Black Box SYH4K6RMT-P1, SYH6K6RMT, SYH6K6RMT-P1, SYH4K6RMT, SYH2K6RMT-P1 Specifications

Page 1
1
Black Box Corporation • 1000 Park Drive • Lawrence, PA 15055-1018 • Tech Support: 724-746-5500 • www.blackbox.com e-mail: info@blackbox.com
© 2005. All rights reserved.
Black Box Corporation.
11/30/2000 #25041
The first rackmount enterprise-level power protector with redundancy!
Flexible range of capacity and runtimes.
Integrated Web/SNMP management features.
Easy-to-manage, menu­based diagnostics.
Occupies 8 or 10U of rack space.
Built-in automatic and manual bypass feature.
NEMA L6-30 plug makes installation easy in 208-VAC environments.
W
ith more servers, storage
products, and other mission­critical networking equipment becoming rack-based, there’s a growing need for innovative rack­mounted power protectors. The Symmetra RM provides 2-, 4-, or 6-kVA power increments that provide N+1 redundancy in just 8 or 10U of rack space.
Like the Symmetra, the Symmetra RM lets multiple power modules share the power array’s connected load. All modules run in parallel and share the load evenly. If a module fails or is removed, there’s nothing to worry about: The Symmetra has one more module than is necessary for full-load operation. So you’re still functioning at full power.
This load-sharing is what’s known as N+1 redundancy. It ensures maximum uptime and continuous availability. The
Bringing all the time-tested advantages
of Symmetra to your rack.
Key Features
SYMMETRA RM
Symmetra RM is the first rackmount enterprise-level power protector to offer redundancy.
And you won’t experience any downtime when you upgrade your Symmetra RM: hot-swappable components keep your network up and running.
To set up your Symmetra system, choose the Symmetra model that you need based on your current VA load and future expansion needs. All Symmetra RM units are available with 208­VAC output. Three units also feature a stepdown transformer that converts 208-VAC output into 120-VAC output. This conversion enables you to power the data center or rack enclosure from a single high-powered circuit while providing UPS-protected 120 VAC to each piece of equipment. Add an additional power module for N+1 redundancy. Choose
additional battery modules for longer run times if needed; these hot-swappable modules fit into any vacant slot in the Symmetra RM.
To expand your power capacity, add more power modules in increments of 2 kVA, up to a maximum of 6 kVA per Symmetra RM unit.
If there’s an extended power outage, included PowerChute Network Shutdown software helps you save data and shut down multiple servers over the network. In addition, units with up to 6 kVA are optimized for eight minutes, allowing you to perform orderly shutdowns.
And with Symmetra’s menu­based remote display, power and UPS information is always available at the touch of a button. You can monitor parameters such
(continued on page 2)
Page 2
2
as input voltage, temperature, level of redundancy, and humidity.
The power-factor correction feature also eliminates power-line harmonics and neutral overloads that can cause building wiring to overheat. Symmetra RM also
Output
Capacity:
SYH2K6RMT: 2 kVA/1.4 kW; SYH4K6RMT: 4 kVA/2.8 kW; SYH6K6RMT: 6 kVA/4.2 kW; SYH2K6RMT-P1: 2 kVA/1.4 kW; SYH4K6RMT-P1: 4 kVA/2.8 kW; SYH6K6RMT-P1: 6 kVA/4.2 kW
Voltage: SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 208 VAC (240-VAC configurable); SYH2K6RMT-P1, SYH4K6RMT-P1, SYH6K6RMT­P1: 208 VAC120 VAC (240-VAC configurable)
