the backing pump.
2. Press the start/stop button on the EXC controller to switch off the EXT555H.
3. When the EXT555H speed has fallen to 50% of full rotational speed, turn the manual vent valve anticlockwise to open it. Ensure that the rate of pressure rise does not exceed the allowed rate of pressure rise otherwise you can damage the pump - refer to Sections 3.4 and 2.3.
4. If water cooling is in use, turn off the cooling water supply.
4.4 Safety interlocks and control system
The pump protection and safety interlock features are listed below. Refer to the EXC controller instruction manual for a full description of these features.
The EXC controller monitors the
temperature of the EXC pump and the electrical power consumption of the pump. If the EXC controller detects excessive power consumption or temperature, the rotational speed of the pump rotor is reduced until the power and temperature return to normal.
Issue A Jun 01
PAGE
20
EXT555H
OPERATION
20
If the rotational speed is reduced to 50% of nominal speed, then the pump is stopped immediately (or after a user defined time delay) and the Fail LED on the EXC controller lights.
If pump rotational overspeed is detected by the EXC Controller, the pump is stopped immediately and the FAIL LED on the EXC Controller lights.
If the Fail LED lights, switch off the backing-pump immediately and vent the EXT pump. Once the EXT pump has stopped, rectify the cause of the failure (refer to Section 5.4), press the EXC Controller Start/Stop button to reset the Fail condition, and restart the EXT pump. If the pump is hot, allow sufficient time for it to cool before you restart it.
4.5 Bakeout (conflat only)
If you heat your EXT555H pump (and your vacuum system), you will speed up the degassing process so that the pump will reach ultimate vacuum in the shortest possible time. If you heat the pump, this will also prevent condensation of vapours inside the pump.
You can use the Edwards BX bakeout band to heat the pump (refer to Section 7). Fit the band around the pump, just below the inlet-flange. When you bake the pump or the system, make sure that the temperature of the inlet-flange does not exceed 100 °C.
If you bake your vacuum system and the temperature of the system exceeds 110 °C, you must put a radiation shield between the system and the EXT555H pump. This radiation shield will reduce the heat radiated onto the pump rotor.
CAUTION
When you bake the EXT555H pump to above
70 °C at the inlet-flange, you must cool the pump
by water-cooling, to prevent damage to the
bearing lubricant.
Typically, a bakeout of four hours is long enough to remove water condensation from the pump. However, the bakeout time will depend on the amount of condensation in the pump and the vacuum system, and the ultimate pressure you want to achieve.
Jun 01 Issue A
MAINTENANCE
PAGE
21
21
5 MAINTENANCE
5.1 Introduction
The maintenance operations for the EXT555H Turbomolecular pumps are described in the following sections. The inlet-screen, the WCX water-cooler accessory, the inlet-strainer and inlet­flange seals are available as spares (refer to Section 7). Fit the ISX inlet-screen as described in Section 3.3.1. Fit the WCX water-cooler as described in Section 3.7.3.
5.2 Bearing maintenance
When supplied, the pump contains sufficient lubricant to supply the bearings for life. No routine maintenance is therefore required between bearing replacements. The bearings are not user­serviceable. The bearings will need to be replaced when they reach the end of their service life. This is typically more than 20,000 hours, but may be less; this depends on the type of pumping duty on which the pump is used.
When the bearings need replacement, we recommend that you exchange your pump for a factory reconditioned replacement. Alternatively, you can send your pump to an Edwards Service Centre to have the bearings replaced.
When you return EXT555H pumps to Edwards Service Centres please use the procedure included at the end of this manual.
WARNING
Allow the pump-rotor to stop, then
disconnect the EXC Controller
before you remove the pump from
your vacuum system for maintenance
or fault-finding procedures.
5.3 Clean the pump
If the EXT555H pump is contaminated inside, it may not be possible to achieve the specified ultimate vacuum, or pump-down time may increase. The pump should be returned to a BOC Edwards Service Centre where the pump will be dismantled and cleaned. Use the procedure included at the end of this manual.
