Blue Angel Pumps SSBCS100 User Manual [en, es, fr]

Sump, Effl uent and Sewage pumps
INSTALLATION MANUAL
Read and save these instructions. This manual contains very important Safety Warnings and Operating Instructions. You will need to refer to it before attempting any installation or maintenance. Always keep this manual with the unit so that it will be easily accessible. Failure to read and follow these warnings and instructions could result in property damage, serious injury or death.
DESCRIPTIONS
SUMP PUMPS
EFFLUENT PUMPS
Effl uent pumps are pumps used to remove grey water from septic tanks, sump pits or laundry tray systems. Grey water is waste water from bathtubs, sinks, washing machines, and other kitchen appliances. The pumps are designed to pass solids 1/2 to 3/4 inches in diameter.
SEWAGE PUMPS
Sewage pumps are pumps used to remove waste water that contains solids up to 2 inches in diameter. The most common application is for draining bathroom waste water to a sewer or septic line.
IMPORTANT SAFETY INFORMATION
UNPACKING
Inspect your pump. Occasionally, products are damaged during shipment. If the unit is damaged, contact our Customer Service department at the number listed on the parts and warranty sheet.
READ & FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS — DO NOT DISCARD
SAFETY GUIDELINES
This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe all safety information labeled danger, warning, caution, and notice.
DO NOT USE AN EXTENSION CORD. Extension cords could present a safety hazard if not sized properly, become damaged or the connection falls into the sump. If receptacle is not within reach of the pump’s power cord, contact a qualifi ed licensed electrician to install a new receptacle.
WARNING INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.
RISK OF ELECTRIC SHOCK. TO REDUCE THIS RISK, OBSERVE THE FOLLOWING WARNINGS:
MAKE SURE THERE IS A PROPERLY GROUNDED RECEPTACLE AVAILABLE. This pump is supplied with a
grounding conductor and grounding-type attachment plug. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding-type receptacle.
NEVER REMOVE THE GROUND PRONG from the plug or bypass the grounding wires.
FOR ADDED SAFETY the receptacle should be protected with a ground fault circuit interrupter (GFCI). All wiring must be performed by a qualifi ed licensed electrician and comply with the National Electric Code and all applicable local codes and ordinances.
DO NOT REMOVE POWER SUPPLY CORD and strain relief or connect conduit directly to the pump.
MAKE SURE THE POWER SUPPLY HAS A FUSE OR CIRCUIT BREAKER rated to handle the current (amps) noted
on the pump nameplate or cordtag.
ALWAYS DISCONNECT THE PUMP from power supply before installing, servicing or making any adjustments.
DO NOT SUBMERGE PEDESTAL MOTOR or allow motor to be exposed to water.
DO NOT WALK on the fl oor when water is present until all power is turned off. If the electric panel is in the basement, call an electrician.
NEVER HANDLE A PUMP or motor with wet hands or when standing on a wet or damp fl oor while the pump is plugged into the power supply.
WASH HANDS AFTER HANDLING. According to the state of California (Prop 65), this product may contain chemicals known to the state of California to cause cancer and birth defects or other reproductive harm.
RISK OF ELECTRIC SHOCK. This pump has not been investigated for use in swimming pool and marine areas.
DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS
such as gasoline, fuel oil, kerosene, etc. Do not use in a fl ammable and/or explosive atmosphere. Pump should only be used to pump clear water. Personal injury and/or property damage could result.
PUMPS ARE NOT DESIGNED TO TRANSFER WATER INTENDED FOR DRINKING. Do not use the pump for moving
water that will be used for potable/drinking water. Pump should only be used in applications for which it is designed.
Printed on 100% Recycled Paper
200001-015 6/11© 2011
INSTALLATION MANUAL
CAUTION INDICATES A POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.
TO REDUCE THE RISK OF HAZARDS THAT CAN CAUSE INJURY OR PROPERTY DAMAGE, OBSERVE THE FOLLOWING WARNINGS:
IT IS RECOMMENDED TO USE A CHECK VALVE with this
pump to prevent the back-fl ow of fl uid after each pump cycle.
DO NOT INSTALL OR OPERATE THE PUMP IF IT HAS BEEN DAMAGED IN ANY WAY.
DO NOT LIFT OR CARRY THE PUMP BY THE POWER CORD. Use the pump’s handle.
IF THIS PUMP CONTAINS A SWITCH FOR AUTOMATIC OPERATION, IT IS THE INSTALLER’S RESPONSIBILITY TO MAKE SURE THE SWITCH IS ABLE TO OPERATE WITHOUT ANY OBSTRUCTIONS WITHIN THE BASIN. It is
recommended that the installer test and observe the pump’s operation for several cycles after installation.
