Black Box 32144 User Manual

Page 1
1000 Park Drive • Lawrence, PA 15055-1018 • 724-746-5500 • Fax 724-746-0746
© Copyright 1999. Black Box Corporation. All rights reserved.
Page 2
1
FCC STATEMENT
FEDERAL COMMUNICATIONS COMMISSION
AND
INDUSTRY CANADA
RADIO FREQUENCY INTERFERENCE STATEMENTS
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This digital apparatus does not exceed the Class A limits for radio noise emission from digital apparatus set out in the Radio Interference Regulation of Indusrty Canada.
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de classe A prescrites dans le Règlement sur le brouillage radioélectrique publié par Industrie Canada.
Page 3
10
MODEM 32144
1. Specifications
Ringer Equivalence — 0.8 B
Environment — Ambient temperature:
32 to 122° F (0 to 50° C); Storage temperature: -4 to 158° F (-20 to 70° C); Relative humidity: 10 to 95%
Power — 90-132 VAC, 60 Hz
Size — 2.5"H x 10.1"W x 9.7"D (6.4 x 25.7 x
24.6 cm)
Weight — 4 lb. (1.8 kg)
Standards — Bell 103, 212, 208, CCITT
V.13, V.17, V.22, V.32, V.22 bis, V.25, V.32 bis, V.33, V.29, V.32terbo
Protocol — Sync and async
Data Rate — Up to 16.8 and 19.2 Kbps
Operation — Full duplex over 2- or 4-wire
leased lines or dialup lines
Connectors — (1) DB25 female, (5) RJ-45 female, (1) 5-pin DIN
Configuration — AT Command set or front-panel
Error Correction/Data Compression —
MNP 1-5, V.42, V.42 bis
Page 4
13
CHAPTER 2: Quick Start
2. Quick Start
Note that if you ordered the Modem 32144 Card, all you will receive is the Card itself. It does not come with the power transformer or cables listed below.
If you ordered the Modem 32144, in addition to the modem, the shipping carton should contain—
• A power transformer (with cable attached)
• A two-conductor crossover cable with an eight-pin modular connector on one end and a six-pin modular connector on the other end
• A four-conductor cable with two six-pin modular connectors on each end and spade lugs on the other end
Two cables are supplied with the modem, but both cables aren’t always needed, depending on the application. You will need an EIA RS-232 interface cable (not supplied) to connect the modem to the DTE (data terminal equipment, usually a computer). If the modem will be operated in a manual dial mode, you will also need a standard telephone set.
This instruction manual applies to the Modem 32144.
All information applies to both the stand-alone and full-size rack­mount versions of the modem. Specialized low-profile rack-mount versions, designed for use in high­density rack enclosures, are described in Appendix A.
QUICK SETUPS FOR A QUICK
START
The simplest and fastest way to set up the modem for immediate use is to select one of the factory-preset Quick Setup configurations. For most applications, once you have selected the proper Quick Setup, the modem will be ready for operation. You will not need to make further adjustments.Quick Setups are explained fully beginning in Section 2.3, following installation instructions and a brief introduction to the front panel display and controls.
2.1 Installation
2.1.1 U
NPACKING
Keep the original shipping carton in case you need to return the modem for any reason.
Page 5
38
MODEM 32144
3. Options: Customizing the Modem Setup
• Summary Setup. This is the fastest way to selectively change multiple options. All options are accessed using just a few of the LCD screens. However, because these screens show numerical codes with very little explanation, Summary Setup is recommended only for experienced users. Summary Setup is explained in Appendix B.
3.2 Front-Panel Options
This chapter describes the standard instead of selecting options from the front panel. An alternate method for selecting options from the front panel (Summary Setup) is explained in Appendix B.
3.2.1 P
USHBUTTONS AND THE
LCD
Options are selected from the front panel by pressing the front panel pushbuttons (Fig. 3-1). The possible choices for each option are shown on the liquid-crystal display (LCD).
3.1 Methods for Selecting Options
The modem allows you to easily select options in order to tailor the modem’s operation to suit a particular application. Options can be selected in any of the following ways:
• Quick Setup. This is the easiest way to set up the modem. Quick Setup (explained in Chapter 2) automatically sets all options according to a preset configuration.
• Front-panel option selection. This is the easiest and most commonly used method for selecting individual option choices. Typically you would select an overall configuration via Quick Setup and then modify it to suit your application by changing selected options from the front panel. Changes are made by accessing individual option screens on the front panel LCD and then making selections using the control pushbuttons. (An alternate way to change options from the front panel is to use the modem’s Summary Setup feature, which is described below.)
Page 6
MODEM 32144
74
4. General Operation and Special Features
4.1 Quick Reset
For a reset of the modem, whereby option settings are not changed but the modem is cleared for a new start and the ROM memory chip is checked, select RESET from MAIN MENU screen 3. The modem will display the power-on screen for a few seconds and then the EIA status screen. This feature enables you to reset the modem without powering down the unit.
4.2 Storing Phone Numbers
4.2.1 U
SES
The front panel PHONE screen allows you to store a single phone number to be used later for—
• Autodialing from the front panel or using the Hayes or V.25 bis mode autodialer
• DTR dialing
• Leased-line or dial-line auto­recovery.
This chapter describes the following features and operational modes (listed here in the order in which they are presented):
• Quick reset
• Phone number storage
• Automatic fallback
• Dumb mode and Bell 208 operation
• V.13 operation
• DTR dialing
• Dial Line Auto-Recovery
• Leased Line Auto-Recovery
• Security operation
• Modem-controlled remote control
• Diagnostic interface control
The status screens, which display data concerning the operational status of the modem, are discussed in Section 7.6 . Instructions for using the pushbutton controls and LCD are included in Section 3.2.
Page 7
97
CHAPTER 5: Hayes Emulation Mode
5. Hayes Emulation Mode
to a preset configuration suitable for typical Hayes mode applications. To select the 2-wire dial Hayes Quick Setup, access QUICK SETUP screen 1 on the LCD and press pushbutton 2.
• DIALER MODE. If you enabled the Hayes mode autodialer using the Dialer Mode option, no other options will be changed. To enable the autodialer this way, select DIALER from SETUP screen 2. Then select HAYES from the DIALER screen.
5.1.2 C
OMMANDGUIDELINES
The following guidelines for using Hayes-compatible AT commands also provide a summary of the fundamentals of Hayes mode autodialer operation.
NOTE
Although carriage returns are not shown in the examples in this chapter, a carriage return is required at the end of each command line.
For easy reference, the following tables appear consecutively at the end of this chapter:
• Hayes-Compatible Commands (Table 5-1)
• Hayes Mode Result Codes (Table 5-2)
• S Register Functions (Table 5-3)
5.1 Hayes Mode Autodialer
When the Hayes emulation mode is enabled, the modem emulates a Hayes autodialer and functions much like a Hayes modem. Commands are issued from the computer keyboard (or other DTE), and the modem is compatible with software written to drive a Hayes-style “AT” command set.
