• 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
• NEMA 4X, IP65 Front
• Universal 85-265 VAC,or 12/24 VDC Input Power Models
• Large Dual-Line 6-Digit Display, 0.60” & 0.46”
• Dual-Scale for some Level Applications - Single Input
• Sunlight Readable Display Models
• Isolated 24 VDC Transmitter Power Supply
• Signal Input Conditioning for Flow & Round Horizontal Tanks
• Programmable Display & Function Keys
• 32-Point, Square Root, or Exponential Linearization
• Multi-Pump Alternation Control
• 2 or 4 Relays + Isolated 4-20 mA Output Options
• External 4-Relay & Digital I/O Expansion Modules
• USB, RS-232, RS-485 Serial Communication Options
• Tare Function
• Modbus® RTU Communication Protocol Standard
• Configure, Monitor, and Datalog from a PC with
Free BULLDOG Pro Software
Model BD300 Analog Input Process Meter Instruction Manual
DISCLAIMER:
The information contained in this document is subject to change without notice. Blue Ribbon Corp. makes no representations
or warranties with respect to the contents herein adn specifically disclaims any implied warranties of merchantability or
fitness for a particular purpose.
CAUTION:
instructions prior to installation
and operation of the meter.
R
ead complete
WARNING:
Risk of
electric shock or
personal injury.
This product is not recommended for life support
applications or applications where malfunctioning
could result in personal injury or property loss.
Anyone using this product for such applications does
WARNING!
so at his/her own risk. Blue Ribbon Corporation
shall not be held liable for damages resulting from
such improper use.
Limited Warranty
Blue Ribbon Corporation warrants this product against defects in material or
workmanship for the specified period under “Specifications” from the date of
shipment from the factory. Blue Ribbon’s liability under this limited warranty shall
not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
All trademarks mentioned in this document are the property of their respective
Figure 21. Acknowledge Relays w/Function Key or Digital Input ................. 57
Figure 22. 1/8 DIN Panel Cutout Template .................................................... 97
Model BD300 Analog Input Process Meter - Instruction Manual
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
DISCLAIMER:
The information contained in this document is subject to change without notice.
Blue Ribbon Corp. makes no representations or warranties with respect to the contents herein adn specifically disclaims any implied warranties of merchantability or
fitness for a particular purpose.
1. IntroductIon
The BULLDOG BD300 is a multi-purpose, easy to use digital process meter ideal for
level, flow rate, temperature, or pressure transmitter applications. It accepts current
and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the front panel buttons can be
custom-programmed for a specific operation. The analog input can be scaled to
display the process in two different scales; for example the main display could indicate
level in feet and the second display could indicate the volume in gallons.
The basic model includes an isolated 24 VDC transmitter power supply that can be
used to power the input transmitter or other devices. An additional isolated 24 VDC
power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded BD300 meter has the following: four SPDT relays, 4-20 mA output, and two
24 VDC power supplies. The BD300 capabilities may be enhanced by adding the
following external expansion modules: four SPST relays (creating an eight-relay process
meter), two digital I/O modules with four inputs and four outputs each, and USB, RS-232
or RS-485 communication adapters.
The eight relays can be used for alarm indication or process control applications, such as
pump alternation control. The 4-20 mA isolated output, Modbus RTU serial
communications, and digital I/O options make the BD300 an excellent addition to any
system.
1
Model BD300 Analog Input Process Meter Instruction Manual
2. orderIng InformatIon
2.1. Standard Models
85-265 VAC Model12/24 VDCOptions Installed
BD300-10BD300-20No Options
BD300-12BD300-222 Relays
BD300-11BD300-214-20 mA Output
BD300-14BD300-244 Relays
BD300-13BD300-232 Relays & 4-20 mA Output
BD300-15BD300-254 Relays & 4-20 mA Output
Model BD300 Analog Input Process Meter Instruction Manual
2.3. Accessories
ModelDescription
BDRMKDIN rail mounting kit for two expansion modules
BDXM4 SPST (Form A) relays
BDIO4 Digital inputs & 4 digital outputs (2 may be connected)
BDCCCMeter copy cable
BD232SARS-232 serial adapter
BD422SARS-485 serial adapter
BDI232-422/485RS-232 to RS-422/485 isolated converter
BDN232-422/485RS-232 to RS-422/485 non-isolated converter
BDUSBSAUSB serial adapter
BDNUSB-232USB to RS-232 non-isolated converter
BDIUSB-422/485USB to RS-422/485 isolated converter
BDNUSB-422/485USB to RS-422/485 non-isolated converter
BD6901Suppressor (snubber): 0.01 µF/470 Ω, 250 VAC
Return to Table of Contents
2.4. Enclosures
ModelDescription
BD2811 Meter Plastic NEMA 4X Enclosure
BD2822 Meter Plastic NEMA 4X Enclosure
3
Model BD300 Analog Input Process Meter Instruction Manual
3. SpecIfIcatIonS
Except where noted, all specifications apply to operation at +25 °C (+77 °F).
NORMAL MODE REJECTION
ISOLATION
OVERVOLTAGE CATEGORY
Main display: 0.60” (15mm) high, red LEDs
Second display: 0.46” (12mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
Eight user selectable intensity levels
5/second (200 ms)
Display flashes 999999
Display flashes -99999
The main (Big) and small (Little) displays may be assigned to PV1, PV2, PCT, d
r4-u, d gross, d-nt-g, max/min max & min, set points, units (small display only, or
Modbus input.
Four front panel buttons, digital inputs, PC and BULLDOG Pro software, Modbus
registers, or cloning using Copy function.
Programmable from 2 to 199 (0 will disable filter)
Programmable from 0.1 to 99.9% of calibrated span
All ranges are calibrated at the factory. Recalibration is recommended at least every
12 months.
Max/Min readings reached by the process are stored until reset by the user or until
power to the meter is turned off.
Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs, and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs
85-265 VAC 50/60 Hz, 90-625 VDC, 20 W max or jumper selectable 12/24 VDC
±10%, 15 W max
Terminals P+ & P-: 24 VDC ± 10%. 12/24 VDC powered models selectable for
24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200
mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5
or 10 VDC supply.
All programmed settings are stored in non-volatile memory for a minimum of ten
years if power is lost.
Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Greater than 60 dB at 50/60 Hz
4 kV input/output-to-power line 500 V input-to-output or output-to-P+ supply
Installation Overvoltage Category II: Local level with smaller transient overvoltages
than Installation Overvoltage Category III.
4
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
SLAVE ID
BAUD RATE
TRANSMIT TIME DELAY
DATA
PARITY
BYTE-TO-BYTE TIMEOUT
TURN AROUND DELAY
Note: Refer to the BULLDOG ModBUS Register Tables located at www. blueribboncorp.com for details.
1-247 (Meter address)
300 – 19,200 bps
Programmable between 0 and 199 ms
8 bit (1 start bit, 1 or 2 stop bits)
Even, Odd, or None with 1 or 2 stop bits
0.01 – 2.54 second
Less than 2 ms (fixed)
8
Model BD300 Analog Input Process Meter Instruction Manual
3.6. COMPLIANCE INFORMATION
Safety
Return to Table of Contents
UL & c-UL LISTED
UL FILE NUMBER
FRONT PANEL
LOW VOLTAGE DIRECTIVE
USA & Canada
UL 508 Industrial Control Equipment
E350669
UL TYPE 4X, NEMA 4X, IP65; panel gasket provided
EN61010-1:2001
Safety requirements for measurement, control, and laboratory use
3.7. ELECTROMAGNETIC COMPATIBILITY
EMISSIONS
Radiated EmissionsClass A
AC Mains
Conducted
Emissions
IMMUNITY
RFI - Amplitude
Modulated
Electrical Fast
Transients
Electrostatic
Discharge
RFI - Conducted10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge±2kV Common, ±1kV Differential
Surge1KV (CM)
Power-Frequency
Magnetic Field
Voltage Dips40%V for 5 & 50 periods
Voltage
Interruptions
EN 55022:2006/A1:2007
Class A
EN61326-1:2006
Measurement, control, and laboratory equipment
EN61000-6-2:2005
EMC heavy industrial generic immunity standard
80 - 1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1kHz)
±2kV AC mains, ±1kV other
±4kV AC contact, ±8kV air
3 A/m 70%V for 0.5 period
70%V for 25 periods
<5%V for 250 periods
9
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
NOTE:
Testing was conducted on BD300 meters installed through the covers of
grounded metal enclosures with cable shields grounded at the point of
entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.blueribboncorp.com
4. Safety InformatIon
CAUTION:
instructions prior to installation
and operation of the meter.
R
ead complete
WARNING:
Risk of
electric shock or
personal injury.
Hazardous voltages exist within enclosure.
Installation and service should be performed only by
WARNING!
trained service personnel.
5. InStallatIon
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC
and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see
page 13.
5.1. Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages,
if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for
assistance.
10
Model BD300 Analog Input Process Meter Instruction Manual
5.2. Panel Mounting Instructions
Prepare a standard ⅛ DIN panel cutout – 3.622” x 1.772” (92 mm x 45 mm).
Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0” (152 mm) behind the panel for wiring. Panel thickness: 0.04” - 0.25” (1.0 mm - 6.4 mm). Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼” (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
Insert meter into the panel cutout. Install mounting brackets and tighten the screws against the panel. To achieve
a proper seal, tighten the mounting bracket screws evenly until meter is snug
to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
Return to Table of Contents
11
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
Mounting Dimensions
12
Model BD300 Analog Input Process Meter Instruction Manual
5.3. Conguration for 12 or 24 VDC Power Option
Do not exceed voltage rating of the selected
configuration.
WARNING!
