Blodgett AB2A Installation Manual

Page 1
Since 1848
INSTALLATION INSTRUCTIONS FOR
AB2A VENTILATION SYSTEM
FOR BLODGETT DOUBLE DECK MT3870
COMPUTERIZED CONVEYOR OVEN
LISTED
BLODGETT OVEN COMPANY
A Division of
50 Lakeside Avenue, Box 586, Burlington, Vermont 05402 USA Telephone (800) 3315842, (802) 8603700 Fax: (802)8640183
PN M9519 (3/98)
1998 - G.S. Blodgett Corporation
Page 2
TABLE OF CONTENTS
Delivery and Inspection Page 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Page 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning and Maintenance Page 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Page 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Flow Measurement Page 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AGENCY APPROVALS
The InVent Hood Systems are Listed by Underwriters Laboratories Inc. (UL) in category YYCW as Exhaust Hoods Without Exhaust Dampers. They are intended to be installed in accordance with NFPA 96, the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. The basic Standard used by UL to investigate products in this category is UL 710, the Standard for Exhaust Hoods for Commercial Cooking Equipment.
These hoods are considered to be Type 1 according to the International Mechanical Code (IMC); that is, they are, installed at or above all commercial food heatprocessing equipment that produces grease vapors or smoke." IMC is published by the International Code Council, Inc. and is compatible with codes written by the Building Officials and Code Administrators International, Inc., (BOCA), the International Conference of Building Officials (ICBO), and Southern Building Code Congress International, Inc. (SBCCI). The Uniform Mechanical Code (UMC) published by ICBO defines a Type I Hood as, a kitchen hood for collecting and removing grease and smoke." A Type II Hood is a general hood for collecting and removing steam, vapor, heat or odors." The hood type is determined by the intended use. UL tested and approved the InVents for use in the Type I environment.
These Hoods are NSF approved to ANSI/NSF21992, Food Equipment corrosion resistant. Furthermore, that there be no sharp corners or open seams where food, residue or soil collect.
Page 1
. ANSI/NSF21992 requires that all materials used be
Page 3
DELIVERY AND INSPECTION
Upon arrival of your AB2A ventilator, inspect the crate for damage and inform the shipper if necessary. Carefully unpack the unit and match the parts to the list below.
Item Blodgett P/N Qty Description
A AB2AA 1 AMU/Exhaust Manifold A1 AB2AA1 1 AMU Duct Extension A2 AB2AA2 1 Exhaust Duct Extension A3 AB2AA3 1 Top Exhaust Enclosure Bracket, Left A4 AB2AA4 2 Exhaust Duct Ceiling Trim A5 AB2AA5 2 AMU Duct Ceiling Trim B AB2AB 1 AMU Support Bracket, Right C AB2AC 1 AMU Support Bracket, Left D AB2AD 1 Lower Front AMU Plenum E AB2AE 1 Middle Front AMU Plenum F AB2AF 1 Upper Front AMU Plenum G AB2AG 2 Filter Trough/Receptacle H1 M9500 2 Filter,10x16" H2 M9501 2 Filter, 10 x 20" J AB2AJ 1 Vertical Exhaust Manifold, Left K AB2AK 1 Cooling Fan Exhaust Enclosure L AB2AL 1 Upper Top End Enclosure, Right L1 AB2AL1 1 Lower Top End Enclosure, Right L2 AB2AL2 1 Upper Heat Sheild, Right M AB2AM 1 Lower End Enlosure, Right M1 AB2AM1 1 Lower Heat Shield, Right N AB2AN 1 Upper Top End Enclosure, Left N1 AB2AN1 1 Lower Top End Enclosure, Left N2 AB2AN2 1 Upper Heat Shield, Left P AB2AP 1 Lower End Enclosure, Left P1 AB2AP1 1 Lower Heat Shield, Left Q AB2AQ 1 Hardware Bag (includes the following)
Q1 M9519 1 Installation Instructions Q2 M0652 4 1/4"20 Lock Nut Q3 M0222 8 1/4"20 x 1/2" Hex Head Screw Q4 R1417 1 1/4"20 Shoulder Bolt
Page 2
Page 4
Item Blodgett P/N Qty Description
Q5 M9509 1 1/4"20 x 1/2" Thumb Screw with Shoulder Washer Q6 M3828 2 Stacking Pins Q7 653 12 1/4" Flat Washer
Q8 M6315 3 #1024 x 1/2" Slotted Hex Head Screw R AB2AR 3 Oven Securing Clip S AB2AS 1 Mounting Bracket (Rev. A) S1 AB2AS1 1 Mounting Bracket (Rev. B) T AB2AT 1 Vertical Exhaust Manifold, Right
[G]
[P1]
[A4]
[A5]
[A3]
[N1]
[N2]
[A2]
[P]
[A]
[N]
[J]
[A1]
[C]
[S1]
[S]
[K]
[M]
[F]
[D]
[L2]
[L]
[L1]
[M1]
[E]
[T]
[H1]
[B]
[H2]
Figure 1
Page 3
Page 5
INSTALLATION
Step 1 - Oven Preparation
Assemble both ovens as described in the Blodgett MT3870 OwnerOperator Manual.
