4.9CONNECTIONS FOR VERSION LE (MOTOCONDENSING) AND LC (MOTOEVAPORATING) 36
4.9.1Refrigerant connections36
4.9.2Route of pipes and maximum distance between sections36
4.9.3Procedures to follow when sizing refrigerant lines36
4.9.4Version LE: evaporating section at lower level than condensing section:36
4.9.5Version LE: evaporating section positioned higher than the condensing unit section37
TABLE 1 - EXTERNAL PIPE DIAMENTERS FOR VERSIONS LE, LE/HP37
4.9.6Version LC: remote condenser above the evaporating unit:38
4.9.7Version LC: remote air cooled condenser below the evaporating unit:38
TABLE 2 - PIPE DIAMETER FOR VERSIONS LC39
4.9.8Connection of Sigma 2002 LC/HP units to a remote air cooled condenser.39
TABLE 3 - CONNECTION PIPE EXTERNAL DIAMETERS FOR VERSIONS LC/HP40
4.10PRESSURE RELIEF VALVES40
4.11WATER QUALITY40
4.12LOW TEMPERATURE WATER AT CONDENSER41
4.13OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR41
TABLE 4 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES41
OPERATING LIMITS42
4.14Water flow rate to evaporato and condenser43
4.15EVAPORATOR ChilleD water temperature43
CONDENSER PRESSURE DROP43
EVAPORATOR PRESSURE DROP45
4.16ELECTRICAL CONNECTIONS46
4.16.1General46
4.16.2Power supply to crankcase heaters47
4.16.3Potential free contacts47
4.16.4Flow switch electrical connections47
4.16.5Circulating pump electrical connections47
4.16.6External interlock47
4.17MICROPROCESSOR CONTROLLERS47
4.17.1Microprocessor controller for /LE and HP/LE versions48
4.17.2RS485 serial interface (optional)48
5.START-UP56
5.1PRELIMINARY CHECKS56
6UNIT WITH mCHILLER MICROPROCESSOR (models from 3.2 to 13.2)57
6.1.1Display57
6.1.2Machine status information57
6.1.3Keypad57
6.1.4Control and display screens58
6.1.5Muting the BUZZER58
6.1.6ALARMS reset58
6.1.7Activation/deactivation of COOLING operation (summer mode)59
6.1.8Activation/deactivation of HEATING mode (winter mode)59
Blue Box
Page 5
6.1.9Switching off the machine (stand by)59
6.1.10Inlet water temperature control60
6.1.11Defrosting (only /LC, heat pump units)60
6.2STARTING THE UNIT62
6.3STOPPING THE UNIT62
6.3.1Temporary stop62
6.3.2Seasonal stop:63
6.4EMERGENCY STOP63
7.TROUBLESHOOTING63
8UNIT WITH pCO2 MICROPROCESSOR (models from 14.4 to 26.4)71
8.1General71
8.1.1Display71
8.1.2Keypad71
8.2OPERATING DESCRIPTION73
8.2.1Introduction73
8.2.2Unit in stand-by mode73
8.2.3Enabling the unit73
8.2.4Pumps management73
8.2.5Compressor start-up73
8.2.6Chiller mode operation73
8.2.7Heat pump mode operation74
8.2.8Evaporator low temperature chilled water protection74
8.2.9Evaporator anti-freeze protection electric heater (optional)74
8.2.10Compressor operation74
8.2.11Compressor management75
8.2.12High and low pressure alarms75
8.2.13Changeover from chiller to heat pump and vice versa75
8.2.14Desuperheater (Option)75
8.2.15Total heat recovery (only SIGMA 2002/DC)75
8.2.16Dual set-point (option)76
8.2.17Leaving water temperature control (option)76
8.2.18Defrost (heat pumps units /LC)76
8.3STARTING THE UNIT78
8.4STOPPING THE UNIT78
8.4.1Temporary stop:78
8.4.2Seasonal stop:78
8.5EMERGENCY STOP78
9TROUBLESHOOTING79
10CHECKS DURING OPERATION87
10.1Checking the refrigerant charge87
11.CALIBRATION OF CONTROL EQUIPMENT88
11.1INTRODUCTION88
TABLE 5 - CALIBRATION OF CONTROL EQUIPMENT88
TABLE 6 - CALIBRATION OF SAFETY DEVICES88
12.MAINTENANCE AND PERIODIC CHECKS89
12.1WARNINGS89
12.2INTRODUCTION89
12.3REPAIRING THE REFRIGERANT CIRCUIT90
12.3.1Leak test90
12.3.2High vacuum and dehydration of the refrigerant circuit90
12.3.3Refrigerant charge91
Blue Box
Page 6
12.4ENVIRONMENTAL CONSIDERATIONS91
13.DECOMMISSIONING THE UNIT92
REFRIGERANT CIRCUIT DIAGRAM93
DIMENSIONS, WEIGHTS AND HYDRAULIC CONNECTIONS105
Blue Box
Page 7
SIGMA 2002 - water chiller
Water-cooled liquid chillers with hermetic scroll compressors and plate type evaporator, suitable for inside
installations.
TECHNICAL CHARACTERISTICS
UNIT FRAME
Self supporting frame, constructed in galvanized sheet steel with RAL 7032 powder paint baked at 180°C to
provide a durable weatherproof finish.
Models 3.2 to 7.2 and model 14.4 are completely enclosed by painted steel panels fully lined with a sound
absorbing material.
On models 8.2 to 13.2 only the upper compartment, which contains the compressors, is fully enclosed on all sides
by painted steel panels fully lined with a sound absorbing material.
On models 8.2 to 13.2 only the upper compartment , which contains the compressors, and the separator between
this compartment and the lower part of the unit are enclosed by painted steel panels fully lined with a sound
absorbing material.
Models 16.4 to 26.4 do not have panels.
COMPRESSORS
Hermetic scroll type with orbital motion, connected in tandem and equipped with oil level sight glass, Klixon
internal thermal protection and oil equalisation line.
EVAPORATOR AND CONDENSER
Brazed plate type in 316 AISI stainless steel. Thermal insulation of evaporator is provided by closed cell expanded
material. Each evaporator is equipped with a low water temperature probe for freeze protection and each unit is
equipped as standard with a mechanical flow switch.
REFRIGERANT CIRCUIT
Comprising: liquid valve, charge connection, liquid sight-glass, filter/dryer, thermostatic expansion valve with
external pressure equalisation, high and low pressure switches for 2-compressor models.
For 4-compressor models high and low pressure values and relative condensation and evaporation temperatures
are measured by pressure transducers that relay the signals to the controller so that they can be read directly on
the display. The high pressure side of the circuit is equipped with high pressure switches and relief valves.
ELECTRICAL PANEL
The electrical panel includes:
- main switch
- fuses for the auxiliary and power circuit
- compressor contactors
- microprocessor mCHILLER for 2 compressor units and PCO2 for 4 compressors units, controlling the following
functions:
- water temperature regulation
- freeze protection
- compressor time intervals
- compressor start sequence and automatic lead/lag selection
- alarm reset
- common alarm contact for remote signalling
- operating and alarm indicator LEDs
- LCD display of the following information:
- water inlet and outlet temperature
- programmed temperature set-point and differential
- alarms description
- compressor hours run meter for units with PCO2 control
- number of starts of the unit and the compressors
- high and low pressure values and relative condensation and evaporation temperature values.
Electrical power supply [V/f/Hz]: 400/3~/50 ±5%
Blue Box - 1
Page 8
CONTROLS AND SAFETY DEVICES
- High pressure switch with manual reset.
- High pressure safety, with manual reset, controlled by the unit controller on four compressors models.
- Low pressure safety switch, with manual reset, controlled by the unit controller for four compressor models, low
pressure switch, with manual reset, controlled by the unit microprocessor for the two compressors models.
- High pressure relief valve
- Chilled water temperature sensor (at the evaporator inlet); on four compressors model it is installed on one
evaporator only.
- Freeze protection sensor at the outlet of each evaporator.
- Mechanical flow switch supplied as standard as kit with the unit.
- Compressor over-temperature protection
TESTING
The units are subjected to a dry run in the factory and supplied complete with oil and refrigerant.
SIGMA UNIT VERSIONS
SIGMA 2002/HP: reverse cycle heat pump
The heat pump version operates as a water cooled chiller in summer and a water to water heat pump in winter
by reversing the refrigerant flow to suit the required operating mode.
In addition to the components of version SIGMA 2002, the heat pump version includes:
REFRIGERANT CIRCUIT: 4-way reversing valve and a second thermostatic expansion valve.
ELECTRICAL PANEL: Microprocessor programmed for summer/winter changeover (the Macroplus microprocessor
is used on 4 compressor HP units).
SIGMA 2002/LE: motocondensing unit
The unit is designed to operate with a remotely located refrigerant to air evaporator. It is supplied without a
refrigerant to water evaporator and thermostatic expansion valve. The solenoid valve on the liquid line is supplied
as standard. Models 3.2 to 13.2 have mchiller control and the remainder of the range is supplied without control.
The standard supply is ON/OFF for each compressor from a digital entry.
SIGMA 2002/LE/HP: motocondensing unit
The unit is designed to operate with a remotely located refrigerant to air evaporator. It is supplied without a
refrigerant to water evaporator and thermostatic expansion valve.
The solenoid valve on the liquid line and liquid receivers are supplied as standard. Models 3.2 to 13.2 have
mCHILLER control and the remainder of the range is supplied without control. The standard supply is ON/OFF for
each compressor from a digital entry.
SIGMA 2002/LC: motoevaporating unit.
The unit is supplied without a water cooled condenser and is designed to be connected to a remotely located air
cooled condenser.
SIGMA 2002 / LC /HP: motoevaporating unit
The unit is supplied without a water cooled condenser and is designed to be connected to a remotely located air
cooled condenser.
The solenoid valve on the liquid line and the liquid receivers are supplied as standard.
ACCESSORY VERSIONS
SIGMA 2002 /DC: unit with heat recovery condenser.
Not available for HP versions.
In addition to the components of version SIGMA 2002 this unit includes a 100% heat recovery condenser, for the
production of hot water, and a liquid receiver on each refrigerant circuit.
SIGMA 2002 /DS: unit with desuperheaters
Available for all models. A brazed plate type heat recovery exchanger (desuperheater) is arranged in series with
the condenser. Also available on all HP models. In this case an isolating valve must be fitted on the water
recovery circuit and be closed during heat pump mode operation as described in the manual.
Blue Box - 2
Page 9
SIGMA LN: low noise unit
Low noise units units are completely enclosed with painted steel panels lined with sound absorption material
having an intermediate layer of high acoustic impedance material.
REFRIGERANT CIRCUIT ACCESSORIES:
- Compressor suction and discharge valves
Ball valve fitted in the equalisation line
- Pressostatic valve (with solenoid valve on heat pump)
- Liquid line solenoid valve
- Pressure gauges.
On all units with a PCO2 controller the suction and discharge pressures are displayed on the controller. Gauges
on standard units are located inside the compressor compartment.
- Liquid receivers (standard on versions /LE/HP e LC/HP LC/DC e DC)
- Dual set-point.
With double thermostatic expansion valves and solenoid valves, the evaporator of “double set point units” is
sized on the basis of high temperature operation.
On units with mCHILLER control, the set must be manually modified on the microprocessor control panel.
On units with pCO2 control the two values can be set from the keypad or via a digital input. In all cases the
commutation between the two thermostatic expansion valves is automatic on the basis of the water tempera-
ture. Thermostatic expansion valve selection is made according to the temperature values specified at the time
of order. The operating limits remain unchanged and are as per the catalogue. If glycol is used, in a sufficient
percentage to avoid freezing, the lower limit of the leaving water is extended to a minimum of -5 °C.
- Condenser for well water (only standard version and LE).
HYDRAULIC CIRCUIT ACCESSORIES
- Leaving water temperature control.
Available only on units with control pCO2 (not HP versions).
- Water manifold
(only 4 compressors models). Available for condensers, evaporators and heat recovery.
ELECTRICAL ACCESSORIES
- Power factor correction cos f fg0.9 at nominal operating conditions
- Single voltage-free contacts for machine status signals
- Serial interface. In units with a mCHILLER controller ( 3.2-13.2) the serial interface is the RS485 type with a Carel
protocol. In units with a PC02 control (from 14.4-26.4 excluding HP versions) the serial interface is the RS485
type with a Modbus protocol. Special protocols can be ordered: Carel; Echelon in RS485 or FTT10 versions. HP
units can be supplied with a Macroplus microprocessor controller with a RS422 type serial interface; refer to the
manual enclosed with the unit.
- Remote user terminal panel (in addition to the standard terminal)
Not available on HP units (with a Macroplus controller)
- Set point variable with remote signal (0-1V, 0-10V, 0-4mA, 0-20mA) available only on units with a PC0
controller, only in cooling mode. At the time of order. The set point values must be specified at the time of
order.
2
VARIOUS ACCESSORIES
- Rubber antivibration mountings.
- Timber crate packing
- Pallet/skid for shipment in a container
- Non-standard RAL paint colours
- Unit completely pre-assembled, the unit will be supplied without refrigerant charge, test and PED certificate.
- Modular pre-asembled unit, only 4 compressors models, with the exception of model 14.4.
Blue Box - 3
Page 10
SERIES
Press. massima circuito refriger.
Max. Refrigerant circuit pressure
Pression maxi circuit refrigerant
Carica refrigerante per circuito(kg)/Refrigerant charge per circuit
C3
C4
0062
0062
Via Enrico Mattei, 20
Via Enrico Mattei, 20
REFRIGERANTE
The SIGMA 2002 series of water cooled chillers, for installation inside the building, are available in various sizes
with capacities from 42 to 297 kW.
Model designations consist of two numbers:
SIGMA 2002 16.4
Shows the model number of compressors
The model, serial number, characteristics, power supply, etc. are shown by means of decals on the unit.