Meters equipped with the 12/24 VDC power option are shipped
from the factory ready to operate from 24 VDC.
Return to Table of Contents
To configure the meter for 12 VDC power.
1.
Remove all the connectors.
2.
Unscrew the back cover.
3.
Slide the back cover about 1 inch.
4.
Configure the J9 jumper, located behind the power
connector, for 12 V as shown below.
13
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.4. Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the
factory configured to provided 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured
accordingly.
To access the voltage selection jumper:
1.
Remove all the wiring connectors.
2.
Unscrew the back cover.
3.
Slide out the back cover by about 1 inch.
4.
Configure the J4 jumper, located behind the input signal connector,
for the desired excitation voltage shown.
5.5. Connections
All connections are made to removable screw terminal connectors located at the rear of the
meter.
Use copper wire with 60 °C or 60/75 °C insulation for all line voltage
connections. Observe all safety regulations. Electrical writing should be
performed in accordance with all applicable national, state, and local
codes to prevent damage to the meter and ensure personnel safety.
14
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.6. Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with
requested configuration.
Do not connect any equipment other than Blue Ribbon’s
expansion modules, cables, or meters to the RJ45 M-LINK
connector. Otherwise damage will occur to the equipment
WARNING!
and the meter.
5.7. Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 7 on page
19. The meter will operate regardless of DC polarity connection. The + and – symbols are only
a suggested wiring convention.
15
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.8. Signal Connections
Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 7. The COM
(common) terminal is the return for the 4-20 mA and the ±10 V input signals.
5.9. Current and Voltage Connections
The following figures show examples of current and voltage connections.
There are no switches or jumpers to set up for current and voltage inputs. Setup and programming is performed through the front panel buttons.
The current input is protected against current overload by a resettable fuse. The display may or
may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condition, and automatically
resets itself when the fault condition is removed.
16
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
The meter is capable of accepting any voltage from -10 VDC to +10 VDC
5.10. ModBUS RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 7.
For interfacing to the BULLDOG, use the BD232SA for RS-232, the BD422SA for RS-485, or the
e.g.
BDUSBSA for the USB. The same port is used for interfacing with all expansion modules (
external relays, digital I/O).
Using the BDCCC meter copy cable for meter-to-meter interfacing for cloning purposes (
i.e.
copying settings from one meter to other meters).
5.11. Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY 4 on Figure
7. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC)
contacts of the corresponding relay. The relays’ C terminals should not be confused with the
COM (common) terminal of the INPUT SIGNAL connector.
17
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.12. Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to
prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the
relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled
by the user or purchased as complete assemblies. Refer to the following circuits for RC network
assembly and installation:
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contracts
Notes:
1.
Use capacitors rated for 250 VAC
2.
RC networks may affect load release time of solenoid loads. Check to confirm proper
operation.
3.
Install the RC network at the meter’s relay screw terminals. An RC network may also
be installed across the load. Experiment for best results.
18
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.13. RC Networks Available from Blue Ribbon Corp
RC networks are available from Blue Ribbon Corp and should be applied to each relay contact
switching an inductive load. Part number: BD6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
5.14. F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input is connected with a normally open
contact across F4 and COM, or with an active low signal applied to F4.
5.15. 4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled
MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
19
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.16. Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other
devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the
return.
5.17. External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules BDXM & BDIO are connected to the meter
using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion
modules are identical and interchangeable; they are used to connect additional modules to the
system.
Note: The jumper located between the RJ45 connectors of the BDIO must be removed on the
second digital I/O module in order for the system to recognize it as module #2.
WARNING!
Do not connect ar disconnect the expansion modules with
the power on!
More detailed instructions are provided each optional
expansion module.
20
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
5.18. Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one or more alarm/control relays for
use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock
relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page 61).
In one example, dry interlock contacts are connected in series to one digital input which will be
used to force on (energize) the assigned interlock power relay when all interlock contacts are
closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay
would be wired in-series with the load (N/O contact). See below.
21
Model BD300 Analog Input Process Meter Instruction Manual
6. Setup and programmIng
The meter is factory calibrated prior to
shipment to read in milliamps and volts
depending on the input selection. The
calibration equipment is certified to NIST
standards.
Overview
Return to Table of Contents
There are no jumpers to set for the meter input selection. Setup and programming is done
through the front panel buttons. After power and input signal connections have been completed
and verified, apply power to the meter.
22
Model BD300 Analog Input Process Meter Instruction Manual
6.1. Front Panel Buttons and Status LED Indicators
Return to Table of Contents
Button
Description
Symbol
Menu
Right Arrow/F1
Up Arrow/F2
Enter/F3
Note:
F4 is a digital input. Alarms 5-8
are enabled when relay expansion
module is installed.
LEDStatus
1-8Alarm 1-8 Indicator
Flashing: Relay in
1-8 M
manual control mode
TFlashing: Tare
Flashing: Relay
1-8
interlock switch open
Note:
LEDs for relays in manual mode flash
with the “M” LED every 10 seconds.
“M” flashing by intself indicates Aout -
manual control is used.
23
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
• Press the Menu button to enter or exit the Programming Mode at any time.
• Press the Right arrow button to move to the next digit during digit or decimal point
programming.
• Press or hold the Up arrow button to scroll through the menus, decimal point, or to
increment the value of a digit.
• Press the Enter button to access a menu or to accept a setting.
• Press and hold the Menu button for three seconds to access the advanced features of
the meter.
6.2. Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation.
The following table shows the main menu functions and messages in the order they appear in
the menu.
DisplayParameterAction/Setting Description
SEtuP
InPut
mA
UoLt
d-SCAL
units
dEc Pt
PU 1
PU 2
ProG
Setup
Input
4-20 mA
0-10 VDC
Dual-scale
Units
Decimal Point
PV1
PV2
Program
Enter
Setup
menu
Enter
Input
selection menu
Set meter for 4-20 mA Input
Set meter for ±10 VDC input
Press Enter to select dual-scale display for
some level applications (Select Yes or No)
Select the display units/tags
Set decimal point
PV1 decimal point (Level)
PV2 decimal point (Level)
Enter the
Program
menu
SCALE
SCAL 1
SCAL 2
Scale
Scale 1
Scale 2
Enter the
Enter the
Enter the
24
Scale
menu
Scale
Menu for PV1
Scale
menue for PV2
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting Description
Return to Table of Contents
CAL
InP 1
di5 1
InP 2
dis 2
Error
dSPLAy
biG
LittlE
d-Inty
rELAY
Calibrate
Input 1
Display 1
Input 2
Display 2
Error
Display
Big Display
Little Display
Display Intensity
Relay
Enter the
Calibrate input 1 signal or program input
1 value
Program display 1 value
Calibrate input 2 signal or program input 2
value (up to 32 points)
Program display 2 value (up to 32 points)
Error, calibration not successful, check sig-
nal or programmed value
Enter the
Press Enter to assign the Main display pa-
rameter (default: PV)
Press Enter to assign the small display pa-
rameter (default: engineering units)
Set display intensity level from 1 to 8
Enter the
Calibration
Display
Relay
menu
menu
menu
rLy 1
Act 1
Auto
A-mAn
LAtCH
Lt-Clr
AltErn
SamPL
OFF
SEt 1
Relay 1
Action 1
Automatic
Auto-manual
Latching
Latching-cleared
Alternate
Sampling
Off
Set 1
Relay 1 setup
Set relay 1 action
Set relay for automatic reset
Set relay for automatic & manual reset any
time
Set relay for latching operation
Set relay for latching operation with man-
ual reset only after alarm condition has
cleared
Set relay for pump alternation control
Set relay for sampling operation
Disable relay and front panel status LED
(Select Off to enable Interlock feature)
Program set point 1
25
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting Description
Return to Table of Contents
rSt 1
rly 2
FAiLSF
FLs 1
on
off
FLS 2
dELAy
dly 1
On 1
OFF 1
Reset 1
Relay 2
Fail-safe
Fail-safe 1
On
Off
Fail-safe 2
Delay
Delay 1
On 1
Off 1
Program reset point 1
Relays 2-8 setup
Note: Relays 5-8 are shown, only if
expansion relay module is installed.
Enter
Fail-safe
Set relay 1 fail-safe operation
Enable fail-safe operation
Disable fail-safe operation
Set relays 2-8 fail-safe operation
Enter relay
Enter relay 1 time delay setup
Set relay 1 On time delay
Set relay 1 Off time delay
menu
Time Delay
menu
dly 2
brEAK
iGnorE
On
Off
Aout
di5 1
Out 1
diS 2
Out 2
Delay 2
Loop Break
Ignore
On
Off
Analog Output
Display 1
Output 1
Display 2
Output 2
Enter relays 2-8 time delay setup
Set relay condition if loop break detected
Ignore loop break condition
(Processed as low signal condition)
Relay goes to alarm condition when loop
break is detected
Relay goes to non-alarm condition when
loop break is detected
Enter the
Program display 1 value
Program output 1 value (e.g. 4.000 mA)
Program display 2 value
Program output 2 value (e.g. 20.000 mA)
26
Analog Output
scaling menu
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting Description
Return to Table of Contents
rESEt
rSt Hi
rSt Lo
rSt HL
rSt tr
ContrL
Auto
mAn
PASS
PASS 1
PASS 2
Reset
Reset High
Reset Low
Reset High & Low
Reset Tare
Control
Automatic
Manual
Password
Password 1
Password 2
Press Enter to access the
Press Enter to reset max display
Press Enter to reset min display
Press Enter to reset max & min displays
Reset Tare
Enter
Control
Press Enter to set meter for automatic
operation
Press Enter to manually control relays or
analog output operation
Enter the
Set or enter Password 1
Set or enter Password 2
men
Password
menu
Reset
menu
PASS 3
unLoc
Locd
999999
-99999
Password 3
Unlocked
Locked
Flashing
Set or enter Password 3
Program password to lock meter
Enter password to unlock meter
Over/under range condition
27
Model BD300 Analog Input Process Meter Instruction Manual
6.3. Main Menu
Return to Table of Contents
The main menu consists of the most commonly used functions:
Setup, Reset, Control,
Password.