Use the three (3) Oven Securing Clips [R] to secure the two decks together and prevent shifting. (See Figure 2)
[R]
[R]
[R]
Page 4
Figure 2
Page 6
If the ovens are equipped with align ment knockouts, remove the two (2) front indents. Those holes should match the two (2) shown in Figure 3.
If the ovens are not equipped with align ment indents, locate the center, front, top edge of the upper oven. Drill two (2) 7/16" diameter holes in the top of the oven as indicated in Figure 3. The holes should penetrate both the top skin" of the oven as well as the angle frame members. There is no need to penetrate the top of the oven by more than 7/8".
68 1/2
34 1/4 34 1/4
7/16 (2 PLS)
2 7/162 7/16
Page 5
FRONT OF OVEN
Figure 3
Page 7
If the ovens are equipped with louvered cooling fan exhaust outlets, attach the Cooling Fan Exhaust Enclosure Mount ing Plate [S1] to the top oven using two #1024x1/2" screws [Q8] provided. See Figure 4. For older oven models use the alternate Cooling Fan Exhaust Enclo sure Mounting Plate [S].
[S1]
Page 6
Figure 4
Page 8
Step 2 - AMU Installation:
Thread two (2) Stacking Pins [Q6] into the fittings on the bottom of the AMU/Ex haust Manifold/Duct Connection as sembly [A]. Carefully lift the AMU/Ex haust Manifold/Duct Connection as sembly [A] and place it on top of the ovens. The alignment pins will fit into the alignment holes in the top of the oven and prevent the AMU/Exhaust Manifold/ Duct Connection assembly [A] from shifting on top of the oven. (See Figure 5)
If the AMU/Exhaust Manifold/Duct Con nection assembly [A] does seat tightly against the top of the oven, apply a bead of high temperature silicone sealant in the seam between the AMU/Exhaust Manifold/Duct Connection assembly [A] and the sides of the oven.
[A]
[Q6]
Silicone Sealant
Alignment Hole
Page 7
Figure 5
Page 9
Attach the AMU Support Bracket, Right [B] to the AMU/Exhaust Manifold/Duct Connection assembly [A] using two (2) 1/4"20 x 1/2" Hex Head Cap Screws [Q3] and 1/4" Flat Washers [Q7]. (See Figure 6)
Attach the AMU Support Bracket, Left [C] to the AMU/Exhaust Manifold/Duct Connection [A] assembly using two (2) 1/4"20 x 1/2" Hex Head Cap Screws [Q3] and 1/4" Flat Washers [Q7]. (See Figure 6)
[Q3] (4)
[Q7] (4)
[B]
[C]
Page 8
Figure 6
Page 10
Secure the AMU Support Bracket, Right [B] below the right front support leg mounting flange. (See Figure 7) Use the same inner, front bolt and washer that secures the leg in place to hold the AMU Support Bracket, Right [B].
Secure the AMU Support Bracket, Left [C] below the left front support leg mounting flange. (See Figure 7) Use the same inner, front bolt and washer that secures the leg in place to hold the AMU Support Bracket, Left [C].
The AMU Support Bracket, Right [B] and AMU Support Bracket, Left [C] should be parallel and square and held firmly against the front of the ovens.
[B]
Page 9
Figure 7
Page 11
Place the Lower Front AMU Panel [D] on the lower pins of the AMU Support Bracket, Right [B] and AMU Support Bracket, Left [C]. (See Figure 8)
Place the Middle Front AMU Panel [E] in the middle pins of the AMU Support Bracket, Right [C] and AMU Support Bracket, Left [D].
[B]
Place the Upper Front AMU Panel [F] in the upper pins of the AMU Support Bracket, Right [C] and AMU Support Bracket, Left [D].
