Black Box MX515A, MX515AE User Manual

Page 1
CUSTOMER
SUPPORT
INFORMATION
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) FREE technical support 24 hours a day, 7 days a week: Call 724-746-5500 or fax 724-746-0746 Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018 Web site: www.blackbox.com • E-mail: info@blackbox.com
MX515A
MX515AE
Local Mux-6
Local Mux-6
POWER
RLB
LLB
TEST
LOCAL
REMOTE
SYNC
LOSS
Page 2
3
LOCAL MUX-6
FEDERAL COMMUNICATIONS COMMISSION
AND
CANADIAN DEPARTMENT OF COMMUNICATIONS
RADIO FREQUENCY INTERFERENCE STATEMENTS
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer’s instructions, may cause interference to radio communication. It has been tested and found to comply with the limits for a Class A computing device in accordance with the specifications in Subpart J of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user at his own expense will be required to take whatever measures may be necessary to correct the interference.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This digital apparatus does not exceed the Class A limits for radio noise emission from digital apparatus set out in the Radio Interference Regulation of the Canadian Department of Communications.
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de classe A prescrites dans le Règlement sur le brouillage radioélectrique publié par le ministère des Communications du Canada.
Page 3
4
LOCAL MUX-6
NORMAS OFICIALES MEXICANAS (NOM)
ELECTRICAL SAFETY STATEMENT
INSTRUCCIONES DE SEGURIDAD
1. Todas las instrucciones de seguridad y operación deberán ser leídas antes de que el aparato eléctrico sea operado.
2. Las instrucciones de seguridad y operación deberán ser guardadas para referencia futura.
3. Todas las advertencias en el aparato eléctrico y en sus instrucciones de operación deben ser respetadas.
4. Todas las instrucciones de operación y uso deben ser seguidas.
5. El aparato eléctrico no deberá ser usado cerca del agua—por ejemplo, cerca de la tina de baño, lavabo, sótano mojado o cerca de una alberca, etc..
6. El aparato eléctrico debe ser usado únicamente con carritos o pedestales que sean recomendados por el fabricante.
7. El aparato eléctrico debe ser montado a la pared o al techo sólo como sea recomendado por el fabricante.
8. Servicio—El usuario no debe intentar dar servicio al equipo eléctrico más allá a lo descrito en las instrucciones de operación. Todo otro servicio deberá ser referido a personal de servicio calificado.
9. El aparato eléctrico debe ser situado de tal manera que su posición no interfiera su uso. La colocación del aparato eléctrico sobre una cama, sofá, alfombra o superficie similar puede bloquea la ventilación, no se debe colocar en libreros o gabinetes que impidan el flujo de aire por los orificios de ventilación.
10. El equipo eléctrico deber ser situado fuera del alcance de fuentes de calor como radiadores, registros de calor, estufas u otros aparatos (incluyendo amplificadores) que producen calor.
11. El aparato eléctrico deberá ser connectado a una fuente de poder sólo del tipo descrito en el instructivo de operación, o como se indique en el aparato.
Page 4
5
LOCAL MUX-6
12. Precaución debe ser tomada de tal manera que la tierra fisica y la polarización del equipo no sea eliminada.
13. Los cables de la fuente de poder deben ser guiados de tal manera que no sean pisados ni pellizcados por objetos colocados sobre o contra ellos, poniendo particular atención a los contactos y receptáculos donde salen del aparato.
14. El equipo eléctrico debe ser limpiado únicamente de acuerdo a las recomendaciones del fabricante.
15. En caso de existir, una antena externa deberá ser localizada lejos de las lineas de energia.
16. El cable de corriente deberá ser desconectado del cuando el equipo no sea usado por un largo periodo de tiempo.
17. Cuidado debe ser tomado de tal manera que objectos liquidos no sean derramados sobre la cubierta u orificios de ventilación.
18. Servicio por personal calificado deberá ser provisto cuando:
A: El cable de poder o el contacto ha sido dañado; u
B: Objectos han caído o líquido ha sido derramado dentro del
aparato; o
C: El aparato ha sido expuesto a la lluvia; o
D: El aparato parece no operar normalmente o muestra
un cambio en su desempeño; o
E: El aparato ha sido tirado o su cubierta ha sido dañada.
Page 5
6
LOCAL MUX-6
TRADEMARKS
All applied-for and registered trademarks are the property of their respective owners.