IT IS RECOMMENDED TO USE RIGID PIPING AND FITTINGS to secure the pump in the basin and reduce pump
movement. Pump movement can prevent the switch from operating correctly.
THIS PUMP SHOULD BE INSPECTED 3 TO 4 TIMES PER YEAR for pump movement or buildup of debris on the switch or
fl oat. Reposition pump if it has moved. Remove any debris that could interfere with the operation of the switch.
DO NOT USE THIS PUMP IN MUD, SAND, CEMENT, OIL OR CHEMICALS.
DO NOT USE SUMP AND EFFLUENT PUMPS TO HANDLE RAW SEWAGE.
AN INDEPENDENT HIGH WATER ALARM OR BACK UP PUMP SHOULD BE USED when risk of property damage from
high water levels exists
THE SWITCH SHOULD BE REPLACED EVERY TWO (2) YEARS. This maintenance will reduce the risk of improper
pump operation, switch failure, or fl ooding.
TYPICAL SUMP INSTALLATION DIAGRAMS
Figure 1: Submersible Sump
1
Figure 2: Pedestal Sump
2 3
4
1
7
2
3
8
12
5
6 7 8
MINIMUM
BASIN
HEIGHT
(SEE
CHART A,
COLUMN B)
MAXIMUM BASIN HEIGHT (SEE CHART B,
COLUMN B)
9
MINIMUM BASIN DIAMETER
(SEE CHART A, COLUMN A)
1. GFCI OUTLET 5. PIPE INLET 9. SUMP BASIN
2. CHECK VALVE 6. DISCHARGE PIPE 10. FLOAT ROD
3. VENT PIPE 7. SUMP PUMP 11. FLOAT GUIDE
4. GASKET/BASIN LID 8. SWITCH (SEE CHART A, ON PAGE 3) 12. SWITCH ARM
2
Printed on 100% Recycled Paper
9
4
11
5
10
6
MINIMUM BASIN
DIAMETER
(SEE CHART B,
COLUMN A)
TYPICAL SUMP INSTALLATION
INSTALLATION MANUAL
1. This installation must be in accordance with the National Electric Code and all applicable local codes and ordinances.
2. Use a basin that is large enough to accommodate the pump. The minimum requirements for the sump pumps are:
CHART — A
Switch Type
Sumps
Submersible
CHART — B
Switch Type
Pedestal Float Switch
A
Minimum
Basin Diameter
Tether Float Switch 14 in. 22 in.
Diaphragm Switch 11 in. 22 in.
Vertical Float Switch 11 in. 22 in.
A
Minimum
Basin Diameter
(Figure 2, on page 2)
14 in. 24 in.
B
Minimum
Basin Height
B
Maximum
Basin Height
9. Install a union to allow for easy removal of the pump for cleaning or service.
10. Install a check valve (required) to prevent back-fl ow. The check valve may be positioned just above the basin to allow easy removal of the pump for cleaning and service.
11. Install a gate valve or ball valve if required by local, regional or state code.
12. Secure power supply cord to discharge pipe using cable or zip ties to prevent possible switch entanglement.
13. Connect pump power supply cord to a ground fault circuit interrupter (GFCI) receptacle.
14. Fill the basin with water. The pump will start when the water level has reached the switch-on level.
15. The pump will stop when the water level has reached the switch-off level.
16. Verify the switch is operating without any obstruction from the pump, piping and basin.
3. Clean the basin of all debris.
4. Assemble switch or fl oat if needed. Refer to warranty and service parts sheet for specifi c directions.
5. Set the pump on a solid, level surface. Do not place pump directly on clay, earth, gravel or sand. A brick or block may be installed under the pump to provide a solid base.
6. Position pump so the switch is away from the inlet so switch is clear from incoming water. Verify the switch has at least 1 in. clearance to the side wall of the basin and is free to move throughout its movement. If optional control device or fl oat is used, follow mounting instruction supplied with device or fl oat.
7. Install discharge plumbing according to local, regional and state codes. Rigid PVC pipe is recommended.
8. If required, drill 1/8 in. “weep” hole in the discharge pipe 1 in. above the pump discharge. Water stream will be visible from the hole when the pump is running. The hole must be cleaned periodically.
17. Fill the basin with water again. While the pump is draining the basin, verify the discharge pipe is carrying the water to a point at least 3 ft. away from the foundation. If the discharge line is exposed to freezing temperatures, the pipe must be positioned in a downward slope away from the foundation so any remaining water will drain away and not freeze.