You can use any organic solvent to clean the external surfaces of your pump. We recommend that you use non-CFC solvents, such as isopropanol or ethanol. Use a cleaning solution which is suitable for the contaminants on the pump surfaces.
For environmental reasons, keep wastage of cleaning solutions and solvents to a minimum.
5.4 Fault finding
Refer to Table 8 for the possible causes of faults and for the recommended actions to rectify faults. Table 8 is applicable to a basic, manually controlled pumping system with an EXC Controller configured for local (manual) operation.
Note that if you use an EXC Controller configured for remote operation to control the EXT555H pump, or if you use an EXDC Pump Drive Module to control the EXT555H pump, some of the checks and actions in Table 8 may not apply to your system.
CAUTION
Do not attempt to clean any parts of the pump
other than external surfaces. Use of solvents may
damage internal pump components.
WARNING
Clean the external surfaces of the
pump in a well-ventilated location.
When you use cleaning solutions and
solvents to clean the pump, observe
all precautions specified by the
manufacturer. Avoid inhalation of any
particulates which may be present in
the pump.
Issue A Jun 01
PAGE
22
EXT555H
MAINTENANCE
22
Refer to the fault finding section of the instruction manual supplied with your EXC Controller or EXDC Pump Drive Module for further fault finding information.
Symptom Check Action
The pump does not rotate. After pressing start - Fail LED not lit.
Is the EXC Controller power LED lit?
If not, check that the electrical supply is on, check that the switch at the rear of the EXC Controller is on, check the fuse in the rear of the EXC Controller.
If all of the above are OK then the EXC Controller is faulty. Consult Edwards or your supplier.
Is the EXC Controller Start/Stop LED flashing?
If so, check that the correct links are made on the EXC Controller logic interface (refer to the instruction manual supplied with the EXC Controller).
Check that any system interlocks are correctly made (refer to the instruction manual supplied with the EXC Controller).
Check that the pump-to-controller lead is connected.
If all the above checks are OK then consult BOC Edwards or your supplier.
Is the EXC Controller first speed indication LED lit?
If not, the EXC Controller is faulty. If lit, then the EXT pump is faulty. Consult BOC Edwards or your supplier.
The EXC Controller trips into Fail
- at any speed.
Are the system interlocks correctly connected?
Ensure that the system interlocks do not open after the EXT pump has started.
The EXC Controller trips into Fail during the ramp-up and before 50% speed is reached.
Is the inlet pressure too high? Is the backing pressure too high?
If so, reduce the pumping load, or check for a gross leak into the system.
Is the EXT pump running too hot? Increase the cooling or decrease
the gas load. (Refer to Section 2 for maximum inlet pressure and cooling requirements). Check that external heat sources (such as system bakeout heaters) are not excessive.
Table 8 - Fault finding
Jun 01 Issue A
MAINTENANCE
PAGE
23
23
Does the rotor rotate freely? If not, the EXT pump-bearings are
damaged. Consult Edwards or your supplier.
Is the timer set incorrectly? Increase the timer setting (refer to
the instruction manual supplied with the EXC Controller). If the EXC Controller still trips into Fail consult Edwards or your supplier.
The EXC Controller trips into Fail after 50% speed has been reached
- the first two speed LEDs are lit.
Is the pressure too high? If so, reduce the pumping load or
check for a gross leak into the system.
If the high gas load is temporary, configure the EXC Controller to delay the Fail trip on 50% speed and set an appropriate delay time (refer to the instruction manual supplied with the EXC Controller).
Is the EXT pump running too hot? Increase the cooling to the pump
or decrease the gas load.
Does the rotor rotate freely? If not, the EXT pump-bearings are
damaged. Consult Edwards or your supplier.
The EXC Controller trips into Fail
- all the speed LEDs are lit
- Consult BOC Edwards or your supplier.
Ultimate pressure cannot be reached.
Is the pressure limited by water vapour?
Bake the system and pump.
Are any of the vacuum gauges contaminated?
If so, clean or replace them.