5.1.1 E
NABLING THEHAYESMODE
A
UTODIALER
The Hayes mode autodialer can be enabled in either of two ways—by using the Quick Setup feature or by selecting HAYES from the DIALER screen:
• QUICK SETUP. If you select 2­Wire Dial (Hayes) by using the Quick Setup feature, the Hayes mode autodialer will be enabled, and all modem options will be automatically set
Page 8
127
CHAPTER 6: V.25 bis Autodialer
6. V.25 bis Autodialer
6.1.1 Q
UICKSETUP
Three Quick Setup configurations are available for 2-wire dial V.25 bis operation. Selecting any of the three V.25 bis Quick Setups (via QUICK on SETUP screen 1) enables the V.25 bis autodialer and causes all modem options to be automatically set to a preset configuration. Each V.25 bis Quick Setup is suitable for a typical V.25 bis application, depending on the DTE to be used.
To select a 2-wire dial V.25 bis Quick Setup, access QUICK SETUP screen 2, 3, or 4 (for asynchronous; synchronous, character-oriented; or synchronous, bit-oriented operation, respectively) on the LCD, and then press pushbutton 2. After selecting the desired V.25 bis Quick Setup configuration, you can reset individual options to suit your application, if desired, as explained in Chapter 3.
In accordance with the CCITT V.25 bis Recommendation, the modem V.25 bis asynchronous Quick Setup sets the character length to 10 bits, including 1 even parity bit. Both V.25 bis synchronous Quick Setups set the modem for odd parity. (For synchronous operation, the character-length option setting has no effect.)
For international compatibility, the modem can be configured to function as a V.25 bis autodialer. In V.25 bis mode, the modem is compliant with CCITT Recommendation V.25 bis, an internationally recognized standard for serial automatic call origination and answering.
The V.25 bis autodialer uses the dialing command set defined by the V.25 bis Recommendation. It allows you to store and dial phone numbers from the DTE in both synchronous and asynchronous applications. You can dial numbers directly or you can instruct the modem to automatically dial a previously stored number.
6.1 Enabling the V.25 bis Autodialer
The V.25bis autodialer can be enabled in either of two ways—by using the Quick Setup feature or by selecting one of the Dialer Mode options.
Page 9
138
MODEM 32144
7. Diagnostics
7.2 Symptoms and Scope of the Problem
As a first step toward isolating the problem, carefully consider each of the following questions:
• When did the problem begin?
• What is malfunctioning? Try to isolate the component or components of your system that are malfunctioning.
• Has there been a recent change in the system?
• Has the modem been reconfigured?
You can quickly find out if the modem has been reconfigured by checking the checksum shown in the SUMMARY screen (accessed via SETUP screen 6) and comparing it with the checksum displayed when the modem was operating properly—if you made a note of the previous checksum. If the checksum is different from the original checksum, one or more option settings have been changed. If you previously recorded the number strings (i.e., option parameters) displayed in the setup screens accessed via the SUMMARY screen, you should be able to determine which option settings have been changed (by comparing the previous and current option parameters).
The troubleshooting information in this chapter applies to all modem applications (all dialup and leased-line modes), unless specifically stated otherwise.
For specific test procedures, turn to one of the following sections in this chapter:
Section 7.8, Local Modem
Diagnostics
Section 7.9, Remote Diagnostics
7.1 When and Why to Test
If you are experiencing communications difficulties, the overall objective in correcting the problem should be to specifically isolate the defective component in your communications system. This typically involves three steps: Identifying the symptoms and scope of the problem, performing a physical inspection of all units and connections in the system and, finally, conducting diagnostic tests. Very often the diagnostic testing capabilities of the modem can help identify the specific faulty component, whether it is the modem, the DTE or telephone line.
Page 10
5
MODEM 32144
Contents
1. Specifications.............................................................................................10
2. Quick Start.................................................................................................13
2.1 Installation ........................................................................................13
2.1.1 Unpacking...............................................................................13
2.1.2 Connections ............................................................................14
2.1.3 Jumpers ...................................................................................15
2.2 Front-Panel LCD and Controls .......................................................16
2.2.1 Power-On Screen ....................................................................17
2.2.2 EIA Status Screen....................................................................17
2.3 Quick Setup ......................................................................................18
2.3.1 How to Select a Quick Setup .................................................18
2.4 Basic Operation................................................................................25
2.4.1 2-Wire Dial Hayes Mode (Quick Setup 1) ............................25
2.4.2 2-Wire Dial V.25 bis Mode (Quick Setup 2-4).......................26
2.4.3 2-Wire Dial Dumb Mode (Quick Setup 5)............................27
2.5 Leased Line (2- or 4-Wire) Mode (Quick Setup 6-9) ....................29
2.6 V.33 Leased Line Operation (Quick Setup 10) .............................29
2.7 2-Wire Dial Bell 208 Operation (Quick Setup 11-12)....................30
2.8 Two Types of Bell 208 Operation....................................................31
2.8.1 Bell 208 Operation (Exclusive) .............................................31
2.8.2 V.32/208 Auto-Select Mode ...................................................32
2.9 4-Wire Leased Line V.29 Mode (Quick Setup 13) .........................32
2.9.1 V.32 Dial Backup.....................................................................33
2.10 V.29 Fast Master and Slave Modes (Quick Setup 14-15) ..............33
2.11 If You Have Problems.....................................................................35
2.11.1 All Modes...............................................................................35
2.11.2 All Dial Modes (Hayes, V.25 bis, Dumb, Bell 208,
and V.32/208).......................................................................35
2.11.3 All Asynchronous Modes......................................................37
2.11.4 Hayes Mode...........................................................................37
2.11.5 All Leased-Line Modes (2-Wire, 4-Wire, V.33,
and V.29) ...............................................................................37
2.11.6 Leased Line (Excluding V.33 and V.29 Operation)...........37
3. Options: Customizing the Modem Setup...............................................38
3.1 Methods for Selecting Options .......................................................38
3.2 Front-Panel Options.........................................................................38
3.2.1 Pushbuttons and the LCD .....................................................38
Page 11
156
MODEM 32144
Appendix A: Quick Setup
Configurations
Some options can be selected via Summary Setup only. These options are not listed in Table A-1. The factory-default settings for these options are shown in
Appendix B.
Table A-1 shows the modem
configuration—i.e., the default setting for each option—for each of the Quick Setup modes. When you select a Quick Setup, the modem automatically sets all options as indicated in the table. The options are listed in the same order in which they appear on the LCD flow chart.
Instructions for selecting Quick
Setups are included in Chapter 2.
Page 12
166
MODEM 32144
Appendix B: Summary Setup
If you select AT, the AT PROFILES screen will be displayed. When you select a Hayes mode configuration profile (user profile) from the AT PROFILES screen, the MODEM displays a setup screen for the selected profile. The selected profile is used as the active configuration and is also designated as the default user profile. Select 0 (pushbutton 1) to select profile 0; select 1 (pushbutton 2) to select profile 1. Pushbutton 3, with the AT PROFILES screen displayed, enables you to select the default configuration profile: By pressing pushbutton 3, you can toggle (switch) between profile 0 or profile 1 as the default—the effect is the same as issuing the &Y command (&Y0 or &Y1).