• Press Menu button to enter Programming Mode then press the Up arrow button to
scroll main menu.
and
• Press Menu, at any time, to exit and return to Run Mode. Changes made to settings
prior to pressing Enter are not saved.
• Changes to the settings are saved to memory only after pressing Enter/F3.
• The display moves to the next menu every time a setting is accepted by pressing
Enter/F3.
28
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.4. Setting Numeric Values
The numeric values are set using the Right and Up arrow buttons.
• Press Right arrow to Select next digit and Up arrow to increment digit value.
The digit being changed is displayed brighter than the rest.
• Press and hold up arrow to auto-increment the display value.
• Press the enter button, at any time, to accept a setting, or Menu button to exit without
saving changes.
29
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5. Setting Up the Meter (SEtuP)
The
Setup
menu is used to select:
1. Input signal the meter will accept for Channel A and Channel B
2. Decimal point position A, B, and C
3. Units for A, B, and C
4. Program the meter using the Scale or Calibrate functions
5. Display parameter and intensity
6. Relay assignment and operation
7. 4-20 mA analog output scaling
Press the Enter button to access any menu or press Up arrow button to scroll through choices.
Press the Menu button to exit at any time.
Note:
Use the d-SCAL selection
to activate the dual-scale
level feature - PV1 & PV2
(see introduction on page 1).
Set d-SCAL to “No” if both
displays are to be used for
anything other than PV1 or PV2.
Note:
Scal 1 & Scal 2 are
dislayed instead of
Scale if d-SCAL is
selected under the
Setup Input menu.
They correspond to
the PV1 & PV2 scales.
30
Model BD300 Analog Input Process Meter Instruction Manual
6.5.1. Setting the Input Signal (InPut)
Return to Table of Contents
Enter the
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from –10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or ±10 VDC signals.
After selecting mA or
Selecting
(unitS) menus to be used to scale the same input in two different scales for PV1 & PV2.
Input
menu to set up the meter to display current (mA) or voltage (Uolt) inputs.
Volt
input,
“Yes”
enables the dual-sale feature, which allows for the Scale (SCALE) and Units
d-SCAL
is displayed; press Enter to select
“Yes”
or
“No”
.
Set d-SCAL to no if both displays are to be used for anything other than PV1 & PV2.
31
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.2. Setting the Input Units or Custom Tags (units)
Enter the input unit or custom tag that will be displayed if d unit is selected as the little display parameters. See the flow chart on page 43 to access the display menu to show the unit or
tag on the little display. The engineering units or custom legends can be set using the following
7-segment character set:
DisplayCharacter
D
1
2
3
4
5
6
7
8
9
A
b
C
c
d
0
1
2
3
4
5
6
7
8
9
A
b
C
c
d
DisplayCharacter
K
L
m
n
O
o
P
q
r
s
t
u
U
w
X
K
L
m
n
O
o
P
q
r
S
t
u
V
w
X
E
F
G
g
H
h
I
i
J
Notes:
Degree symbol represented by (<) if programming with BULLDOG Pro. The letters “m” and
“w” use two 7-segment LEDs each; when selected, the characters to the right are shifted one
position.
Press and hold up arrow to auto-scroll the characters in the display.
E
F
G
g
H
h
Y
Z
-
/
[
]
I
i
J
32
=
o
Y
Z
/
(
)
=
Degree (<)
Space
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.3. Setting the Decimal Point (dEc Pt)
The decimal point may be set with up to five decimal places or with no decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right until no decimal point is
displayed, and then it moves to the leftmost position. Pressing the Up arrow moves the decimal
point one place to the left.
If the dual-scale level feature is selected, the decimal point selections for PV1 & PV2 are
enabled.
33
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.4. Programming the Meter (ProG)
It is very important to read the following information before proceeding to program the
meter:
• The meter is factory calibrated prior to shipment to read in milliamps and volts
depending on the input selection. The calibration equipment is certified to NIST
standards.
• Use the
source is not needed to scale the meter.
• Use the
• The BD300 is a single input meter with dual-scale capability.
The
Program
Scale
menu to scale the process input (e.g. 4-20 mA). A calibrated signal
Calibrate
menu contains the
menu to apply a signal from a calibrator or a flowmeter.
Scale
and the
Calibrate
menus.
Note: The Scale and Calibrate functions are exclusive of each other. The meter uses the last
function programmed. Only one of these methods can b e employed at a time. The Scale and
Calibrate functions can use up to 32 points (default is 2). The number of points should be set in
the Advanced menu under the Multi-Point Linearization
(LinEAr)
menu selection prior to scaling
and calibration of the meter, see page 73 for details.
If the dual-scale level feature is selected in the
enabled for PV1 & PV2 respectively.
The process input may be calibrated or scaled to any display value within the range of the
meter.
6.5.4.1. Program Menu for Single Scale Process
6.5.4.2. Program Menu for Dual-Scale Level Applications
Setup
menu, the
Scale 1
and
Scale 2
menus are
Additional parameters, not needed for most applications, are programmed in the
Features
menu; see
Advanced Features Menu
Advanced
, page67.
34
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.4.3. Multi-point Calibration & Scaling
The meter is set up at the factory for 2-point linear calibration. The number of points for multi-
point calibration/scaling is set up in the Advanced Features menu. Up to 32 linearization points
may be selected for PV1 and up to 8 linearization points may be selected for PV2. See page 73
for details.
6.5.4.4. BULLDOG Pro Software
The meter can also be programmed using the PC-based BULLDOG Pro Software available for
free download at www.blueribboncorp.com.
Data logging for one meter at a time is available with BULLDOG Pro Software. More advanced
data acquisition may be accomplished b y using any ModBUS RTU compliant software.
In order to program the meter using a computer, the meter must be connected using a USB,
RS-232, or RS-485 serial adapter, see ORDERING INFORMATION on page 7 for details.
6.5.4.5. Scaling the Meter (
SCALE)
The process input (4-20 mA, ± VDC) can be scaled to display the process variable in
engineering units.
A signal source is not needed to scale the meter; simply program the inputs and corresponding
display values.
35
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.4.6. Dual-Scale for Level Application
The analog input can be displayed in two different scales, by enabling the dual-scale feature
(d-SCAL) in the
To enable the dual-scale feature for some level applications, you must select d-SCAL in the Input
selection menu.
Setup-Input
menu, see page 30.
36
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.4.7. Error Message (Error)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed the meter reverts to the input prior to the failure during
calibration or scaling and to input 1 during internal calibration, allowing the appropriate input
signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1. Input signal is not connected to the proper terminals or it is connected backwards.
2. Wrong signal selection in
3. Minimum input span requirements not maintained.
4. Input 1 signal inadvertently applied to calibrate input 2.
6.5.4.8. Minimum Input Span
Setup
menu.
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
37
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.5.4.9. Calibrating the Meter with External Source (CAL)
Note: To scale the meter without a signal
source refer to Scaling the Meter (SCALE),
page 38.
The meter can be calibrated to display the process variable in engineering units by applying the
appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter.
Warm up the meter for at least 15 minutes
before performing calibration to ensure
specified accuracy.
38
Model BD300 Analog Input Process Meter Instruction Manual
6.5.5. Setting the Display Parameter & Intensity (dSPLAY)
The main display (biG) can be programmed to display:
1. Process value 1 (PV1)
2. Process value 2 (PV2)
3. Percent of PV1 (PCT)
4. Relay set points
5. Max & min values
6. ModBUS input
7. Display reading and units
8. Display gross
9. Toggle net & gross
The small display (LittLE) can be programmed to display:
1. Unit
2. Process value 1 (PV1)
3. Process value 2 (PV2)
4. Percent of PV1) (PCT)
5. Relay set points
6. Max & min values
7. Engineering units or custom legends
8. ModBUS input
9. Off (no display)
10. Toggle reading and units
11. Display gross
12. Toggle net/gross
Return to Table of Contents
Display Intensity: The meter has eight display intensity levels to give the best performance under various lighting conditions. Select intensity 8 for outdoor applications. The default intensity
settings is 8.
39
Model BD300 Analog Input Process Meter Instruction Manual
6.5.6. Display Setup Menu
Return to Table of Contents
After setting up the input and display, press the Menu button to exit programming and skip the
rest of the setup menu. Press the Menu button again and the Up arrow to reach the Program
Menu and complete the scaling or calibration of the meter.
40
Model BD300 Analog Input Process Meter Instruction Manual
6.6. Setting the Relay Operation (rELAy)
The menu is used to set up the operation of the relays.
During setup, the relays do not follow the input and
they will remain in the state found prior to entering
the Relay menu.
CAUTION!