[E]
[F]
[D]
[C]
Figure 8
Page 10
Page 12
Step 3 - Exhaust Installation:
Attach the Vertical Exhaust Manifold, Right [T] to the AMU Support Bracket, Right [B] with two (2) 1/4"20 x 1/2" Thumb Screws [Q5]. (See Figure 9)
Attach the Vertical Exhaust Manifold, Left [J] to the AMU Support Bracket, Left [C] with two (2) 1/4"20 x 1/2" Thumb Screws [Q5]. (See Figure 9)
[A]
[Q5]
[J]
[Q5]
[T]
[K]
Page 11
Figure 9
Page 13
Attach the Cooling Fan Exhaust Enclo sure [K] to the AMU/Exhaust Manifold/ Duct Connection [A].
Flange
Ta b
[K]
On ovens with louvered exhaust ports, remove the tab from the Cooling Fan Ex haust Enclosure [K] and replace the fas teners into the holes. The Cooling Fan Exhaust Enclosure [K] will be held in place by the Cooling Fan Exhaust En closure Mounting Plate [S or S1].
For ovens that have separate cooling fans and grills on the right side (oppo site the control cabinets), a tab on the Cooling Fan Exhaust Enclosure [K] will fit over the rivet in the AMU/Exhaust Man ifold/Duct Connection [A]. (See Figure 10) The flange on the Cooling Fan Exhaust Enclosure [K] should rest on top of the oven before the rivet bot toms out in the slot of the flange.
[S or S1]
Oven
[A]
Rivet
Page 12
Figure 10
Page 14
Caution: The hole location described below should not interfere with any oven control center components. Care must be taken when locating and drilling this hole to avoid damage to internal components.
Drill one (1) 1/4" diameter hole into the upper control cabinet as shown in Figure 11. The distance from the top of the upper oven to the center line of the hole should be the same as the distance from the top of the upper oven to the center line of the pin welded in the sur face of the Vertical Exhaust Manifold, Left [J].
Insert one (1) 1/4"-20 Shoulder Bolt [Q4] through the hole and secure it in place with one (1) 1/4" Flat Washer [Q7] and one (1) 1/4"-20 Lock Nut [Q2].
1
15 9/16
Shoulder Bolt [Q5]
Page 13
FRONT VIEW
Figure 11
Page 15
Locate the Bracket, Top Exhaust Enclo sure, Left Hand [A3] at the junction of the AMU/Exhaust Manifold, Duct As sembly [A] and the forward, inboard edge of the upper oven control cabinet. (See Figure 12). The forward edge of the Bracket, Top Exhaust Enclosure, Left Hand [A3] should be vertical. There should be a minimum of 343/16" be tween the front face of the control cabi net and the rear face of the Vertical Ex haust Manifold, Left [J]. If necessary, loosen the bolts that hold the control cabinet to the oven and shift the control cabinet rearward.
Using the Bracket, Top Exhaust Enclo sure, Left Hand [A3] as a template, draw marks on the top of the control cabinet. Drill one (1) 1/4" diameter hole in the spot marked. Secure the Bracket, Top Exhaust Enclosure, Left Hand [A3] in place using 1/4"20 x 1/2" Hex Head Cap Screws [Q3], 1/4" Flat Washers [Q7], and 1/4"20 Lock Nuts [Q2] as shown in Figure 12.
[Q2]
[Q7]
[Q3]
[A3]
Figure 12
Page 14
Page 16
Install one (1) Filter Trough/Receptacle [G] into the opening in each end of the AMU/Exhaust Manifold/Duct Connec tion [A] assembly. The tabs in the Filter Trough/Receptacle [G] fit into the slots on the sides of the openings in the AMU/ Exhaust Manifold/Duct Connection [A] assembly. (See Figure 13)
Insert one (1) 10 x 16" Filter [H1] and one (1) 10 x 20" Filter [H2] into each end of the AMU/Exhaust Manifold/Duct Con nection [A] assembly. Install the top of the Filter [H1 and H2] into the channel in the top of the AMU/Exhaust Manifold/ Duct Connection [A] assembly first. Then allow the bottom of the Filter [H1 and H2] to drop into the Filter Trough/ Receptacle [G].
Repeat the above procedure on the oth er end of the oven for the remaining Fil ter Trough/Receptacle [G], one (1) 10 x 16" Filter [H1] and one (1) 10 x 20" Filter [H2].
[G]
Page 15
Figure 13
Page 17
Mount the Lower Top End Enclosure, Right Hand [L1] in place. The slots on the sides toward the rear of the Lower Top End Enclosure, Right Hand [L1] will fit over the pins in the Cooling Fan Ex haust Enclosure [K] and the Vertical Ex haust Manifold, Right Hand [T].
