BLAUBERG Ventilatoren ISO-RB EC 200, ISO-RB EC 100, ISO-RB EC 150, ISO-RB EC 160, ISO-RB EC 125 User Manual

...
Page 1
Centrifugal duCt fan
USER’S MANUAL
EN
ISO-RB EC
Page 2
www.blaubergventilatoren.de
2
Safety requirements .....................................................................................................................................................................2
Purpose ................................................................................................................................................................................................4
Delivery set ........................................................................................................................................................................................ 4
Designation key .............................................................................................................................................................................. 4
Technical data ..................................................................................................................................................................................5
Unit design and operating principle ................................................................................................................................. 6
Installation and connection .................................................................................................................................................... 6
Connection to power mains .................................................................................................................................................. 8
Control ................................................................................................................................................................................................. 8
Technical maintenance .............................................................................................................................................................. 9
Troubleshooting ............................................................................................................................................................................. 9
Storage and transportation regulations .......................................................................................................................... 9
Manufacturer’s warranty ........................................................................................................................................................... 10
Certificate of acceptance .......................................................................................................................................................... 11
Seller information .......................................................................................................................................................................... 11
Installation certificate .................................................................................................................................................................. 11
Warranty card ...................................................................................................................................................................................11
SAFETY REQUIREMENTS
• Please read the user’s manual carefully prior to installing and operating the unit.
• All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
• The warnings contained in the user’s manual must be considered most seriously since they contain vital personal safety information.
• Failure to follow the rules and safety precautions noted in this user’s manual may result in an injury or unit damage.
• After a careful reading of the manual, keep it for the entire service life of the unit.
• While transferring the unit control, the user’s manual must be turned over to the receiving operator.
CONTENTS
UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS
• Disconnect the unit from power mains prior to any installation operations.
• Unpack the unit with care.
• The unit must be grounded!
• While installing the unit, follow the safety regulations specific to the use of electric tools.
This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the ISO-RB EC unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country. The information in this user’s manual is correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means in any information search system or translated into any language in any form without the prior written permission of the Company.
Page 3
www.blaubergventilatoren.de
3
• Do not change the power cable length at your own discretion. Do not bend the power cable. Avoid damaging the power cable. Do not put any foreign objects on the power cable.
• Do not lay the power cable of the unit in close proximity to heating equipment.
• Do not use damaged equipment or cables when connecting the unit to power mains.
• Do not operate the unit outside the temperature range stated in the user’s manual. Do not operate the unit in aggressive or explosive environments.
• Do not touch the unit controls with wet hands. Do not carry out the installation and maintenance operations with wet hands.
• Do not wash the unit with water. Protect the electric parts of the unit against ingress of water.
• Do not allow children to operate the unit.
• Disconnect the unit from power mains prior to any technical maintenance.
• Do not store any explosive or highly flammable substances in close proximity to the unit.
• When the unit generates unusual sounds, odour, or emits smoke, disconnect it from power supply and contact the Seller.
• Do not open the unit during operation.
• Do not direct the air flow produced by the unit towards open flame or ignition sources.
• Do not block the air duct when the unit is switched on.
• In case of continuous operation of the unit, periodically check the security of mounting.
• Do not sit on the unit and avoid placing foreign objects on it.
• Use the unit only for its intended purpose.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED MUNICIPAL WASTE.
Page 4
www.blaubergventilatoren.de
4
The centrifugal fan in a sound insulated casing is designed for supply and exhaust ventilation of domestic, public and industrial premises with high requirements to the noise level and with limited space for mounting. The unit is rated for continuous operation. The unit is a component part and is not designed for stand-alone operation. Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).
THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED
PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE
TRAINING. THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY
QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED
ACCESS BY UNATTENDED CHILDREN.
PURPOSE
DELIVERY SET
DESIGNATION KEY
Designation example: ISORB EC 100 L W1
Centrifugal duct fan
Motor type
_ — asynchronous
ЕС — electronically commutated
Spigot connecting diameter [mm]
Motor options
max — high-powered motor
L — low-noise and low-power motor
Connection options
W — power cord with an IEC C14 connector
W1 — power cord with a plug
NAME NUMBER
Fan 1 pc. User’s manual 1 pc. Packing box 1 pc.