Page 6
7
LOCAL MUX-6
Contents
1. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.1 Sub-Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.2 Main Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.2 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
2.3 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.1 Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.2 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.3 Installation in 19" Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3.2 Installation of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4.1 AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4.2 Sub-Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4.3 Main Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4. Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4.2 Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4.3 Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.4 System Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.5 Fault Isolation annd Troubleshooting . . . . . . . . . . . . . . . .25
Page 7
8
LOCAL MUX-6
1. Specifications
1.1 Sub-Channels
Transmission Format—Asynchronous
Data Rate—Up to 19.2 kbps (refer to Table 2-1)
Distortion—Refer to Table 2-1
Interface—EIA RS-232-C/CCITT V.24
Connectors—(6) DB25 female
Number of Sub-channels—Up to twelve by attaching a channel doubler
to each of the connectors
Mode of Operation—Full duplex
1.2 Main Channel
Electrical Interface
Transmission Line—4-wire unconditioned telephone lines (two twisted pairs)
Operating Range—Maximum of 1.6 km (1 mile) on 22 AWG cable
Data Rate—1.2288 Mbps
Output Format—Balanced, transformer-isolated 6 Vp-p (on 100 )
Input Resistance—100
Connector—Terminal block
Page 8
9
LOCAL MUX-6
1.3 General
Diagnostics
Local digital loopback—Activated by pushbutton.
Remote digital loopback—Activated by pushbutton.
Switches/Indicators
Power Indicator (Green)—On when unit is powered.
Test Indicator (Yellow)—On when local or remote unit is performing
a loopback.
Local Sync Loss Indicator (Red)—On when synchronization is lost at local unit.
Remote Sync Loss Indicator (Red)—On when synchronization is lost at remote unit.
LLB Switch—When pressed, unit is performing local loopback.
RLB Switch—When pressed, unit is performing remote loopback.
Physical Description
Size—1.72"H (1U) x 13.3"W x 8.6"D (4.4 x 33.8 x 22 cm)
Weight—3.5 lb. (1.6 kg)
Environment
Temperature—32 to 122°F (0 to 50°C)
Humidity—Up to 90% non-condensing.
Power
Power Requirements—MX515A: 115 VAC, 60 Hz; MX515AE: 230 VAC, 50 Hz
Page 9
10
LOCAL MUX-6
2. Introduction
2.1 General
The Local Mux-6 is a full-duplex time-division asynchronous multiplexor enabling up to twelve async terminals to be multiplexed onto a single channel. The Local Mux-6 is intended for use in manufacturing facilities, building complexes, campuses, and other similar point-to-point applications.
2.2 Functional Description
The Local Mux-6 contains six sub-channels that can be expanded to twelve through connection of channel-doubler cables. The number of channels available (6/12) is set by a user-selectable strap.
When the unit is set for six channels, each channel can be used to transmit full-duplex data end to end. When the unit is set for twelve channels, each sub-channel can be used for either data or control-signal transmission, according to the specific application. For example, six channels can be used to transmit full-duplex data and six can be used to transmit control signals end to end, or else the full twelve channels can be used to transmit full duplex data end to end.
The Local Mux-6 comes with a 4-wire terminal block for transmission over two twisted pairs.
Multiplexing is implemented using an over-sampling technique. Each of the twelve channels is sampled at 78.6 kbps. Table 2-1 summarizes Local Mux-6 performance.
NOTE
Whenever possible (if the number of channels is less than or equal to 6), we recommend that you operate the Local Mux-6 in the six-channel mode, which results in less distortion.
Page 10
11
LOCAL MUX-6
Table 2-1. Performance in Various Modes of Operation.
No. of Max Electrical Distortion (%)
Sub-channels Data Rate
in use (Kbps)
6 19.2 12.5
6 38.4
12 19.2 25.0
2.3 Applications
The Local Mux-6 is used mainly for point-to-point configurations where distances of up to several kilometers are involved. A typical application is demonstrated in Figure 2-1, where a cluster of terminals is connected to a host computer through a single link. Different configurations are available using the 4-wire transmission media. The maximum data rate in a point-to­point configuration is 19.2 kbps for 12 data subchannels, 6 data subchannels, or 6 data and 6 control subchannels.
Page 11
12
LOCAL MUX-6
Figure 2-1. Typical Point-to-Point Installation.