Mount the Upper Top End Enclosure, Right Hand [L] in place. The angle to the rear of the Upper Top End Enclosure, Right Hand [L] will fit into the angle in the AMU/Exhaust Manifold/Duct Connec tion [A].
Mount the Lower End Enclosure, Right Hand [M] in place. The slots on the sides towards the rear of the Lower End Enclo sure, Right Hand [M] will fit over the pins in the Cooling Fan Exhaust Enclosure [K] and the Vertical Exhaust Manifold, Right Hand [T]. (See Figure 14)
[A]
[T]
[L1]
[L]
[M]
[K]
Page 16
Figure 14
Page 18
Mount the Upper Right Hand Heat Shield [L2] in place by locating the slots over the pins in the Upper Top End En closure, Right Hand [L].
[L]
Mount the Lower Right Hand Heat Shield [M1] in place by locating the slots over the pins in the Lower End Enclosure, Right Hand [M]. (See Figure 15)
[L1]
[L2]
[M1]
[M]
Figure 15
Page 17
Page 19
Mount the Lower Top End Enclosure, Left Hand [N1] in place. The slots on the sides towards the rear of the Lower Top End Enclosure, Left Hand [N1] will fit over the pins in the Bracket, Top Ex haust Enclosure, Left Hand [A3] and the Vertical Exhaust Manifold, Left Hand [J].
Mount the Upper Top End Enclosure, Left Hand [N] in place. The angle to the rear of the Lower End Enclosure, Left Hand [N] will fit into the angle in the AMU/Exhaust Manifold/Duct Connection [A].
[A]
[A3]
[N1]
Mount the Lower End Enclosure, Left Hand [P] in place. The slots on the sides towards the rear of the Lower End En closure, Left Hand [P] will fit over the Shoulder Bolt [Q5] in the control cabi net and the pin on the Vertical Exhaust Manifold, Left Hand [J]. (See Figure 16).
[N]
[P]
[J]
Figure 16
Page 18
Page 20
Mount the Upper Left Hand Heat Shield [N2] in place by locating the slots over the pins in the Upper Top End Enclo sure, Left Hand [N].
Mount the Lower Left Hand Heat Shield [P1] in place by locating the slots over the pins in the Lower End Enclosure, Left Hand [P]. (See Figure 17).
[N]
[N2]
[P1]
Page 19
[P]
Figure 17
Page 21
Step 4 - Duct Connection:
Note: The Duct Collar Extensions [A1 and A2] are designed to remain in place when the oven is rolled away for maintenance
or cleaning. Therefore, they should be rigidly fastened to the ceiling structure as they are not intended to support the weight of the duct work and/or fans.
Roll the oven into its operating location. Locate the Exhaust Duct Extension [A2] on top of the exhaust duct collar (part of the AMU/Exhaust Manifold/Duct Con
AMU Duct
Exhaust Duct
nection [A]) and secure it in place with the two (2) overcenter latches. The ex haust duct extension is designed to penetrate an eight foot (8'0") tall ceiling by approximately two inches (2"). Con nect the duct from the exhaust fan to the
Finished Ceiling
[A1]
[A]
[A2]
[A]
Exhaust Duct Extension [A2]. (See Figure 18)
Locate the AMU Duct Extension [A1] on top of the Air Make Up duct collar (part
Wall
of the AMU/Exhaust Manifold/Duct Con nection [A]) and secure it in place with the two (2) overcenter latches. The AMU duct extension is also designed to penetrate an eight foot tall ceiling by approximately two inches (2"). Connect the duct from the Air Make Up fan to the AMU Duct Extension [A1].
Page 20
Figure 18
Page 22
CLEANING AND MAINTENANCE
Caution: The oven and the ventilation system get hot during operation. Allow the oven/ventilation system assembly to cool so as to avoid possible injury.
Note: NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, requires that "hoods,
grease removal devices, exhaust fans, and ducts shall have a clearance of at least 18" (457.2 mm) to combustible mate rial, 3" (76.2 mm) to limited combustible material, and 0" (0 mm) to noncombustible material." The AB2A InVent is equipped with louvers on the top of the hood which supply makeup air to the general vicinity of the oven and help to cool the area around the oven. DO NOT store or place items on top of the hood.
Every month:
Remove the Heat Shields [L2, M1, N2 and P1] and End Enclosures [L, L1, M, N, N1 and P] by lifting them up and pulling them away from the oven. Remove the Filters [H1 and H2] by lifting them up and then swinging the bottom out and down. Remove the Filter Trough Receptacles [G]. Clean the parts by running them through a dishwasher or wash them by hand with hot, soapy water. Do not use scouring pads (plastic or metal) on the exterior surfaces as they will scratch and mar the exterior finish. Rinse the panels in warm water and dry them. Install the Filter Trough/Receptacles, Filters, End Enclosures and Heat Shields as described on pages 15 through 19.