(l/h)8.80910.61612.36714.280
Condenser pressure dropkPa72,565,95751,5
Evaporator water flowl/s1,8432,2162,592,997
(l/h)6.6367.9799.32410.788
Evaporator pressure dropkPa21,220,92215,3
Compressorstype
Quantityn
Refrigerant circuitsn
Absorbed power cooling (*)kW9,911,813,515,8
Absorbed power heating (**)kW12,615,317,720,3
Capacity steps%0-50-1000-50-1000-50-1000-50-100
Refrigerant charge
Chiller versionkg1 x 3,81 x 4,81 x 5,91 x 8 ,5
Heat pump versionkg1 x 4,31 x 5,11 x 6,11 x 6 ,6
Oil
Oil chargel2 x 3,32 x 3,252 x 3,81 x 4 + 1 x 3,8
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel1 x 2,91 x 3,81 x 4,91 x 5,5
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 3,11 x 3,91 x 4,71 x 7,5
Max operating pressure water sidebar30303030
Dimension and weight
Lengthmm1.3341.3341.3341.334
Widthmm797797797797
Heigthmm962962962962
Shipping weightkg379403414447
scroll
2
1
Maneurop
160 SZ
plate heat exchanger
plate heat exchanger
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 5
Page 12
TECHNICAL DATATECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATATECHNICAL DATA
Refrigerant R407CRefrigerant R407C
Refrigerant R407C
Refrigerant R407CRefrigerant R407C
MODEL SIGMA 20027.28.29.210.2
Cooling (*)
Nominal capacitykW7889,9105,9121,8
Evaporator water flowl/s3,7274,2965,0585,82
(l/h)13.41815.46718.21020.953
Evaporator pressure dropkPa35,43541,437
Condenser water flowl/s4,5875,2916,2367,18
(l/h)16.19318.69522.06225.429
Condenser pressure dropkPa50,550,259,353,4
Evaporator water flowl/s3,4043,914,6155,32
(l/h)12.25314.07516.61319.150
Evaporator pressure dropkPa14,815,415,616,8
Compressorstype
Quantityn
Refrigerant circuitsn
Absorbed power cooling (*)kW1820,824,628,5
Absorbed power heating (**)kW22,926,931,736,5
Capacity steps%0-50-1000-50-1000-50-1000-50-100
Refrigerant charge
Chiller versionkg1 x 9,91 x 11,41 x 12,91 x 15,9
Heat pump versionkg1 x 7,71 x 91 x 10,41 x 13
Oil
Oil chargel2 x 42 x 6,61 x 8 + 1 x 6,62 x 8
Oil producer
Oil type
Evaporatortype
Heat exch anger water volumel1 x 6,31 x 7,41 x 8,41 x 10,5
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 8,751 x 101 x 11,251 x 13,75
Max operating pressure water sidebar30303030
Dimension and weight
Lengthmm1.3341.3561.3561.356
Widthmm797768768768
Heigthmm9621.7001.7001.700
Shipping weightkg470483560648
plate heat exchanger
plate heat exchanger
scroll
2
1
Maneurop
160 SZ
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 6
Page 13
TECHNICAL DATATECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATATECHNICAL DATA
Refrigerant R407CRefrigerant R407C
Refrigerant R407C
Refrigerant R407CRefrigerant R407C
MODEL SIGMA 200212.213.214.416.4
Cooling (*)
Nominal capacitykW135,2148,5156179,9
Evaporator water flowl/s6,4587,0957,4548,593
(l/h)23.24725.54126.83630.934
Evaporator pressure dropkPa3536,135,435
Condenser water flowl/s7,9628,7439,17410,582
(l/h)28.36331.29732.38637.391
Condenser pressure dropkPa51,153,150,550,2
Evaporator water flowl/s5,9396,5596,8077,82
(l/h)21.38223.61324.50628.150
Evaporator pressure dropkPa18,116,414,815,4
Compressorstype
Quantityn
Refrigerant circuitsn
Absorbed power cooling (*)kW31,534,53641,6
Absorbed power heating (**)kW40,644,745,853,7
Capacity steps%0-50-1000-50-1000-25-50-75-100 0-25-50-75-100
Refrigerant charge
Chiller versionkg1 x 17 ,41x 20 ,72 x 9,92x 11,4
Heat pump versionkg1 x 14,41 x 17,82 x 7,72 x 9
Oil
Oil chargel2 x 82 x 84 x 44 x 6,6
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel1 x 11,61 x 14,32 x 6,32 x 7,4
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 151 x 17,52 x 8,752 x 10
Max operating pressure water sidebar30303030
Dimension and weight
Lengthmm1.3561.3561.4262.476
Widthmm768768801768
Heigthmm1.7001.7001.7871.700
Shipping weightkg688741810928
24
12
scroll
Maneurop
160 SZ
plate heat exchanger
plate heat exchanger
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 7
Page 14
TECHNICAL DATATECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATATECHNICAL DATA
Refrigerant R407CRefrigerant R407C
Refrigerant R407C
Refrigerant R407CRefrigerant R407C
MODEL SIGMA 200218.420.424.426.4
Cooling (*)
Nominal capacitykW211,7243,6270,3297
Evaporator water flowl/s10,11711,64112,91514,19
(l/h)36.42041.90646.49451.083
Evaporator pressure dropkPa41,4373536,1
Condenser water flowl/s12,47114,36115,92417,487
(l/h)44.12450.85856.72662.593
Condenser pressure dropkPa59,353,451,153,1
Evaporator water flowl/s9,22910,63911,87913,118
(l/h)33.22638.30142.76347.225
Evaporator pressure dropkPa15,616,818,116,4
Compressorstype
Quantityn
Refrigerant circuitsn
Absorbed power cooling (*)kW49,356,96369
Absorbed power heating (**)kW63,47381,289,3
Capacity steps%0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100
Refrigerant charge
Chiller versionkg2 x 12,92 x 15,92 x 17,42 x 20,7
Heat pump versionkg2 x 10,42 x 132 x 14,42 x 17,8
Oil
Oil chargel2 x 8 + 1 x 6,64 x 84 x 84 x 8
Oil producer
Oil type
Evaporatortype
Heat exch anger water volumel2 x 8,42 x 10,52 x 11,62 x 14,3
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel2 x 11,252 x 13,7 52 x 152 x 17 ,5
Max operating pressure water sidebar30303030
Dimension and weight
Lengthmm2.4762.4762.4762.476
Widthmm768768768768
Heigthmm1.7001.7001.7001.700
Shipping weightkg1.0691.2101.2261.270
plate heat exchanger
plate heat exchanger
scroll
4
2
Maneurop
160 SZ
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 8
Page 15
ELECTRICAL CHARACTERISTICS Refrigerant R407C
MODEL SIGMA 20023.24.25.26.2
Maximum absorbed power
Maximum starting currentA115150145175
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW16,419,424,427,3
A34405054
400/3~/50
230/~/50
MODEL SIGMA 20027.28.29.210.2
Maximum absorbed power
Maximum starting currentA179210250265
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW30,236,241,446,6
A587085100
400/3~/50
230/~/50
MODEL SIGMA 200212.213.214.416.4
Maximum absorbed power
Maximum starting currentA320339237280
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW51,656,660,472,4
A119138116140
400/3~/50
230/~/50
MODEL SIGMA 200218.420.424.426.4
Maximum absorbed power
Maximum starting currentA335365439477
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW82,893,2103,2113,2
A170200238276
400/3~/50
230/~/50
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size
the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the
unit).
Blue Box - 9
Page 16
TECHNICAL DATARefrigerant R22
MODEL SIGMA 20023.24.25.26.2
Cooling (*)
Nominal capacitykW42,551,959,168,1
Evaporator water flowl/s2,032,482,8233,253
(l/h)7.3098.92810.16211.710
Evaporator pressure dropkPa48,345,137,334,1
Condenser water flowl/s2,4973,0323,4493,981
Nominal capacitykW52,463,972,483,5
Condenser water flowl/s2,5053,0513,4583,989
(l/h)9.01810.98412.45014.360
Condenser pressure dropkPa73,167,855,650,2
Evaporator water flowl/s1,9122,3452,6613,065
(l/h)6.8848.4439.57811.034
Evaporator pressure dropkPa21,922,522,315,4
Compressorstype
Quantityn
Absorbed power cooling (*)kW9,811,513,115,2
Absorbed power heating (**)kW12,414,816,719,3
Capacity steps%0-50-1000-50-1000-50-1000-50-100
Refrigerant charge
Chiller versionkg1 x 3,81 x 4,81 x 5,91 x 8,5
Heat pump versionkg1 x 4,31 x 5,11 x 6,11 x 6,6
Oil
Oil chargel2 x 3,32 x 3,252 x 3,81 x 4 + 2 x 3,8
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel1 x 2,91 x 3,81 x 4,91 x 5,5
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 1,71 x 2,11 x 2,51 x 1,5
Max operating pressure water sidebar30303030
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 10
Page 17
TECHNICAL DATARefrigerant R22
MODEL SIGMA 20027.28.29.210.2
Cooling (*)
Nominal capacitykW77,188,5104,5120,5
Evaporator water flowl/s3,6834,2284,9925,757
(l/h)13.25715.22017.97220.725
Evaporator pressure dropkPa33,432,73935
Condenser water flowl/s4,5135,1856,1297,074
Nominal capacitykW94,6108,4128,7148,9
Condenser water flowl/s4,5195,186,1487,116
(l/h)16.26918.64922.13425.619
Condenser pressure dropkPa49,148,157,652,3
Evaporator water flowl/s3,4693,9714,7095,447
(l/h)12.48914.29516.95219.609
Evaporator pressure dropkPa14,815,315,617
Compressorstype
Quantityn
Absorbed power cooling (*)kW17,42023,827,6
Absorbed power heating (**)kW2225,330,134,9
Capacity steps%0-50-1000-50-1000-50-1000-50-100
Refrigerant charge
Chiller versionkg1 x 9,91 x 11,41 x 12,91 x 15,9
Heat pump versionkg1 x 7,71 x 91 x 10,41 x 13
Oil
Oil chargel2 x 42 x 6,61 x 8 + 1 x 6,62 x 8
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel1 x 6,31 x 7,41 x 8,41 x 10,5
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 1,81 x 21 x 2,31 x 2,8
Max operating pressure water sidebar30303030
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 11
Page 18
TECHNICAL DATARefrigerant R22
MODEL SIGMA 200212.213.214.416.4
Cooling (*)
Nominal capacitykW133,7146,9154,2177
Evaporator water flowl/s6,3897,0217,3658,455
(l/h)23.00025.27526.51430.440
Evaporator pressure dropkPa33,134,133,432,7
Condenser water flowl/s7,8488,6239,02610,369
Nominal capacitykW166,1183,3189,2216,8
Condenser water flowl/s7,9378,7589,03810,36
(l/h)28.57431.52832.53837.298
Condenser pressure dropkPa49,951,949,148,1
Evaporator water flowl/s6,0816,7166,9397,942
(l/h)21.89324.17724.97928.590
Evaporator pressure dropkPa18,316,514,815,3
Compressorstype
Quantityn
Absorbed power cooling (*)kW30,633,534,840,1
Absorbed power heating (**)kW38,842,743,950,6
Capacity steps%0-50-1000-50-1000-50-1000-25-50-75-100
Refrigerant charge
Chiller versionkg1 x 17,41x 20,72 x 9,92x 11,4
Heat pump versionkg1 x 14,41 x 17,82 x 7,72 x 9
Oil
Oil chargel2 x 82 x 84 x 44 x 6,6
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel1 x 11,61 x 14,32 x 6,32 x 7,4
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel1 x 31 x 3,52 x 1,82 x 2
Max operating pressure water sidebar30303030
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 12
Page 19
TECHNICAL DATARefrigerant R22
MODEL SIGMA 200218.420.424.426.4
Cooling (*)
Nominal capacitykW209241267,4293,9
Evaporator water flowl/s9,98511,51412,77814,042
(l/h)35.94441.44946.00050.550
Evaporator pressure dropkPa393533,134,1
Condenser water flowl/s12,25814,14715,69717,247
Nominal capacitykW257,4297,9332,3366,6
Condenser water flowl/s12,29714,23315,87417,516
(l/h)44.26851.23857.14763.056
Condenser pressure dropkPa57,652,349,951,9
Evaporator water flowl/s9,41810,89412,16313,432
(l/h)33.90439.21843.78648.354
Evaporator pressure dropkPa15,61718,316,5
Compressorstype
Quantityn
Absorbed power cooling (*)kW47,655,161,167,1
Absorbed power heating (**)kW60,369,977,785,5
Capacity steps%0-25-50-75-100 0-25-50-75-100 0-25-50-75-100 0-25-50-75-100
Refrigerant charge
Chiller versionkg2 x 12,92 x 15,92 x 17,42 x 20,7
Heat pump versionkg2 x 10,42 x 132 x 14,42 x 17,8
Oil
Oil chargel2 x 8 + 2 x 6,64 x 84 x 84 x 8
Oil producer
Oil type
Evaporatortype
Heat exchanger water volumel2 x 8,42 x 10,52 x 11,62 x 14,3
Max operating pressure water sidebar30303030
Condensertype
Condenser water volumel2 x 2,32 x 2,82 x 32 x 3,5
Max operating pressure water sidebar30303030
(*) evaporator entering/leaving temperature 12-7 °C;
condenser entering/leaving temperature 30-35 °C
(**) condenser entering/leaving temperature 40-45 °C;
evaporator entering/leaving temperature 15-10 °C.
Blue Box - 13
Page 20
ELECTRICAL CHARACTERISTICS Refrigerant R22
MODEL SIGMA 20023.24.25.26.2
Maximum absorbed power
Maximum starting currentA115150145175
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW16,418,422,825,8
A34405054
400/3~/50
230/~/50
MODEL SIGMA 20027.28.29.210.2
Maximum absorbed power
Maximum starting currentA179210250265
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW28,83439,945,8
A587085100
400/3~/50
230/~/50
MODEL SIGMA 200212.213.214.416.4
Maximum absorbed power
Maximum starting currentA320339237280
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW50,655,457,668
A119138116140
400/3~/50
230/~/50
MODEL SIGMA 200218.420.424.426.4
Maximum absorbed power
Maximum starting currentA335365439477
Full load current
(2)
Power supplyV/f/Hz
Control power supplyV/f/Hz
(1)
kW79,891,6101,2110,8
A170200238276
400/3~/50
230/~/50
(1) mains power supply to allow unit operation.
(2) maximum current before safety cut-outs stop the unit. This value is never exceeded and must be used to size
the electrical supply cables and relevant safety devices (refer to electrical wiring diagram supplied with the
unit).
Lw: sound power values in free field conditions are calculated in accordance with ISO 3746.
Lp : sound pressure values measured at 1 m from the unit in free field conditions in compliance with ISO 3746
Blue Box - 15
Page 22
1. SAFETY PRECAUTIONS
1.1 DEFINITION OF DANGER ZONE
Only authorised operators must be allowed in the vicinity of the unit.
- The external danger zone concerns a space of approximately 2 m in width around the perimeter of the machine.
Access to this area must be prevented by suitable guarding in the event that the unit is located in an unprotected
area that is easily accessible to unauthorised persons.
1.2 SAFETY RULES
The unit is designed and built in accordance with the PED 97/23CE rules, to ensure the maximum level of safety.
To avoid possible situations of risk adhere to the following rules at all times:
- All work on the unit must be performed by qualified personnel. Before working on the unit, ensure that the
designated personnel are conversant with the documentation supplied. Always ensure there is a copy of the
documentation in the immediate vicinity of the unit.
- Use the appropriate personal safety equipment (gloves, helmet, safety goggles, safety footwear, etc.) for all
maintenance and control operations on the unit.
- Use only tools and equipment that are in good working order.
- The compressor compartment contains various high temperature components. Adopt the maximum caution
when working in the vicinity of the compressors and avoid touching any parts of the unit without appropriate
protection.
- Pipe the discharge of the relief valves.
- Do not work within the theoretical discharge trajectory of the relief valves.
Blue Box - 16
Page 23
MECHANICAL HAZARDS
The pipes are rigidly anchored to reduce
Operating mode Analysed risk or hazard Solution adopted
Normal operating regime
Maintenance
Handling during transport
and installation.
Normal Operating regime
Maintenance
Normal Operating regime
Maintenance Surfaces, sharp corners edges. In the interior parts of the unit it is not
Normal Operating regime
Maintenance Cutting or severing. The inside part of the unit does not have
Normal operating regime
Maintenance Entanglement, dragging,
Normal Operating regime
Maintenance
Stability Because of their intrinsic characteristics, the
units are not associated with problems of
possible falling or tipping while in operation.
However, you must carefully read the
descriptions given in this manual concerning
the methods of positioning the unit.
Stability The unit's base frame has specific lifting
holes, the positions of which are marked
with yellow decals, designed to eliminate the
risk of the unit tipping.