For installations involving clusters of terminals distributed in several locations, Local Mux-6 units may be installed in a ring-type configuration (refer to Figure 2-2). At each site the unconnected channels must be bypassed by shorting Pins 2 and 3 of the relevant sub-channel connector.
Local Mux-6
Local Mux-6
Async
Computer
Page 12
13
LOCAL MUX-6
Table 2-2. Distortion.
Data Rate Distortion Number of
on Each per Node Nodes/Sites
Sub-Channel (%)
19.2 kbps 25.00 2
9.6 kbps 12.50 3
4.8 kbps 6.250 4
2.4 kbps 3.125 8
1.2 kbps 1.5625 16
Figure 2-2. Typical Ring Installation.
4
TERM
4
TERM
4
TERM
T
R
9
12
5
8
1
4
T
R
R
T
R
T
1
12
HOST
2WIRE
2WIRE
2WIRE
2WIRE
Page 13
14
LOCAL MUX-6
3. Installation
3.1 Site Preparation
The Local Mux-6 must be installed within 5 feet (1.5 m) of a grounded AC outlet.
3.2 Setup
1. Unscrew the two upper cover screws located at the back of the unit (refer to Figure 3-3).
2. Slide the rear drawer out.
3. Locate the strap marked “select 6 or 12 channels” (indicated by an arrow on the circuit board). For up to 6 channels with no control applications, place the strap between the center pin, and the one marked “6.” For any other applications, place the strap between the center pin and the one marked “12” (refer to Figure 3-1).
4. Locate the strap marked GND. According to your requirements, set the signal ground to be connected to shielding (chassis) ground or floating (NC).
5. Replace the rear drawer.
6. Fasten the two upper cover screws at the back of the unit.
Figure 3-1. Strapping Diagram.
12
6
SELECT
6 OR 12
CHANNELS
GND
NC
Page 14
15
LOCAL MUX-6
3.3 Installation in 19” Racks
3.3.1 G
ENERAL
The Local Mux-6 can be installed in a 19" rack. Its height is slightly less than 1U (1.75"), and the width is slightly less than the available mounting width.
WARNING
Disconnect the units from mains power while performing the following procedures. If you don’t, you could be shocked!
3.3.2 I
NSTALLATION OF AUNIT
The rack adapter components for single-unit installation include two short brackets. The brackets are fastened by means of screws to the side walls for the case, as shown in Figure 3-2. The brackets are attached to the two side walls of the unit.
1. To prepare the unit for rack installation, attach the two brackets to the side walls of the unit. Each bracket is fastened by means of two screws (with flatwashers), which are inserted into the two front holes on the wide wall (nuts are already in place, on the inner side of the wall).
2. After attaching the brackets, the unit is ready for installation in the 19” rack. Fasten the brackets to the side rails of the 19" rack by means of four screws—two per side.
Page 15
16
LOCAL MUX-6
Figure 3-2. Installation of a Unit in a 19" Rack.
3.4 Electrical Installation
In the following discussions, refer to Figure 3-3 (rear panel).
3.4.1 AC P
OWER
AC power is supplied to the Local Mux-6 through a 5 feet (1.5 m) cord terminated by a grounded 3-wire plug. The AC cord is fused at the rear panel AC power receptacle of the unit. A slow-blow fuse of 0.1A is required for 230V operation, and a 0.2A fuse is required for 115V operation.
3.4.2 SUB-
CHANNELS
Six D-type 25-pin female connectors on the rear panel enable connection to the unit. Detailed information about the signals present at these connectors is given in Table 3-1. For twelve-channel operation, channel doublers (CD) are required. Refer to Figure 3-4 for the pinout of the CD. For six-channel operation, with full duplex data and end-to-end control signals on each channel, refer to Figure 3-5 (DTR to DSR control signal) or to Figure 3-6 (RTS to DCD control signal).
Page 16
17
LOCAL MUX-6
3.4.3 M
AINCHANNEL
A 5-screw terminal block is located at the rear panel, marked TX-A, TX-B, CHASSIS GND, RX-A, RX-B for connecting transmit and receive wires and the cable shield (if available). TX connectors at the local unit must be connected to RX connectors at the opposite unit.
Figure 3-3. Rear Panel.
CH 1/7 CH 2/8 CH 3/9
CH 4/10 CH 5/11 CH 6/12
MAIN CHANNEL
FUSE
~115V/O.2AS.B.
