Block LR348-3/6 Datasheet

Product Ident
Line-Reactor
Datasheet
LR3 48-3/6
Original Date:
15/04/20
Observe protection clause to ISO 16016
Index
0
Name:
Lüning
Doc. type
Date:
15/05/06
Checked:
Wesner
Pages
1 of 2
Type Designation
LR3 48-3/6
Type of reactor
3~ Line Reactor
Series
LR3 Core Rating
150.65 var
Core type
3UI 48/17
Drive HP
3
No. of phase
3 Circuit type
III0 Rated Voltage
[ V ]
480 Rated current
[ A ]
6.0
Rated Frequency
[ Hz ]
50 - 60
Impedance
[ % ]
3.0 Inductance L
[ mH ]
3.700
L tolerance
[ % ]
±10%
Linearity
133% In
Losses (typical)
[ W ]
19.43
Test voltage
[ kV ]
4.0 Isolation System Class
class 130
Ambient temperature
[ °C ]
-10 … +40°C
Ambient temperature
[ F ]
14 … 104°F
Type of cooling
AN
Operating conditions
24/7
Type:
Signs
VDE 0570 / EN 61 558 Part 1 VDE 0570 / EN 61 558 Part 20
UL 508
E219022
NMTR
UL 5085-1
E103521
XPTQ
Identification
Technical Data
Operating conditions
Standards
Approvals
Product Ident
Line-Reactor
Datasheet
LR3 48-3/6
Original Date:
15/04/20
Observe protection clause to ISO 16016
Index
0
Name:
Lüning
Doc. type
Date:
15/05/06
Checked:
Wesner
Pages
2 of 2
Variations may apply due to material’s and production‘s tolerances. Objected to modifications without notice.
A B C* F D
d1
d2 E e1
e2
Drill
3.74
2.36
4.57 - 2.20
2.80 - 1.50
1.77
-
0.19
0.19
-
* = Typical variable air gab
Weight
[ kg ]
0.73
[ lbs ]
1.60
Technical specifications in the drawing are not binding. General tolerance to DIN 7168-m. Subject to change. Mounting plates also available in stainless steel as OEM application. Ask for detailes.
Dimensions / Mounting in Inches
Weight
Notes
Loading...