Pipe bursts.
vibration, a major cause of pipe fracture.
Surfaces, sharp corners and
edges.
Cutting or severing. The inside part of the unit does not have
Entanglement, dragging,
impact.
impact.
Projection of high pressure jets
of fluid - Explosion hazard
The machine is designed and manufactured
to minimise the presence of sharp corners
and edges as far as possible. If the unit is
located in areas easily accessible by non
qualified people provide suitable protection.
possible to completely eliminate risks derived
from the presence of surfaces, sharp corners
and edges. For this reason the user,
installation, and maintenance manual
specifies that maintenance operations be
carried out exclusively by qualified personnel,
simultaneously providing indications on the
protection to be utilised.
moving parts
moving parts
The inside part of the unit does not have
moving parts
The inside part of the unit does not have
moving parts
All units are equipped with relief valves to
eliminate the risk of explosion.
The outlet from the relief valves must be
piped appropriately to eliminate risks of
expulsion of high pressure gas from the
machine. The warnings regarding this
discharge are fixed to the unit and given in
the use and maintenance manual.
Blue Box - 17
Page 24
THERMAL HAZARDS
Operating mode Analysed risk or hazard Solution adopted
Normal operating regime
Maintenance
Burns caused by high
temperatures.
Burns caused by high
temperatures.
NOISE-RELATED HAZARDS
Operating mode Analysed risk or hazard Solution adopted
Normal operating regime
Maintenance
Hearing damage. All units are designed and manufactured
Most of the pipes that could cause burns are
lagged with thermo insulating material.
If the unit is positioned in locations easily
accessible by non qualified people provide
suitable protection.
Most of the pipes that could cause burns are
lagged with thermo insulating material.
If the unit is positioned in locations easily
accessible by non qualified people provide
suitable protection.
with to reduce noise emissions to the
minimum.
ELECTRICAL HAZARDS
Operating mode Analysed risk or hazard Solution adopted
Operating regime
Maintenance
Operating regime
Maintenance
Operating regime
Maintenance
Operating regime
Maintenance
Contact with live electrically
components (direct contact).
Elements carrying electrical
current in the case of faults.
Inappropriate insulation.
Radiated heat due to shortcircuits or overloads.
The units are designed and built in
compliance with harmonised standard EN
60204-1.
HAZARDS PRODUCED BY SUBSTANCES
Operating mode Analysed risk or hazard Solution adopted
Normal operating regime
Maintenance
contained in the unit See safety sheets of refrigerants R407C and
R22
FURTHER HAZARDS
o eliminate any further hazard it is necessary to provide adequate protection to avoid access to the unit by non
qualified people.
Liquefied gas: may cause frostbite. Contact with eyes may cause
irritation.
Keep eye wide open while rinsing. If symptoms persist, call a
physician.
plenty of water. Do not remove clothing. Wash off with warm
water. if skin irritation persists, call a physician.
Oxygen or artificial respiration if needed. Do not apply artificial
respiration if patient is breathing; Consult a physician after
significant exposure. Do not give adrenaline or similar drugs.
immediately. Do not give drugs from adrenaline-ephedrine
group.
The product itself does not burn. Extinguish with carbon dioxide,
dry chemical, foam or water spray. Use extinguishing measures
that are appropriate to the environment.
None
the presence of F and/or Cl groups. Fire or intense heat may
cause violent rupture of packages.
In case of fire, west a self contained breathing apparatus.
Protective suit.
tanks with water spray.
areas. Do not breath vapours or spray mist. Ensure adequate
ventilation.
Shut off leaks it without risk. Solid evaporates. Ensure adequate
ventilation.
Blue Box - 19
Page 26
REFRIGERANT SAFETY DATA R407C
7. HANDLING AND
STORAGE:
8. EXPOSURE
CONTROLS /
PERSONAL
PROTECTION:
9. STABILITY AND
REACTIVITY:
10. TOXICOLOGICAL
INFORMATION:
11. DISPOSAL
CONSIDERATIONS:
INFORMATIQN:
7.1 Handling: Keep away from heat, sources of ignition. Do not puncture or
drop container, Provide sufficient air exchange and / or exhaust in
work rooms.
7.2 Storage: Keep containers tightly closed in a cool, well-ventilated place.
Store in a cool and shaded area. Do not expose to temperatures
above 50 °C. Keep tightly closed.
8.1 Engineering measures
to reduce exposure:
Personal protection
8.2
equipment:
Respiratory protection: In case of insufficient ventilation wear suitable respiratory
Hand protection: Impervious butyl rubber gloves.
Eye protection: Wear as appropriate: safety glasses, gaggles, Wear face-shield
Offer surplus and non-recyclable solutions to an established
disposal company. In accordance with local and national
regulations. S59 - Refer to manufacturer/supplier for information
on recovery/recycling.
Do not reuse empty containers. Empty pressure vessels should be
returned to supplier.
Label: 2
Blue Box - 20
Page 27
REFRIGERANT SAFETY DATA - R22
1. IDENTIFICATION OF
THE SUBSTANCE
INGREDIENTS
3. HAZARDS 3.1 Major hazards: Causes damage to ozone layer.
Chemical Name CAS-No - Wt % - Symbol(s): & phrases "R" 2. COMPOSITION /
Chlorodifluoromethane 75/45/6 - 100 - R59
Eyes Rinse immediately with plenty of water for at least 15 minutes.
4.1
Skin Liquefied gas may cause frostbite. Wash frostbitten areas with
Inhalation Move to fresh air in case of accidental inhalation of vapours. Use
Ingestion Do not induce vomiting without medical advice. Call a physician
General advice Consult a physician alter significant exposure.
5.1 Suitable extinguishing
media:
5.2 Extinguishing media
which must not be
used for safety reasons:
5.3 Specific hazards: Possibility of generating hazardous reactions during a fire due to
5.4 Special protective
equipment for firefighters:
5.5 Specific methods: Standard procedure for chemical fires. In the event of fire, cool
6.1 Personal precautions: Use personal protective equipment. Evacuate personnel to safe
6.2 Methods for cleaning
up:
HCFC-22
Keep eyes wide open while rinsing. If symptoms persist, call a
physician.
plenty of water. Do not remove clothing. Wash off with warm
water. if skin irritation persists, call a physician.
oxygen or artificial respiration if needed. Do not apply artificial
respiration if patient is breathing; Consult a physician after
significant exposure. Do not give adrenaline or similar drugs.
immediately. Do not give drugs from adrenaline-ephedrine
group.
The product itself does not burn. Extinguish with carbon dioxide,
dry chemical, foam or water spray. Use extinguishing measures
that are appropriate to the environment.
None
the presence of F and/or Cl groups. Fire or intense heat may
cause violent rupture of containers.
In case of fire, wear a self contained breathing apparatus.
Protective suit.
tanks with water spray.
areas. Do not breath vapours or spray mist. Ensure adequate
ventilation.
Shut off leaks if without risk. Solid evaporates. Ensure adequate
ventilation.
Blue Box - 21
Page 28
REFRIGERANT SAFETY DATA - R22
7. HANDLING AND
STORAGE:
8. EXPOSURE
CONTROLS /
PERSONAL
PROTECTION:
9. STABILITY AND
REACTIVITY:
10. TOXICOLOGICAL
INFORMATION:
11. DISPOSAL
CONSIDERATIONS:
INFORMATIQN:
7.1 Handling: Keep away from heat, sources of ignition. Do not puncture or
drop container. Provide sufficient air exchange and / or exhaust in
plant rooms.
7.2 Storage: Keep containers tightly cl osed in a cool, well-ventilated place.
Store in a cool and shaded area. Do not expose to temperatures
above 50 °C. Keep tightly closed.
8.1 Engineering measures
to reduce exposure:
Personal protection
8.2
equipment:
Respiratory protection: In case of insufficient ventilation wear suitable respiratory
Hand protection: Impervious butyl rubber gloves.
Eye protection: Wear as appropriate: safety glasses, goggles, Wear a face-shield
No. O.N.U. 1018 12. TRANSPORT
ADR/RID UN 1018 Chlorodifluoromethane, 2, 2° A, ADR/RID
Ensure adequate ventilation, especially in confined areas.
equipment, preferably a compressed airline breathing apparatus.
and protective suit for abnormal processing problems.
Chemical resistant apron, long sleeved clothing, safety shoes.
burned, the product can give off toxic fumes . use self-contained
breathing apparatus.
halogenated compounds (e. g. acids), carbonyl halides.
10,000 ppm
Offer surplus and non-recyclable solutions to an established
disposal company. In accordance with local and national
regulations. S59 - Refer to manufacturer/supplier for information
on recovery/recycling.
Do not reuse empty containers. Empty pressure vessels should be
returned to supplier.
Label: 2
Blue Box - 22
Page 29
2. APPLICATION FIELD
SIGMA 2002 units have been designed for cooling water or water-glycol and are generally used in air conditioning
or refrigeration applications.
See chapter 6 for recommended operating ranges.
2.1 GENERAL
- When installing or servicing the unit, it is necessary to strictly follow the rules described in this manual, to
conform to all the items detailed on the unit labels and take any necessary precaution.
- Pressure in refrigerant circuits and danger from electrical shock can be hazardous when installing or servicing the
unit.
Any work on the unit must be carried out by trained people only.
The warranty will be invalid if the rules described in this manual are not observed and if any modifications are
made to the unit without prior authorisation of the manufacturer.
Attention: before repairing or servicing the unit, ensure that the electrical
supply is disconnected.
3. INSPECTION, TRANSPORT, SITE HANDLING
3.1 INSPECTION
After receiving the unit, immediately check its integrity. The unit will have left the factory in perfect condition.
Therefore on receiving the unit any damage must be verbally described to the carrier and recorded on the
Delivery Note before it is signed by both parties. Blue Box or their Agent must be informed as soon as possible of
the extent of the damage.
The Customer should prepare a written statement and photographic evidence regarding any severe damage.
3.2 LIFTING AND SITE HANDLING
Avoid sudden movements and jolts when unloading and positioning the unit. Internal handling procedures must
be conducted with care. Do not exert leverage on the components of the machine. The unit must be lifted by
inserting steel tubes through the lifting attachments shown by the relative signs (yellow arrow).
The unit must be lifted by harnessing it as shown in figure 1: use ropes or straps of sufficient length and spacer
bars to avoid damage to the unit’s side panels and cover. Alternatively, the unit (with a maximum length less than
3.5 m) can be lifted by a forklift truck, inserting the forks under the pallet.
Blue Box - 23
Page 30
Caution: ensure that the method of lifting does not allow the unit to slip
from chains and slings and does not allow the unit to turn over or slide
from lifting devices.
Side protection
(not supplied)
Side protection
(not supplied)
Space bars
(not supplied)
2 m min.
Space bars
(not supplied)
2 m min.
2 m min.
Figure 1
Blue Box - 24
Page 31
3.3 UNPACKING
When unpacking the unit pay attention not to damage the unit. Packaging consists of different materials: wood,
paper, nylon etc. Separate the materials and deliver to the proper gathering centre in order to reduce their
environmental impact.
3.4 LOCATION
The unit is suitable for inside locations where the temperature never falls below 4 °C.
Unit vibration is very low. However it is advisable, to fit a rigid rubber pad between the floor or basement and unit
base-frame.
If very low levels of vibration are required spring or rubber anti-vibration isolators should be installed. For details
see paragraph 4.2.
Rubber pad
Slab
Figure 2
Blue Box - 25
Page 32
4. INSTALLATION
4.1 CLEARANCES
Minimum clearances for all units should be as follows:
- Long side: 800 mm to allow hydraulic connection to the system and servicing operations;
- Front side: 800 mm to allow access to electric board;
- Rear side: 800 mm to allow maintenance operations;
- Above the unit: 1000 mm.
800
800
800
800
Figure 3
4.2 ANTI-VIBRATION ISOLATORS (option)
It is recommended that the unit is installed on rubber or spring anti-vibration mountings, supplied as an option, to
reduce vibrations transmitted to the building structure. It is advisable to use rubber isolators for units installed in
the basement, or ground floors in contact with the earth, and spring isolators for units installed on intermediate
floors.
The anti-vibration isolators must be installed before the unit is positioned.
Ensure that during lifting the unit is firmly secured with straps.
4.2.1 Rubber Anti-Vibration Isolators
Rubber isolators are made of an upper metallic bell with a fixing screw to the base-frame of the unit. The isolator
is fixed at the foundation via 2 holes on the flange. On the flange there is a number (45, 60, 70 ShA) which
identifies the hardness of the rubber isolator. The dimensional drawing, enclosed in the machine, shows the unit
footprint with the position and weight of each isolator.
Rubber/metal anti-vibration
isolator
Designed to reduce the vibration.
Figure 4
Blue Box - 26
Page 33
4.3 WATER PIPING CONNECTIONS
Unit water pipework must be installed in accordance with national and local regulation and codes.
Follow the recommendations below when designing the water piping circuit (refer to the diagrams included in this
manual).
- Piping should be connected to the unit with flexible joints, to avoid vibration transmission and allow for thermal
expansion (the same procedure should be adopted for the circulating pumps).
- The following devices should be located on the piping system:
- isolating/regulating valves, temperature gauges or thermometer pockets, pressure gauges or binder points
required for servicing operations.
- Serviceable mesh strainer, with a filtration level no larger than 1mm, located on the unit inlet to prevent
debris from entering the heat exchangers.
- vent valves, to be installed in the upper parts of the circuit, for air bleeding.
- expansion device with accessories for circuit pressurisation, water thermal expansion compensation and
system filling.
- unload valve and if necessary drainage tank for circuit emptying during maintenance and seasonal stop.
It is recommended that a safety valve is installed that can discharge the
system in dangerous situations such as fire. The valve must be connected
to a vent pipe with a cross sectional area equal to or greater than the
valve and must be directed into a safe zone where people cannot be
injured.
In all units with four compressors the water inlets and outlets of the
condensers, evaporators and heat recovery heat exchangers must be
connected together with a manifold (available as an option).
Blue Box - 27
Page 34
8 Thermometer
9 Water filter
10 Vent valve
11 Flexible connection
12 System filling valve
2 Expansion tank
3 Safety valve
4 Check valve
1 Circulating pump
5 Ball valve
* Only HP version
13 Water drain
14 Flow switch
6 Tank
7 Water gauge
SUGGESTED HYDRAULIC CIRCUIT DIAGRAM FOR UNITS SIGMA 2002
Blue Box - 28
LEGEND
Page 35
4.4 EVAPORATOR WATER PIPE CONNECTIONS
The water inlet and outlet must be connected in the positions indicated
as labelled on the unit.
EVAPORATOR WATER
If incorrectly connected the antifreeze thermostat will not operate and the evaporator may freeze.
The hydraulic connections are threaded. The type and size are indicated on the dimensional drawings at the end
of this manual.
A constant water flow to the evaporator must be guaranteed at all
operating conditions to prevent liquid refrigerant from entering the
compressor and causing irreparable damage.
Compressors start and stop often due to changes in cooling demand. In hydraulic circuits with low water volume,
where the thermal inertia action is low, it is advisable to verify that the water volume equals or exceeds the
following ratio:
24 · Q
COMPTOT
M>= ---------------------
N
where:
M= system water content [kg]
Q
COMPTOT
= unit cooling capacity [kW]
N= number of capacity steps
If the water volume does not reach the value given by the formula, it is advisable to provide the circuit with a
storage vessel to increase the volume (tank + circuit) to match the result of the formula.