Is the pumping speed insufficient (due to poor conductance between the pump and the gauge or too large a chamber)?
Increase the conductance or reduce the volume.
Is the backing pressure > values given in Table 7?
Check for backing line leaks. If the backing pressure is too high, you may need a larger backing-pump.
Is the high-vacuum area of the system contaminated?
If so, clean the high-vacuum system.
Check the rest of your system for leaks and contamination.
If found, clean the contaminated areas and repair the leaks.
Symptom Check Action
Table 8 - Fault finding (continued)
Issue A Jun 01
PAGE
24
EXT555H
MAINTENANCE
24
Remove the pump from the system and test the ultimate pressure of the pump alone (see Section 3 for specification).
If poor, check the pump for contamination and if necessary clean as described in Section 5.3. Leak-check the pump. If the leak rate > 10
-7
mbar l s
-1
(10-5 Pa l s-1) consult BOC Edwards or your supplier.
The EXT is very noisy or there is excessive vibration or both.
Is the pump rotational speed the same as the resonant frequency of the attached system?
If so, change the natural frequency of your system or isolate the pump using flexible bellows.
Is the vibration being transmitted from the rotary pump?
If so, fit flexible bellows or a vibration isolator in the backing line.
Is the noise irregular and getting progressively worse?
If so, a bearing is defective. Switch off the pump and consult Edwards or your supplier.
Is the EXT making a constant high­pitched noise?
If so, the rotor might be out of balance. Consult Edwards or your supplier.
None of the above. - Consult Edwards or your supplier.
Symptom Check Action
Table 8 - Fault finding (continued)
Jun 01 Issue A
STORAGE AND DISPOSAL
PAGE
25
25
6STORAGE AND
DISPOSAL
6.1 Storage
Use the following procedure to store the pump.
1. Place protective covers over the inlet, outlet, interstage (EXT555Hi only), purge and vent ports.
2. Place the pump in its packing materials. For fastest pump-down when the pump is put back into service, seal the pump inside a plastic bag together with a suitable desiccant.
3. Store the pump in cool, dry conditions until required for use. When required, prepare and install the pump as described in Section 3.
4. Avoid long-term storage if possible. When long­term storage is necessary, the pump should be set up and run for at least eight hours every six months.
6.2 Disposal
Dispose of the EXT555H Turbomolecular Pump and any components and accessories safely in accordance with all local and national safety and environmental requirements.
Particular care must be taken with any components which have been contaminated with dangerous process substances.
Take appropriate action to avoid inhalation of any particulates which may be present in the pump.
Do not incinerate the pump. The pump contains phenolic and fluorosilicone materials which can decompose to very dangerous substances when heated to high temperatures.
Issue A Jun 01
EXT555H
PAGE
26
26
This page intentionally blank.
Jun 01 Issue A
SERVICE, SPARES AND ACCESSORIES
PAGE
27
27
7SERVICE, SPARES
AND ACCESSORIES
7.1 Introduction
BOC Edwards products, spares and accessories are available from BOC Edwards companies in Belgium, Brazil, Canada, France, Germany, Hong Kong, Italy, Japan, Korea, Switzerland, United Kingdom, USA and a worldwide network of distributors. The majority of these employ service engineers who have undergone comprehensive BOC Edwards training courses.
Order spare parts and accessories from your nearest BOC Edwards company or distributor. When you order, please state for each part required:
Model and Item Number of your equipment
Serial number (if any)
Item Number and description of the part
7.2 Service
BOC Edwards products are supported by a worldwide network of BOC Edwards Service Centres. Each Service Centre offers a wide range of options including: equipment decontamination; service exchange; repair; rebuild and testing to factory specifications. Equipment which has been serviced, repaired or rebuilt is returned with a full warranty.
Your local Service Centre can also provide BOC Edwards engineers to support on-site maintenance, service or repair of your equipment.
For more information about service options, contact your nearest Service Centre or other BOC Edwards company.