18. Secure the basin cover and gasket to the basin to prevent debris from falling into the basin, prevent personal injury, and to contain gases and/or odors.
This pump is not designed to handle salt water, brine, laundry discharge, water softener, sewage, grey water, or any other application which may contain caustic chemicals and/or foreign materials. Pump damage could occur if used in these applications and will void warranty
Printed on 100% Recycled Paper
3
INSTALLATION MANUAL
TYPICAL EFFLUENT INSTALLATION
1. This installation must be in accordance with the National Electric Code and all applicable local codes and ordinances.
16. Secure a basin/tank cover and gasket to the basin to prevent debris from falling into the basin, prevent personal injury, and to contain gases and/or odors.
2. For sump applications, follow typical sump installation instructions (page 3). For effl uent applications, continue to step 3.
3. Clean the basin of all debris.
4. Set the pump on a solid, level surface. Do not place pump directly on clay, earth, gravel, or sand. A brick or block may be installed under the pump to provide a solid base.
5. Verify the fl oat switch has at least 1 inch clearance to the side wall of the basin and is free of any possible obstructions.
6. If optional control device or fl oat is used, follow mounting instructions supplied with device or fl oat.
7. Install discharge plumbing according to local, regional and state codes. Do not reduce the discharge pipe size below that which is provided on the pump.
8. If required, drill a 1/8 in. “weep” hole in the discharge pipe 1 in. above the pump discharge. Water stream will be visible from the hole when the pump is running. The hole must be cleaned periodically.
9. Install a union to allow easy removal of the pump for cleaning and service.
10. Install a check valve (required) to prevent back-fl ow. It should be installed above the union.
11. A gate valve or ball valve should be installed above the check valve as required by local, regional or state codes.
Figure 3: Effl uent Pump in Septic Tank
34
5
6 7
8
2
12
1
12. Connect remaining discharge pipe. The remainder of the discharge line should be as short as possible with a minimum number of turns.
13. Secure power supply cord to discharge pipe using cable or zip ties to prevent possible switch entanglement.
14. Connect pump power supply cord to a ground fault circuit interrupter (GFCI) receptacle.
15. Fill the basin with water. The pump will start when the water level has reached the switch-on level. Verify the pump is operating normally. If the discharge line is exposed to freezing temperatures, the pipe must be positioned in a downward slope away from the foundation so any remaining water will drain away and not freeze.
4
Printed on 100% Recycled Paper
9
10 11
1. Discharge Outlet Pipe 7. Septic Tank
2. Junction Box 8. Effl uent Pump
3. Pump/Switch Wires 9. Brick or Block
4. Union 10. Discharge Pipe
5. Effl uent Inlet Pipe 11. Check Valve
6. Switches 12. Tank Lid
INSTALLATION MANUAL
TYPICAL SEWAGE INSTALLATION
1. This installation must be in accordance with the National Electric Code and all applicable local codes and ordinances.
2. For sump applications, follow typical sump installation instructions (page 3). For effl uent applications, follow typical effl uent installation instructions (page 4). For sewege applications, proceed to step 3.
3. Use a basin that is large enough to accommodate the pump. The basin diameter should be a minimum of 18 inches and the depth a minimum of 24 inches.
4. Clean the basin of all debris.
5. Set the pump on a solid, level surface. Do not place pump directly on clay, earth, gravel, or sand. A brick or block may be installed under the pump to provide a solid base.
6. Position pump in the basin so the switch is away from incoming water. Verify the fl oat switch has at least 1 inch clearance to the side wall of the basin and is free of any possible obstructions.
17. Fill the basin with water. The pump will start when the water level has reached the switch-on level. Verify the pump is operating normally.
18. Install a basin cover and gasket to prevent debris from falling into the basin, prevent personal injury and to contain gases and odors.
Figure 7: Submersible Sewage Pumps
1
2
11
10
3
7. Install discharge plumbing according to local, regional and state codes. Do not reduce the discharge pipe size below that which is provided on the pump.
8. If required, drill a 1/8 in. “weep” hole in the discharge pipe 1 in. above the pump discharge. Water stream will be visible from this hole when the pump is running. The hole must be cleaned periodically.
9. If optional control device or fl oat is used, follow mounting instruction supplied with device or fl oat.
10. A union should be installed above the basin to allow easy removal of the pump for cleaning and service.
11. Install a check valve (required) to prevent back-fl ow. It should be installed above the union.
12. A gate valve or ball valve should be installed above the check valve as required by local, regional or state codes.
13. Connect remaining discharge pipe. The remainder of the discharge line should be as short as possible with a minimum number of turns.