The chilled water piping and storage vessel must be insulated to prevent condensation on the pipe surfaces and
to avoid circuit performance losses.
On all units it is compulsory to install a flow switch. If a flow switch is not
installed, on the evaporator leaving water connection, the warranty will
be terminated immediately.The flow switch must be installed, by the
contractor, on the evaporator water outlet connection labelled with:
EVAPORATOR WATER
HEAT PUMP units require a second flow switch is provided with the unit.
This must be installed, by the contractor, on the condenser outlet
connection labelled with:
CONDENSER WATER
Blue Box - 29
Page 36
All units are equipped with plate heat exchangers. It is compulsory to
install a metallic filter, on the water inlet piping, with a mesh not larger
than 1 mm. If a filter is not installed the warranty will be terminated
immediately.
We strongly recommend installing a pressure relief valve on the hydraulic
circuit. In the event of serious system breakdown or emergency (e.g.
fire), the relief valve will make it possible to depressurise the system
thus forestalling possible pipe bursts. Always connect the relief valve
outlet to a pipe of diameter no smaller than the valve opening, and route
it to a location in which persons are protected from the jet of expelled
water.
Caution: When making hydraulic connections never use naked flames
close to or inside the unit.
4.5 CONDENSER WATER PIPE CONNECTIONS
The water inlet and outlet must be connected in the positions indicated
as labelled on the unit.
IN
ACQUA CONDENSAZIONE
CONDENSER WATER
All units are provided with stainless steel threaded hydraulic connections. Sizes and locations are indicated in the
dimensional data at the end of this manual.
For units equipped with more than one compressor, water inlets and outlets must be manifolded together.
For connection locations and dimensions see the dimensional drawings at the end of this manual.
4.5.1 Pressostatic valve
When using city water, rather than a cooling tower, it is recommended that a pressostatic valve is installed to
ensure the correct operation of the unit.
The pressostatic valve is also recommended for closed circuit installations. This valve guarantees regular operation
of the unit with changing condenser water conditions (for example when restarting after a weekend pause). The
pressostatic valve is absolutely necessary if the tower water entering into the condenser can decrease below 20
°C (see figure 5). The pressostatic valve must provide a condensing pressure higher than 12.5 bar relative.
Consult Blue Box for further information.
ACQUA CONDENSAZIONE
Blue Box - 30
Page 37
Pressostatic valve
Refrigerant gas inlet
Condenser water outlet
Condenser water inlet
Refrigerant gas outlet
1Condenser
2Pressostatic valve
3Pocket
Figure 5
4.5.2 3 way valve
A three way modulating valve, with temperature probe fitted on the condenser water inlet, can be provided,
instead of the pressostatic valve, to maintain the inlet condenser water temperature higher than 20 °C. (See
figure 6).
For units provided with desuperheaters it is recommended that a pressostatic or three way modulating valve is
installed with a temperature sensor fitted on the condenser water inlet.
The water inlet and outlet must be connected in the positions indicated as labelled on the unit.
ACQUA DESURRISCALDATORE
WATER DESUPERHEATER
OUT
ACQUA DESURRISCALDATORE
In this way the system will be kept under optimal operating parameters. See paragraph 4.5.
In HP version units the hydraulic connections of the desuperheater must
be isolated when working in heat pump mode.
For all units equipped with a heat recovery condenser, the hydraulic circuit connections are male threaded steel
pipes.
These units are equipped with a sensor monitoring the temperature of water returning from the system.
The microprocessor controller enables heat recovery when required, and restarts regular operation once the
water has reached the setpoint temperature.
If faults occur on the recovery condenser the microprocessor controller restarts the cooling through the condenser.
The calibration values of the thermostat and pressure switches are given in the specific controller instruction
manual.
The water inlet and outlet must be connected in the positions indicated
as labelled on the unit.
ACQUA RECUPERO
RECOVERY WATER
OUT
To ensure that the unit operates at optimal parameters in the heat recovery mode, the condensing temperature
must be maintained at around 53 °C. The leaving water temperature from recovery condenser must be between
the limits of the "OPERATING LIMITS" diagram (T min. out = 25 °C, T max out = 50 °C).
Water flow to the main condenser and recovery condenser must be controlled in order to obtain the set recovery
temperature and always maintain the condensing pressure higher than 12.5 bars.
The hydraulic circuits to main condenser and recovery condenser will therefore have variable water flows.
To keep the condensing pressure higher than 12.5 bars, two possible solutions are suggested:
1Heat recovery condenser
2Main condenser
33 way valve
4Circulating pump
53 way valve
Condenser water outlet
Refrigerant gas outlet
Condenser water inlet
Figure 8
Blue Box - 33
Page 40
4.8 WATER FLOW SWITCH INSTALLATION INSTRUCTIONS
(supplied as a kit for each evaporator)
- Clean the piping system into which the flow switch is to be fitted and remove any magnetic particles, such as
welding residues etc.
- To prevent turbulent flow there must be straight pipework, equal to 5 times the diameter of the pipe, either side
of the flow switch.
" Connect the "T" shaped metallic manifold (on which the flow switch is mounted) into the evaporator male
threaded water outlet labelled with:
EVAPORATOR WATER
For HEAT PUMP units, repeat the operation and screw the "T" shaped brass manifold (on which the second flow
switch is mounted) into the condenser male threaded water outlet labelled with:
CONDENSER WATER
To avoid leakage, seal the connection by using teflon. The flow switch should be installed on the heat exchanger
that is closer to the electrical board.
Heat pump version
only
Heat exchanger
(condenser)
Heat exchanger
Hole for
electrical cable
Connect to
terminal box
Connect to terminal box
Heat exchanger
(evaporator)
Heat exchanger
(condenser)
Heat exchanger
(evaporator)
Figure 9
Blue Box - 34
Page 41
- The flow switch must be tightened on the “T” shaped metallic manifold by the plastic knurled union nut. Check
that the arrow located on the upper side is pointing in the direction of flow.
- Be sure to fit the O-ring seal, through the brass manifold and the plastic ring nut. The O-ring seal is supplied in
a plastic cover to protect the flow switch shaft.
- Connect the flow switch to the other end of the “T” manifold.
- Route the flow switch electrical cable through the hole in the unit structure and run it to the electrical panel by
ascending the upright in the machine interior. Connect the flow switch to terminals 1-14 as indicated on the
electrical drawing.
- The flow switch can be removed by screwing out the plastic knurled union nut. In order to reassemble it, ensure
that the o-ring seal is positioned in the proper location. (See figure10).
Arrow
Flow switch
Electric cable
Plastic union nut
O Ring
Flow direction
“T” shaped brass manifold
Figure 10
Warning: When connecting or fabricating pipework never work with naked
flames either inside the unit or in the immediate vicinity of the unit.
Blue Box - 35
Page 42
4.9 CONNECTIONS FOR VERSION LE (MOTOCONDENSING) AND LC (MOTOEVAPORATING)
4.9.1 Refrigerant connections
Version LE units (motocondensing) and LE (motoevaporating) must be connected with refrigerant pipelines.
4.9.2 Route of pipes and maximum distance between sections
For units types with separate sections, the route followed by refrigerant lines depends on the location of the
sections and the characteristics of the surrounding building structure.
Pipe runs should be as short as possible to limit the pressure drop and the refrigerant charge volume. The
maximum permissible pipeline length is 30 metres.
If this limits cannot be adhered to contact Blue Box for further information.
4.9.3 Procedures to follow when sizing refrigerant lines
Depending on the relative position of the sections, there are certain procedures to follow when installing the
refrigerant line.
The diameter of pipes for versions LE and LC can be obtained from tables 1, 2 and 3, according to the selected
model and length of connecting pipes.
4.9.4 Version LE: evaporating section at lower level than condensing section:
a) The vertical riser must be equipped with siphons at least every 6 metres to facilitate the return of oil to the
compressor;
b) Make a collection pit on the suction line downstream of the thermostatic valve bulb;
c) Horizontal sections of the suction line should follow a grade of at least 1% to facilitate oil return to the
compressor (see above).
Figure 11
Blue Box - 36
Page 43
4.9.5 Version LE: evaporating section positioned higher than the condensing unit section
a) Form a siphon on the suction line, at the same height as the evaporator, to avoid drainage of liquid towards the
compressor when the unit is stopped.
b) Make a collection pit on the suction line, downstream from the thermostatic valve bulb, for the collection of
liquid refrigerant that can accumulate during unit shutdown. When the compressor restarts the refrigerant will
evaporate rapidly: it is advisable to create the accumulation pit well away from the bulb to avoid the risk of
affecting the operation of the thermostatic valve.
c) Horizontal sections of the suction line should follow a grade of at least 1% to facilitate oil return to the
compressor.
Figure 12
TABLE 1 - EXTERNAL PIPE DIAMENTERS FOR VERSIONS LE, LE/HP
Distance between unit and remote evaporator [m]
102030
MODEL
SIGMA 2002/LE
SuctionLiquidSuctionLiquidSuctionLiquid
[mm][mm][mm][mm][mm][mm]
3.2351835184218
4.2352242224222
5.2352242224222
6.2422242224222
7.2422842284228
8.2422854285428
9.2542854285428
10.2542854285428
12.2543554355435
13.2543567356735
14.4422842285428
16.4422854285428
18.4542854285428
20.4542854285428
24.4543554356735
26.4543567356735
Diameter connection pipes between unit
and remote evaporator
Blue Box - 37
Page 44
4.9.6 Version LC: remote condenser above the evaporating unit:
a) Make a trap on the supply line, immediately downstream from the compressor, to collect the liquid refrigerant
which can develop during unit shutdown and could irreparably damage the compressor.
b) Install siphons at least every 6 metres on vertical upward sections of pipelines in order to facilitate the return of
oil to the compressor.
c) Ensure that there is a gradient of at least 1% on horizontal sections of the refrigerant lines to facilitate oil
drainage in the correct direction of the flow.
d) Install a non return valve close to condenser inlet, to avoid liquid refrigerant entering the compressor during unit
shutdown. This must be done with the unit off and when the ambient temperature of the condenser is higher
than that of the compressor.
Figure 13
4.9.7 Version LC: remote air cooled condenser below the evaporating unit:
There are no special suggestions for this installation.
It is however advisable to install a non return valve close to the compressor inlet, to avoid liquid refrigerant
entering the compressor during unit shutdown. This must be done with the unit off and when the ambient
temperature of the condenser is higher than that of the compressor.
Figure 14
Blue Box - 38
Page 45
TABLE 2 - PIPE DIAMETER FOR VERSIONS LC
Distance between unit and remote air cooled condenser [m]
1020
MODEL
SIGMA 2002/LC
DeliveryLiquidDeliveryLiquidDeliveryLiquid
[mm][mm][mm][mm][mm][mm]
3.2221622162216
4.2221822182218
5.2221822182818
6.2282228222822
7.2282228222822
8.2282228222822
9.2352835283528
10.2352835283528
12.2352835283528
13.2352835283528
14.4282228222822
16.4282228222822
18.4352835283528
20.4352835283528
24.4352835283528
26.4352835283528
Diameter connection pipes between unit
and remote air coole condenser
30
4.9.8 Connection of Sigma 2002 LC/HP units to a remote air cooled condenser.
In motoevaporating units LC/HP during the winter operating mode (heat pump), the finned coil of the remote
condenser operates as an evaporator; the refrigerant pipes connecting the remote condenser/evaporator will
therefore need to have an increased diameter.
If the remote condenser is supplied by Blue Box, the installer make the connection between the defrost temperature sensor terminals (inside the electric box) and the thermostat terminals inside the electric control box of the
motoevaporating unit (see the electrical diagram).
If the remote condenser is not supplied by Blue Box, the defrost is controlled only by the evaporating pressure (for
more information see the paragraph “Defrost”) and there is not a temperature sensor on the remote condenser.
Blue Box - 39
Page 46
TABLE 3 - CONNECTION PIPE EXTERNAL DIAMETERS FOR VERSIONS LC/HP
Distance between unit and remote condenser/evaporator [m]
Pressure relief valves are fitted on the high pressure side and low pressure side of the refrigerant circuit. The
valves must be vented, to outdoors, through a vent pipe.
The vent pipe must be sized no smaller than the relief valve and it must not be supported from the valve.
Caution: The relief valve must be directed into a safe zone where no
injuries can be caused to people.
4.11 WATER QUALITY
When well or river water is applied for chilled water or condenser water, corrosion or debris problems may occur
due to water quality. It is therefore necessary to analyse the quality of water by checking pH, electrical conductivity,
ammonia ion content, sulphur and chloride content, total hardness, etc. and where necessary provide chemical
treatment.
Blue Box - 40
Page 47
4.12 LOW TEMPERATURE WATER AT CONDENSER
The units are not designed to operate with a condenser cooling water temperature below 20 °C. Below this limit,
the unit could require substantial changes. Contact Blue Box for further information.
4.13 OPERATION WITH LOW TEMPERATURE CHILLED WATER AT EVAPORATOR
Standard units are not designed to operate with a water temperature
below 5°C at the evaporator outlet. To operate below this limit, the unit
will need to be modified. Contact Blue Box for further information.
If chilled water at the evaporator outlet is required below 5 °C, it is necessary to operate with a mixture of water
and ethylene glycol. In this case, control and antifreeze set points must be changed. If low temperature is
specified the set-points will be factory set.
The ethylene glycol percentage must be selected in relation to the required chilled water temperature (see Table
4).
TABLE 4 - FREEZING POINT FOR WATER-ANTIFREEZE MIXTURES
LIQUID OUTLET TEMPERATURE
OR MINIMUM AMBIENT TEMPERATURE (°C)
FREEZING POINT (°C)-5°-10°-15°-20°-25°-30°-35°-40°-45°
ANTIFREEZE
ETHYLENE GLYCOL62230364146505356
PROPYLENE GLYCOL152533394448515457
METHANOL81420263034384145
CALCIUM CHLORIDE91418212426272830
TEMPER -20
TEMPER -40--TEMPER -60
TIFOXITE5060636973--FREEZIUM102025303437404345
PEKASOL 50596875818690---
50
T -20°C
40
-20°-25°-30°-35°+0°-5°-10°-15°
% BY WEIGHT
---
T -40°C
T -60°C
-40°
If ambient temperatures lower than the freezing point of water can be
expected, antifreeze mixtures in the percentages indicated in table 4
must be utilised.
If the glycol percentage is higher than 30%, units with special pump
seals must be used.
Blue Box - 41
Page 48
OPERATING LIMITS
SIGMA 2002 - Refrigerant R22 - R407C
Refrigeratore
Chiller
20
15
10
5
Raffreddamento
Cooling
(1)
0
-5
-10
-10-5051015202530354045505560
(2)
Leaving chilled water temperature [°C]
Leaving condenser water temperature [°C]
55
50
45
40
35
30
25
20
(2)
Pompa di calore
Heat pump
15
10
5
0
Leaving warm water temperature [°C]
-5
-10
-10-5051015202530354045505560
Raffreddamento
Cooling
(1)
(2)
Leaving source water temperature [°C]
The water temperature rise for all versions must be between 4 °C (min) and 7 °C (max)
(1) Working limits of units with 2 compressors
(2) Working limits of units with glycol and water mixture
Blue Box - 42
Page 49
4.14 Water flow rate to evaporato and condenser
Perdite di carico [Kpa]
The nominal water flow rate given by Blue Box refers to a 5 °C temperature difference between inlet and outlet
in relation to the rated cooling capacity.