1. Relay Action
a. Automatic reset only (non-latching)
b. Latching (manual reset only)
c. Latching with Clear (manual reset only after alarm condition has cleared)
d. Pump alternation control (automatic reset only)
e. Sampling (the relay is activated for a user-specified time)
f. Off (relay state controlled by Interlock feature)
2. Set Point
3. Reset Point
4. Fail-safe Operation
a. On (enabled)
b. Off (disabled)
5. Time Delay
a. On Delay (0-999.9 seconds)
b. Off Delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
Return to Table of Contents
41
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.6.1. Setting the Relay Action
Operation of the relays is programmed in the Action menu. The relays may be set up for any of
the following modes of operation:
Automatic reset (non-latching)
8. Automatic + manual reset at any time (non-latching)
9. Latching (manual reset only, at any time)
10. Latching with Clear (manual reset only after alarm condition has cleared)
11. Pump alternation control (automatic reset only)
12. Sampling (the relay is activated for a user-specified time)
13. Off (relay state controlled by Interlock feature)
The following graphic shows relay 1 action setup; relay 2-8 are set up in a similar fashion.
42
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.6.2. Programming Set and Reset Points
High alarm indication: program set point above reset point.
Low alarm indication: program set point below resent point.
The deadband is determined by the difference between set and rest points. Minimum deadband
is one display count. If the set and reset points are programmed with the same value, the relay
will reset one count below the set point.
Note: Changes are not saved until the reset point has been accepted.
6.6.3. Setting Fail-Safe Operation
In fail-safe mode of operation, the relay coil is energized when the process variable is within
safe limits and the relay coil is de-energized when the alarm conditions exists. The fail-safe
operation is set independently for each relay. Select on to enable or oFF to disable fail-safe
operation.
6.6.4. Programming Time Delay
On
and
Off
The
The relays will transfer only after the condition has been maintained for the corresponding time
delay.
The On time delay is associated with the set point.
The
Off
time delay is associated with the reset point.
time delays may be programmed for each relay between 0 and 999.9 seconds.
43
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.6.5. Relay Action for Loss of 4-20 mA Input (Loop Break)
The look break feature is associated with the 4-20 mA input. Each relay may be programmed to
go to one of the following conditions when the meter detects the loss of the input signal (i.e. <
0.005 mA):
Turn On (Go to alarm condition).
14. Turn
15. Ignore (Processed as a low signal condition)
Note: This is not a true loop break condition; if the signal drops below 0.005 mA, it is
interpreted as a “loop break” condition.
6.7. Relay and Alarm Operation Diagrams
The following graphs illustrate the operation of the relays, status LEDs, and ACK button.
Off
(Go to non-alarm condition)
6.7.1. High Alarm Operation (Set > Reset)
For Manual reset mode, ACK can be pressed anytime to turn “off” relay. To detect a new alarm
condition, the signal must go below the set point, and then go above it.
44
Model BD300 Analog Input Process Meter Instruction Manual
6.7.3. Low Alarm Operation (Set < Reset)
Return to Table of Contents
For Manual reset mode, ACK can be pressed anytime to turn “off” relay. To detect a new alarm
condition, the signal must go below the set point, and then go above it.
45
Model BD300 Analog Input Process Meter Instruction Manual
6.7.4. High Alarm with Fail-Safe Operation (Set > Reset)
Return to Table of Contents
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
46
Model BD300 Analog Input Process Meter Instruction Manual
6.7.5. Low Alarm with Fail-Safe Operation (Set < Reset)
Return to Table of Contents
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
47
Model BD300 Analog Input Process Meter Instruction Manual
Model BD300 Analog Input Process Meter InstructionManual
6.7.2. Pump Alternation Control Operation
Return to Table of Contents
Pump Alternation Control Operation
Input
Relay1 &
Relay1 Set
Relay2 Set
Relay2 Reset
de-energized energized
LEDs indicate the relay status
Input
de-energized energized
Pump 1
Pump 1
Pump 2
Relay1 Set
Relay2 Set
Relay2 Reset
Relay1 Reset
Pump 2
48
Input
Relay2 Set
de-energized energized
Pump 2
Pump 1
Relay1 Set
Relay1 Reset
Relay2 Reset
Model BD300 Analog Input Process Meter Instruction Manual
6.7.6. Relay Sampling Operation
Return to Table of Contents
When the signal crosses the set point, the relay trips and the sample time starts. After the sample
time has elapsed, the relay resets. The cycle repeats every time the set point is crossed, going up
for high alarms and going down for low alarms.
The sample time can be programmed between 0.1 and 5999.9 seconds.
49
Model BD300 Analog Input Process Meter Instruction Manual
6.7.7. Signal Loss Or Loop Break Operation
Return to Table of Contents
When the meter detects a break in the 4-20 mA loop, the relay will go to one of the following
selected actions:
1. Turn On (Go to alarm condition)
2. Turn
Off
(Go to non-alarm condition)
3. Ignore (Processed as a low signal condition
50
Model BD300 Analog Input Process Meter Instruction Manual
6.7.8. Time Delay Operation
The following graphs show the operation of the time delay function.
Return to Table of Contents
When the signal crosses the set point, the On time delay timer starts and the relay trips when the
time delay has elapsed. If the signal drops below the set point (high alarm) before the time delay has elapsed, the On time delay timer resets and the relay does not change state. The same
principle applies to the
Off
Note: If “Automatic or Manual (A-m An)” reset mode is selected, the LED follows the reset point
and not the relay state when the relay is acknowledged.
time delay.
51
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8. Relay Operation Details
6.8.1. Overview
The relay capabilities of the meter expand its usefulness beyond simple indication to provide users with alarm and control functions. These capabilities include front panel alarm status LEDs as
well as either 2 or 4 optional internal relays and/or 4 external relays expansion module. Typical
applications include high or low temperature, level, pressure or flow alarms, control applications
such as simple on/off pump control, and pump alternation control for up to 8 pumps. There are
four basic ways the relays can be used:
1. High or Low Alarms with Latching or Non-Latching Relays
2. Simple On/Off Control with 100% Adjustable Deadband
3. Sampling (Based on Time)
4. Pump Alternation Control for up to 8 Pumps
6.8.2. Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm relays will reflect the state
of the input to the meter. The following table indicates how the alarm LEDs and relays will react
on power-up based on the set and reset points:
The following table indicates how the relays behave based on the fail-safe selection for each
relay:
Fail-Safe
Selection
Non-Alarm State Alarm State
Power Failure
NONCNONC
OffOpenClosedClosedOpenRelays go to non-alarm state
OnClosedOpenOpenClosed Relays go to alarm state
Note: NO = Normally Open, NC = Normally Closed. This refers to the condition of the relay
contacts when the power to the meter is off.
52
Model BD300 Analog Input Process Meter Instruction Manual
6.8.4. Front Panel LEDs
The LEDs on the front panel provide status indication for the following:
Return to Table of Contents
LEDSTATUS
1Alarm 1
2Alarm 2
3Alarm 3
4Alarm 4
The meter is supplied with four alarm points that include front panel LEDs to indicate alarm
conditions. This standard feature is particularly useful for alarm applications that require visual-only indication. The LEDs are controlled by the set and reset points programmed by the user.
When the display reaches a set point for a high or low alarm, the corresponding alarm LED will
turn on. When the display returns to the reset point, the LED will go off. The front panel LEDs
respond differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition and always on during
alarm condition, regardless of the state of the relay (e.g. Relay acknowledged after alarm condition).
For latching relays, the alarm LEDs reflect the status of the relays, regardless of the alarm condition. The following tables illustrate how the alarm LEDs function in relation to the relays and the
acknowledge button (Default: F3 key assigned to ACK):
LEDSTATUS
1Alarm 5
6Alarm 6
7Alarm 7
8Alarm 8
53
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8.5. Latching and Non-Latching Relay Operation
The relays can be set up for latching (manual reset) or non-latching (automatic reset) operation.
Relay terminology for following tables
TerminologyRelay Condition
OnAlarm (Tripped)
OffNormal (Reset)
ACKAcknowledged
The On and Off terminology does not refer to the status of the relay’s coil, which depends on
the fail-safe mode selected.
In latching relay mode, latched relays will reset (unlatch
WARNING!
6.8.6. Non-Latching Relay (Auto)
Automatic reset only
ConditionLEDRelay
NormalOffOff
AlarmOnOn
Ack (No effect)OnOn
NormalOffOff
In this application, the meter is set up for automatic reset (non-latching relay). Acknowledging
the alarm while it is still present has no effect on either the LED or the relay. When the alarm
goes away, the relay automatically resets and the LED also goes off.
when power is cycled.
54
Model BD300 Analog Input Process Meter Instruction Manual
6.8.7. Non-Latching Relay (A-m An)
Automatic + manual reset t any time
ConditionLEDRelay
NormalOffOff
AlarmOnOn
NormalOffOff
Next AlarmOnOn
AckOnOff
NormalOffOff
Return to Table of Contents
In this application, the meter is set up for automatic and manual reset at any time (non-latching
relay). The LED and the relay automatically reset when the meter returns to the normal condition.
The next time an alarm occurs, the operator acknowledges the alarm manually while the alarm
condition still exists. This causes the relay to reset, but the LED stays on until the meter returns to
the normal condition.
6.8.8. Latching Relay (LAtcH)
Manual reset any time
ConditionLEDRelay
NormalOffOff
AlarmOnOn
AckOffOff
In this application, the meter is set up for manual reset at any time. Acknowledging the alarm
even if the alarm condition is still present resets the relay and turns off the LED.
55
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8.9. Latching Relay (Lt-Clr)
Manual reset only after alarm condition has cleared
ConditionLEDRelay
NormalOffOff
AlarmOnOn
Ack (No effect)OnOn
NormalOnOn
AckOffOff
In this application, the meter is set up for manual reset only after the signal passes the reset
point (alarm condition has cleared).
Acknowledging the alarm while it is still present has no effect on either the LED or the relay.
When the alarm is acknowledged after it returns to the normal state, the LED and the relay go
off. Notice that the LED remains on, even after the meter returns to the normal condition. This
is because, for latching relays, the alarm LED reflects the status of the relay, regardless of the
alarm condition.