14. A vent pipe is required. It removes gases and odors and should be installed as required by local, regional or state codes.
15. Secure power supply cord to discharge pipe using cable or zip ties to prevent possible switch entanglement.
16. Connect pump power supply cord to a properly grounded receptacle.
4 5
6
9
7
8
1. Check Valve 7. Switch
2. Union 8. Minimum Diameter (18 in.)
3. Discharge Pipe 9. Minimum Depth (24 in.)
4. Inlet Pipe 10. Gasket/Basin Lid
5. Basin 11. Vent Pipe
6. Pump
Printed on 100% Recycled Paper
5
INSTALLATION MANUAL
MAINTENANCE
ALWAYS DISCONNECT THE PUMP FROM POWER SUPPLY before installing, servicing or making any adjustments.
LET PUMP COOL FOR A MINIMUM OF 2 HOURS BEFORE ATTEMPTING TO SERVICE. Submersible pumps contain oil that
become pressurized and hot under normal operating conditions.
1. Submersible pump models have permanently lubricated bearings and require no additional lubrication.
2. The pump should be inspected 3-4 times per year for pump movement or buildup of debris on the switch or fl oat. Reposition pump if it has moved. Remove any debris that could interfere with the operation of the switch.
DO NOT SUBMERGE PEDESTAL MOTOR or allow motor to be exposed to water.
3. Submersible pump may contain dielectric oil for cooling. Dielectric oil can be harmful to the environment. Follow state environmental laws when disposing of oil.
4. The pump motor is equipped with automatic resetting thermal protector and may restart unexpectedly. Protector tripping is an indication of motor overloading as a result of operating the pump at low heads, excessively high or low voltage, inadequate wiring, incorrect motor conditions, or a faulty motor or pump.
DO NOT USE AN EXTENSION CORD. Extension cords could present a safety hazard if not sized properly, become damaged or the connection falls into the sump. If receptacle is not within reach of the pump’s power cord, contact a qualifi ed licensed electrician to install a new receptacle.
TROUBLESHOOTING
Symptoms Possible Cause(s) Suggested Remedies
Pump will not start or run
Pump starts and stops too often
1. Water level too low
2. Blown fuse or tripped circuit breaker
3. Low line voltage
4. Motor
5. Switch
6. Inlet screen clogged
7. Switch obstruction
1. Back-flow of water from discharge pipe
2. Switch
3. Check valve not functioning properly or leaking
1. Water must be at the appropriate level to activate switch
2. If blown, determine cause and then either replace with proper sized fuse or reset breaker
3. Contact an electrician
4. Replace pump
5. Replace switch
6. Remove debris
7. Remove obstruction to ensure free motion of switch
1. Install check valve
2. Replace switch
3. Remove and examine check valve for prop er in stal la tion and free operation. Replace check valve if necessary.
6
Printed on 100% Recycled Paper
TROUBLESHOOTING (CONTINUED)
Symptoms Possible Cause(s) Suggested Remedies
INSTALLATION MANUAL
Pump shuts off and turns on independently of switch (trips thermal overload protection)
Pump operates noisily or vibrates excessively
Pump will not shut off
Pump operates but delivers little or no water
1. Excessive water temperature
2. Switch
3. Switch obstruction
4. Obstruction in discharge pipe
5. Low line voltage
1. Worn bearings
2. Impeller obstructed or broken
3. Piping attachments to building structure too rigid or too loose
1. Switch
2. Switch obstructions
3. Restricted discharge (obstruction in piping)
4. Excessive inflow or pump not properly sized for application
1. Low line voltage
2. Inlet screen clogged
3. Broken impeller or debris in impeller cavity
5. Pump not properly sized for application
6. Check valve stuck closed or installed backwards
7. Shut off valve closed
1. Pump should not be used for water above 120º F
2. Replace switch
3. Remove obstruction to ensure free motion of switch
4. Remove obstruction in discharge piping
5. Contact an electrician.
1. Replace pump
2. Where applicable, remove screen and volute, clean impeller and/or replace impeller
3. Install rubber coupling (available at local hardware stores) to isolate pump vibration from discharge plumbing
1. Replace switch
2. Remove obstruction to ensure free motion of switch
3. Remove obstruction from discharge piping
4. Recheck all sizing calculations to determine proper pump size
1. Contact an electrician
2. Remove debris
3. Remove screen and volute, clean impeller and/or replace impeller
5. Recheck all sizing calculations to determine proper pump size
6. Remove and examine check valve for proper installation and free operation
7. Open valve
Printed on 100% Recycled Paper
7
INSTALLATION MANUAL
NOTES
8
Printed on 100% Recycled Paper