The maximum permissible flow rate is that which represents a temperature difference of 4 °C. Higher flow rates
would lead to excessive pressure drops and could damage the heat exchanger.
The minimum permissible flow rate is that which would result in a temperature difference of 7 °C or a pressure
drop of no less than 10 kPa. Lower flow rates would lead to excessively low evaporation temperatures or to high
condensing temperatures with consequent tripping of safety devices and shutdown of the unit.
4.15 EVAPORATOR CHILLED WATER TEMPERATURE
The minimum evaporator leaving water temperature is 5 °C: for lower temperatures refer to paragraph 4.12. The
maximum water temperature at the evaporator inlet is 20 °C. In the case of higher temperatures specific solutions
are necessary (dual circuits, three-way valves, by-pass, storage tanks)
CONDENSER PRESSURE DROP
100
90
80
70
60
50
40
30
Pressure drop
20
3.2
4.2
5.2
6.2
7.2
8.2
13.2
9.2
10.2
12.2
The water temperature rise for all versions must be between 4 °C (min) and 7 °C (max)
1
2
379
4
Portata acqua [l/s]
Water Flow
6
5
Blue Box - 43
810
12 14 16 18 20
Page 50
CONDENSER PRESSURE DROP
Portata acqua [l/s]
Perdita di carico [Kpa]
100
90
80
70
16.4
18.4
20.4
24.4
60
50
40
30
Pressure drop
20
2
26.4
14.4
4
68
711
Water Flow
12141618202522
9
10
The water temperature rise for all versions must be between 4 °C (min) and 7 °C (max)
Blue Box - 44
Page 51
EVAPORATOR PRESSURE DROP
Portata acqua [l/s]
Perdita di carico [Kpa]
100
90
80
70
60
50
40
30
Pressure drop
Perdite di carico [Kpa]
20
3.2
4.2
5.2
6.2
7.2
8.2 9.2
10.2
12.2
13.2
1
100
90
80
70
60
50
40
30
Pressure drop
20
2
Portata acqua [l/s]
Water Flow
64
14.4
10 12 14 16 18 20
8
16.4
18.4
20.4
24.4
26.4
The water temperature rise for all versions must be between 3 °C (min) and 8 °C (max)
2
4
68
Water Flow
10
12141618202522
Blue Box - 45
Page 52
4.16 ELECTRICAL CONNECTIONS
4.16.1 General
Electrical connections must be made in accordance with the information given on the electrical drawing attached
to the unit and in compliance with the applicable local regulations.
An Earth (ground) connection is compulsory. The installer must connect the earth cable with a dedicated terminal
on the earth bar in the electrical board (refer to the illustration on the following page) labelled PE.
It must be verified that the electrical supply corresponds to the unit electrical nominal data (tension, phases,
frequency) indicated on the label on the front panel of the unit.
Line voltage fluctuations must not be more than ±5% of the nominal value, while the voltage unbalance between
one phase and another must not exceed 2%. If these tolerances are not possible contact Blue Box to provide the
necessary devices.
Check that the line is connected with the correct phase sequence.
Cable power inlet into the electric panel:
- Models from 3.2 to 13.2, from the left side of electric panel.
- Models from 14.4 to 26.4, from the top of electric panel
The control circuit is derived from the power supply through a transformer located inside the electrical panel.
The control circuit is protected by fuses.
Electrical cable anchorage: anchor the electrical power cables with fixing
systems able to withstand pulling and torsional stress.
Before any operation on the electrical section, be sure that the electric
supply is disconnected.
Power cable and line protection must be sized according to the specification
indicated on the wiring diagram and the documents supplied with the
unit.
The crankcase heaters must be connected at least 12 hours before starting
the unit; the heaters are automatically connected when the main
disconnect switch is set to the ON position.
The electrical supply must be within the limits shown. If this is not the
case the warranty will be terminated immediately.
Blue Box - 46
Page 53
4.16.2 Power supply to crankcase heaters
1) Close the main disconnect switch by turning it from position "0" to position "1"
2) Check that the word "OFF" is shown on the display
3) Ensure that the unit is in "OFF" status and that the external enabling contact is open
4) After a few moments, if the phase sequence is incorrect the alarm "INCORRECT PHASE SEQUENCE" will be
displayed (4-compressor models from 14.4 to 26.4 only, with pCO2 controller). In this case invert the connections
of two of the power line phase wires.
5) Leave the unit in this condition for at least 12 hours to allow the crankcase heaters to perform their function
4.16.3 Potential free contacts
The following potential free contacts are available:
- 1 potential free contact for general alarm (terminals 100 - 101 - 102)
- 1 potential free contact for each compressor (option)
4.16.4 Flow switch electrical connections
Flow switch electrical connections (see paragraph 4.5 ) must be connected to terminal 1-14 for chiller units.
For heat pump units evaporator (user exchanger) flow switch must be connected to terminals 1-15 while condenser
(source exchanger) flow switch must be connected to terminals 14-15.
4.16.5 Circulating pump electrical connections
The external interlocks of unit must close for the unit to operate. The normally open external water circulating
pump contactor terminals must be wired in series with terminals 1 and 2, on the unit control panel, to ensure that
the chiller can only start after the pump is in operation.
Turn on the pump before the unit starts and stop it after the unit has
stopped (recommended time delay: 60 sec).
4.16.6 External interlock
If a remote ON-OFF is required connect the external interlock to terminals 1 and 2. If an external interlock is not
required, bridge therminals 1 and 2 to enable the unit to start.
4.17 MICROPROCESSOR CONTROLLERS
Chillers in the SIGMA 2002 series with 2 scroll compressors, models from 3.2 to 13.2, are equipped with the
mCHILLER type microprocessor controller.
Chillers in the SIGMA 2002 series with 4 scroll compressors, models from 14.4 to 26.4, are equipped with the
pCO2 microprocessor controller.
Blue Box - 47
Page 54
4.17.1 Microprocessor controller for /LE and HP/LE versions
- Versions SIGMA 2002 /LE and SIGMA 2002 HP/LE with two compressors are equipped with an mCHILLER
controller.
- Versions SIGMA 2002 /LE and SIGMA 2002 HP/LE with four compressors do not have an integral controller and
therefore an external controller, or thermostats, must be connected to the auxiliary terminals 1-21, 1-31, 1-41
and 1-51.
Consult the electrical diagram attached to the unit.
4.17.2 RS485 serial interface (optional)
All units can be equipped with a serial interface board for supervision or remote diagnostic
functions via a computer.
The serial interface board plugs into a dedicated slot on the connection board.
Connection to the supervision or remote diagnostics serial line is executed in compliance with standard RS485
and is achieved by means of the serial interface boards.
Models from 3.2 to 13.2 with two scroll compressors and mCHILLER controller
When the serial interface board is inserted the Carel communications protocol is available.
A conversion gateway is required for Modbus-jbus and BacNet protocols.
Models from 14.4 to 26.4 with four scroll compressors and pCO2 controller
When the serial interface board is inserted the following communications protocols are available: Carel, Modbusjbus, BacNet. If a connection is to be made with networks that utilise the Lon-Talk protocol, a dedicated board
must be installed.
In this case, a conversion gateway is not required.
KM1CONTACTOR COMPRESSOR 1
KM2CONTACTOR COMPRESSOR 2
KM21CONTACTOR FAN 1
KM23CONTACTOR FAN 1 HP
FU1FUSES COMPRESSOR 1
FU2FUSES COMPRESSOR 2
FU20 FUSES FAN SPEED CONTROL
FU21FUSES FAN 1
FU56PHASE SEQ. RELAY FUSES
FU50FUSES AUX. TRANSFORMER
FU51AUX. CIRCUIT FUSES
FU52FUSE CONTROL
KA5PHASE SEQUENCE RELAY
TC1AUX. TRANSFORMER
QS1MAIN SWITCH
PANEL LOGIC SECTION WITH CONTROL
OPTIONAL
KA1VOLTAGE RELAY
KA2RELAY ALARM FANS
KA3RELAY HP/LC
KA31RELAY HP 1
A4BOARD FOR REMOTE CONTROL
A2CONTROL BOARD
A3EXPANSION BOARD 2 COMPR.
A13THERMOSTAT COIL
A10CONTROL BOARD ON/OFF
OPTIONAL
Blue Box - 53
Page 60
ELECTRIC PANEL LAY OUT
SIGMA 2002 LC - SIGMA 2002 LC/HP - WITH ARRANGEMENT FOR REMOTE CONDENSER AND
POWER FACTOR CORRECTION CONDENSERS - Models 8.2 - 13.2
Blue Box - 54
Page 61
ELECTRIC PANEL LAY OUT
SIGMA 2002 LC - SIGMA 2002 LC/HP - WITH ARRANGEMENT FOR REMOTE CONDENSER AND
POWER FACTOR CORRECTION CONDENSERS - Models 8.2 - 13.2
KA1VOLTAGE RELAY
KA2RELAY ALARM FAN
KA3RELAY HP/LC
KA31RELAY HP 1
KM1CONTACTOR COMPRESSOR 1
KM2CONTACTOR COMPRESSOR 2
KM21CONTACTOR FAN 1
KM22CONTACTOR FAN 2
KM23CONTACTOR FAN 3
KM24CONTACTOR FAN 4
KM41CONTACT. CAPACITOR POW. FACT. CORRECT. 1
KM42CONTACT. CAPACITOR POW. FACT. CORRECT. 2
FU1FUSES COMPRESSOR 1
FU2FUSES COMPRESSOR 2
FU20FUSES FAN SPEED CONTROL
FU21FUSES FAN 1
FU22FUSES FAN 2
FU41FUSES CAPACITOR POW. FACT. CORRECT. 1
FU42FUSES CAPACITOR POW. FACT. CORRECT. 2
A10CONTROL BOARD ON/OFF
A13THERMOSTAT COIL
FU50FUSES AUX. TRANSFORMER
FU51AUX. CIRCUIT FUSES
FU52FUSE CONTROL
FU56PHASE SEQ. RELAY FUSES
TC1AUX. TRANSFORMER
A5PHASE SEQUENCE RELAY
OPTIONAL
PANEL LOGIC SECTION WITH CONTROL
A4BOARD FOR REMOTE CONTROL
A2CONTROL BOARD
A3EXPANSION BOARD 2 COMPRESSORS
Blue Box - 55
Page 62
5. START-UP
5.1 PRELIMINARY CHECKS
- Check that the electrical connections have been made correctly, and that all terminals are tight.
- Check that the voltage on the RST terminals is 400 V ± 5% (or the unit’s rated value, in the event of units
supplied to run on non-standard power supplies). If the mains voltage is subject to frequent fluctuations, consult
our Engineering Department to discuss the necessary protection systems.
- Check that the display shows the gas pressure in the refrigerant circuit (4-compressor models only).
- Inspect the unit for refrigerant leaks using a leak detector if necessary.
- Check that the crankcase heaters are correctly supplied with power.
- Verify that the heaters are working correctly. After the warm up period the crankcase must be warm to the
touch and be at a temperature of at least 10 to 15 °C higher than the ambient temperature.
- Check that all hydraulic connections are correctly installed and all indications on the unit labels are observed.
- Check that the hydraulic system has been vented to eliminate any air remaining. Fill the system gradually and
open the vent devices on the higher sections. The installer must provide a correctly sized expansion device.
Significant leakage of R407C refrigerant, in a gaseous state, will alter
the percentages of the remaining mixture with a consequent reduction in
performance.
The heaters must be connected at least 12 hours before starting the unit.
The heaters are automatically connected when the main disconnect switch
is set to the ON position.
Warning: before starting the unit check that all the enclosure panels are
in position and secured with the relative screws.
Blue Box - 56
Page 63
Models 3.2 - 13.2, controller µchiller
6 UNIT WITH mCHILLER MICROPROCESSOR (models from 3.2 to 13.2)
6.1 INTRODUCTION
“mCHILLER” is an electronic microprocessor system designed to control all the unit’s functions.
The terminal is equipped with five LEDs indicating the operating status of the machine (summer/winter), the
compressor status (On/Off) and indication of the compressors/pump hour counter after the first 100 hours of
operation. An internal beeper (which can be inhibited by means of a microswitch or a parameter) sounds to warn
of machine operating anomalies.
6.1.1 Display
The display comprises three digits with automatic display of the decimal point. During normal operation the
display shows the value of the evaporator inlet water temperature.
“mCHILLER” can be connected to a computer, by means of an optional electronic board, making available
remote supervision and telediagnostic services for complete management, supervision and diagnostics of the
systems from a remote location.
Figure 15
6.1.2 Machine status information
Machine status information is shown by five LEDs on the remote control display (figure 16).
Figure 16
6.1.3 Keypad
The keypad allows machine operating parameters to be programmed. The wall-mounted version features an
extended number of keys to facilitate use. The function of each key is illustrated on the following pages.
Figure 17
Blue Box - Page 57
Page 64
Models 3.2 - 13.2, controller µchiller
6.1.4 Control and display screens
Method of accessing the set-point and main machine control parameters.
Parameter
scroll keys
Figure 18
Pressing the keys marked with an up or down arrow allows you to scroll through the parameters. The SEL key is
pressed again to display the value of the selected parameter, with the facility to edit the value if required using
the Up or Down keys. The PRG key is pressed to store changed values and to stop the procedure, while pressing
the SEL key returns you to the parameter selection menu. If no keys are pressed, in an interval of 10 seconds,
during parameter editing the display starts flashing. If no keys have been pressed within 60 seconds, after
activating the programming procedure, the controller will return to the temperature display without saving any
changes that have been made. This procedure is useful if it proves unnecessary to alter any parameters.
6.1.5 Muting the BUZZER
Press the MUTE key to silence the buzzer if it is currently sounding.
Figure 19
6.1.6 ALARMS reset
Pressing the Up or Down keys for more than 5 seconds cancels any alarms currently in the memory (manual
reset), clear the associated message from the display and deactivate the alarm relay. In wall mounted models this
function is obtained by pressing the CLEAR key for 5 seconds.
Figure 20
Blue Box - Page 58
Page 65
Models 3.2 - 13.2, controller µchiller
6.1.7 Activation/deactivation of COOLING operation (summer mode)
Pressing the key for more than 5 seconds activates or deactivates the summer operating mode (refer also to
parameter P6). It is not possible to switch directly from Winter mode to Summer mode without first deactivating
Winter mode. If the machine was previously running in Winter mode pressing this key will have no effect.
Figure 21
6.1.8 Activation/deactivation of HEATING mode (winter mode)
Pressing the key for more than 5 seconds activates or deactivates the winter operating mode. It is not possible to
switch directly from Summer mode to Winter mode. If the machine was previously running in Summer mode
pressing this key will have no effect - Summer mode must be deactivated before the change can be made.
Figure 22
6.1.9 Switching off the machine (stand by)
To switch off the machine deactivate both Summer and Winter modes.
Switch off the unit when working in cooling mode
(Summer).
Figure 23
Switch off the unit when working in heating mode
(Winter).
Figure 24
Blue Box - Page 59
Page 66
Models 3.2 - 13.2, controller µchiller
6.1.10 Inlet water temperature control:
To edit the operating values (within the operating limits) hold down the SEL button for 5 seconds. When it flashes
use the Up or Down arrow keys to enter the required inlet water temperature on the display. Confirm the value
you have just entered by pressing the SEL button again (figure 25).