Max. Configurable Power with
Additional Power Modules:
SYH2K6RMT, SYH4K6RMT, SYH6K6RMT: 6 kVA/4.2 kW; SYH2K6RMT-P1, SYH4K6RMT­P1, SYH6K6RMT-P1: 6 kVA/
4.2 kW (max. 5 kVA of 120 VAC)
Connections (Always check with
local electrical requirement and regulations): SYH2K6RMT, SYH4K6RMT, SYH6K6RMT: (2) NEMA L6-20R, (1) NEMA L6­30R; SYH2K6RMT-P1, SYH4K6RMT-P1, SYH6K6RMT­P1: (2) NEMA L6-20R, (12) NEMA 5-15R
Efficiency at Full Load:
SYH2K6RMT, SYH4K6RMT, SYH6K6RMT: 91%; SYH2K6RMT­P1, SYH4K6RMT-P1, SYH6K6RMT-P1: 86%
Bypass: Internal bypass (automatic
and manual)
Voltage Distortion: <5% at full load
Frequency (Sync): 57–63 Hz
Frequency (Not Sync): 60 Hz
Crest Factor: Up to 5:1
Input
Nominal Voltage: 208 or 240 VAC
Frequency: 50/60 Hz ±5 Hz
(autosensing); SYH2K6RMT-P1: 60 Hz ±3 Hz
Connection (Always check with
local electrical requirements and regulations): (1) NEMA L6-30P
Voltage Range: 155–276 V
Power Factor: 0.98
Cord Length: 6 feet (1.8 m)
Batteries
Battery Type: Maintenance-free,
sealed lead-acid battery with suspended electrolyte; leakproof
Typical Recharge Time (Recharge
time to 90 after full discharge): 4 hours
Replacement Battery Module:
SYH2K6RMT, SYH2K6RMT-P1: (1) SYBT2; SYH4K6RMT, SYH4K6RMT-P1: (2) SYBT2; SYH6K6RMT, SYH6K6RMT-P1: (3) SYBT2
Communications/ Management
Interface Port: (1) DB9 RS-232,
(1) RJ-45 10BASE-T Ethernet for Web, (2) SmartSlot™
Control Panel: Multi-function LCD
status and control console
Management Software:
PowerChute
®
Network Shutdown, Web/SNMP Management Card included with each unit
Audible Alarm: Distinctive low-
battery alarm
Emergency Power Off (EPO): Yes
Conformance
Approvals: FCC, CSA, UL®1778
Environmental
Operating Temperature: 32 to 104°F
(0 to 40°C)
Operating Relative Humidity: Up to
95%
Operating Elevation: Up to
10,000 feet (3048 m)
Storage Temperature: 5 to 113°F
(-15 to +45°C)
Storage Relative Humidity: Up to
95%
Storage Elevation: Up to 50,000 feet
(15,240 m)
Audible Noise at 3 ft. (0.9 m):
60 dBA
On-Line Thermal Dissipation:
SYH2K6RMT: 430 BTU/hr.; SYH4K6RMT: 860 BTU/hr.; SYH6K6RMT: 1290 BTU/hr.; SYH2K6RMT-P1: 590 BTU/hr.; SYH4K6RMT-P1: 1542 BTU/hr.; SYH6K6RMT-P1: 2143 BTU/hr.
Physical
Size: SYH2K6RMT, SYH4K6RMT,
SYH6K6RMT: 14"H (8U) x 19"W x
28.75"D (35.6 x 48.3 x 73 cm); SYH2K6RMT-P1, SYH4K6RMT­P1, SYH6K6RMT-P1: 17.5"H (10U) x 19"W x 28.75"D (44.5 x
48.3 x 73 cm)
Weight: SYH2K6RMT: 164 lb.
(74.4 kg); SYH4K6RMT: 229 lb. (103.9 kg); SYH6K6RMT: 294 lb. (133.4 kg); SYH2K6RMT-P1: 259 (117.5 kg); SYH4K6RMT-P1: 324 lb. (147 kg); SYH6K6RMT-P1: 389 (176.5 kg)
Shipping Weight: SYH2K6RMT:
185 lb. (83.9 kg); SYH4K6RMT: 256 lb. (116.1 kg); SYH6K6RMT: 327 lb. (148.3 kg); SYH2K6RMT­P1: 295 lb. (133.8 kg); SYH4K6RMT-P1: 366 lb. (166 kg); SYH6K6RMT-P1: 437 lb. (198.2 kg)
Specifications
performs self-diagnosis. In the event of an internal failure, the unit sends you an alert via network, SNMP, or Web-based commands. Because of Symmetra RM’s redundancy, the system remains up, running, and protected during repairs.
(continued from page 1)
• (1) Symmetra RM
• Rackmounting brackets
• Rackmounting support rails
• CD with software
• Users’ manual
What the package includes
Page 3
3
Runtime by Load for Symmetra RM
VA 50 100 200 300 400 500 600 700 800
Watts 33 65 130 195 260 325 390 455 520
SYH2K6RMT-P1 3 hr., 49 min. 3 hr., 3 min. 2 hr., 7 min. 1 hr., 35 min. 1 hr., 13 min. 59 min. 48 min. 40 min. 34 min.