The SUMMARY screen includes a four-digit checksum value to the right of the word “SUMMARY.” This number will change if any of the option settings are changed, so it allows you to determine if any of the modem’s option settings have been changed, although you cannot determine from this number which options have been changed. After setting up the MODEM, record this number for possible later reference.
Summary Setup is an advanced feature designed to allow exper­ienced users to quickly change option settings for any mode. Most options can be viewed from and changed using a single LCD screen. Summary Setup is the fastest way to selectively change multiple options; however, because the Summary Setup screens show numerical codes with very little explanation, this method of options selection is recommended only for experienced users.
Even though Summary Setup offers these advantages, it is recom­mended only for experienced users because there is very little guidance on the LCD screen to indicate which option is being changed.
Changes made through Summary Setup modify the active modem configuration and are saved to memory when you exit Summary Setup.
B.1 Summary Setup LCD Screens
Summary Setup (SUMMARY) is accessed from screen 6 of the SETUP menu. From the SUMMARY screen, choose SETUPS to change options—but for Hayes mode operation (only), choose AT to change options for which there are associated AT commands (Table B-1).
Page 13
176
MODEM 32144
Appendix C: Connectors, Adapters,
and Jumpers
• LEASED LINE—RJ-11 modular jack, for (6-pin) leased line connection
• PHONE—RJ-11 modular jack, for connection to a telephone handset (optional)
These connectors are illustrated in Chapter 2, which explains how to install the modem and how to make the connections referred to above.
The modem includes an edge connector for optional rack mounting. When the modem is rack mounted, the edge connector performs the functions of all the connectors listed above (and the other connectors are not used).
C.1.1 C
ONNECTORPINASSIGNMENTS
For users who need to know connector pin assignments, this information is provided in Figure C-1 (DIAG, TX DIAL, RX DIAL, LEASED LINE, and PHONE connectors) and in Table C-1 (DTE interface connector).
This appendix provides a detailed description of al modem connectors, including pin assignments. It also includes a description of the modem jumper functions and a diagram that shows you where to find the jumpers.
C.1 Connectors and Adapters
The modem includes the following connectors (labeled on the rear panel as indicated below):
• DTE—25-pin (DB25) RS-232/D female cable connector, for connection to DTE (computer or terminal)
• DIAG—RJ-45 modular jack (diagnostic connector), for diagnostic port control (optional)
• POWER—Five-pin DIN connector for AC power
• TX DIAL—RJ-45 modular jack for connection to a dial line
• RX DIAL—(Ignore “RX DIAL” label.) RJ-45 modular jack for alternate leased line connection (when an 8-pin connector is required)
Page 14
181
APPENDIX D: DC Voltage Models
Appendix D: DC Voltage Models
D.1 Introduction
The modems with codes MD833A-D12, MD833A-D24, and MD833A-D48 are pre-configured for DC voltage operation. The MD833A-D12 is pre­configured for use with a -12 VDC power source, the MD833A-D24 is pre­configured for use with a -24 VDC power source, and the MD833A-D48 is pre-configured for use with a -48 VDC power source.
This addendum provides installation and jumper information for the DC pre-configured modems for applications where an external DC power source will be used (i.e., not DC power provided from a rack enclosure). If the modem is to be installed in a rack, refer to the instruction manuals for the modem and the rack.
CAUTION
The -48 VDC model should be used only with an external DC power source.
For modems using an external DC power source, the information in this addendum about installation and jumper settings supersedes the information in the rest of the Modem 32144 manual. However, all other information in the instruction manual is applicable.
Page 15
Power-on Screen
Appendix E: LCD Flow Chart
DCE-DTE
V.32bis/14.4M V.32 V4.51/3.25
Software revision levels (may be different than shown here.)
QUICK SETUP 2-W DIAL (HAYES)
TALK QUICK DIAL
SPEED TYPE DEC INC
* See reverse side of chart.
Continued from
SETUP TEST EIA MODEM
EIA CTS CD DSR
CTS to EIA NORM RTS TRUE
TEST OPTIONS DSR RMT
DSR during ALB ON OFF
EIA status screen: Not all abbreviations will be present at same time. (R in upper left corner indicates an incoming ring.)
D TR MR RS CS
TD LINE LEVELS. dBm
9600 TM ER CD RD
QUALITY 000 PKT: SIZE
Bar graph
<1> QUICK SETUP
<1>
****
SETUP TYPE LINE SPEED
V32
LINE TYPE 2W-D 2W-LL 4W-LL
<4>
<1>
DSR to EIA NORM TRUE XOVER
CD to EIA NORM TRUETOGGLE
REMOTE TEST ENABLE DISABLE
V25 DIAL (Async)
SETUP TEST RMT
<1>
MAX MIN
MAX RATE: DEC INC
EIA DTR ALBT RDLT
DTR from EIA NORMAL TRUE
<2> QUICK SETUP
V25 DIAL (Syn_c)
MAIN MENU
<2>MAIN MENU
RESET RATE
(Resets modem)
MIN RATE: DEC INC
19,200
<2>
RDL - DTE Ctrl'ed ENABLE DISABLE
ALB - DTE Ctrl'ed ENABLE DISABLE
TX=-09 RX=-24
<3> QUICK SETUP
V25 DIAL (Syn_b)
<3>MAIN MENU
RATE DOWN UP
0-300
V42 MODE OFF MANDAT AUTO
EIA TM
TM to EIA NORMAL TRUE
STATUS SCREENS
ECHO: msec
<4> QUICK SETUP
This screen is displayed only
if V.32bis mode is selected.
V42 MODE CLASS BREAK
MNP CLASS DEC INC
<3>
MODEM SETUPS CDLVL TXLVL
TRANSMIT LEVEL LEASED DIAL
TX LEVEL DEC INC
CARRIER DET. LEASED DIAL
CD LEVEL LEASED
-26 -33 -43
020 1.0
2-W DIAL (DUMB)
V42 CONTROL V42 SEL BUFFER
5
<1>
TX LEVEL (DL) PROG PERMIS
0 dBm
LVL
CD LEVEL DIAL
-26 -33 -43
Hz CHANNEL FREQ
OFFSET: 1.0 Hz
The Quick Setup screens are used to quickly select pre-set modem configurations for various applications.
<5> QUICK SETUP
2-W LEASED (ORG)
<1>
BUFFER SELECT ENABLE DISABLE
V42 SELECTION PROTOCOL V42bis
LAPM/MNP DEC INC
BREAK: DEC INC
MODEM SETUPS SQ COMEQ TREL
SIGNAL QUALITY 10^3 10^5
THROUGHPUT
<6> QUICK SETUP
V.42bis ENABLE DISABLE
NDT/NEXP
<2>
TRELLIS CODE ENABLE DISABLE
COMPR EQUAL DEC INC
15000 BPS
2-W LEASED (ANS)
V42 CONTROL DTE FLOW
Set
automatically
in Hayes
mode only.