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual rest:
1. Via the programmable front panel function keys F1-F3 (Default: F3 assigned to ACK).
2. Remotely via a normally open pushbutton wired across one of the digital inputs and
the +5 V terminals on the digital I/O modules, or using the F4 digital input, which is
triggered with a contact closure to COM, or with an active low signal (see page 19).
When the ACK button or the assigned digital input is closed, all relays programmed for manual
reset are acknowledged.
56
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8.10. Pump Alternation Control Applications (ALtErn)
For pump control applications where two or more similar pumps are used to control the level of a tank
or a well, it is desirable to have all the pumps operate alternately. This prevents excessive wear and
overheating of one pump over the lack of use of the other pumps.
Up to 8 relays can be set up to alternate every time an on/off pump cycle is completed. The set points
can be programmed, so that the first pump on is the first pump off.
6.8.10.1. Application #1: Pump Alternation Using Relays 1 & 2
1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.
Set and Reset Point Programming
RelaySet PointReset PointFunction
130.00010.000Controls Pump #1
235.0005.000Controls Pump #2
34.0009.000Controls Low Alarm
440.00029.000Controls High Alarm
57
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
Pump Alternation Operation
1. Pump #1 turns on when level reaches 30.000, when level drops below 10.000,
pump #1 turns off.
2. The next time level reaches 30.000, pump #2 turns on, when level drops below
10.000, pump #2 turns off.
3. If the level doesn’t reach 35.000, pump #1 and pump #2 will be operating alternately.
4. If pump #1 cannot keep the level below 35.000, pump #2 will turn on at 35.000,
then as the level drops to 10.000, #1 turns off, pump #2 is still running and shuts
off below 5.000.
5. Notice that with the set and reset points of pump #2 outside the range of pump
#1, the first pump on is the first pump to go off. This is true for up to 8 alternating
pumps, if setup accordingly.
6. Relay #3 will go into alarm if the level drops below 4.000 and relay #4 will go into
alarm if the level exceeds 40.000.
7. Adding the 4 external relays, expansion module allows using the 4 SPDT internal
relays for pump alternation and the 4 SPST external relays for high, high-high, low,
and low-low alarm indication.
6.8.10.2. Application #2: Pump Alternation Using Relays 3 & 4
1. Relays 1 and 2 are set up for pump alternation.
2. Relays 3 and 4 are set up for low and high alarm indication.
Set and Reset Point Programming
RelaySet PointReset PointFunction
1495750Controls Low Alarm
275006900Controls High Alarm
37000900Controls Backup Pump
460001000Controls Main Pump
58
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
The following graphics provide a visual representation of a typical pump alternation application
with high and low alarm monitoring:
1. Relay #4 turns the main pump on at 6000 gallons and turns it off at 1000 gallons.
2. With the Pump Alternation feature activated, the next time the level reaches 6000
gallons, relay #3 transfers and starts the backup pump.
3. If the backup pump is not able to keep up, and the level reaches 7000 gallons, relay
#4 transfers and starts the main pump as well.
59
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
4. Relay #2 trips the High Level Alarm at 7500 gallons and resets at 6900 gallons.
5. Relay #1 trips the Low Level Alarm at 495 gallons and resets at 750 gallons.
60
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8.11. Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the interlock feature:
1. Access the
2. In the Advanced features –
any of the internal relays (1-4).
Setup – Relay – Action
menu and set the action to off.
User
menu program any of the digital inputs to
Force On
3. Connect a switch or dry contact between the +5V terminal and the corresponding
digital input (dI-1 to dI-4 terminal.
61
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.8.11.1. Interlock Relay Operation Example
Relays 1 & 2 are configured to energize (their front panel LEDs are off) when SW1 and SW2
switches (above) are closed. If the contacts to these digital inputs are opened, the corresponding
front panel LEDs flash indicating this condition. The processes being controlled by the interlock
relay will stop, and will re-start only after the interlock relay is reactivated by the digital inputs
(switches).
Note: If multiple digital inputs are assigned to the same relay, then the corresponding logic is
(AND) - i.e. both switches must be closed to trip the relay.
6.9. Scaling the 4-20 mA Analog Output (Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal for any display range
selected.
No equipment is needed to scale the analog output; simply program the display values to the
corresponding mA output signal.
The
Analog Output
menu is used to program the 4-20 mA output based on display values.
For instructions on how to program
numeric values see
Values
Setting Numeric
, page 32.
62
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.10. Reset Menu (rESEt)
The Reset menu is used to reset the maximum or minimum reading (peak or valley) reached by
the process; both may be reset at the same time by selecting “reset high & low” (
tare value used to zero the display may be reset by selecting “reset tare” (
rSt tr
rSt HL
).
). the
6.11. Control Menu (
The
Control
noring the input. Each relay and analog output can be programmed independently for manual
control. Selecting automatic control sets all relays and analog out put for automatic operation.
menu is used to control the 4-20 mA analog output and the relays manually, ig-
Contrl
)
Once Manual mode is initiated on any relay or
analog output, an LED labeled “M” is turned
on. Every few seconds, all LEDs representing
outputs that are in Manual mode, as well as
the “M” LED flash. This process will continue as
long as any output is in manual mode.
63
Model BD300 Analog Input Process Meter Instruction Manual
6.12. Setting Up the Password (PASS)
The
Password
changes to the programmed parameter settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs, and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs
6.12.1. Protecting or Locking Meter
Enter the Password menu and program a six-digit password.
menu is used for programming three levels of security to prevent unauthorized
Return to Table of Contents
For instructions on how to program numeric values, see
Record the password for future reference. If appropriate, it may be recorded in the space
provided.
Setting Numeric Values
, page 32.
Model:
Serial Number:
Password 1:
Password 2:
Password 3:
Model BD300 Analog Input Process Meter Instruction Manual
6.12.2. Making Changes to a Password Protected Meter
Return to Table of Contents
If the meter is password protected, the meter will display the message Locd (
Menu button is pressed. Press the Enter button while the message is being displayed and enter
the correct password to gain access to the menu. After exiting the programming mode, the meter returns to its password protected condition.
6.12.3. Disabling Password Protection
To disable the password protection, access the Password menu and enter the correct password
twice, as shown below. The meter is now unprotected until a new password is entered.
Locked
) when the
If the correct six-digit password is entered, the meter displays the message (unlocked) and the
protection is disabled until a new password is programmed.
If the password entered is incorrect, the meter displays the message Locd (Locked) for about
two seconds, and then it returns to Run Mode.
To try again, press Enter while the
The password may be disabled by entering a master
password once. If you are authorized to make changes,
enter the master password 508665 to unlock the meter.
Locked
message is displayed.
Did you forget the password?
65
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.13. Advanced Features Menu
To simplify the setup process, functions not needed for most applications are located in the Advanced Features menu.
Press and hold the Menu button for three seconds to access the advanced features of the meter.
66
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.13.1. Advanced Features Menu & Display Messages
The following table shows the functions and messages of the Advanced Features menu in the
order they appear in the menu.
DisplayParameterAction/Setting
FiLtEr
byPASS
round
SEriAL
SLAUE Id
bAud
tr dLy
PArity
t-byt
SELEct
Functn
Filer
Bypass
Round
Serial
Slave ID
Baud Rate
Transmit Delay
Parity
Time Byte
Select
Signal Input
Conditioning
Set noise filter value
Set filter bypass value
Set the rounding value for display variables
Set serial communication parameters
Set slave ID or meter address
Select baud rate
Set transmit delay for serial communication
Select parity
Even, Odd, or None with 1 or 2 stop bits
Set byte-to-byte timeout
Enter the Select menu (function, cutoff, out)
Select linear, square root, programmable
exponent, or round horizontal tank function
LinEAr
PU 1
PU 2
no PtS
SquArE
ProG E
rht
Inch
Linear
PV1
PV2
Number of
Points
Square Root
Programmable
Exponent
Round
Horizontal Tank
Dimension
Set meter for linear function and select
number of linearization points
Select PV1 number of linearization points
Select PV 2 number of linearization points
Set PV1 for 2 to 32-point linearization
Set PV2 for 2 to 8-point linearization
Set meter for square root extraction
Set meter for programmable exponent and
enter exponent value
Set meter for round horizontal tank volume
calculation
Calculate volume in gallons
67
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
cm
diAmr
LEnGth
CutoFF
AoutPr
SourcE
O-rAnG
u-rAnG
brEAK
mAX
min
Dimension
Diameter
Length
Cutoff
Analog Output
Programming
Source
Overrange
Underrange
Break
Maximum
Minimum
Calculate volume in liters
Enter the tank’s diameter in inches
Enter the tank’s length in inches
Set low-flow cutoff
Program analog output parameters
Select source for the 4-20 mA output
Program mA output for display overrange
Program mA output for display underrange
Set input break condition operation
Program maximum mA output allowed
Program minimum mA output allowed
CALib
4 mA
20 mA
usEr
F1
F2
F3
F4
d11
d01
Calibrate
4 mA Output
20 mA Output
User I/O
F1 Function Key
F2 Function Key
F3 Function Key
F4 Function Key
Digital Input 1
Digital Output 1
Calibrate 4-20 mA output (internal
reference source used for scaling the
output)
Enter mA output value read by miliamp
meter with at least 0.001 mA resolution
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Assign function keys and digital I/O
Assign F1 function key
Assign F2 function key
Assign F3 function key
Assign F4 function (digital input)
Assign digital input 1-8, if expansion
modules are connected
Assign digital output 1-8, if expansion
modules are connected
68
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
iCAl
C CAL
C Lo
C Hi
U CAL
U Lo
U Hi
CoPy
SEnd
donE
Internal Source
Calibration
Current
Calibration
Current Low
Current Hight
Voltage
Calibration
Voltage Low
Voltage High
Copy
Send
Done
Enter internal source calibration (used for
scaling the meter without a signal source)
Calibrate 4-20 mA current input (internal
reference source used for scaling the input)
Calibrate low current input (e.g. 4 mA)
Calibrate high current input (e.g. 20 mA)
Calibrate voltage input
Calibrate low voltage input (e.g. 0 V)
Calibrate high voltage input (e.g. 10 V)
Enter copy function
Send meter settings to another meter
Copy function completed
diAG
InPut
unitS
FiltEr
byPASS
round
Functn
SCALE
CutofF
dSPLAy
rELAy
Diagnostics
Input
Untis
Filter
Bypass
Round
Function
Scale
Cutoff
display
Relays
Display parameter settings
Input selection
Select the display units/tags
Filter value
Bypass value
Round value
Function selected
Scaling parameter
Cutoff value
Display assignments
Relay settings
69
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
Aout
Analog Output
Analog output scaling
Analog Output
AoutPr
SEriAL
LEd t
InFo
6.13.2. Noise Filter (
The noise filter is available for unusually noisy signals that cause an unstable process variable
display. The noise filter averages the input signal over a certain period. The filter level determines the length of time over which the signal is averaged. The filter level can be set between 2
and 199. The higher the filter level, the longer the averaging time and so the longer it takes the
display to settle to its final value. Setting the filter level to zero disables the filter function.