Page 5
www.blaubergventilatoren.de
5
Model
Overall and connecting dimensions of the fan [mm]
Weight [kg]
D H L A A1 A2 A3 B B1 d
ISO-RB EC 100 99 270 517 414 458 507 515 420 228
14
12
ISO-RB EC 125 124 270 517 414 458 507 515 420 228 12
ISO-RB EC 150 149 270 517 414 458 507 515 420 228 12
ISO-RB EC 160 159 270 517 414 458 507 515 420 228 12
ISO-RB EC 200 198 328 648 553 597 645,5 654 551 374 20
ISO-RB EC 250 248 371 762 616 660 709 717 665 487 27
ISO-RB EC 315 313 505 904 737 790 818 832 807 600
9
47
ISO-RB EC 355 354 505 904 737 790 818 832 807 600 47
ISO-RB EC 400 399 505 904 737 790 818 832 807 600 47
ISO-RB EC 450 449 580 982 805 858 886 900 885 670 60
ISO-RB EC 500 499 660 1146 998 1051 1079 1094 1049 800 86
H
ØDx2
L
Ø
dx4
B
B1
A1
A2
A3
A
ISO-RB EC 100
ISO-RB EC 125
ISO-RB EC 150
ISO-RB EC 160
ISO-RB EC 200
ISO-RB EC 250
ISO-RB EC 315
ISO-RB EC 355
ISO-RB EC 400
ISO-RB EC 450
ISO-RB EC 500
Unit voltage [V/50 (60) Hz] 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230 1~ 230
Power [W] 69 78 81 85 111 164 531 527 513 1200 752
Current [A] 0.55 0.58 0.59 0.60 0.88 1.32 2.32 2.31 2.25 1.95 3.42
Maximum air flow [m³/h] 341 444 495 454 740 1099 3053 3417 3633 5620 7145
RPM [min¹] 3270 3270 3270 3600 2400 2800 2360 2360 2360 2580 1440
Sound pressure level at 3 m distance [dBA] 37 39 40 40 42 45 47 50 51 54 56
Transported air temperature [°C] -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55 -25..+55
Ingress protection rating IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4 IPX4
SEC class ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018 ErP 2018
TECHNICAL DATA
The unit is rated as a Class I electrical appliance.
Page 6
www.blaubergventilatoren.de
6
Cover
Terminal box
Sound-insulated casing
Motor impeller
Electric lead-ins
Mounting brackets
Transported air ow direction
The fan casing is made of aluzinc. For easy installation and operation, the top cover of the fan is secured with a special lock. The casing is heat- and sound-insulated with a 50 mm layer of non-flammable mineral wool. To ensure better noise absorption, the inner surface of the insulation is made of a perforated metal sheet. The round connecting spigots are rubber sealed.
The fan is equipped with an electronically commutated motor with an external rotor and an impeller with backward curved blades. The low-noise motor with ball bearings with specially selected grease ensures maintenance-free operation of the fan.
Duct fans are intended for mounting to round air ducts. The fans are installed between the air ducts. In case the fan is mounted on flexible joints, attach the fan to a structural unit by means of supports, suspension links or brackets (purchased separately). The fan may be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing).
UNIT DESIGN AND OPERATING PRINCIPLE
INSTALLATION AND CONNECTION
WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT
MAINTENANCE AND REPAIR.
THE UNIT MUST BE MOUNTED ON A PLANE SURFACE.
MOUNTING OF THE UNIT TO AN UNEVEN SURFACE CAN LEAD TO THE UNIT CASING
DISTORTION AND OPERATION DISTURBANCE.
• Before installing the fan, make sure the casing has no visible damages and check the integrity of power supply wires. The fan casing must not contain any foreign objects which can damage the impeller blades.
• Make sure the impeller rotates freely without touching the flange and the casing.
• Mount the fan in such a way that the arrow on the fan casing matches the air flow direction in the system.
• The casing has mounting brackets to facilitate the fan installation.
• The fan may be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing).
• To attain the best performance of the fan and to minimize turbulence-induced air pressure losses while mounting, connect the straight air duct section to the fan spigots on both sides of the fan. The minimum straight air duct length is equal to 1 air duct diameter on the intake side and 3 air duct diameters on the exhaust side. No filters or any other similar devices are allowed to be installed in these sections.
Page 7
www.blaubergventilatoren.de
7
1. Mark the holes for mounting the fan. 2. Drill the holes according to the markings.
3. Fix the fan on the mounting brackets using the appropriate
fasteners.