RX-B TX-BRX-A TX-A
m
Page 17
18
LOCAL MUX-6
Table 3-1. Sub-Channel Connector Pin Assignment.
CCITT EIA Pin Signal Name Description V.24 RS-232C No.
101 AA 1 Protective Ground Chassis ground. May be
isolated from signal ground.
102 AB 7 Signal Ground Common signal and DC
power-supply ground.
103 BA 2 (14) Transmit Data Serial digital data from a
terminal or other source into the Local Mux-6.
104 BB 3 (16) Receive Data Serial digital data output
from the Local Mux-6.
105 CA 4 (19) Request to Send A positive level to the
Local Mux-6 when data transmission is desired.
106 CB 5 (13) Clear to Send A positive level from the
Local Mux-6 (if data transmission is possible).
107 CC 6 (21) Data Set Ready A positive DC voltage
(+8V) from the Local Mux-6 indicating the unit is powered.
109 CF 8 (12) Receive Line A positive level from the
Signal Detector Local Mux-6 except when (Carrier Detect) either a sync loss occurs
or remote loopback is performed.
—— 9 +8 volts These signals are
10 -8 volts reserved for data-set
testing and for powering miniature modems.
NOTE: Pin numbers in parentheses are for the secondary channel
available when using a channel-doubler cable.
Page 18
19
LOCAL MUX-6
Figure 3-4. Connecting Channel Doubler to Local Mux-6 Sub-Channel.
1 2 3 4 5 6 8 15 17 20 24 7
14 16 19 13 21 12 11 18 25 23
1 2 3 4 5 6 8 15 17 20 24 7
14 16 19 13 21 12 11 18 25 23
1 2 3 4 5 6 8 15 17 20 24 7
1 2 3 4 5 6 8 15 17 20 24 7
Local Mux-6
Sub-Channel
Connector
Channel Doubler
Port A
Port B
Not used
Signal Ground
Not used
Protective Ground
Transmitted Data (TD)
Received Data (RD)
Request to Send (RTS)
Clear to Send (CTS)
Data Set Ready (DSR)
Received Line Signal Detector
Secondary TD
Secondary RD Secondary RTS Secondary CTS Secondary DSR
Secondary RLSD
Page 19
20
LOCAL MUX-6
Figure 3-5. DTR to DSR End-to-End Control Signal.
Figure 3-6. RTS to DCD End-to-End Control Signal.
1 2 3 4 5 6 8 7 14 16
1 2 3 4 5 6
7
8
1 2 3 4 5 6 8 7 14 16
1 2 3 4 5 6 8 7 14 16
1 2 3 4 5 6 8 20 7
1 2 3 4 5 6 8 7 14 16
Local Mux-6
Sub-Channel
Connector
Channel Doubler
Special
Cable 1
Protective Ground
Transmitted Data (TD)
Received Data (RD)
Request to Send (RTS)
Clear to Send (CTS)
Data Set Ready (DSR)
Received Line Signal Detector
Signal Ground
Secondary TD
Secondary RD
Local Mux-6
Sub-Channel
Connector
Channel Doubler
Special Cable 2
Protective Ground
Transmitted Data (TD)
Received Data (RD)
Request to Send (RTS)
Clear to Send (CTS)
Data Set Ready (DSR)
Received Line Signal Detector
Signal Ground
Secondary TD
Secondary RD
Page 20
21
LOCAL MUX-6
4. Operating Instructions
4.1 General
This chapter covers:
• A list of controls and indicators together with their functions.
• An operating procedure covering turning on the power, operating instructions, and turning off the power.
• Information on strapping.
• A unit system test procedure for use by the operator and technician.
Installation procedures given in Chapter 3 must be completed and
checked before operating the Local Mux-6.
4.2 Controls and Indicators
Tables 4-1 and 4-2 list the function of the Local Mux-6 indicators and switches. The Local Mux-6 front panel is shown in Figure 4-1.
Figure 4-1. Local Mux-6 Front Panel.
Page 21
22
LOCAL MUX-6
Table 4-1. Local Mux-6 Indicators.
Item Indicator Function
1 Power Green LED lights when power is present.
2 Test Yellow LED lights when either local or remote
unit is performing a test.
3 Local Sync Loss Red LED lights when synchronization is lost at
the local unit.