DTE SPEED:
38,400
DEC INC
MODEM SETUPS TXCLK T1 RETRN
TRANSMIT CLOCK INT RX-CLK EXT
T1 timer: 0.8sec DEC INC
AUTO-RETRAIN ENABLE DISABLE
T-III
ERTX MODE
255 0233 00
QUICK SETUP MENU
<7> QUICK SETUP
4-W LEASED (ORG)
<2>
FLOW CONTROL DTE-DCE DCE-DTE
DCE-DTE NONE CTSon/off
DTE-DCE
RTS
DEC INC
<3>
RATE
V42bis 38400
<8> QUICK SETUP
4-W LEASED (ANS)
SETUP V42 ADDR DIALER
ADDRESS: DEC INC
<1>
<1> DCE-DTE
DTE-DCE DEC INC
MODEM SETUPS ANS/ORG ANSFREQ
ANSWER TONE 2225Hz 2100Hz
ANS/ORG DEFAULT ANSWER ORIGINATE
Except for the power-on screen, the data shown on these screens will change, depending on external conditions and the modem's operational status.
999,999
DC1/DC2 DC1/DC3
CTS
<4>
MODEM SETUPS FP SPK SPKVOL
FP ENABLE DISABLE
<9> QUICK SETUP
<2>
FLOW CONTROL PASSTHRU
PASSTHRU MODE ENABLE DISABLE
4-WLL V.33
DIALER DEC INC
<2>
<2>
<5>
SPEAKER VOLUME LOW MEDIUM HIGH
SPEAKER CONTROL OFF TILL-CD ON
<10> QUICK SETUP
2-W DIAL (208)
HAYESSPEED LIMIT
These screens are only displayed on models that support these
options. MODEM SETUPS screens may be numbered differently.
MODEM SETUPS
<6>
GUARD V13
V.13 DEC INC
GUARD TONE
550Hz 1800HzOFF
Use INC (increase) and DEC (decrease) to cycle through digits (0-9); use CTRL to cycle through dialing control characters(T, *, #, etc.).
<11> QUICK SETUP
2-W DIAL V32/208
AUTO-ANSWER ENABLE DISABLE
MODEM SETUPS PSWD
OFF
TRAINING LENGTH LONG SHORT TER
PASSWORD CHANGE CLEAR
CONFIRM
DEC SKIP INC
<12> QUICK SETUP
SETUP ANSWER DATA DISC
DATA FORMAT SYNC ASYNC
MODEM SETUPS
<7>
CARR CTS RTS-CTS
TRAIN
CARRIER SWITCH CONSTANT
CTS RTS ON
CTS DELAY: 0 ms DEC INC
4-WLL V.29
DATA FORMAT TYPE LENGTH PAR
CHAR LENGTH 91110
PHONE CELL: DEC PROG INC
<13> QUICK SETUP
V.29 FAST MASTER
<3>
DISCONNECT RX TX
RX SPACE DISC'T ENABLE DISABLE
PARITY: DEC INC
SETUP PHONE AUTO LCDI
<8>
AUTO-RECOVERY SELECT RETN TEST
NO AUTO-RECOVERY DEC INC
301-555-1234 DEC CTRL INC
<14> QUICK SETUP
Continued below
<1>
TX SPACE DISC'T ENABLE DISABLE
Set automatically in Hayes mode only.
NONE
<5>
LCD INTENSITY 5 DEC INC
TEST EVERY 20min DEC INC
RETURN: DEC INC
00
<15>
V.29 FAST SLAVE
DISCONNECT
<2>
CARR. CURR. RTS
RTS DISC'T
OFF
DEC INC
CURRENT DISC'T ENABLE DISABLE
CARRIER DISC'T ENABLE DISABLE
Hayes mode only: Use S register S10 to change these options.
<6>
314E
AT
S-REG DEC INC
ATbefImqvwxy
0102101341
AT&c
Checksum. If this number changes, at least one option has been changed.
AT&c
SETUP SUMMARY
SUMMARY SETUPS S-REG
PRI
addr
0011214E0 999 99
AT PROFILES
0 1 &Y0
OFF
ATbefImqvwxy
0102101341
These screens allow for quick option selections. (Use arrow pushbuttons to view full display.) For further explanation, see Instruction Manual, appendix C, Summary Setup.
00:01
Pushing 3 changes from &Y0 to &Y1
Page 16
Power-on Screen
Displayed on the Modem 32144.
V.32bis/14.4M V.32 V4.51/3.25
Software revision levels (may be different than shown here.)
D TR MR RS CS 9600 TM ER CD RD
TALK QUICK DIAL
MANUAL-DIAL TALK DATA
TD LINE LEVELS. dBm
QUALITY 000 PKT: SIZE
TX=-09 RX=-24
ECHO: msec
020 1.0
Hz CHANNEL FREQ
OFFSET: 1.0 Hz
THROUGHPUT
15000 BPS
Bar graph
STATUS SCREENS
<1>
AUTO-DIAL
* **
DIAL HANGUPCELL
DIAL FAILURE NO DTR
DIAL CELL: DEC DIAL INC
e00
This screen appears only in the event of a dial failure. Specific message appears on bottom line.
SETUP TEST RMT
<2>MAIN MENU
REMOT DIGIT LOOP ON OFF
255 0233 00
REMOTE CONTROL TEST
REMOTE TEST RDL RDLST
<1>
RDL SELFTEST ON OFF
ERTX MODE
V42bis 38400
Displayed only on the ALX V.32M and ALX V.32/14.4M.
RATE
REMOTE CTRL ADDR/C ADDR
Use pushbutton 2 to toggle between ADDR/C and SLOT/C.
<2>
ADDRESS : DEC INC
999,999
MAIN MENU RESET RATE
(Resets modem. LCD returns to power-on screen, then EIA status screen.)
If SLOT/C is selected from REMOTE screen 2 (above), the top line here will read SLOT NUMBER: 01.
<3>MAIN MENU
CHECKSUM MAIN PUMP
MAIN
m1_mt9bf2
V3.02.02
Data displayed here is for use by servicing personnel. Screens show software revision levels and various checksums for both the main processor and the data pump (transmitter, T, and receiver, R). It is unlikely that the numbers on your unit will match those shown here—this is normal.
19BB
Pump V2.03.1 U52 280C
(Accessed by pressing 1 from EIA status screen.)
U51 C5E8
LOCAL TEST ALB ALBST ST/E
ANALOG LOOPBACK ON OFF
ANALOG SELFTEST ON OFF
SELFTEST w/ERROR ON OFF
<1>
LOCAL TEST DLB ALBX ALXST
DIGITAL LOOPBACK ON OFF
ANALOG LOOP (EXT) ON OFF
ANALOG ST (EXT) ON OFF
Note: When a test is activated, the EIA status screen will be displayed.
<2>
Page 17
182
MODEM 32144
D.2 Installation
Use the supplied cable to attach the modem to the external DC power source, as shown in Fig. D-1.
Fig. D-1. Attaching the supplied cable to the DC power source.
Refer also to Section 2.1, Installation but ignore information
about the AC power transformer cable.
DIAG
POWER
TX
DIAL
LEASED
LINE
PHONE
Black
Red
Pos. (+) source
Neg. (-) source
Page 18
183
APPENDIX D: DC Voltage Models
D.3 Jumper Settings
The power jumpers have been pre­set at the factory for DC voltage operation as shown in Tables D-1.