6.13.3. Noise Filter Bypass (
The noise filter bypass changes the behavior of the meter so that small variations in the signal
are filtered out but large abrupt changes in the input signal are displayed immediately. The bypass value determines the minimum amount of signal change to be displayed immediately. All
signal changes smaller than the bypass value are filtered or averaged by the meter. The noise
filter bypass may be set between 0.1 and 99.9% of full scale.
Programming
Serial
LED Test
Information
FiLtEr)
Analog output programming
Serial communication settings
Test all LEDs
Display software and S/N information
byPASS)
6.13.4. Rounding Feature (
The rounding feature is used to give the user a steadier display with fluctuating signals. Rounding is used in addition to the filter function. Rounding causes the display to round to the nearest
value according the rounding selected. See examples below:
Model BD300 Analog Input Process Meter Instruction Manual
6.13.5. Modbus RTU Serial Communications (SEr iAL)
The meter is equipped with serial communications capability as a standard feature using Modbus RTU Serial Communication Protocol.
To communicate with a computer or other data terminal equipment, an RS-232, RS-485, or USB
adapter (BDUSBSA) option is required; see
Ordering Information
on page 7 for details.
Do not connect any equipment other than Blue Ribbon’s
expansion modules, cables, or meters to the RJ45 M-LINK
connector. Otherwise damage will occur to the equipment
WARNING!
and the meter.
Note: More detailed instructions are provided with each optional serial
communications adapter.
Note: Refer to the BULLDOG Modbus Register Tables located at
www.blueribboncorp.com for details.
When using more than one meter in a multi-drop mode, each meter must be provided with its
own unique address. The meter address (Slave ID) may be programmed between 1 and 247.
The transmit delay may be set between 0 and 199 ms. The parity can be set to even, odd, or
none with 1 or 2 stop bits.
The BD300 can also be connected to another BD300 with a special BDCCC cable, allowing the
user to copy all the settings from one meter to another, using the
71
Copy
function.
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.13.6. Select Menu (SELEct)
The
Select
root, programmable exponent, or round horizontal tank), low-flow cutoff, and analog output
programming. The multi-point linearization is part of the linear function selection.
menu is used to select the signal input conditioner applied to the input (linear, square
6.13.7. Signal Input Conditioning (Functn)
The
Function
menu is used to select the signal input conditioner applied to the input: linear,
square root, programmable exponent, or round horizontal tank volume calculation. The multipoint linearization is part of the linear function selection.
Meters are set up at the factory for linear function with 2-point linearization. The linear function
provides a display that is linear with respect to the input signal.
72
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.13.8. Square Root Linearization (SquArE)
The square root function can be used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units.
6.13.9. Programmable Exponent Linearization (
ProG E)
The programmable exponent can be used to linearize the signal from level transmitters in
open-channel flow applications using weirs and flumes.
6.13.10. Multi-Point Linearization (
L inEAr)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 linearization points can be selected for PV1 under the linear function. The multi-point linearization can
be used to linearize the display for non-linear signals such as those from level transmitters used
to measure volume in odd-shaped tanks or to convert level to flow using weirs and flumes with
complex exponent.
If the dual-scale level feature has been selected, the menus for PV1 & PV2 are enabled. PV2 can
be programmed with up to 8 linearization points.
73
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.13.11. Round Horizontal Tank Linearization (rHt)
This function automatically calculates the volume in a round horizontal tank with flat ends.
Set the display for the desired decimal point and engineering units before entering the round
horizontal tank function. Select units, inches or cm for the tank dimensions. Enter the diameter
and the length in inches and the results are calculated automatically in US gallons.
The meter can be scaled to display the volume in any engineering unit.
Note: After Scale is displayed continue pressing the Enter button until the
meter completes the scaling of the input and display values.
6.13.12. Changing the Volume from Gallons to Liters
In the above graphic, entering the 48” for the diameter and 120” for the length of the round
horizontal tank, the meter automatically calculates that the volume of the tank is 940.02 gal-
lons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the Setup menu and change the decimal point to 1 decimal.
3. Go to the
display.
4. Press Enter and change the display 2 value to 3558.4.
5. The meter is now displaying the volume in liters.
Program – Scale
menu and press Enter until diS 2 is shown on the main
Note: The display can be scaled to display the volume in any
engineering units.
74
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.14. Low-Flow Cutoff (CutOff)
The low-flow cutoff feature allows the meter to be programmed so that the often-unsteady out-
put from a differential pressure transmitter, at low flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will display zero below the
cutoff value. Programming the cutoff value to zero disables the cutoff feature.
6.15. Analog Output Programming (
AoutPr)
The Analog Output Programming menu is used to program the behavior of the 4-20 mA output.
The following parameters and functions are programmed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. PV)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to scale the
4-20 mA output
6.15.1. Analog Output Source
The source for generating the 4-20 mA output may be assigned to the process variable, maximum or minimum value reached by the process, one of the et points, or the ModBUS PV input.
6.15.2. Analog Output Calibration
To perform the analog output calibration, it is recommended to use a milliamp meter with a resolution of at least 0.1 µA to measure the output current. The values saved internally during this
procedure are used for scaling the 4-20 mA output in the
75
Setup
menu.
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.16. Programmable Function Keys User Menu (uSEr)
The
User
menu allows the user to assign the front panel function keys F1, F2, and F3, the digi-
tal input F4, and up to eight additional digital inputs to access most of the menus or to activate
functions immediately (e.g. Reset max & min). F4 is a digital input on the signal input connector.
Up to eight digital outputs can be assigned to a number of actions and functions executed by
the meter (e.g. Alarms, relay acknowledgment, etc.).
76
Model BD300 Analog Input Process Meter Instruction Manual
6.16.1. Function Keys & Digital I/O Available Settings
DisplayDescriptionDisplayDescription
ACH
rSt Hi
rSt Lo
rSt HL
rELAy
SEt 1
rLy d
rLy E
O Hold
d HoLd
d AbC
Acknowledge relays
Reset Max (A, B, C)
Reset Min (A, B, C)
Reset Max & Min
(A, B, C)
Relay Menu
Set Point 1-8
Disable Relay
Enable Relay
Relay Output Hold
Display Hold While
Active
Scrolls the values for
A, B, C every time it
is actiabted. Stays on
the last value for 10
seconds and then it
returns to its assigment. The values are
displayed on the big
display and the corresponding channel
and units on the small
display
Lit HC
Lit LC
LitHLC
diSAbL
mEnu
riGHt
uP
EntEr
ALrm 1
F on 1
F on 2
Max on little display
(Channel C)
Min on little display
(Channel C)
Max/min little display
(Channel C)
Disable function key
Menu button
Right arrow button
Up arrow button
Enter button
Alarm 1 - 8
(Digital Output)
Force on relay 1
Force on relay 2
77
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
DisplayDescriptionDisplayDescription
Lit Hi
Lit Lo
Lit HL
6.17. Tare (
tArE)
Max on Little Display
Min on Little Display
Max/Min Little Display
F On 1
F On 2
F On 3
F On 4
Force Relay 1 On
Force Relay 2 On
Force Relay 3 On
Force Relay 4 On
The tare function zero’s out the display. In the case of scale weight, tare is used to eliminate
container weight and provide net weight readings.
There are two functions; Capture Tare and Reset Tare.
When the capture tare function is used the display reading is offset by the displayed amount to
make the displayed value zero. This modified display value is the net value. The originally dis-
played value without the tare offset is the gross value. Both may be chosen as a display option.
Reset tare removes the display offset of the net value, and the gross and net values become the
same until a new capture tare is entered.
78
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
6.18. Internal Source Calibration (ICAL)
The meter is factory calibrated priot to shipment
to read in milliamps and volts depending on the
input selection. The calibration equipment is
certified to NIST standards.
The use of calibrated signal sources is necessary to calibrate the internal source of the meter.
The meter’s internal source is what allows the user to scale the meter without applying a signal.
Check calibration of the meter at least every 12 months. Each input must be recalibrated sepa-
rately.
Notes:
1.
If meter is in operation and it is indended to
accept only one input type (e.g. 4-20 mA),
recalibration of other input is not necessary.
2.