7.3 Spares
7.3.1 ISX inlet-screen
An inlet-screen is fitted to your pump as supplied to prevent damage from the entry of debris into the pump. The Item Numbers of replacement inlet­screens are given below. There are two mesh sizes available - fine and coarse. Select the mesh size appropriate to your requirements. The fine mesh (1 mm hole size) provides better protection against falling objects e.g. fine pieces of filament, small grub screws. The coarse mesh (2 mm hole size) gives better pumping performance. The coarse inlet screen is provided as standard.
Flange size Inlet-screen Item Number
DN160ISO-K/DN160CF Inlet screen (coarse) B580-51-007
Inlet screen (fine) B580-51-008
Table 9 - ISX inlet-screen
Issue A Jun 01
PAGE
28
EXT555H
SERVICE, SPARES AND ACCESSORIES
28
7.3.2 Inlet-strainer (EXT555Hi pump only)
The EXT555Hi pump is supplied with an inlet­strainer for the interstage-port. The Item Number of a replacement inlet-strainer is given below.
Flange size Item Number
NW25ISO-K A223-05-067
Table 10 - Inlet-strainer (EXT555Hi pump only)
Inlet-flange Inlet seal Item Number
DN160ISO-K ISO100 trapped 'O' ring, fluoroelastomer B271-58-172
DN160CF Copper compression gasket (pack of 5) C083-00-003
Table 11 - Inlet-flange seals
7.3.3 Inlet-flange seals
EXT pumps are supplied with an inlet seal. The Item Numbers of replacement seals are given below.
7.4 Accessories
7.4.1 Installation
The accessories available for use with the EXT555H turbomolecular pumps are described in the following Sections. Figure 5 shows how the accessories are fitted to an EXT pump.
7.4.2 EXC controller
The Edwards EXC Controllers provide the facilities necessary for operating a pumping system based on an EXT255H or EXT255Hi pump. The Item Numbers of the EXC Controllers are given below.
Controller Voltage Item Number
EXC250E 90 - 264 V ac D396-36-000
EXC250L 90 - 264 V ac D396-35-000
EXC300 90 - 132/180 - 264 V ac D396-14-000
Table 12 - EXC controller
Jun 01 Issue A
SERVICE, SPARES AND ACCESSORIES
PAGE
29
29
Figure 5 - Installation of EXT555H optional accessories and spares
1. Vibration isolator
2. Bakeout band
3. Inlet flange seal (supplied)
4. Inlet screen (fitted)
5. EXT555H pump
6. TAV solenoid vent valve
7. DN10NW adaptor
8. Manual vent valve (fitted)
9. VRX vent restrictor
10. Vent port (supplied with manual vent valve fitted)
11. WCX water cooling accessory
12. Purge port
13. Purge plug (fitted)
14. DN10NW adaptor
15. PRX purge restrictor
16. Bakeout band position
17. ACX air cooler assembly
Issue A Jun 01
PAGE
30
EXT555H
SERVICE, SPARES AND ACCESSORIES
30
7.4.3 Pump-to-controller cable
You must fit a pump-to-controller cable between an EXC Controller and the EXT pump. A cable is not supplied with the EXT Pump or the EXC Controller (except EXC250L). The following cables are available:
Cable Length Item Number
Pump-to-controller 1 m D396-18-010
Pump-to-controller 3 m D396-18-030
Pump-to-controller 5 m D396-18-050
Table 13 - Pump-to-controller cable
7.4.4 EXDC drive modules
Fit an EXDC Drive Module as an alternative to an EXC Controller and pump-to-controller cable.
Drive module Item Number
EXDC160 D396-41-000
Table 14 - EXDC drive modules
7.4.5 BX bakeout band (conflat only)
A BX bakeout band accelerates the degassing of the pump to enable it to achieve lower pressures. It may also be used to protect the pump from condensation of contaminants. The bakeout bands are available in 110-120 V or 220-240 V versions and may be powered from a rear panel socket on the EXC Controller.