Table D-1. Jumper Settings for -12/-24/-48 VDC Operation
Jumper(s) Setting
JP2 Pins 2 and 3 connected JP3, JP4 Pins 1 and 2 connected (set to same position)
For other jumper settings, refer to the rest of this manual. (But for the DC modems, ignore the information in the manuals for jumpers JP2, JP3, and JP4.)
Page 19
184
MODEM 32144
D.4 Jumper Locations
The jumper locations are shown below for your information; however, since the jumper settings are pre-configured, you should not have to change them.
Fig. D-2. Partial view of modem circuit board, showing jumper
locations.
For each jumper, pin 1 is identified by a “1” on the modem circuit board. (The JP2 pin 1 label may be difficult to read; JP2 pin 1 is the pin closest to the edge connector.)
JP6
JP1
JP4
JP3
JP5
JP2
JP8
JP7
Page 20
NOTES
Page 21
NOTES
Page 22
NOTES
Page 23
NOTES
Page 24
NOTES
Page 25
NOTES
Page 26
177
APPENDIX C: Connectors, Adapters, and Jumpers
Figure C-1. Connector Pin Assignments.
All connectors are shown as viewed from the back of the modem. Pins not included in the listings above are not used.
Dial Line Connector
Pin
Function
3
A/MI
4
1 2 3 4 5 6 7 8
RJ-45
Ring
5
Tip
6
A1/MIC
7
PC
8
PR
REAR PANEL
DTE
DB25
Diagnostic Connector
1 2 3 4 5 6 7 8
RJ-45
Phone Connector
Pin
Function
2
1 2 3 4 5 6
RJ-11
RX
TX
POWER
DIAG PHONE
DIAL
DIAL
3 4 5
LEASED
LINE
A Ring Tip A1
Leased Line
Connector
Pin
Function
2
1 2 3 4 5 6
RJ-11
RXLL
3
TXLL
4
TXLL
5
RXLL
Pin Function
1 Constellation Y Output 2 Constellation X Output 4 Ground (for transmit and
receive data and constellation)
5 Receive Data (output from
modem)
6 Transmit Data (input to modem)
DIAG port always appears to a
system as a DCE port.
Line Connector
(Ignore “RX DIAL” Label)
Pin
1 2 3 4 5 6 7 8
RJ-45
1 2 7 8
Function TXLL TXLL RXLL RXLL
Alternate Leased
Page 27
178
MODEM 32144
Table C-1. Pin Assignments—DB25 TIA/EIA Interface Connector
Pin Function Designation Source
EIA ITU-T LCD
1 Frame ground—not connected AA 101
2 Transmit (send) data (TD) BA 103 TD DTE
3 Received data (RD) BB 104 RD Modem
4 Request to send (RTS) CA 105 RS DTE
5 Clear to Send (CTS) CB 106 CS Modem
6 Data Set (modem) Ready (DSR) CC 107 MR Modem
7 Signal ground (SG) AB 102 Ground
8 Carrier detect (CD) CF 109 CD Modem
9 Testing voltage, +10V +P Modem
10 Testing voltage, -10V -P Modem
15 Transmit clock (TC) DB 114 Modem
17 Receive clock (RC) DD 115 Modem
18 Analog loopback (ALB) control
1
CN DTE 20 Data terminal ready (DTR) CD 108/2 TR DTE 21 Remote digital loopback (RDL) CN DTE
control
1
22 Ring indicator (RI) CE 125 R Modem 24 External transmit clock (XTC) DA 113 DTE 25 Test mode indicator (TM)
2
CN TM Modem
1
+ voltage activates indicated loopback test (but only if ALB-DTE Ctrl’ed or RDL-
DTE Ctrl’ed option is enabled);—voltage disables test.
2
Alternately, pin 25 may be used for analog loopback (ALB) control.
Page 28
179
APPENDIX C: Connectors, Adapters, and Jumpers
C.2 Jumpers
WARNING
Jumpers should be switched only by qualified service personnel.
For most applications, there is no need to reset the modem’s internal jumper switches. However, a jumper switch will have to be reset if you need to—
Connect frame ground to signal ground, Switch from A/A1 control to MI/MIC control, Strap the modem for use in a DC rack enclosure, or Change the function of EIA interface pin 25.
If you need to reset a jumper switch, refer to the following page to determine the jumper that should be switched, where it is located, and how it should be set. The jumpers are numbered on the circuit board; for example, JP4 is jumper 4. To access the jumpers, unscrew the four screws on the bottom of the modem and carefully lift off the cover.
WARNING
Improper setting of AC and DC power jumpers could result in serious damage to the modem.
Page 29
180
MODEM 32144
Table C-2. Jumper Switch Functions
Jumper(s) Position
1
Function
JP1 FG Frame and signal ground connected
Alternate position Not connected (no legend)
JP2, JP3 A1 A/A1 control (Set to same MI MI/MIC control position)
JP4, JP5, AC AC power JP8 Alternate position DCpower (for Telco 48 VDC battery) (Set to same position)
JP7 TM(output) Pin 25 used as test mode indicator
AL (input) Pin 25 used for analog loopback
1
As indicated by legend printed on modem circuit board.
Factory settings are shown in boldface.
Page 30
167
APPENDIX B: Summary Setup
B.2 Changing Options via Summary Setup
The appearance of the three setup screens selected via SETUPS and AT (profile 0 or 1) is essentially the same: Brief descriptive information on the top line and a long string of numbers on the bottom line. The numbers are broken down into groups, with each group representing a category of options (dial line options, EIA interface options, etc.).
Each digit position represents an option, and the number in each digit position indicates the current option setting (parameter). To change an option setting, use the front panel pushbuttons to change the parameter (number), as explained in the following section.
The diagrams on the following pages show—
• Which options are included in each option group
• Which option is indicated by each digit position within the group
• The possible parameters for each option
B.2.1 S
UMMARYSETUPPUSHBUTTON
F
UNCTIONS
The three Summary Setup screens are different from all other modem screens in that you can scroll across the string of numbers; also, the pushbutton functions are different. For the three Summary Setup screens only, the modem pushbuttons function as follows:
• Pushbutton 1 moves the cursor to the left. Pushbutton 3 moves the cursor to the right. If the cursor is at the end of the screen, the screen will scroll one character at a time.
• Pushbutton 2 increments the blinking value (i.e., the parameter, or current option setting). The value will cycle through the highest possible parameter value and then back to 0 or 1.
• The right arrow button moves the screen to the beginning of the next group of options to the right. The left arrow button moves the screen to the beginning of the next group of options to the left. Groups of options are separated by blank spaces on the LCD.
Page 31
000
MODEM 32144
NOTE
On the Summary Setup screens that show AT profiles 0 and 1, the cursor location is indicated by a solid black box when the cursor is positioned in a blank cell (one with no characters).
B.2.2 E
XPLANATION OF
S
UMMARY
S
ETUPSCREENS
Note that options are identified on the Summary Setup screens only by the relative positions of the numbers within the number string, as indicated in the following diagrams. Each digit position represents an option, and the number in each digit position indicates the current option setting (parameter).