Parameter
scroll keys
Figure 25
6.1.11 Defrosting ( only /LC/HP, heat pump units)
During winter mode operation (heat pump) the the remote condenser finned coil functions as an evaporator,
cooling and dehumidifying ambient air.
During heat pump operation, the evaporation pressure is monitored to prevent it from falling below a preset
value. The evaporation control is active only during heating mode operation.
Depending on the ambient air temperature and humidity conditions, condensate or frost will tend to form,
consequently obstructing the free passage of air and causing thermal insulation. The frost that builds up on the
coil obstructs the passage of air, reduces the available heat exchange surface area (and thus the thermal efficiency),
and can damage the exchanger.
Defrosting is the procedure that serves to prevent or eliminate the formation of ice on the evaporator coil during
heat pump mode operation of an air to water unit.
Defrosting is performed simultaneously for the entire unit.
All heat pump versions are equipped with a control that activates an automatic coil defrost cycle when necessary.
After starting however, the first defrost cycle will be started after a preset minimum operating time to allow the
formation of sufficient thermal inertia to allow the cycle to be completed successfully.
Defrost cycle demands are based on detection of a low suction pressure value, due to the insufficient heat
exchange between the evaporator and the air because of the formation of a layer of ice, which exerts a thermal
insulation effect. For a defrost cycle to be able to start the suction pressure of at least one of the currently
operating compressors must remain below the pressure set for the defrost cycle trip signal for a given time
interval.
Before starting to defrost the coils, all the compressors are started, after which the unit is switched from heat
pump to cooling mode.
When the cycle is reversed the fans stop and the compressors force hot gas into the coil.
A pressure switch on the high pressure circuit maintains the gas discharge pressure below the defrost end value.
To maintain the pressure lower than the defrost end pressure the pressure switch activates the fans.
To reduce the air flow, and obtain more efficient heating of the outer part of the coil, the pressure switch signal
causes the fans to rotate in reverse.
On remote condensers/evaporators supplied by Blue Box when the defrost end temperature is reached, as measured
by a thermostat with the relative sensor located in the lower part of the coil, the pressure switch allows the
delivery pressure to reach the defrost end pressure.
With remote condensers/evaporators not supplied by Blue Box the heat exchanger is controlled by pressure only.
When the defrost end pressure has been reached the controller reverses the unit from chiller mode to heat pump
mode thereby terminating the defrost procedure.
Even though in certain conditions the surface temperature of the coil and the condensation pressure fail to reach
the defrost values, within the preset time limit, the defrost cycle is forcibly terminated as though the defrost end
signal were present. The controller restarts the fans and when the pressure returns to the preset value it reverses
the unit’s operating mode again.
If the defrost cycle is forcibly interrupted with the timeout signal it is signalled on the display even though no
Blue Box - Page 60
Page 67
Models 3.2 - 13.2, controller µchiller
controller functions are activated.
The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminates
normally because the defrost end pressure has been reached. In any event, the alarms historical file will contain
a record of all defrost cycles that were terminated forcibly due to a timeout intervention.
Consecutive defrost cycles must be at least 30 minutes apart. If a forced defrost signal persists inform the Service
organisation.
If the unit fails to start:
do not change internal electrical connections on penalty of immediate invalidation of the warranty.
Warning: The operating mode changeover should only be seasonal.
Frequent changeover from summer to winter operating mode and viceversa could cause damage to the compressors.
During idle periods do not disconnect the unit from the power supply (the
compressor crankcase heaters must remain switched on in these intervals).
Disconnect the unit from the power supply only in the event of prolonged
disuse (e.g. seasonal shutdowns). For temporary shutdown of the unit
refer to the guide lines given in paragraph 6.3.1.
Electronic components of the microprocessor may be damaged at
temperatures below - 20 °C.
Blue Box - Page 61
Page 68
Models 3.2 - 13.2, controller µchiller
6.2 STARTING THE UNIT
The SIGMA 2002 unit is equipped, as standard, with direct keypad control.
Optionally the unit can be equipped to operate via a remote permissive (e.g. a clock, etc.). The remote interlock
must be connected across terminals 1-2. Enabling the unit to start or stop is only possible via the keypad.
6.2.1 COOLING:
- Press the button as shown in figure 26.
Figure 26
6.2.2 HEATING (operation in heat pump mode):
- Press the button as shown in figure 27.
Figure 27
6.3 STOPPING THE UNIT
6.3.1 Temporary stop
The unit is stopped by pressing the cooling key or, in the case of a heat pump unit operating in winter mode, by
pressing the heating key.
Shutdown of unit operating in summer cooling mode
Figure 28
Shutdown of unit operating in winter heating mode
Figure 29
Warning: do not use the machine main power switch to stop the unit.
The crankcase heaters will be disconnected, resulting in serious risk to
the compressors when the unit is started again.
Blue Box - Page 62
Page 69
Models 3.2 - 13.2, controller µchiller
6.3.2 Seasonal stop:
- Disconnect the power supply
- Drain the system circuit (unless it contains a water/glycol solution)
- When the unit is to be restarted repeat the initial start-up procedure
Warning: do not use the machine main power switch to stop the unit:
6.4 EMERGENCY STOP
Emergency stops are obtained by turning the red colour main disconnect switch on the electrical panel to position
0.
this switch must be used to disconnect the electrical supply when no
current is flowing on the circuit, i.e. only when the unit is in OFF status.
Note also that if power is disconnected from the unit the crankcase
heaters will be switched off with the resulting risk of compressor damage
at the time of restarting.
7. TROUBLESHOOTING
The following pages contain a list of the most common causes that can result in the shutdown or anomalous
operation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.
In relation to possible corrective action pay maximum attention to the
operations you intend to perform as overconfidence coupled with
insufficient attention due to lack of expertise can lead to serious accidents.
We therefore recommend that Blue Box or other skilled HVAC engineers
are contacted to identify and correct the problem.
Blue Box - Page 63
Page 70
Models 3.2 - 13.2, controller µchiller
SYMPTOM
A)
No compressor
running.
(display off)
B)
No compressor
running.
(display on,
no alarm messages)
OPERATION
COOLING
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
HEATING
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
No mains power Check presence of mains power
Main power switch Off
(position "O")
Turn mains power selector to
position "I"
No power to control circuits Check condition of fuses FU50,
FU51, FU52.
Check operation of the
transformer
Incorrect phase sequence
(relay KA5 with only green
LED lit)
Invert two of the phase wires of
the power feeding line; when the
unit is powered up again both
the green LED and the yellow
LED should light
Relay KA5 with green and
yellow LEDs off
Check fuses FU56;
If fuses are OK replace phase
sequence relay
Unit in stand-by mode Start unit (see relative section of
the manual)
No consent from service
thermostat
System at set-point temperature,
no heating/cooling demand;
check settings and operation.
No external consent Check operation of circulator
pumps, flow switches, bleed air
from the system; check that
contacts 1 and 2 are closed,
check other external consents.
Compressor motor burnt
Replace compressor
out or compressor seized
Anti-recycle timer running Wait for 5 minutes until the
timer generates a consent
Blue Box - Page 64
Page 71
Models 3.2 - 13.2, controller µchiller
SYMPTOM
C)
No compressor
running.
(display On with alarm
"FL")
D)
No compressor
running. Fans stopped
(display On with alarm
“F1” or “F2”)
(only version LC and
LC/HP)
E)
No compressor
running. (display On
with alarm "A1")
F)
No compressor
running. (display On,
with alarm "E1")
OPERATION
COOLING
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
HEATING
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
No water flow at
Check hydraulic system
evaporator
Faulty flow switch Check contact of flow switch
and replace if necessary
Fan thermal protection
intervention
Check insulation between
windings and between windings
and earth; replace fan if
necessary.
No consent of defrost
thermostat due to
insufficient water flow rate
Check hydraulic circuit and wait
until the water temperature
exceeds the value necessary for
the unit to restart
No consent of defrost
thermostat due to
insufficient glycol
concentration
The programmed set-point is too
low for the percentage of glycol
in the circuit. Increase the glycol
percentage and reduce the
defrost set-point.
Connections to evaporator
inlet temperature sensor
Restore correct connection of
temperature sensor
interrupted
Evaporator inlet
Replace temperature sensor
temperature sensor faulty
Blue Box - Page 65
Page 72
Models 3.2 - 13.2, controller µchiller
SYMPTOM
G)
No compressor
running. (display On,
with alarm "E3" or
"E5")
H)
Unit runs with
insufficient capacity
(Display On without
alarms)
OPERATION
COOLING
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗
HEATING
PROBABLE CAUSE
Resistance RK3 or RK4
faulty or disconnected (only
version LC and LC/HP)
Connections to pressure
sensor interrupted (HP
version only or if
condensation pressure
control with fan speed
regulator is fitted with
version LC and LC/HP)
Faulty pressure sensor (only
on HP version or if
condensation pressure
control with fan speed
regulator is fitted with
version LC and LC/HP)
Insufficient refrigerant
charge
Presence of moisture in
refrigerant circuit
One compressor fails to
start, power circuit open
and compressor contactor
energised
A compressor fails to start,
fuses are OK and
compressor contactor is deenergised
4-way reversing valve
locked or coil faulty
POSSIBLE CORRECTIVE ACTION
Check resistance and replace if
necessary
Restore correct connections to
pressure sensor ("E3" refers to
compressor 1, "E5" refers to
compressor 2)
Replace pressure sensor ("E3"
refers to compressor 1, "E5"
refers to compressor 2)
Check refrigerant circuits with
leak detector, repair leak and
recharge circuit
Replace refrigerant filter and, if
necessary, dehydrate and
recharge circuit
Find and eliminate the cause of
the protection intervention;
change the fuses.
If the fuses blow immediately,
replace the compressor.
Check voltage across compressor
contactor coil and continuity of
coil; if necessary, replace coil
Check power supply and coils of
valves and replace valves if
necessary
Blue Box - Page 66
Page 73
Models 3.2 - 13.2, controller µchiller
SYMPTOM
I)
Compressor 1 and/or 2
not working (display
On with alarm
“H1” and/or “H2”)
OPERATION
COOLING
⊗ ⊗
PROBABLE CAUSE
HEATING
Circuit overcharged (only
version LC and LC/HP)
⊗ ⊗
⊗ ⊗
High pressure switch faulty Check and replace if necessary
Coil filters clogged; air flow
too low (version LC and
LC/HP)
⊗ ⊗
Presence of incondensable
gas in the refrigerant circuit
⊗ ⊗
Fans faulty (version LC and
LC/HP)
⊗ ⊗
Faulty circulating pump Check and replace
⊗
Defrost-end pressure switch
not working (only version
LC/HP)
⊗ ⊗
Metallic filter of condenser
clogged
⊗ ⊗
Insufficient condenser
water flow
⊗ ⊗
Condenser entering water
temperature too high
POSSIBLE CORRECTIVE ACTION
Check refrigerant charge and
remove if necessary;
Clean filters with compressed air
Empty circuit, apply vacuum, and
recharge
Check and replace fans
Check and replace
Clean filter
Check hydraulic circuit and
condenser water flow
Check condenser hydraulic circuit
Blue Box - Page 67
Page 74
Models 3.2 - 13.2, controller µchiller
SYMPTOM
L)
Compressor 1 and/or 2
not working (display
On with alarm “L1”
and/or “L2”)
OPERATION
COOLING
⊗ ⊗
PROBABLE CAUSE
HEATING
Refrigerant circuit
completely empty
⊗ ⊗
⊗
Low pressure switch faulty Check and replace if necessary
Metallic coil filter clogged;
air flow too low (only
LC/HP)
⊗ ⊗
Refrigerant filter clogged Check and replace if necessary
⊗ ⊗
Faulty water circulator
pump
⊗
Defrost pressure switch
with incorrect setting (only
version LC/HP)
⊗ ⊗
Liquid refrigerant valve not
completely open (if present)
⊗ ⊗
Thermostatic expansion
valve not operating
correctly
⊗ ⊗
Evaporator metallic filter
clogged
⊗ ⊗
Evaporator circulating
pump faulty
POSSIBLE CORRECTIVE ACTION
Check refrigerant circuit with
leak detector after pressurising to
approximately 4 bar. Repair leak,
apply vacuum, charge circuit.
Clean filter with compressed air
Check and replace if necessary
Check and correct setting
Check and open fully
Check, clean, or replace if
necessary
Clean the filter
Check, and replace if necessary
Blue Box - Page 68
Page 75
Models 3.2 - 13.2, controller µchiller
SYMPTOM
M)
Compressor 1 and/or 2
not working (display
On with alarm
“C1” and/or “C2”)
N)
Ice on liquid refrigerant
pipe
O)
Compressors run
constantly
OPERATION
COOLING
⊗ ⊗
⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
HEATING
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
Insufficient refrigerant
charge
Find leak with leak detector,
repair, and recharge circuit
4-way valve locked Replace valve
Lack of oil Check quantity of oil in circuit
and replenish as necessary.
Check that the circuit has all the
necessary measures to ensure oil
return to the compressor
Condenser entering water
temperature too high
Check temperature and flow of
condenser entering water
Liquid refrigerant filter
Replace filter
clogged
Valve on liquid refrigerant
Open valve fully
line (if present) not
completely open
Operating thermostat
incorrectly set or faulty
Check setting; replace
thermostat if necessary
Lack of refrigerant gas
Check and recharge if necessary
charge
Excess thermal load Reduce thermal load
Blue Box - Page 69
Page 76
Models 3.2 - 13.2, controller µchiller
SYMPTOM
P)
Anomalous noise from
system
OPERATION
COOLING
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
HEATING
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
Compressor noisy Contact service organisation for
check and replacement if
necessary
Thermostatic valve noisy Contact service organisation for
check and replenish refrigerant
charge
Vibrating pipes Contact service organisation to
secure pipelines
Casing panels vibrate Check that panels are properly
fastened; contact service
organisation if necessary
If the display presents alarms other than those described previously,
contact the Service organisation.
Blue Box - Page 70
Page 77
Models 14.4 - 26.4, controller pCO
8 UNIT WITH pCO2 MICROPROCESSOR (models from 14.4 to 26.4)
8.1 GENERAL
The pCO2 electronic microprocessor controller with the DBBB0*P20Z program is designed to manage chiller and
heat pump units, with control of 4 compressors.
The program provides the facility to control water-cooled units with plate heat exchangers and to manage
compressor start and stop times, safety devices and auxiliary functions including condensation control in cooling
mode, heat recovery functions, and other functions described later in this manual.
The necessary hardware is optimised to obtain the maximum advantage from the available inputs and outputs;
the connection between various circuit boards and the user interface terminal is achieved via the pLANE using the
dedicated RS485 serial connector for network connections.
Each unit can also be connected to remote supervision and/or telediagnostics systems by means of an RS485
serial line.
Detailed information on the operation of the above systems is provided in the specific controller manual supplied
with the unit.
8.1.1 Display
The back-lit LCD display comprises 4 lines and 20 columns.
2
Figure 30
8.1.2 Keypad
In addition to the LCD display, the user interface is equipped with the following function keys:
“Menu” key: press this key from any menu to return to the opening menu.
Maintenance key: press this key to access the maintenance menus.
Print key: this key is currently not used.
"I/O" key: pressing this key opens the menus containing the status of the digital inputs and outputs
together with the values read on the analogue inputs and the value of the analogue outputs
Blue Box - Page 71
Page 78
Models 14.4 - 26.4, controller pCO
“Clock” key: press this key to open the clock menus.