Every three (3) months:
Remove the Heat Shields [L2, M1, N2 and P1] and End Enclosures [L, L1, M, N, N1 and P] by lifting them up and pulling them away from the oven. Remove the Filters [H1 and H2] by lifting them up and then swinging the bottom out and down. Remove the Filter Trough Receptacles [G]. Lift off the Cooling Fan Exhaust Enclosure [K]. Remove the Vertical Exhaust Manifolds, [T and J], by removing the thumb screws [Q5]. Clean the parts by running them through a dishwasher or wash them by hand with hot, soapy water. Do not use scouring pads (plastic or metal) on the exterior surfaces as they will scratch and mar the exterior finish. Wipe out the exhaust channel portion of the AMU/Exhaust Manifold/Duct Connection [A] assembly. Brush and clean the louvers or guards of the oven cooling fans. Dry the parts and return them to their posi tions as described in the Exhaust Installation portion of this manual (pages 11 through 18).
Note: This regular maintenance is in addition to the daily, quarterly, semiannual and annual cleaning schedule included in
the oven operating manual.
Page 21
Page 23
SERVICING
For servicing the oven, disconnect the gas and electric services from the oven as described in the MT3870 Owner  Op erator Manual. To move the oven/ven tilation system assembly for mainte nance, release the overcenter latches on the exhaust and Air MakeUp duct collars. Slide the clamping collars up and secure them out of the way. Release the brakes on the front locking casters of the oven assembly. Roll the oven out away from the wall. (See Figure 19).
[A2]
Clamping Collars
OverCenter Latches
Exhaust Duct
AMU Duct
[A1]
Clamping Collar
A
Page 22
B
Figure 19
Page 24
AIR FLOW MEASUREMENT
Ports are provided on both the exhaust and makeup air duct collars of the AMU/Exhaust Manifold/Duct Connec tion [A] assembly. (See Figure 20). The ports are sealed with 1/4"20 threaded fasteners. After removing the threaded fasteners, a manometer can be con nected to the ports using 1/4" soft vinyl tubing. After adjusting the air flow using the manometer and the graphs on the following pages, the tubing is to be re moved and the threaded fasteners rein stalled into the ports. High temperature sealant should be applied to the threads of the fastener inserted into the exhaust duct port to ensure a greasetight seal.
Pressure Ports
Figure 20
Page 23
Page 25
The recommended minimum exhaust air flow is onethousand, sixhundred cubic feet per minute (1600 CFM). The recom mended maximum makeup air flow is onethousand twohundred cubic feet per minute (1200 CFM). The recommended net amount of air exhausted from the kitchen is fourhundred cubic feet per minute (400 CFM). The ventilator will perform satisfactorily with onehundred percent (100%) makeup air. However, it is generally recommended that the kitchen area be slightly negative in pressure relative to the rest of the building.
Exhaust air static pressure should be taken at the port provided on the Exhaust Duct on the AMU/Exhaust Manifold/Duct Connection [A] with a manometer. See Figure 20 for port location. Refer to the chart below to reference static pressure to air flow. A static pressure of one inch of water column (1.0" w.c.) is recommended to achieve an air flow of sixteenhundred cubic feet per minute (1600 CFM).
AB2A Exhaust Air Flow
2500
2000
1500
1000
Cubic Feet per Minute
500
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
Static Pressure (inches w.c.)
Page 24
Page 26
Makeup air should be tempered to prevent temperatures from dropping below 40F (4.4C) or exceeding 90F (32.2C). The ventilator will operate satisfactorily at temperatures outside of these limits, however, operator comfort may be affected. Additional loading of the building's Heating Ventilation and Air Conditioning (HVAC) system may also result.
Makeup air static pressure should be taken at the port provided on the Supply Duct on the AMU/Exhaust Manifold/Duct Con nection [A] with a manometer. See Figure 20 for port location. Refer to the chart below to reference static pressure to air flow. A static pressure of ninehundredths of an inch of water column (0.09" w.c.) is recommended to achieve an air flow of twelve hundred cubic feet per minute (1200 CFM).
AB2A MakeUp Air Flow
2500
2000
1500
1000
Cubic Feet per Minute
500
0
0.00 0.05 0.10 0.15 0.20 0.25
Static Pressure (inches w.c.)
Page 25
Page 27
Figure 21
Page 26
Loading...