The string of numbers in each diagram shows the factory default setting for each option (i.e., the Hayes mode default settings). Each diagram also identifies all possible settings for each option.
NOTE
Numbers that are not identified in the following diagrams represent option settings that are reserved for future use or factory use. These settings should not be changed.
168
Page 32
169
APPENDIX B: Summary Setup
Fig. B-1. Primary Options.
PRI
NOTES: Speed limit, min., and speed limit, max.: 7200 bps parameters are available only if V.32bis mode is enabled. ALX V.32 and ALX V.32M only: Available speed limit selections: Max., 0-7 and A; min., 0=6 and 9. Default max. speed limit setting: 0 (9600 bps). Speed type: Settings 0, 1 and 3 are not available on all all ALX models.
258021210
Speed type: 0=Auto (V.32/208), 1=V.33, 2=V.32/32bis, 3=Bell 208 Speed limit, min. (bps): 0=9600, 1=4800, 2=2400,3=1200
4=600, 5=0-300,6=1200/75,7=14,400, 8=12,000, 9=7200 Speed limit, max. (bps): 0=9600,1=4800,2=2400,3=12000,4=600,
5=0-300, 6=EIA-23, 7=1200/75, 8=14,400,9=12,000,A=7200 Buffer mode/speed conversion: 0=enable, 1=disable
V.42 mode : 0=off, 1=mandatory, 2=automatic Dialer mode: 0=off, 1=Hayes, 2=DTR dialing;
3=V.25bis, async; 4=V.25bis, sync, character-oriented; 5=V.25bis, sync, bit-oriented; 6=Penril mode
Character length (bits): 0=8, 1=9, 2=10, 3=11 Data format: 0=sync, 1=async Line type: 0=2--wire dial, 1=2-wire leased, 2=4-wire leased
LCD
Page 33
170
MODEM 32144
Fig. B-2. Address.
Fig. B-3. Dial Line Options.
a d d r
address
dial 0 0 0 0 0 0 1 0 2 1 0
9 9 9
Group
9 9 9
Unit
address
Pulse dialing rate (pulse per sec): 0=10, 1=20 Wait for carrier (sec): 0=30, 1=45, 2=60, 3=75 T1 timer (sec): 0=0, 1=0.3, 2=0.8, 3=1.6, 4=3. Carrier detect level, dial (dBm): 0= -51, 1= -41, 2= -34 TX level, dial: 0=programmable, 1=permissive Disconnect, RTS (sec): 0=off, 1=20, 2=40 . . .7=140 Disconnect, line current: 0=enable, 1=disable Disconnect, carrier: 0=enable, 1=disable Disconnect, TX space: 0=enable, 1=disable Disconnect, RX space: 0=enable, 1=disable Auto-answer: 0=enable, 1=disable
Page 34
171
APPENDIX B: Summary Setup
Fig. B-4. EIA Interface Options.
Fig. B-5. V.42 Error Correction Options.
eia 0 1 0 1 1 1 0 0 0
CD and DSR delay: 0=disable, 1=enable Test mode: 0=normal, 1=true Remote digital loopback test: 0=enable, 1=disable Analog loopback test: 0=enable, 1=disable CTS: 0=normal, 1=follow RTS, 2=true, 3=on Carrier detect: 0=normal, 1=true, 2=toggle DSR: 0=normal, 1=true, 2=crossover DTR: 0=normal, 1=true
V.42 <1> V.42 <1>
2 0 0 0 0 1 0 2 10 0 3 3 5 3 1 1
V.42bis: 0=enable, 1=disable V.42 protocol: 0=LAPM only, 1=MNP only, 2=LAPM/MNP
DTE pass-through flow control: 0=enable, 1=disable Flyback buffer: 0=enable, 1=disable Break handling: 0=none, 1=destr./expedited, 2=non-destr./expedited,
3=non-destr./non-expedited MNP class (limit): 1=class 1, 2=class 2, 3=class 3, 4=class 4, 5=class 5 Flow control, DCE to DTE: 0=none, 1=CTS, 2=DC1/DC2, 3=DC1/DC3 Flow control, DTE to DCE: 0=none, 1=RTS, 2=DC1/DC2, 3=DC1/DC3 Parity: 0=none, 1=odd.2=even, 3=mark, 4=space DTE speed (bps): 0=38,400, 1=19,000, 2=9600, 3=4800, 4=2400, 5=1200, 6=600, 7=300, 8=110
"V.42 <1>" and "V.42 <2>" are displayed to help indicate the relative position of individual options across the LCD.
Link flow control: 0=disable, 1-enable, 2=slaved DCE pass-through flow control: 0=disable, 1=enable Selective retransmission: 0=disable, 1=enable
Page 35
172
MODEM 32144
Fig. B-6. Leased Line Options.
L. L. 1 0 0 2 0 0 1 0
Auto-recovery test interval (min): 0=10, 2=40, 3=60 Auto-recovery return (sec): 0=off, 1=10, 2=40, 3=60, 4=120 Auto-recovery select: 0=none, 1=dial if bad 1 min ... 4=dial if bad 4 min,
5=dial if bad 30 sec 96-8 not used), 9=manual recovery Carrier detect level, leased (dBm): 0= -43, 1= -33, 2=-26 TX level, leased (dBm): 0=0, 1= -1... 9= -9, A= -10 ... F= -15 TX clocking: 0=internal, 1=received clocking, 2=external Answer/originate: 0=answer, 1=originate
Page 36
173
APPENDIX B: Summary Setup
Fig. B-7. Data Pump 1 Options.
pump 1
Fig. B-8. Data Pump 2 and 3 Options.
2 0 0 2 1 0 3 0 0 0 1
"pump1," "pump2," and "pump3" are displayed to help indicate the relative positions of individual options across the LCD. The "pump2", and "pump3" options are identified below.
Phase reversal in answer tone: 0=enable, 1=disable Auxiliary channel: 0=enable, 1=disable Speed fallback: 0=enable, 1=disable
Trellis coding: 0=enable, 1=disable Answer tone: 0=2225 Hz, 1=2100 Hz Guard tone: 0=550 Hz, 1=1800 Hz, 2=off Auto-retrain: 0=enable, 1=disable Signal quality level (error/bits): 0=1 in 10^3, 1=1 in 10^5 Compromise equalizer type: 0=I, 1=II< 2=III, 3=IV, 4=off
pump 2 0 0 0 0 0 1 1 0 0 0
8
6
5
Turnaround delay: 0=disable, 1=enable
4
Satellite delay: 0=disable, 1=enable
3
RTS-to-CTS delay (ms): 0=none, 1=15, 2=50, 3=150
2
1
CTS: 0=always ON, 1=follow RTS Carrier type: 0=switched, 1=constant
pump 3 0 0 0 0 0 1 0 0
8
V.26 scrambler: 0=disable, 1=enable
7
Anti-streaming timer: 0=disable, 1=enable
6
5
4
3
2
1
10
Forward rate renegotiation: 0=disable, 1=enable
9
Retrain threshold (error/bits): 0=10^4, 1=10^6 208 phase detection: 0=normal, 1=compensated
Rate renegotiation (RRP): 0=disable, 1=enable
V.26 dibit encoding: 0=alternative A, 1=alt. B
Echo protection tone: 0=disable, 1=short, 2=long V.27bis 2400-bps alternatives: 0=alternative i, 1=alt. ii V.3x/208 auto-detect mode: 0=disable, 1=enable V.22bis S1 duration (ms): 0=100, 1=150 Fast connect 103 mode: 0=disable, 1=enable
Page 37
174
MODEM 32144
Fig. B-9. Miscellaneous Options.