4 Remote Sync Loss Red LED lights when synchronization is lost at
the remote unit.
Table 4-2. Local Mux-6 Switches.
Item Switch Function
5 LLB When pressed (pushed in) the unit performs
local loopback.
6 RLB When pressed (pushed in) the unit performs
remote loopback.
Page 22
23
LOCAL MUX-6
4.3 Operating Procedure
WARNING
BEFORE SWITCHING ON THIS INSTRUMENT, the protective earth terminals of this instrument must be connected to the protective conductor of the (mains) power cord. The mains plug shall only be inserted in a socket outlet provided with a protective earth contact. Do NOT use an extension cord (power cable) without a protective conductor (grounding).
Make sure that only fuses with the required rated current are used for replacement. The use of repaired fuses and the short-circuiting of fuse holders must be avoided.
Whenever it is likely that the protection offered by fuses has been impaired, the instrument must be made inoperative and secured against any unintended operation.
Turning On the Power
Apply AC power by connecting the AC power cord to an acceptable AC source. If the power indicator lights, then the Local Mux-6 is powered. If the local and remote Local Mux-6 units are in operation and properly connected via the main channel, no other indicator should be ON. If any other indicators light, refer to Section 4.5 for troubleshooting information.
Operation
The Local Mux-6 operates entirely unattended except when performing system tests.
Turning Off the Power
To turn off Local Mux-6, simply remove the AC power cord from the AC source.
Operational Field Strapping Changes
If you need to reconfigure the Local Mux-6 for twelve-channel mode or six-channel mode, follow the appropriate set-up procedure described in Section 3-2.
Page 23
24
LOCAL MUX-6
4.4 System Tests
Two system tests are available in the Local Mux-6: local loopback and remote loopback.
Local Loopback
When performing local loopback, the data from the local transmitter is looped back to the local receiver at the digital level, thus checking all local digital circuitry for proper operation. This test is activated by pressing the LLB push-button on the front panel. If the local unit is operating properly, the yellow TEST indicator should light, and all other indicators should be OFF.
If the local and remote units are properly connected via the main channel, the local transmitter analog interface and both the remote analog and digital receiver sections are checked. The yellow TEST indicator on the remote unit should also be lit if the units are properly connected.
Remote Loopback
Remote loopback loops back data from the remote receiver to the remote transmitter, thus checking:
• All local digital circuitry
• Both local and remote analog interfaces
• Main channel link
• Remote digital receiver section.
This test is performed by pressing the RLB push-button on the front panel. If both local and remote units operate properly, the yellow TEST indicators should be lit at both units and all other indicators should be OFF.
NOTE
When either the local or the remote loopback test is performed, the following signals at the remote unit sub-channels are set to OFF (negative voltage) condition: Received Data (Circuit 104), Clear to Send (Circuit 106), Receive Line Signal Detector (Circuit 109)
Page 24
25
LOCAL MUX-6
4.5 Fault Isolation and Troubleshooting
The symptoms and corresponding procedures listed in Table 4-3 enable the user to identify, isolate, and correct faults in accordance with the knowledgeable tools and replacement parts available.
WARNING
These service instructions are for use by qualified personnel only. To avoid electric shock, do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so.
Table 4-3. Fault Isolation and Troubleshooting.
Symptom Action
All front-panel indicators are OFF. (a) Check that power is supplied to the unit.
(b) Check the fuse inside the AC receptacle on the rear panel and replace it with a new one. (c) Replace unit. The fault is probably in the units power-supply circuits.
Red LOCAL SYNC LOSS is ON (a) Perform LLB. Yellow TEST indicator
should light and LOCAL SYNC LOSS should go OFF. If not, replace the local unit. Otherwise, proceed to step (b). (b) Perform local RLB. Yellow TEST indicator should light and LOCAL SYNC LOSS should go OFF. In that case, replace the remote unit. Otherwise, proceed to step (c). (c) Perform steps (a) and (b) at the remote site. If the fault is still not located, replace both units one at a time. If the problem remains, the main-channel link between the units is probably defective and should be checked.
Red REMOTE SYNC LOSS is ON Perform all the tests as in the case of
LOCAL SYNC LOSS, starting at the remote site.
Page 25
1000 Park Drive • Lawrence, PA 15055-1018 • 724-746-5500 • Fax 724-746-0746
© Copyright 1997. Black Box Corporation. All rights reserved.
Loading...