Allow the meter to warm up for at least 15
minutes before performing the internal
source calibration procedure.
The
Internal Calibration
1. Press and hold the Menu button for three seconds to access the advanced features of the
meter.
2. Press the Up arrow button to scroll to the
3. The meter displays either current calibration (C CAL) or voltage calibration (U CAL), according to the input setup. Press Enter to start the calibration process.
Example of Internal Calibration for current input:
4. The meter displays
Enter. The display flashes for a moment while the meter is accepting the low input signal.
5. After the display stops flashing, a number is displayed with the leftmost digit brighter than
the rest. The bright digit is the active digit that can be changed by pressing the Up arrow
button. Press the Right arrow button to move to the next digit.
6. Set the display value to correspond to the input signal being calibrated, typically 4.000 mA.
7. The display moves to the high input calibration (C Hi). Apply the high input signal and press
Enter.
8. Set the display for the high input calibration, in the same was as it was set for the low input
calilbration, typically 20.000 mA.
menu is part of the
low
input current message (C Lo). Apply the low input signal and press
Advanced Features
Internal Calibration
menu.
menu (iCAL) and press Enter.
79
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
The graphic above shows the calibration of the current input. The Voltage input is calibrated in a
similar way.
Tips:
• Low and high input signals ca be any valid values within the range of the meter.
• Observe minimum input span requirements between input 1 and input 2.
• Low input should be less than high input signal.
6.18.1. Error Message (
Error)
An error message indicates that the calibration or scaling process was not successful.
The error message might be caused by any of the following conditions:
6.18.2. Minimum Input Span
1. Input signal is not connected to the proper terminals, or it is connected backwards.
Setup
2. Wrong signal selection in
menu.
3. Minimum input span requirements not maintained.
The minimum input span is the minimum difference between input 1 and input 2 signals required to complete the calibration or scaling of the meter.
80
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
Input RangeInput 1 & Input 2 Span
4-20 mA0.15 mA
± VDC0.10 VDC
6.19. Meter Copy Function (
Copy
The
requiring exactly the same setup and programming (
filter, bypass, etc.).
function is used to copy (or clone) all the settings from one meter to other meters
Copy)
i.e.
type of input, scaling, decimal point,
Only the BDCCC meter copy cable must be used for
meter-to-meter interfacing. The BDCCC is a special
eight-conductor flat cable with two wires swapped.
WARNING!
Using standard CAT5 or other cable will cause
damage to both meters.
6.19.1.
To successfully copy settings from one meter to another, both meters must have the same software version and baud rate settings. See Determining Software Version, page 85, for instructions.
Copy Function Requirements
6.19.2. Meter Copy or Cloning Instructions
CAUTION!
UDo not connect the two meters
to the same signal source while
cloning. Internal calibration may
be affected.
81
Model BD300 Analog Input Process Meter Instruction Manual
1. Connect two meters using a DBCC meter copy cable.
Using standard CAT5 or other cable will cause
damage to both meters. Use DBCCC meter copy
Return to Table of Contents
WARNING!
2. Do not connect the two meters to the same signal Run Mode.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter the
page 67.
5. Scroll to the
6. The meter displays teh message SEnd. Press Enter, the display flashes while sending data.
The message donE is displayed when copying is completed.
Advanced Features
Copy
function using the Up arrow button then press Enter.
cable only.
menu of the Master meter; see
Advanced Features Menu
on
7. The Clone meter displays the message CPy rC while being programmed then the message
donE when copying is completed. The meter initializes and returns to Run Mode using the
same settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer to Copy Function Requirments above.
82
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
7. meter operatIon
The meter is capable of accepting current (0-20 mA, 4-20 mA) and voltage signals (0-5 V, 1-5
V, 0-10 V, ± 10 V) and displaying these signals in engineering units from -99999 to 999999
(
e.g.
a 4-20 mA signal could be displayed as -50.000 to 50.000).
The dual-line display can be customized by the user to operate in such a way as to satisfy a
specific application. Typically the main display is used for the process variable; while the second
display is used for engineering units, custom legend, or set point indication.
The analog input can be scaled to display the process in two different scales; for example: with
d-SCAL enabled, the main display could indicate level in feet and the second display could
indicate the volume in gallons.
Additionally the meter can be set up to display the analog input on the main display and the
ModBUS input on the second display. The relays and analog output can be programmed to
operate from the ModBUS PV input.
7.1. Front Panel Buttons Operation
Button
Description
Symbol
Press to enter or exit Programming Mode,
view settings, or exit max/min readings
Press to reset max/min readings or other
parameter/function assigned through the
menu
Press to display max/min readings or other
parameter/function assigned through the
menu
Press to acknowledge relays or other
parameters/function assigned through the
User
menu
User
User
83
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
7.2. Function Keys Operation
During operation, the programmable function keys operate according to the way they have
been programmed in the
The table above shows the factory default settings for F1, F2, F3.
7.3. F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to func-
tion keys F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active
low signal. During operation, F4 operates according to the way it has been programmed in the
Advanced Features
–
Advanced Features
User
menu.
–
User
menu.
7.4. Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or momentary:
1. Display briefly by assigning to the F1-F3 function keys or to the digital
User
inputs in the
2. Display continuously by assigning either display to max/min through the
Display
Any of the F1-F3 function keys (buttons) and the digital inputs can be programmed to reset the
max & min readings. The meters are set at the factory to display the max reading by pressing
the Up arrow/F2 button and to use the Right arrow/F1 button to access the
To display max reading using function key with factory defaults:
1. Press Up arrow/F2 button to display maximum readign since the last reset/
power-up.
2. To reset max/min press Right arrow/F1 button to access the Rest menu.
The max & min displays are reset to actual values.
3. Press Menu to exit max/min display reading.
menu.
menu.
Reset
menu.
84
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
To display max reading using function key with factory defaults:
Assign either display to Max (d Hi), Min (d Lo), or toggle between Max
and Min (d HL) every 10 seconds.
8. troubleShootIng
The rugged design and the user-friendly interface of the meter should make it unusual for the
installer or operator to refer to this section of the manual. However, due to the many features
and functions of the meter, it’s possible that the setup of the meter does not agree with what an
operator expects to see.
If the meter is not working as expected, refer to the
below.
8.1. Diagnostics Menu (
The
Diagnostics
see
Advanced Features
It provides an easy was to view the programmed parameter settings for troubleshooting purposes. Press the Enter button to view the settings and the Menu button to exit at any time.
For a description of the diagnostic messages, see
page 68.
menu is located in the
Menu, page 67.
d iAG)
Advanced Features
Diagnostics
menu and recommendations
menu, to access
Advanced Features Menu
Diagnostics
& Display Messages,
menu
85
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
8.1.1. Determining Software Version
To determine the software version of a meter:
8.2. Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to determine what’s happening, it might be better to start the setup process from the factory defaults.
Instructions to load factory defaults:
1. Enter the Advanced Features menu. See
page 67.
2. Press Up arrow to go to Diagnostics menu
3. Press and hold Right arrow for three seconds, press Enter when display
flashes rESEt.
Note: If Enter is not pressed within three seconds, the display returns to
the
4. The meter goes through an initialization sequence (similar as on pow-
Diagnostics
er-up), and loads the factory default settings.
menu.
Advanced Features Menu
,
Note: The dual-scale selection for some level applications (d-SCAL) is not reset to the
single scale factory default. This can be changed using the Setup – Input menu.
86
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
8.2.1. Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the
meter. Next to the factory setting, the user may record the new setting for the particular application.
Model: S/N: Date:
ParameterDisplayDefault SettingUser Setting
Input Type
Dual-Scale Feature
Filter
Bypass
Function
Number of points
Programming
Input 1
Display 1
Input 2
Display 2
InPut
d-SCAL
F iLtEr
bYPASS
Functn
no Pt5
ProG
inP 1
diS 1
inP 2
diS 2
4-20 mA
No (Single Scale)
70
0.2
Linear
2
Scale
4.000 mA
4.000
20.000 mA
20.000
Decimal Point
Cutoff Assignment
Big Display (Main)
Little Display (Small
Display Intensity
Relay 1 Action
dd.ddd
dSPLAy
biG
LittlE
d- inty
Act i
3 places
PV: Process variable
Eng unit default= mA
8
Automatic
87
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
ParameterDisplayDefault SettingUser Setting
Relay 1 Set Point
Relay 1 Reset Point
Relay 2 Action
Relay 2 Set Point
Relay 2 Reset Point
Relay 3 Action
Relay 3 Set Point
Relay 3 Reset Point
Relay 4 Action
Relay 4 Set Point
Relay 4 Reset Point
SEt 1
rSt 1
Act 2
SEt 2
rSt 2
Act 3
SEt 3
rSt 3
Act 4
SEt 4
rSt 4
1.000
Automatic
Automatic
2.000
1.500
Automatic
3.000
2.500
Automatic
4.000
3.500
Fail-Safe Relay 1
Fail-Safe Relay 2
Fail-Safe Relay 3
Fail-Safe Relay 4
On Delay Relay 1
Off Delay Relay 1
On Delay Relay 2
Off Delay Relay 2
On Delay Relay 3
Off Delay Relay 3
On Delay Relay 4
FLS 1
FLS 2
FLS 3
FLS 4
On 1
Off 1
On 2
Off 2
On 3
OFF 3
On 4
Off
Off
Off
Off
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
0.0 sec
88
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
ParameterDisplayDefault SettingUser Setting
Off Delay Relay 4
Loop Break Relay 1
Loop Break Relay 2
Loop Break Relay 3
Loop Break Relay 4
Display 1 Analog Out
Output 1 Value
Display 2 Analog Out
Output 2 Value
Source Analog Output
Overrange Output
OFF 4
iGnorE
iGnorE
iGnorE
iGnorE
diS i
Out i
diS 2
Out 2
SourcE
O-rAnG
0.0 sec
Ignore
Ignore
Ignore
Ignore
4.000
4.000 mA
20.000
20.000 mA
Process Variable
21.000 mA
Underrange Output
Loop Break Output
Maximum Output
Minimum Output
Slave ID (Address)
Baud Rate
Transmit Delay
Parity
Byte-to-Byte Timeout
F1 Function Key
F2 Function Key
u-rAnG
brEAK
m AH
m in
SLAU id
bAud
tr dLy
PAritYy
t-byt
F1
F2
3.000 mA
1.000 mA
23.000 mA
1.000 mA
247
9600
50 ms
Even
010 (0.1 sec)
Reset max & min
Big display: Max (Hi)
89
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
ParameterDisplayDefault SettingUser Setting
F3 Function Key
F4 Funtion
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Output 1
Digital Output 2
Digital Output 3
Digital Output 4
Password 1
F3
F4
di1
d1 2
d1 3
d1 4
d0 1
d0 2
d0 3
d0 4
PASS 1
Acknowledge relays
Acknowledge relays
Menu
Right arrow
Up arrow
Enter
Alarm 1
Alarm 2
Alarm 3
Alarm 4
000000 (unlocked)
Password 2
Password 3
PASS 2
PASS 3
000000 (unlocked)
000000 (unlocked)
90
Return to Table of Contents
Model BD300 Analog Input Process Meter Instruction Manual
8.3. Troubleshooting Tips
SymptomCheck/Action
No display at allCheck power at power connector
Not able to change setup or programming, Locd
is displayed
Meter displays error message during
calibration (Error)
Meter displays
1. 999999
2. -99999
Display is unstable
Display reading is not accurate
Display does not respond to input changes,
reading a fixed number
Display alternates between
1. Hi and a number
2. Lo and a number
Relay operation is reversed
Relay and status LED do not respond to
signal
Flashing relay status LEDs
Meter not communicating with application
prorams.