"misc1," "misc2," and "misc3" are displayed to help indicate
misc 1 1 2 3 0 0 0 0
misc 2 misc 3 0 1 0 0 0 0 0 F F F F 1 0 0 0 0 0 0 0 0
the relative positions of individual options across the LCD. The "misc2", and "misc3" options are identified below.
Op. mode fallback: 0=Bell 212A and 103, 1=V.22/V.21/V.23 Remote test: 0=enable, 1=disable DSR during ALB: 0=enable, 1=disable FP: 0=enable, 1=disable LCD intensity: 0, 1... 7 (7=greatest intensity) Speaker volume: 0=low, 1=medium, 2=high Speaker control: 0=on, 1=on till CD, 2=off
Low-profile DIAG LED: 0=Connect status, 1=DTR status CFI AB response on disconnect: 0=disable, 1=enable
Wait for MNP link request (sec): 0=3, 1=7 Leased line interrupt:0=off, 1=on Remote RTS signaling: 0=off, 1=on
Multimode handshake: 0=T1 timer, 1=V.32bis Annex A
Answer tone detection: 0=enable, 1=disable Answer tone detection: 0=enable, 1=disable
V.13 operation: 0=off, 1=TX only, 2=RX only, 3=TX and RX DTE=DCE speed: 0=disable, 1=enable Penn/V.25bis DTR dialing: 0=enable, 1=disable
Page 38
175
APPENDIX B: Summary Setup
Fig. B-10. Hayes Mode Options—For Each AT Profile.
AT commands
ATbeflmqvxy
110210141
AT & commands
AT&cdgjlpqrsx
1200000000
S registers
s00 s18 s25 s26 001 000 005
Flow control, DCE
Flow control, DTE
Load inactivity timer
AT/ commands
(most are for V.42 options)
AT/abcdfkmnpq t vx
315013032330011
Page 39
157
APPENDIX A: Quick Setup Configurations
Table A-1. Quick Setup Configurations
Page 40
158
MODEM 32144
Table A-1. Quick Setup Configurations (continued)
Page 41
159
APPENDIX A: Quick Setup Configurations
Table A-1. Quick Setup Configurations (continued)
Page 42
160
MODEM 32144
Table A-1. Quick Setup Configurations (continued)
Page 43
161
APPENDIX A: Quick Setup Configurations
Table A-2. Additional Quick Setup Configurations
Default settings listed by Quick Setup mode
Option Bell 4-wire V.29 V.29
208
1
leased fast fast V.29 master slave
Communication Standard option
STD 208 V.29 V.29 V.29
Speed Limit option, V.32, V.32M, V.32/14.4, V.32/14.4M, V.32/19.2, V.32/19.2M
MAX DCE 4800 9600 9600 9600 RATE
MIN DCE 4800 4800 4800 4800
Default settings listed by Quick Setup mode
Option Bell 208
1
4-wire V.29 fast V.29 fast leased V.29 master slave
BUFFER Disable Disable Disable Disable DTE SPEED 38.4 Kbps 38.4 Kbps 38.4 Kbps 38.4 Kbps FLOW RTS RTS RTS RTS
CONTROL DTE-DCE
FLOW CTS CTS CTS CTS CONTROL DCE-DTE
DTE Disable Disable Disable Disable PASS-THRU FLOW CTRL
Page 44
162
MODEM 32144
Table A-2 (continued). Additional Quick Setup Configurations
(Miscellaneous)
ADDRESS2999,999 999,999 999,999 999,999 DIALER OFF OFF OFF OFF
MODE AUTO Enable Enable Disable Disable
ANSWER
Data Format Options
DATA TYPE Sync Sync Sync Sync CHAR 10 10 10 10
LENGTH PARITY None None None None
Disconnect Options
RX SPACE Disable Disable Disable Disable DISC’T
TX SPACE Disable Disable Disable Disable DISC’T
CARRIER Enable Enable Enable Enable DISC’T
LINE CURR Enable Enable Enable Enable DISC’T
RTS DISC’T OFF OFF OFF OFF
2
Quick Setup does not change the address to the default address, but a factory
reset does.
Page 45
163
APPENDIX A: Quick Setup Configurations
Table A-2 (continued). Additional Quick Setup Configurations
Test Options
DSR ON ON ON ON DURING ALB
REMOTE Enable Enable Enable Enable TEST
EIA Options
CTS to EIA Normal Normal Normal Normal CD to EIA Normal Normal Normal Normal DSR to EIA Normal True True True DTR from EIA Normal True True True ALBT DTE Disable Disable Disable Disable
CTRL’ED RDL DTE Disable Disable Disable Disable
CTRL’ED TM to EIA True True True True
Modem Setup Options
CD LEVEL, -26 dBm -26 dBm -26 dBm -26 dBm LEASED
CD LEVEL, -43 dBm -43 dBm -43 dBm -43 dBm DIAL
TX LEVEL, 0 dBm 0 dBm 0 dBm 0 dBm LEASED
TX LEVEL, Permis. Permis. Permis. Permis. DIAL
SIGNAL 10
4
10
4
10
$
10
4
QUAL LEVEL
Page 46
164
MODEM 32144
Table A-2 (continued). Additional Quick Setup Configurations
COMPR T-III T-III T-III T-III EQUAL
TRELLIS Enable Enable Enable Enable CODE
TRANSMIT Internal Internal Internal Internal CLOCKING
T1 TIMER 0.8 sec 0.8 sec 0.8 sec 0.8 sec
Default settings listed by Quick Setup mode
AUTO- Enable Enable Disable Disable RETRAIN
ANS/ORG ORIG ORIG ORIG ANS DEFAULT
ANS TONE 2100 Hz 2100 Hz 2100 Hz 2100 Hz FRONT Enable Enable Enable Enable
PANEL SPKR CTRL Til-CD Til-CD Til-CD Til-CD SPKR VOL Medium Medium Medium Medium GUARD OFF OFF OFF OFF
TONES V.8 PROC Enable Enable Enable Enable V.13 OFF OFF OFF OFF
OPERATION TRAINING Long Long Short Short
LENGTH CARRIER Switched Constant Constant Switched CTS RTS RTS RTS RTS RTS-CTS DLY 150 ms 0 0 0
Page 47
165
APPENDIX A: Quick Setup Configurations
Table A-2 (continued). Additional Quick Setup Configurations
Auto-Recovery Options
AUTO-RECV None None None None SELECT
AUTO-RECV OFF OFF OFF OFF RETURN
AUTO-RECV 20 min 20 min 20 min 20 min TEST INT’VL
AUTO-RECV INTER INTER INTER INTER TEST TYPE
LCD Intensity Option
LCD55 55 INTENSITY
Page 48
166
MODEM 32144
Do not Make PDF of this page
Page 49
6
MODEM 32144
3.3 Selecting Options from the Front Panel ........................................40
3.3.1 DEC/INC (Decrease/Increase) Screens ..............................41
3.3.2 Example of How to Select an Option ...................................42
3.3.3 How to Return to the EIA Status Screen ..............................43
3.3.4 Automatic Configuration Save Feature.................................43
3.3.5 How to Return to Default Settings ........................................43
3.4 Options..............................................................................................44
3.5 Speed (Data Rate) Options .............................................................44
3.6 V.42 Error Correction Options........................................................48
3.7 Address..............................................................................................54
3.8 Dialer Mode ......................................................................................55
3.9 Auto-Answer Option ........................................................................55
3.10 Data Format Options .....................................................................56
3.11 Disconnect Options........................................................................57
3.12 Test Options.....................................................................................58
3.13 EIA Options .....................................................................................58
3.14 Modem Setups................................................................................60
3.15 V.33 and Bell 208A/B Options ......................................................65
3.16 Options Accessible Only via Summary Setup...............................67
3.16.1 Dial Line Options .................................................................67
3.16.2 V.42 Error-Correction Options ............................................67
3.16.3 Data Pump Options..............................................................69
3.16.4 Miscellaneous Options .........................................................70
4.0 General Operation and Special Features..............................................74
4.1 Quick Reset.......................................................................................74
4.2 Storing Phone Numbers ..................................................................74
4.2.1 Uses..........................................................................................74
4.2.2 How to Store a Phone Number .............................................75
4.3 Automatic Fallback...........................................................................77
4.3.1 Operating-Mode Fallback ......................................................77
4.3.2 Automatic Rate Adjustment...................................................79
4.4 Dumb Mode and Bell 208 Operation.............................................80