Pump Bakeout band Item Number
EXT555H/Hi DN160CF BX501 (110 V) B580-52-044
BX501 (240 V) B580-52-064
Table 15 - BX bakeout band
Jun 01 Issue A
SERVICE, SPARES AND ACCESSORIES
PAGE
31
31
7.4.6 FL20K foreline trap
The foreline trap minimises oil vapour backstreaming from the backing pump and is recommended where the highest system cleanliness is required.
Foreline trap Item Number
FL20K A133-05-000
Table 16 - FL20K foreline trap
7.4.7 TAV vent-valve and vent-port
adaptor
Two solenoid-operated vent-valves are available for system venting. The valves are 24 V dc, normally­open, and can be driven automatically from the EXC Controller. The solenoid-valve is fitted in place of the manual-valve, or alternatively can be fitted with an adaptor (supplied with the valve) and be used with any suitable NW10 flanged port on your vacuum system.
The vent-port adaptor allows the vent-port or the purge-port to be used with any suitable NW10 fitting: refer to Figure 5.
Product Item Number
TAV5 vent-valve B580-66-010
TAV6 vent-valve B580-66-020
NW10-1/8 inch BSP male adaptor
B580-66-011
Table 17 - TAV vent-valve and vent-port adaptor
7.4.8 ACX air-cooler
An ACX air-cooler can be fitted to the EXT pump. However, please refer to Section 3.7 and to Table 5 to check the suitability of air-cooling in a particular application.
Pump Air-cooler Item Number
EXT555H/Hi ACX555 B580-53-561
Table 18 - ACX air-cooler
Issue A Jun 01
PAGE
32
EXT555H
SERVICE, SPARES AND ACCESSORIES
32
7.4.10 Vibration isolators
In applications where the small amount of vibration generated by the turbomolecular pump is a problem, a vibration isolator can be fitted. The isolator consists of two special flanges separated by a flexible bellows and a rubber, anti-vibration, outer collar. The isolator required depends on the pump inlet-flange size.
Inlet-flange size Item Number
DN160ISO-K B581-25-000
DN160CF-K B581-10-000
Table 20 - Vibration isolators
7.4.11 PRX purge-restrictor
A modified DN10NW centring-ring is available to filter the purge gas and restrict its flow rate to the recommended flow of 25 sccm. The restrictor is suitable for all EXT pumps fitted with a purge-port.
Purge-restrictor Flange size Item Number
PRX10 NW10 B580-65-001
Table 21 - PRX purge-restrictor
7.4.9 WCX water-cooler
If you wish to water cool your pump, you must order the water cooling plate:
Water cooler Item Number
WCX555 B580-67-003
Table 19 - WCX water-cooler
Jun 01 Issue A
SERVICE, SPARES AND ACCESSORIES
PAGE
33
33
7.4.12 VRX vent-restrictor
Use a VRX fixed orifice vent-restrictor to restrict the flow of vent gas into the EXT pump. Refer to Section 3.4 for information on the selection of the correct VRX vent-restrictor.
Vent-restrictor Orifice diameter (mm) Item Number
VRX10 0.1 B580-66-021
VRX20 0.2 B580-66-022
VRX30 0.3 B580-66-023
VRX50 0.5 B580-66-024
VRX70 0.7 B580-66-025
Table 22 - VRX vent-restrictor
Issue A Jun 01
EXT555H
PAGE
34
34
This page intentionally blank.
Return of Edwards Equipment - Procedure
(Form HS1)
Introduction
Before you return your equipment you must warn your supplier if the substances you used (and produced) in the equipment can be dangerous. You must do this to comply with health and safety at work laws.
You must complete the Declaration (HS2) on the next page and send it to your supplier before you dispatch the equipment. If you do not, your supplier will assume that the equipment is dangerous and
he will refuse to accept it. If the Declaration is not completed correctly, there may be a delay in processing your equipment.
Guidelines
Take note of the following guidelines:
Your equipment is 'uncontaminated' if it has not been used or if it has only been used with substances that are not dangerous. Your equipment is 'contaminated' if it has been used with any dangerous substances.