“Set” key: this key opens the menus in which the various operating set-points can be edited.
“Prog” key: this key opens the service menus.
"? info" key: pressing this key opens a menu in which the address of the component connected to
the terminal can be changed.
"Summer" key (blue) and "winter" key (red): in the case of chiller + heat-pump units,
press these keys to select the required operating mode.
2
“ON/OFF” key: press this key to switch from Stand- by to ON or vice versa.
“Alarm” key: this key serves to mute the alarm buzzer, display any active alarms, and reset them
in certain cases.
Arrow key: the arrow keys allow you to navigate through the menus; when an editable
field is selected, the arrow keys serve to change the current value.
“Enter” key: pressing this key allows you to access fields containing editable parameters and also to
confirm any changes you make to such parameters.
Electronic components could be damaged by air temperature below -20
°C.
Blue Box - Page 72
Page 79
Models 14.4 - 26.4, controller pCO
8.2 OPERATING DESCRIPTION
8.2.1 Introduction
The microprocessor control regulates the water temperature of the evaporator maintaining it at the set-point
value acting on the compressors management.
The control manages all the components of the chiller, the alarms and “ancillary” functions.
Almost all the parameters referred to below (set-points, differentials, calibration, delays...) can be programmed
by means of the various menus. Refer to the specific manual for the pCO2 controller.
8.2.2 Unit in stand-by mode
The unit is in stand-by mode when it is correctly supplied with power but not actually enabled to operate.
In this condition the display shows the values of the various machine parameters, but the operation of the
compressor is not inhibited.
Power-on is obtained by pressing the “ON-OFF” button of the microprocessor control or via an external interlock.
8.2.3 Enabling the unit
2
Start-up of the unit from stand-by mode can be achieved after closing the external enabling contact, by pressing
the "ON/OFF" button, or by means of a signal on the serial line.
Activation of the controller outputs that manage the various sections of the chiller is executed in strict compliance
with the operating times. If the "ON" button is pressed before the external interlocks are closed, the display
indicates which of the external interlocks is not yet enabled.
Operation of the pump has priority to the compressors, which can start only after the evaporator and condenser
pumps are running.
8.2.4 Pumps management
The microprocessor controller does not manage the operation of chilled water and condenser pumps.
When the unit is switched from normal operation to stand-by, due to the opening of an external interlock, the
active pump must be stopped with a delay following the stopping of the last active compressor, to benefit from
the thermal inertia of the system.
8.2.5 Compressor start-up
The controller allows the compressors to be started if the flow switch input is closed within the compressor startup delay time interval. If the flow switch input opens, after the compressor has started, the trip is retarded if it
occurs within the time programmed for the compressor stop.
If the unit trips due to the opening of the flow switch input, the relative alarm is displayed.
Starting and stopping of the compressors and capacity step control is managed by the controller in accordance
with the building cooling demands.
8.2.6 Chiller mode operation
In chiller operation, the controller lowers the water temperature value, maintaining it as close as possible to the
programmed set-point.
In the standard version, in which the control acts on the evaporator entering water, the management of compressor
operation and capacity steps is linked to the difference between the entering water temperature and the programmed
set-point.
Blue Box - Page 73
Page 80
Models 14.4 - 26.4, controller pCO
2
8.2.7 Heat pump mode operation
In heat pump operation, the controller increases the water temperature value, maintaining it as close as possible
to the programmed set-point.
Management of compressor operation is performed in the same way as already illustrated for chiller mode
operation.
8.2.8 Evaporator low temperature chilled water protection
If the evaporator leaving water temperature is lower than the limit value programmed in the low temperature
chilled water protection set-point, the controller will stop all the compressors and activate the low temperature
water alarm.
This alarm must be reset manually and the compressor restarted only when the evaporator leaving water temperature is equal to or higher than the alarm trip value, increased by the low temperature water differential.
The low temperature water alarm can only appear when the unit is switched on (in stand-by conditions the freeze
alarm is not operational).
8.2.9 Evaporator anti-freeze protection electric heater (optional)
In conditions that lead to tripping the freeze alarm, the controller energises the heater.
The heater remains powered for the entire time that the conditions for the freeze alarm continue.
Unlike the low water temperature alarm, which is enabled only when the unit is powered on, the anti-freeze
heater can be energised when the machine is on stand-by.
8.2.10 Compressor operation
When the unit is running correctly and no general alarms are present, the microprocessor controller starts the
compressors in accordance with the water temperature reading.
Compressor starts are staggered in accordance with preset delay intervals, thus avoiding excess input current
surges.
Before starting a compressor, the microprocessor checks the value of the delivery pressure by means of the
relevant transducer, the status of the high pressure switch and the compressor motor windings temperature by
checking the thermal protection.
When the compressor has been started, tripping of any of the safety devices will cause the compressor to stop
immediately and an alarm will be displayed.
While the compressor is running, discharge pressure and suction pressure are monitored constantly by means of
the relevant sensors.
On unit start-up the first compressor is started with a delay, set on the microprocessor controller, after the start of
the hydraulic system circulating pump.
Once started, each compressor must run for a minimum operating period, unless a critical alarm should trip in the
meantime.
The critical alarms which can stop the compressor during the minimum operating time are the high pressure
alarm and the compressor thermal cut-out alarm. Once stopped each compressor can be restarted only after a
minimum idle time or after a minimum time interval between two consecutive starts has elapsed.
The consecutive starting of two compressors or the consecutive starting of one compressor, is executed with
minimum delay intervals equal to the capacity step activation time.
Stopping compressors is also performed with a minimum programmed delay interval.
Blue Box - Page 74
Page 81
Models 14.4 - 26.4, controller pCO
8.2.11 Compressor management
Start-up of the compressors is automatic when the reference water temperature changes with respect to the
programmed set-point.
Normally the reference water temperature is the value detected at the inlet to the chiller unit.
Balancing of duty hours over all the compressors in the unit is performed by selecting the rotation of starts.
With the rotation function of starts active, the first compressor to start is the first one that previously stopped. Also
the first compressor to start will be the one with the most operating hours.
8.2.12 High and low pressure alarms
Discharge pressure (high pressure) and suction pressure (low pressure) are managed by the microprocessor controller
through the relevant sensors.
When a compressor is running, the controller checks that:
- Discharge pressure is always lower than the safety value set for cooling or heating mode operation. If the values
are exceeded, the controller immediately stops the compressor and displays a high pressure alarm. The high
pressure alarm can be reset manually on the controller only when the pressure detected by the discharge
pressure sensor is lower than the value that caused the alarm to trip, less the differential value.
- The suction pressure is always higher than the safety value set for operation in cooling or heating mode. If the
value read by the suction pressure sensor is lower than the limits set for the relative operating conditions, the
controller will stop the compressor and generate a low pressure alarm. The low pressure alarm is not instantaneous,
but operates after a preset delay interval, both in the starting phase and during the normal running of the
machine. The low pressure alarm can be reset automatically or manually, depending on the relative parameter
setting. In all cases the low pressure alarm can only be reset when the pressure detected by the suction sensor
is higher than the value that caused the alarm to trip, plus the differential value. It is possible to program the
number of permissible consecutive compressor starts before the unit shuts down in safety status.
2
8.2.13 Changeover from chiller to heat pump and vice versa
The changeover from chiller to heat pump and back can be performed at any time, either by means of an
external signal on a digital input, from the keypad, or via the serial line. The operating mode changeover must be
only seasonal and only with the unit off.
After a mode changeover, the controller re-starts the unit in the new mode with a factory set minimum delay
time.
The unit operates with temperature control on the inlet to which has been inactive for the longest time. the unit
(or return from the system).
8.2.14 Desuperheater (Option)
The desuperheater recovers part of the total power to be dissipated into the condenser to produce hot water
(water inlet temperature 40 °C, water leaving temperature 45 °C at design conditions). This is energy efficient
and therefore has an economic benefit. Each refrigerant circuit is supplied with a shell and tube desuperheater
positioned in series to the main condenser.
See paragraph 4.6 for the hydraulic diagram.
8.2.15 Total heat recovery (only SIGMA 2002/DC)
The goal of total heat recovery is to recover 100% of the heat energy that would be rejected in the process to
achieve energy efficiency and an economic benefit.
SIGMA 2002/DC units have a 100% heat recovery condenser on each refrigeration circuit for the production of
hot water (water inlet temperature 40 °C, water leaving temperature 45 °C at design conditions). The heat
recovery condenser is positioned between the compressor and the main condenser (see refrigerant diagram). The
heat recovery and condenser water circuits are completely independent to allow maximum working flexibility in
the use of the water which passes through the heat recovery condenser. With the heat recovery off, (when no
water is flowing through the recovery heat exchanger) the unit operates as a standard chiller.
Blue Box - Page 75
Page 82
Models 14.4 - 26.4, controller pCO
2
8.2.16 Dual set-point (option)
With double thermostatic valves and solenoid valves that are automatically switched according to the required
expansion temperature. Two set-point values can be programmed on the microprocessor controller via the keypad
or a digital input. Switching of the thermostatic valves is always automatic, in accordance with the water temperature. The valves are sized on the basis of the temperature values specified at the time of the order. The
machine operating limits shown in the catalogue are not affected. If the hydraulic circuit contains glycol in
sufficient quantities to eliminate the risk of freezing, the lower limit is extended to a minimum of -5 °C leaving
water temperature.
8.2.17 Leaving water temperature control (option)
With leaving chilled water temperature control a reference sensor must be installed on the evaporator outlet.
The unit's capacity steps are activated / deactivated with delay intervals in relation to a dead zone. When the
leaving water temperature is higher than the programmed set-point compressors start is enabled.
8.2.18 Defrost (heat pumps units /LC/HP)
During winter mode operation (heat pump) the the remote condenser finned coil functions as an evaporator,
cooling and dehumidifying ambient air.
During heat pump operation, the evaporation pressure is monitored to prevent it from falling below a preset
value. The evaporation control is active only during heating mode operation.
Depending on the ambient air temperature and humidity conditions, condensate or frost will tend to form,
consequently obstructing the free passage of air and causing thermal insulation. The frost that builds up on the
coil obstructs the passage of air, reduces the available heat exchange surface area (and thus the thermal efficiency),
and can damage the exchanger.
Defrosting is the procedure that serves to prevent or eliminate the formation of ice on the evaporator coil during
heat pump mode operation of an air to water unit.
Defrosting is performed simultaneously for the entire unit.
All heat pump versions are equipped with a control that activates an automatic coil defrost cycle when necessary.
After starting however, the first defrost cycle will be started after a preset minimum operating time to allow the
formation of sufficient thermal inertia to allow the cycle to be completed successfully.
Defrost cycle demands are based on detection of a low suction pressure value, due to the insufficient heat
exchange between the evaporator and the air because of the formation of a layer of ice, which exerts a thermal
insulation effect. For a defrost cycle to be able to start the suction pressure of at least one of the currently
operating compressors must remain below the pressure set for the defrost cycle trip signal for a given time
interval.
Before starting to defrost the coils, all the compressors are started, after which the unit is switched from heat
pump to cooling mode.
When the cycle is reversed the fans stop and the compressors force hot gas into the coil.
A pressure switch on the high pressure circuit maintains the gas discharge pressure below the defrost end value.
To maintain the pressure lower than the defrost end pressure the pressure switch activates the fans.
To reduce the air flow, and obtain more efficient heating of the outer part of the coil, the pressure switch signal
causes the fans to rotate in reverse.
On remote condensers/evaporators supplied by Blue Box when the defrost end temperature is reached, as measured
by a thermostat with the relative sensor located in the lower part of the coil, the pressure switch allows the
delivery pressure to reach the defrost end pressure.
With remote condensers/evaporators not supplied by Blue Box the heat exchanger is controlled by pressure only.
When the defrost end pressure has been reached the controller reverses the unit from chiller mode to heat pump
mode thereby terminating the defrost procedure.
Even though in certain conditions the surface temperature of the coil and the condensation pressure fail to reach
the defrost values, within the preset time limit, the defrost cycle is forcibly terminated as though the defrost end
signal were present. The controller restarts the fans and when the pressure returns to the preset value it reverses
the unit's operating mode again.
If the defrost cycle is forcibly interrupted with the timeout signal it is signalled on the display even though no
Blue Box - Page 76
Page 83
Models 14.4 - 26.4, controller pCO
controller functions are activated.
The defrost timeout alarm is automatically cleared from the active alarms menus when a defrost cycle terminates
normally because the defrost end pressure has been reached. In any event, the alarms historical file will contain
a record of all defrost cycles that were terminated forcibly due to a timeout intervention.
Consecutive defrost cycles must be at least 30 minutes apart. If a forced defrost signal persists inform the Service
organisation.
2
Blue Box - Page 77
Page 84
Models 14.4 - 26.4, controller pCO
2
8.3 STARTING THE UNIT
For the start-up procedure refer also to the microprocessor controller manual.
- Close the external enabling contacts
- Press the "ON" button on the microprocessor controller
- If all the controls are enabled the display will show the message "UNIT ON"
After having performed the above procedures the unit will start automatically after a delay of approximately 5
minutes, assuming that the enabling signals of the microprocessor, the flow switches, and the water pumps
continue to be present.
If the unit fails to start: do not change internal electrical connections
on penalty of immediate invalidation of the warranty.
During idle periods do not disconnect the unit from the power supply (the
compressor crankcase heaters must remain switched on in these intervals).
Disconnect the unit from the power supply only in the event of prolonged
disuse (e.g. seasonal shutdowns). For temporary shutdown of the unit
refer to the guide lines given in paragraph 8.4.
8.4 STOPPING THE UNIT
8.4.1 Temporary stop:
- To stop the unit press the "OFF" button on the front panel.
8.4.2 Seasonal stop:
- Disconnect the power supply
- Drain the system circuit (unless it contains a water/glycol solution)
- When the unit is to be restarted repeat the initial start-up procedure
Figure 31
Warning: do not use the machine main power switch to stop the unit:
this switch must be used to disconnect the electrical supply when no
current is flowing on the circuit, i.e. only when the unit is in OFF status.
Note also that if power is disconnected from the unit, the crankcase
heaters will be switched off with the resulting risk of compressor damage
at the time of restarting.
8.5 EMERGENCY STOP
Emergency stops are obtained by turning the red colour main disconnect switch on the electrical panel to position 0.
Figure 32
Blue Box - Page 78
Page 85
Models 14.4 - 26.4, controller pCO
9. TROUBLESHOOTING
The following pages contain a list of the most common causes that can result in the shutdown or anomalous
operation of the chiller. Faults are arranged in accordance with easily identifiable symptoms.
In relation to possible corrective action, adopt the maximum attention in
the operations you intend to perform as overconfidence coupled with
insufficient attention due to lack of expertise can lead to serious accidents.
We therefore recommend that Blue Box or other skilled HVAC engineers
are contacted to identify and correct the problem.
