Blodgett 957 Installation Manual

Installation, Maintenance, & Repair Series 957, 957RPDA, LF957RPDA
Reduced Pressure Zone Assemblies Reduced Pressure Detector Assemblies
Sizes: 21⁄2" – 10" (65 – 250mm)
RP/IS-957/957RPDA
957 OSY
WARNING
!
You are required to thoroughly read all installation instructions and product safety information before beginning the installa­tion of this product. FAILURE TO COMPLY WITH PROPER
INSTALLATION AND MAINTENANCE INSTRUCTIONS COULD RESULT IN PRODUCT FAILURE WHICH CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY AND/ OR DEATH. Watts is not responsible for damages resulting from
improper installation and/or maintenance.
Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation. If this informa­tion is not consistent with local building or plumbing codes, the local codes should be followed.
Need for Periodic Inspection/Maintenance: This product must be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. Corrosive water conditions, and/or unauthorized adjustments or repair could render the product ineffective for the service in­tended. Regular checking and cleaning of the product’s internal components helps assure maximum life and proper product function.
NOTE: For Australia and New Zealand: Pipeline strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer.
It's important that this device be tested periodically in compli­ance with local codes, but at least once per year or more as service conditions warrant. If installed on a fire sprinkler system, all mechanical checks, such as alarm checks and backflow preventers, should be flow tested and inspected internally in ac­cordance with NFPA 13 and NFPA 25.
Testing
For field testing procedure, send for IS-TK-DL, IS-TK-9A, IS-TK­99E AND IS-TK-99D.
For other repair kits and service parts, send for PL-RP-BPD.
For technical assistance, contact your local Watts representative.
Installation Instructions
Series 957, 957RPDA, LF957RPDA
Guidelines
1. Most field problems occur because dirt and debris are pres­ent in the system at the time of installation and becomes trapped in the #1 check. The system should be flushed before the backflow valve is installed. If the system is not flushed until after the backflow valve is installed, remove both check modules from the valve and open the inlet shutoff to allow water to flow for a sufficient time to flush debris from the water line. If debris in the water system continues to cause fouling, a strainer can be installed upstream of the backflow assembly.
2. Watts Series 957, 957RPDA and LF957RPDA may be in­stalled in either horizontal, “N” pattern, or “Z” pattern position as long as the backflow assembly is installed in accordance with the direction of the flow arrow on the assembly and the local water authority approves the installation.
3. The assembly should be installed with adequate clearance around the valve to allow for inspection, testing and servic­ing. 12" (305mm) should be the minimum clearance between the lower portion of the assembly and the floor or grade. The valve should be protected from freezing.
4. Installing a backflow preventer in a pit or vault is not recom­mended.
5. Normal discharge and nuisance spitting are accommodated by the use of a Watts air gap fitting and a fabricated indirect waste line. Floor drains of the same size must be provided in case of excessive discharge.
6. The 957, 957RPDA and LF957RPDA backflow preventer should be tested by a certified tester at the time of installa­tion.
NOTE: Assembly body should not be painted.
Horizontal Installation
N Pattern
Z Pattern
lpm gpm 1330 350
1140 300
950 250
760 200
570 150
Rate of Flow
380 100
190 50
0 0
Relief Valve Discharge Rates 21⁄2" – 10" (65 - 250mm)
957, 957RPDA and LF957RPDA
0 20 40 60 80 psi 0 138 276 413 551 kPa
Pressure
2
Maintenance Instructions
Series 957, 957RPDA, LF957RPDA
21⁄2" – 6" (65 – 150mm)
Figure A
#1 Check Diagrams
Figure D
#2 Check Diagrams
Figure D
Prior to servicing any Watts valve, it is mandatory to shut down the water system by closing both the inlet and outlet shutoff valves. After shutoff valves are closed, open test cock #2, #3 and #4 to relieve pressure within the backflow assembly.
1. After #3 test cock has been opened to relieve pressure, re­move #3 test cock from housing. (Figure A)
2. Insert a #3 screwdriver through the hole on the top of the cover sleeve and using both hands rotate the cover sleeve ap­proximately to break the sleeve O-ring seals. Using the screwdriver, slowly slide the cover sleeve to the downstream side of the housing. (Figure B)
3. Remove the stainless steel check retainer from the housing. (Figure B)
4. Remove the #1 check module (Figure C) by inserting two flat blade screwdrivers into the slots on either side of the check module and gently pry the check module toward the open zone.
1
4-turn clockwise and 1⁄4-turn counter-clockwise
Figure B
Figure E
Figure E
5. Remove #2 check module with the same instructions as in #4 above. For servicing 6" (150mm) checks see 8" – 10" (200 – 250mm) instructions on p. 4.
6. To clean or inspect either check module, insert a #3 screw­driver through the downstream side of the check module as shown in Figure D and E. When the screwdriver is in place, remove the E-clip (Figure F) and pin connecting the structural members and the check clapper will open with no tension.
7. Thoroughly clean the seating area. The sealing disc may be removed, if necessary, by removing the screws connect­ing the keeper plate to the clapper. The sealing disc may be reversed and reinstalled if the elastomer is cut or damaged.
8. Wash check module and O-ring and inspect for any damage. If damaged, reinstall new parts.
9. After thorough cleaning, lubricate O-ring w/FDA approved lu­bricant, replace pin and E-clip in structural members, remove screw driver and reinstall check modules and assemble hous­ing in reverse order of these instructions.
Figure C
Figure F
Figure F
3
Loading...
+ 5 hidden pages