SYH4K6RMT-P1 5 hr., 18 min 4 hr., 34 min. 3 hr., 31 min. 2 hr., 50 min. 2 hr., 21 min. 2 hr. 1 hr., 43 min. 1 hr., 29 min. 1 hr., 19 min.
SYH6K6RMT-P1 6 hr., 5 min. 5 hr., 25 min. 4 hr., 26 min. 3 hr., 43 min. 3 hr., 11 min. 2 hr., 46 min. 2 hr., 27 min. 2 hr., 11 min. 1 hr., 57 min.
SYH2K6RMT 4 hr., 45 min. 3 hr., 38 min. 2 hr., 24 min. 1 hr., 45 min. 1 hr., 20 min. 1 hr., 3 min. 51 min. 42 min. 35 min.
SYH4K6RMT 6 hr., 8 min. 5 hr., 10 min. 3 hr., 53 min. 3 hr., 5 min. 2 hr., 31 min. 2 hr., 7 min. 1 hr., 48 min. 1 hr., 34 min. 1 hr., 22 min.
SYH6K6RMT 6 hr., 47 min. 5 hr., 58 min. 4 hr., 48 min. 3 hr., 59 min. 3 hr., 23 min. 2 hr., 55 min. 2 hr., 34 min. 2 hr., 16 min. 2 hr., 2 min.
VA 900 1000 1200 1400 1600 2000 2200 2500 3000
Watts 585 650 780 910 1040 1300 1430 1625 1950
SYH2K6RMT-P1 29 min. 24 min. 18 min. 14 min. 11 min. 7 min.
SYH4K6RMT-P1 1 hr., 10 min. 1 hr., 2 min. 51 min. 42 min. 35 min. 25 min. 22 min. 17 min. 12 min.
SYH6K6RMT-P1 1 hr., 46 min. 1 hr., 36 min. 1 hr., 21 min. 1 hr., 9 min. 59 min. 45 min. 40 min. 34 min. 25 min.
SYH2K6RMT 30 min. 25 min. 19 min. 14 min. 11 min. 7 min.
SYH4K6RMT 1 hr., 13 min. 1 hr., 5 min. 52 min. 43 min. 36 min. 26 min. 22 min. 18 min. 13 min.
SYH6K6RMT 1 hr., 50 min. 1 hr., 39 min. 1 hr., 23 min. 1 hr., 10 min. 1 hr. 46 min. 41 min. 34 min. 26 min.
Recognize any of these situations?
• You wait more than 30 minutes to get through to a vendor’s tech support.
• The so-called “tech” can’t help you or gives you the wrong answer.
• You don’t have a purchase order number and the tech refuses to help you.
• It’s 9 p. m. and you need help, but your vendor’s tech support line is closed.
According to a survey by Data Communications magazine, 90% of network managers surveyed say that getting the technical support they need is extremely important when choosing a
vendor. But even though network managers pay anywhere from 10 to 20% of their overall purchase price for a basic service and support contract, the technical support and service they receive falls far short of their expectations—and certainly isn’t worth what they paid.
At Black Box, we guarantee the best value and the best support. You can even consult our Technical Support Experts before you buy if you need help selecting just the right component for your application.
Don’t waste time and money—call Black Box today.
Why Buy From Black Box? Exceptional Value. Exceptional Tech Support. Period.
Ordering Information
ITEM CODE
Symmetra RM
208-VAC Output
2 kVA (Expandable to 6 kVA) ...................SYH2K6RMT
4 kVA (Expandable to 6 kVA) ...................SYH4K6RMT
6 kVA .............................................................SYH6K6RMT
208-VAC Output with 120-Volt Transformer
2 kVA (Expandable to 6 kVA) .............SYH2K6RMT-P1
4 kVA (Expandable to 6 kVA) .............SYH4K6RMT-P1
6 kVA .......................................................SYH6K6RMT-P1
Add optional Power Modules for N+1 redundancy…
2-kVA Power Module ........................................SYPM2KU
Choose single Battery Modules for longer run times (if needed)…
Battery Module..........................................................SYBT2