2
Blue Box - Page 79
Page 86
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
A)
No compressor running
⊗ ⊗
No mains power Check presence of mains power
(display Off)
⊗ ⊗
Main power switch Off
(position "O")
⊗ ⊗
Transformer fuses and/or
fuses 24 V burnt-out
⊗ ⊗
Electronic control card
faulty
B)
No compressor
⊗ ⊗
No external consent Check presence of external
running. Display On:
”OFF from external
consent”
C)
No compressor
running. Display On:
⊗ ⊗
No consent from
supervision system
”OFF from supervision
system”
D)
No compressor
running. Display On:
⊗ ⊗
No consent from “on/off”
key of user interface
”OFF”
POSSIBLE CORRECTIVE ACTION
Turn main power selector to
position "I"
Check fuses and if necessary
replace burned out fuses (FU50
and FU51). If fuses burn-out
again call for assistance
Call assistance
consent; if not present, bridge
terminals 1 and 2
Activate operation from
supervision system
Press “on/off” key
Blue Box - Page 80
Page 87
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
E1)
No compressor
running. Display On:
unit ON with alarm
“High Pressure
Compressor 1, 2, 3, 4”
⊗ ⊗
⊗
220V fuses burnt-out
(FU51) (in version LC and
LC/HP also the alarm “Fans
protection” will be
displayed)
Insufficient condenser
water flow
⊗ ⊗
Entering condenser water
temperature too high
⊗ ⊗
The unit has an excessive
refrigerant charge (only
version LC and LC/HP)
⊗ ⊗
Remote condenser faulty
(only LC version LC and
LC/HP)
E2)
No compressor
running. Display On:
unit ON with alarm
“Thermal protections
Compressor 1, 2, 3, 4”
⊗ ⊗
⊗ ⊗
Entering condenser water
temperature too high
Drop in power feeding
voltage
⊗⊗
Setting of thermal
protections
⊗ ⊗
Circuits partially discharged Call service to replenish charge
POSSIBLE CORRECTIVE ACTION
Change fuses. If fuses burn-out
again contact assistance
Check hydraulic circuit and
condenser water flow
Check hydraulic circuit of
condenser
Call assistance
Check flow and temperature of
condenser entering water
Check voltage stability and fit
appropriate protection if
necessary
Contact assistance
Blue Box - Page 81
Page 88
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
E3)
No compressor
running. Display On:
unit ON with alarm
“Low Pressure
Compressor 1, 2, 3, 4”
⊗ ⊗
⊗ ⊗
Insufficient percentage of
glycol in hydraulic circuit
Both circuits have
insufficient refrigerant
charge
⊗
Incorrect setting of defrost
set-point (only version
LC/HP)
E4)
No compressor
running. Display On:
⊗ ⊗
Insufficient water flow to
evaporator
unit ON with alarm
“Exceeded Threshold
Low Temperature of
leaving User Water”.
⊗ ⊗
Faulty controller Contact service organisation
E5)
No compressor
⊗ ⊗
Excessive thermal load Wait until entering water
running. Display On:
unit ON with alarm
“Exceeded Threshold
High Temperature of
entering User Water
⊗⊗
Refrigerant circuits partially
discharged
E6)
(Only version LC)
No compressor
⊗ ⊗
Depending upon the fan
type installed
running. Display On:
unit ON with alarm
“Fans protection”
POSSIBLE CORRECTIVE ACTION
Restore correct glycol percentage
Find possible leaks in circuit,
repair, and recharge
Check and correct setting if
necessary
Increase water flow to
evaporator and check
temperature rise
temperature is below the alarm
set point. Start hydraulic circuit
of evaporator and unit. If not
sufficient contact assistance.
Call assistance
Check thermal consent of fans
Blue Box - Page 82
Page 89
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
E7)
No compressor
running. Display On:
⊗ ⊗
Power supply voltage not
stable
unit ON with alarm
“No power to Control
circuits”
F1)
No compressor
running.
Display On: unit
OFF with alarm
“Flow Switch Alarm”
⊗ ⊗
⊗ ⊗
No water flow to
evaporator
Flow switch faulty Check flow switch contact and
F2)
No compressor
⊗ ⊗
Incorrect phase sequence Invert two of the phase wires of
running. Display On:
unit OFF with alarm
”Incorrect Phase
Sequence” and phase
sequence relay with
green LED On and
orange LED Off
F3)
No compressor
⊗ ⊗
Faulty relay Check to ensure that relay closes
running. Display On:
unit OFF with alarm
”Incorrect Phase
Sequence” and phase
sequence relay with
green and orange LEDs
On
F4)
No compressor
⊗ ⊗
Fuses FU56 burnt-out Check fuse FU56 and replace if
running. Display On:
unit OFF with alarm
”Incorrect Phase
Sequence”
and phase sequence
relay with green and
⊗ ⊗
One of the three phases is
not present
orange LEDs Off
POSSIBLE CORRECTIVE ACTION
Check power supply voltage; if
not correct contact the electricity
company
Check hydraulic circuit
replace if necessary
the power supply line
contact
necessary
Check connection of each phase
Blue Box - Page 83
Page 90
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
G)
No compressor
running. Display On:
⊗ ⊗
No consent from digital
input to compressors
unit ON without alarm
⊗ ⊗
Unit at temperature Normal operation
⊗ ⊗
Compressor fuses burntout
⊗ ⊗
Controller faulty Call service
H1)
Only 1 compressor
⊗ ⊗
Excess refrigerant charge Check refrigerant charge and call
running. Display On
with alarm
“High Pressure
Compressor 1 and 2 or
3 and 4”
⊗ ⊗
Problems at the condenser
hydraulic circuit
⊗ ⊗
High pressure switch
incorrectly calibrated or
faulty
⊗ ⊗
Pressostatic valve
incorrectly set
H2)
Only 1 compressor
running. Display On
with alarm
⊗ ⊗
Insufficient refrigerant
charge due to a leak in the
circuit
“Low Pressure
Compressor 1 and 2 or
3 and 4”
⊗ ⊗
Thermostatic valve faulty Call service
⊗ ⊗
Solenoid valve of liquid
refrigerant line faulty (if
present)
⊗ ⊗
Dehydrating filter clogged Call service
POSSIBLE CORRECTIVE ACTION
Check consent to compressors
and close relative contacts
Check continuity of fuses; if
burnt-out call service
service organisation
Check flow and temperature of
condenser entering water
Check pressure switch setting
Check setting of pressostatic
valve and call assistance
Call service
Call service
Blue Box - Page 84
Page 91
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
COOLING
OPERATION
HEATING
PROBABLE CAUSE
H3)
One, two or three
⊗ ⊗
Problems at the compressor Call service
compressors running.
Display On with alarm
“Compressor Thermal
Protections”
I)
Only one compressor
⊗ ⊗
Unit capacity step active Normal operation
Running.
Display On
without alarms
⊗ ⊗
Fuses burnt-out Call service
⊗ ⊗
Controller faulty Call service
⊗ ⊗
No external consent to the
compressor
L1)
All compressors
running. Display On
⊗ ⊗
Compressors specified by
alarm require maintenance
with alarm
“Compressor
Maintenance”
L2)
All compressors
⊗ ⊗
Unit maintenance required Call service for scheduled
running. Display On
with alarm “Unit
Maintenance”
M)
All compressors
running without
stopping. Display
On without alarm
⊗ ⊗
⊗ ⊗
Excess thermal load Call service
Refrigerant circuits partially
discharged
⊗ ⊗
Controller not working Call service
POSSIBLE CORRECTIVE ACTION
Check external consent of
compressor
Call service for scheduled
maintenance
maintenance
Call service
Blue Box - Page 85
Page 92
Models 14.4 - 26.4, controller pCO
2
SYMPTOM
N)
Anomalous noise from
system
OPERATION
COOLING
⊗ ⊗
⊗ ⊗
⊗ ⊗
⊗ ⊗
HEATING
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
Compressor noisy Contact service to check and
replace if necessary
Thermostatic valve noisy Contact service to check and add
refrigerant
Vibrating pipes Contact service organisation to
secure pipes
Casing panels vibrate Check that panels are properly
fastened; contact service
organisation if necessary
If the display presents alarms other than those described above, contact
the service organisation.
Blue Box - Page 86
Page 93
10 CHECKS DURING OPERATION
- With the unit at steady conditions check that the entering and leaving condenser water temperatures are inside
the operating limits given in the technical specifications.
10.1 Checking the refrigerant charge
- After a few hours of unit operation check that the sight glass moisture indicator has a green coloured core. if the
core is yellow, moisture is present in the circuit. In such a situation the circuit must be dehydrated by a qualified
technician.
- Check the sight glass for air bubbles. A constant passage of bubbles through the sight glass could indicate that
the refrigerant must be replenished. Occasional bubbles are considered normal.
- A few minutes after the start of the compressors, check that the condensing temperature, equivalent to the
pressure read on the pressure gauge, is approximately 8 °C higher than condenser inlet water temperature.
Also check that the evaporating temperature, equivalent to the pressure read on the pressure gauge, is 5 °C
lower than the evaporator outlet temperature.
- Check that the refrigerant superheating is between 5 and 7 °C; to do this:
1) measure the temperature using a contact thermometer placed on the compressor suction pipeline;
2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the compressor
suction side (saturation temperature corresponding to suction pressure); for units charged with R407C
refrigerant, refer to the D.P. (Dew Point) pressure gauge scale.
The difference between the temperatures measured in this manner is equivalent to the superheating value.
- Check that refrigerant subcooling is between 5 and 7 °C; to do this:
1) measure the temperature using a contact thermometer placed on the compressor discharge pipeline;
2) read the temperature, equivalent to the pressure read on the pressure gauge connected to the liquid
connection at the condenser outlet (saturation temperature corresponding to condenser delivery pressure);
for units charged with R407C refrigerant, refer to the B.P. (Bubble Point) pressure gauge scale.
The difference between the temperature values measured in this manner is equivalent to the subcooling
value.
Blue Box - 87
Page 94
11. CALIBRATION OF CONTROL EQUIPMENT
11.1 INTRODUCTION
All the control equipment is factory calibrated before the machine is shipped. Control equipment and safety
devices should nonetheless be checked after a reasonable period of operation. Calibration values are given in
Tables 5 and 6.
All service operations on the control equipment must be carried out by
QUALIFIED PERSONNEL ONLY; incorrect calibration values can cause
serious damage to the unit and personal injury.
TABLE 5 - CALIBRATION OF CONTROL EQUIPMENT
CAPACITY STEPS
CONTROL ELEMENTSET POINT DIFFERENTIALSET POINT DIFFERENTIAL
Service calibration (summer)°C10293
Service calibration (winter)°C422433
NOTE:
(*) Chiller / Version HP/LC
(**) Only version HP/LC with remote condensers/evaporators supplied by Blue Box
Blue Box - 88
Page 95
12. MAINTENANCE AND PERIODIC CHECKS
12. 1 WARNINGS
All operations described in this chapter MUST BE PERFORMED
EXCLUSIVELY BY QUALIFIED PERSONNEL.
Make sure that the unit has been disconnected from the power supply
before carrying out any work or accessing internal parts.
12.2 INTRODUCTION
Carry out the following periodic checks to ensure the unit is operating correctly:
The compressor head and discharge pipeline can reach high temperatures.
Always exert caution when working in the vicinity of the compressor.
CHECK PERIOD
Check that safety and control devices work correctly as previously described monthly
Check all the terminals on electric board and compressor are well locked. Periodic
cleaning of the sliding terminals of the contactors should be done: if any damage is
found, replace the contactors
Check the sight glass to verify the refrigerant charge. monthly
Check there is no oil leakage from compressor monthly
Check there is no water leakage in the hydraulic system monthly
If the unit is to be stopped for a long period the hydraulic circuit, including all pipes and
heat exchangers, should be drained. This is compulsory if the ambient temperature is
expected to fall below the freezing point of the liquid employed.
Check process water levels monthly
Check that the flow switch is operating correctly. monthly
Check that the crankcase heater operating correctly and the power supply. monthly
Clean metallic filters on water piping monthly
Check the colour of the sight glass core (green = no moisture, yellow = moisture
present): if it has a yellow colour, change the refrigerant filter
Check that the noise level has not increased. every 4 months
monthly
seasonal
operation
every 4 months
Blue Box - 89
Page 96
12.3 REPAIRING THE REFRIGERANT CIRCUIT
If repairs have been made to the refrigerant circuit, perform the following steps:
- leak test;
- vacuum and dehydration of refrigerant circuit;
- refrigerant charge.
If the circuit is to be emptied, use the appropriate equipment to collect
the refrigerant.
12.3.1 Leak test
Charge the refrigerant circuit to a pressure of 15 bar with dry nitrogen gas by means of a cylinder fitted with a
pressure reducer. Check the circuit for leaks with a leak detector. The formation of bubbles or foam indicates the
presence of leaks.
If leaks are found during the test, empty the refrigerant circuit and then repair the point of leakage by welding
with appropriate alloys.
Do not use oxygen instead of nitrogen: explosion hazard.
12.3.2 High vacuum and dehydration of the refrigerant circuit
To generate a high vacuum in the refrigerant circuit use a high vacuum pump able to reach 0.1 mbar of absolute
pressure with a flow rate of 10 m3/h. With this type of pump, a single vacuum cycle is normally sufficient to reach
an absolute pressure of 0.1 mbar.
If this type of pump is not available, or in the event that the circuit has been left open for a long period of time,
you are strongly advised to use the triple evacuation method. This procedure is also prescribed in the event of
moisture in the refrigerant circuit.
Connect the vacuum pump to the charge connector.
Proceed as follows:
- Evacuate the circuit to a pressure of at least 35 mbar absolute. Charge the circuit with nitrogen to a relative
pressure of approx. 1 bar.
- Repeat the operation described above.
- Repeat the operation described above for the third time in order to reach the highest degree of vacuum possible.
This procedure should guarantee the elimination of up to 99% of contaminants.
Blue Box - 90
Page 97
12.3.3 Refrigerant charge
- Connect the refrigerant gas cylinder to the male 1/4 SAE charge connector on the liquid line and allow a small
amount of gas to escape in order to purge the connection hose of air.
- The circuit must be charged exclusively with liquid; therefore, if the cylinder is not equipped with a dip pipe it
must be turned upside-down.
12.4 ENVIRONMENTAL CONSIDERATIONS
Laws governing the use of substances detrimental to the ozone layer prohibit the dispersal of refrigerant gases in
the environment, obliging users to recover refrigerants at the end of their useful life and consign them to the
dealer or to specific collection centres.
Refrigerants R22 and R407C are mentioned among substances subject to special monitoring regimes established
by law, and as such they are subject to the prescriptions indicated above.
Units operating with R407C must be charged exclusively with liquid
refrigerant by way of the charge connection on the liquid line.
Use special care during maintenance work in order to limit the risk of
refrigerant leakage as far as possible.
Blue Box - 91
Page 98
13. DECOMMISSIONING THE UNIT
When the unit has reached the end of its useful life and must therefore be removed and replaced, adhere to the
following rules:
- the refrigerant must be recovered by a qualified technician and sent to an authorised collection centre;
- also the compressor lubrication oil must be recovered and sent to a collection centre;
- the structure and components, if unusable, must be stripped down and separated according to the material
type; this is particularly important for copper and aluminium, which are fairly abundant on the machine.
This procedure is designed to assist the work of collection, disposal, and recovery specialists and to reduce the
associated environmental impact.
Blue Box - 92
Page 99
REFRIGERANT CIRCUIT DIAGRAM
SIGMA 2002 - SIGMA 2002/DC - MODELS 3.2 - 13.2
Blue Box - 93
Page 100
REFRIGERANT CIRCUIT DIAGRAM
SIGMA 2002 - SIGMA 2002/DC - MODELS 14.4 - 26.4
Blue Box - 94
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.