If your equipment has been used with radioactive substances, you must decontaminate it before you return it to your supplier. You must send independent proof of decontamination (for example a certificate of analysis) to your supplier with the Declaration (HS2). Phone your supplier for advice.
We recommend that contaminated equipment is transported in vehicles where the driver does not share the same air space as the equipment.
PROCEDURE
Use the following procedure:
1. Contact your supplier and obtain a Return Authorisation Number for your equipment.
2. Turn to the next page(s), photocopy and then complete the Declaration (HS2).
3. Remove all traces of dangerous gases: pass an inert gas through the equipment and any accessories which will be returned to your supplier. Drain all fluids and lubricants from the equipment and its accessories.
4. Disconnect all accessories from the equipment. Safely dispose of the filter elements from any oil mist filters.
5. Seal up all of the equipment's inlets and outlets (including those where accessories were attached). You may seal the inlets and outlets with blanking flanges or heavy gauge PVC tape.
6. Seal contaminated equipment in a thick polythene bag. If you do not have a polythene bag large enough to contain the equipment, you can use a thick polythene sheet.
7. If the equipment is large, strap the equipment and its accessories to a wooden pallet. Preferably, the pallet should be no larger than 510mm x 915mm (20" x 35"); contact your supplier if you cannot meet this requirement.
8. If the equipment is too small to be strapped to a pallet, pack it in a suitable strong box.
9. If the equipment is contaminated, label the pallet (or box) in accordance with laws covering the transport of dangerous substances.
10. Fax or post a copy of the Declaration (HS2) to your supplier. The Declaration must arrive before the equipment.
11. Give a copy of the Declaration to the carrier. You must tell the carrier if the equipment is contaminated.
12. Seal the original Declaration in a suitable envelope; attach the envelope securely to the outside of the equipment package. WRITE YOUR RETURN AUTHORISATION NUMBER CLEARLY ON
THE OUTSIDE OF THE ENVELOPE OR ON THE OUTSIDE OF THE EQUIPMENT PACKAGE.
Return of Edwards Equipment - Declaration
(Form HS2)
You must: Know about all of the substances which have been used and produced in the equipment before you complete this Declaration
Read the Procedure (HS1) on the previous page before you attempt to complete this Declaration
Contact your supplier to obtain a Return Authorisatio n N um b e r and to obtain advice if you have any quest ions
Send this form to your supplier before you return your equipment
Equipment model ___________________________________________
Serial Number _____________________________________________
Has the equipment been used, tested or operated?
yes
Go to Section 2 no ❏ Go to Section 4
Return Authorisation Number:
FOR SEMICONDUCTOR APPLICATIONS ONLY :
Tool Reference Number ____________________________________
Process __________________________________________________
Failure Date ______________________________________________
Serial Number of Replacement Equipment_____________________________________
SECTION 2: SUBSTANCES IN CONTACT WITH THE EQUIPMENT
Are any of the substances used or produced in the equipment
Radioactive yes
no
Biologically active yes ❏ no
Dangerous to human health and safety? yes ❏ no
If you have answered 'no' to all of these questions, go to Section 4.
SECTION 3: LIST OF SUBSTANCES IN CONTACT WITH THE EQUIPMENT
Substance name Chemical
symbol
Precautions required (for example, use protective
gloves, etc.)
Action required after spillage or
human contact
1
2
3
4
5
6
Your supplier will not accept delivery of any equipment that is contaminated with radioactive substances, unless you:
Decontaminate the equipment
Provide proof of decontamination
YOU MUST CONTACT YOUR SUPPLIER FOR ADVICE
BEFORE YOU RETURN SUCH EQUIPMENT
Reason for return and symptoms of malfunction: _____________________________________________________________________________
_____________________________________________________________________________________________________________________
If you have a warranty claim:
who did you buy the equipment from ? __________________________________________________________________________________
give the supplier's invoice number _____________________________________________________________________________________
SECTION 5: DECLARATION
Print your name: __________________________________Print your job title: ______________________________________________
Print your organisation: ________________________________________________________________________________________________
Print your address: ________________________________________________________________________________________________
________________________________________________________________________________________________
Telephone number: _________________________________ Date of equipment delivery: ________________________________________
I have made reasonable enquiry and I have supplied accurate information in this Declaration. I have not withheld any information. I have followed the Return of BOC Edwards Equipment Procedure (HS1) on the previous page.