If the display locks up or the meter does not
respond at all
Meter is password-protected, enter correct
six-digit password to unlock
Check:
1. Signal connections
Setup
menu
Setup
menu
menu
2. Inut selected in
3. Minimum input span requirments
Check:
1. Input selected in Setup menu
2. Corresponding signal at Signal
connector
Check:
1. Input signal stability and value
2. Display scaling vs. input signal
3. Filter and bypass values (increase)
Check:
1. Signal input conditioner selected:
Linear, square root, etc.
2. Scaling or calibration
Check:
1. Display assignment, it might be
displaying max, min, or set point
Press Menu to exit max/min display
readings.
Check:
1. Fail-safe in
2. Wiring of relay contacts
Check:
1. Relay action in
2. Set and reset points
Relays in manual control mode or relay inter-
lock switches opened.
Check:
1. Serial Adapter and cable
2. Serial Settings
3. Meter address and baud rate
Cycle the power to reboot the micropressor.
Setup
Other symptoms not described aboveCall Technical Support for for assistance.
Note: Certain sequences of events can cause unexpected results. To solve these issues,
it is best to start fresh from factory defaults and map changes ahead of time, rather
than at random.
91
Model BD300 Analog Input Process Meter Instruction Manual
8.4. Alphabetical List of Display Functions & Messages
DisplayParameterAction/Setting
Enter mA output value read by milliamp
20 mA
4 mA
20 mA Output
4 mA Output
meter with at least 0.001 mA resolution
Enter mA output value read by milliamp
meter with at least 0.001 mA resolution
Return to Table of Contents
999999
-99999
AcK
Act 1
ALm 1
AltErn
A-m An
Aout
AoutPr
Auto
bAud
biG
Flashing display
Acknowledge
Action 1
Alarm 1
Alternate
Auto-manual
Analog Output
Analog Output
Programming
Automatic
Baud Rate
Big Display
Overrange condition
Underrange condition
Acknowledge relays
Set relay 1 action
Assign digital output to Alarm 1-8
Set relay for pump alternation control
Set relay for automatic & manual reset
Enter the Analog output scaling menu
Enter analog output programming
Press Enter to set automatic operation
Select baud rate
Press Enter to assign the main display pa-
rameter (default: PV)
biG Hi
biG Lo
brEAK
byPASS
C CAL
C Hi
C Lo
tArE
Max on Big Display
Min on Big Display
Loop Break
Bypass
Current Calibration
Current High
Current Low
Capture Tare
92
Assign digital input to display max on the
main display
Assign digital input to display min on the
main display
Set relay condition if loop break detected
Set filter bypass value
Calibrate 4-20 mA current input (internal
reference source used for scaling the input)
Calibrate high current input (e.g. 20 mA)
Calibrate low current input (e.g. 4 mA)
Capture tare
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
CAL
CAL ib
ContrL
CoPy
CutoFF
d GroS
d nt-G
d Hi
d HL
d HoLd
d Lo
d PCt
Calibrate
Calibrate
Control
Copy
cuttoff
Display Gross
Display Net/Gross
Display High
Display H&L
Display Hold
Display Low
Display PCT
Enter the
Calibrate 4-20 mA output (internal reference
source used for scaling the output)
Enter
analog outpuit manually, or return
meter to automatic operation
Enter copy function
Set low-flow cutoff
Select to display the gross
Select to display the net/gross
Select to display the max
Select to display the max & min toggling
Display hold
Select to display the min
Select to display percent of PV1 (dual-scale
display)
Calibration
Control
menu
menu to turn relays on/off, set
d PU
d PU 1
d PU2
d r-u
d unit
dEc Pt
dELAy
d i 1
diAG
diAmr
d-inty
di5 1
diS 2
Display PV
Display PV1
Display PV2
Display r-u
Display Units
Decimal Point
Delay
Digital Input 1
Diagnostics
Diameter
Display Intensity
Display 1
Display 2
Select to display PV
Select to display PV1 (dual-scale display)
Select to display PV2 (dual-scale display)
Select to display reading and units
Select to display engineering units or label
Set decimal point
Enter relay
Assign digital input 1-8, if expansion modules
are connected
Display parameter settings
Enter the tank’s diameter in inches
Set display intensity level from 1 to 8
Program display 1 value
Program display 2 (up to 32 points)
Time Delay
menu
93
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
diSAbL
dLy 1
d0 1
donE
d-SCAL
dSEt 1
dSPLAy
EntEr
Error
F On 1
F1
F2
Disable
Delay 1
Digital Output 1
Done
Dual-scale
Display Set 1
Display
Enter Button
Error
Force On 1
F1 Function Key
F2 Function Key
Disable function key
Enter relay 1 time delay setup (1-8)
Assign digital output 1-8, if expansion modules
are connected
Copy function completed
Enter
d-SCAL
dual-scale display or
display
Select to display set point 1 (1-8)
Enter the
Assign digital input to Enter button/F3
Error, calibration not successful, check signal
or programmed value
Force relay 1 on using digital input (1-8)
Assign F1 function key
Assign F2 function key
menu and select
No
Display
menu
Yes
for
for single scale
F3
F4
FAiLSF
FiLtEr
FLS 1
ForcE
Functn
iCAL
iGnorE
InFo
InP 1
Inp 2
F3 Function Key
F4 Function Key
Fail-safe
Filter
Fail-safe 1
Force
Signal Input
Conditioner
Internal Source
Calibration
Ignore
Information
Input 1
Input 2
Assign F3 function key
Assign F4 function (digital input)
Enter
Fail-safe
Set noise filter value
Set relay 1 fail-safe operation (1-8)
Force analog output value for loop break
Select linear, square root, programmable ex-
ponent, or round horizontal tank function
Enter internal source calibration (used for scaling the meter without a signal source)
Ignore loop break condition
Display software and S/N information
Calibrate input 1 signal or program input 1
value
Calibrate input 2 signal or program input 2
value (up to 32 points)
menu
94
Model BD300 Analog Input Process Meter Instruction Manual
DisplayParameterAction/Setting
Return to Table of Contents
inPut
LAtCH
LEd t
LEnGth
LinEAr
Lit Hi
Lit HL
Lit Lo
LittLE
Locd
Lt-CLr
m A
m An
Input
Latching
LED Test
Length
Linear
Max on Little Display
Max/Min Little Display
Min on Little Display
Little Display
Locked
Latching-cleared
4-20 mA
Manual
Enter
Input
selection menu
Set relay for latching operation
Test all LEDs
Enter the tank’s length in inches
Set meter for linear function and select number
of linearization points
Assign digital input to display max on the small
display
Assign digital input to toggle max/min on the
small display
Assign digital input to display min or the small
display
Press Enter to assign the small display
Enter password to unlock meter
Set relay for latching operation with manual
reset only after alarm condition has cleared
Set meter for 4-20 mA input
Press Enter to manually control relays or ana-
log output operation
m AX
m buS
m Enu
m in
no PtS
O HoLd
OFF
Off 1
On
On 1
O-rAnG
Maximum
Modbus
Menu Button
Minimum
Number of Points
Relays Output Hold
Off
Off 1
On
On 1
Overrange
Program maximum mA output allowed
Select to display Modbus input or to assign
Modbus input as the analog output source
Assign digital input to Menu button
program minimum mA output allowed
Set meter for 2 to 32-point linearization
Assign digital input to hold all relays state
Disable relay and front panel status LED, turn
relays off, program off time delay
Set relay 1 Off time delay (1-8)
Enable fail-safe operation, turn relays on, pro-
gram on time delay
Set relay 1 On time delay (1-8)
Program mA output for display overrange
95
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.