4. Connect the air ducts (purchased separately) to the fan spigots.
5. Unscrew the terminal box cover. 6. Make the electrical connections in compliance with the wiring
diagram. Re-assemble the terminal box in the reverse order.
Page 8
www.blaubergventilatoren.de
8
Connection of the fan to power mains and to additional external control units is carried out in the control box on the fan casing. External speed control devices must provide voltage from 0 to 10 V at the motor input or PWM signal with an amplitude of 10 V. External control units are purchased separately (shown in dotted lines in the diagram).
Additional external control units can be connected to the fan for speed control. The fan speed control can be either smooth or stepped.
Wiring diagram
QF
L
N
PE
Х1
3
PE
4
2
N
5
+10 V 0-10 V
6
GND
7
1
L
+10 V 0-10 V
GND
External speed controller
of the electric motor
1~230 V
50 (60) Hz
• The unit is rated for connection to 220-240 V/50 (60) Hz power mains.
• The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
• The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown of the unit. The trip current of the automatic circuit breaker QF must exceed the maximum current consumption of the unit (refer to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of the connected unit. Automatic circuit breaker is not included in the delivery set.
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.
THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN
ON THE RATING PLATE.
CONNECTION TO POWER MAINS
CONTROL
Page 9
www.blaubergventilatoren.de
9
STORAGE AND TRANSPORTATION REGULATIONS
• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range up +5 ˚С to +40 ˚С and relative humidity up to 70 %.
• Storage environment must not contain aggressive vapours and chemical mixtures provoking corrosion, insulation, and sealing deformation.
• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
• Avoid sharp blows, scratches, or rough handling during loading and unloading.
• Prior to the initial power-up after transportation at low temperatures allow the unit to warm up at room temperature for at least 3-4 hours.
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE
ANY MAINTENANCE OPERATIONS!
TECHNICAL MAINTENANCE
TROUBLESHOOTING
The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt. The impeller blades require thorough cleaning once in 6 months. Clean the blades with a soft brush or a vacuum cleaner. While cleaning the fan be careful not to displace the impeller counter weights. Protect the electric motor against ingress of liquid.
PROBLEM POSSIBLE REASONS TROUBLESHOOTING
The fan does not start. No power supply.
Make sure that the unit is properly connected to the power mains and make any corrections, if necessary.
Low air flow.
The ventilation system is soiled or damaged.
Make sure the air ducts are clean and intact. Clean them if necessary.
Noise, vibration.
The fan impeller is soiled. Clean the impellers. The screw connection is loose. Tighten the fastening screws.
Page 10
www.blaubergventilatoren.de
10
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Council Directive 2014/30/EU, Low Voltage Directive 2014/35/ EU and CE-marking Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
• User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
• Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual.
• User’s failure to ensure timely technical maintenance of the unit.
• External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
• Redesign or engineering changes to the unit.
• Replacement and use of any assemblies, parts and components not approved by the manufacturer.
• Unit misuse.
• Violation of the unit installation regulations by the user.
• Violation of the unit control regulations by the user.
• Unit connection to power mains with a voltage different from the one stated in the user's manual.
• Unit breakdown due to voltage surges in power mains.
• Discretionary repair of the unit by the user.
• Unit repair by any persons without the manufacturer’s authorization.
• Expiration of the unit warranty period.
• Violation of the unit transportation regulations by the user.
• Violation of the unit storage regulations by the user.
• Wrongful actions against the unit committed by third parties.
• Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
• Missing seals if provided by the user’s manual.
• Failure to submit the user’s manual with the unit purchase date stamp.
• Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLEFREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON
PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL
WITH THE PURCHASE DATE STAMP.
Page 11
www.blaubergventilatoren.de
11
Unit Type Centrifugal duct fan
Seller’s Stamp
Model ISO-RB EC _______________________________
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller
Unit Type Centrifugal duct fan
Model ISO-RB EC _______________________________
Serial Number
Manufacture Date
Quality Inspector’s Stamp
Seller
Seller’s Stamp
Address
Phone Number
E-mail
Purchase Date
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature
The ISO-RB EC _______________________________ unit has been connected to power mains pursuant to the requirements stated in the present user’s manual.
Installation Company Stamp
Seller
Address
Phone Number
Installation Technician’s Full Name
Installation Date: Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
CERTIFICATE OF ACCEPTANCE
SELLER INFORMATION
INSTALLATION CERTIFICATE
WARRANTY CARD