Signed: _____________________________________________________ Date ____________________________________________________
SECTION 1: EQUIPMENT
SECTION 4: RETURN INFORMATION
Corporate Headquarters
BOC Edwards
Manor Royal Crawley West Sussex, RH10 2LW UNITED KINGDOM
+(44) 1293 528844 Fax: +(44) 1293 533453
Asia Headquarters
BOC Edwards (Asia)
2605 Shun Tak Centre, West Wing 200 Connaught Road Central Hong Kong S.A.R
+(852) 2796 9111 Fax: +(852) 2796 9095
CHINA Shanghai +(86) 21 5899 0272
CHINA Tianjin +(86) 22 2834 1981
TAIWAN, R.O.C. Toufen +(886) (0)37 611422
Fax: +(886) (0)37 611401
SOUTH EAST ASIA Singapore +(65) 546 8408
Fax: +(65) 546 8407
Europe Headquarters
BOC Edwards
Manor Royal Crawley West Sussex, RH10 2LW UNITED KINGDOM
+(44) 1293 528844 Fax: +(44) 1293 533453
UK Guildford+(44) 1483 579857
Fax: +(44) 1483 505211
UK Cumbernauld +(44) 1236 730575
BELGIUM Brussels +(32) 2 363 00 30
Fax: +(32) 2 363 00 64
FRANCE Paris +(33) 1 47 98 24 01
Fax: +(33) 1 47 98 44 54
GERMANY Munich +(49) 89 99 19 18 0
Fax: +(49) 89 99 19 18 99
ITALY Milan +(39) 2 48 4471
Fax: +(39) 2 48 401638
ISRAEL Qiryat Gat +(972) 7 681 0633
Japan Headquarters
BOC Edwards
Shuwa Shiba Park Building A-3F 2-4-1 Shibakoen, Minato-ku Tokyo, 105-0011 JAPAN
Tel: +(81) (0) 3 5470 6530 Fax: +(81) (0) 3 5470 6521
OSAKA +(81) (0) 6 6384 7052
Fax: +(81) (0) 6 6384 7504
KYUSHU +(81) (0) 96 326 7300
Fax: +(81) (0) 96 326 7302
SENDAI +(81) (0) 22 373 8525
Fax: +(81) (0) 22 373 9636
Electronic Gases
OSAKA +(81) 3 3434 6789
Fax: +(81) 3 5472 8728
Korea Headquarters
Songwon Edwards Ltd
625-7 Upsong-dong Chunan City Chungchong Nam-do KOREA
+(82) 417 554 7070 Fax: +(82) 417 554 7300
SEOUL +(82) 2 501 7070
Americas USA Headquarters
BOC Edwards
One Edwards Park 301 Ballardvale Street Wilmington, MA 01887 USA
+(1) 978 658 5410 Fax: +(1) 978 658 7969
TOLL FREE (USA only): 800 848 9800
ARIZONA Tempe +(1) 602 777 7007
Fax: +(1) 602 777 2202
ARIZONA Phoenix +(1) 602 777 7007
Fax: +(1) 602 777 2244
CALIFORNIA Santa Clara +(1) 408 496 1177
Fax: +(1) 408 496 1188
TEXAS Austin +(1) 512 491 6622
Fax: +(1) 512 389 3890
TEXAS Richardson +(1) 972 669 9386
Fax: +(1) 972 669 8054
BRAZIL Sao Paulo +(55) 11 8580377
Fax: +(55) 11 2652766
http://www.bocedwards.com
BOC Edwards is a trading name used by affiliate companies of the BOC Group plc. The stripe symbol is a trademark of the BOC Group plc.
Loading...