4.4.1 Manual Originate/Answer Operation ..................................80
4.5 V.32/208 Auto-Detect Mode............................................................81
4.5.1 V.32/V.32 bis Operation.........................................................81
4.5.2 Bell 208 Operation .................................................................82
4.5.3 Automatic Fallback.................................................................82
4.6 V.13 Operation .................................................................................82
4.7 DTR Dialing......................................................................................82
4.7.1 Dialing a Stored Number.......................................................83
4.7.2 Answer Mode Operation........................................................83
Page 50
7
MODEM 32144
4.8 Dial Line Auto-Recovery ..................................................................83
4.8.1 Setting Up the Modem for Dial Line Auto-
Recovery ..................................................................................83
4.8.2 Recovery Procedure ...............................................................84
4.9 Leased Line Auto-Recovery .............................................................84
4.9.1 Autodial Backup .....................................................................85
4.9.2 Exit from Leased Line Auto-Recovery ..................................85
4.9.3 Leased-Line Auto-Recovery Options.....................................86
4.10 Modem Security Operation...........................................................87
4.11 Automatic Password Protection (APP)..........................................87
4.12 Configuring Modems for APP.......................................................89
4.12.1 APP Without Callback ..........................................................89
4.12.2 APP With Callback................................................................89
4.12.3 Password Screens ..................................................................89
4.12.4 Valid Password Characters ...................................................90
4.12.5 APP with Callback: Storing the Password with
Callback Number..................................................................91
4.13 Disabling APP .................................................................................91
4.13.1 Temporarily Disabling APP..................................................91
4.13.2 Clearing the Password ..........................................................92
4.14 Manual-Response Password Protection (MPP)............................92
4.15 Commands for Enabling MPP.......................................................93
4.16 How to Use Password Commands.................................................94
5. Hayes Emulation Mode ............................................................................97
5.1 Hayes Mode Autodialer ...................................................................97
5.1.1 Enabling the Hayes Mode Autodialer...................................97
5.1.2 Command Guidelines ............................................................97
5.2 Result Codes .....................................................................................99
5.3 Transmission Speed........................................................................100
5.4 Hayes Compatible Commands......................................................101
5.5 S Registers .......................................................................................107
5.5.1 Reading and Setting Registers.............................................107
5.5.2 S Register Functions.............................................................108
5.6 Saving Option Selections...............................................................110
5.7 Facsimile (Fax) Transmission ........................................................111
5.8 Hayes Mode Reference Tables ......................................................111
6. V.25bis Autodialer ...................................................................................127
6.1 Enabling the V.25bis Autodialer....................................................127
6.1.1 Quick Setup ..........................................................................127
6.1.2 2=Dialer Mode (DIAL V.25 bis Screen) ..............................128
6.1.3 DTR Dialing in V.25 bis Mode .............................................128
6.2 V.25 bis Autodialer Commands .....................................................128
6.3 Dialing Parameters.........................................................................132
6.4 V.25 bis Result Codes .....................................................................134
Page 51
8
MODEM 32144
6.5 Message Format..............................................................................136
6.5.1 Asynchronous........................................................................136
6.5.2 Synchronous, Character-Oriented ......................................136
6.5.3 Synchronous, Bit-Oriented ..................................................137
7. Diagnostics...............................................................................................138
7.1 When and Why to Test ...................................................................138
7.2 Symptoms and Scope of the Problem...........................................138
7.3 Physical Inspection.........................................................................139
7.4 Overview of Modem Diagnostics...................................................139
7.5 How to Select and Activate Tests ...................................................140
7.5.1 Front-Panel Control .............................................................140
7.5.2 Running Tests in Hayes Mode .............................................140
7.5.3 Remote Test Control ............................................................140
7.6 Diagnostic Monitoring: Status Screens........................................140
7.6.1 EIA Status Screen .................................................................140
7.6.2 Other Status Screens ............................................................141
7.7 Rate Change Screen.......................................................................143
7.8 Local Modem Diagnostics .............................................................144
7.8.1 Analog Loopback (ALB) Test..............................................144
7.8.2 Analog Loopback Self-Test (ALBST) ..................................145
7.8.3 Analog Loopback Self-Test with Errors (ST/E) .................147
7.8.4 External Analog Loopback (ALBX) Test............................147
7.8.5 External Analog Loopback Self-Test (ALXST) ..................149
7.8.6 Digital Loopback Test (DLB) ..............................................151
7.9 Remote Modem Diagnostics..........................................................153
7.9.1 Remote Digital Loopback (RDL) Test ................................153
7.9.2 Remote Digital Loopback Self-Test (RDLST) ....................154
Appendix A: Quick Setup Configurations ................................................156
Appendix B: Summary Setup.....................................................................166
B.1 Summary Setup LCD Screens .......................................................166
B.2 Changing Options via Summary Setup ........................................167
B.2.1 Summary Setup Pushbutton Functions..............................167
B.2.2 Explanation of Summary Setup Screens ............................168
Appendix C: Connectors, Adapters, and Jumpers ...................................176
C.1 Connectors and Adapters .............................................................177
C.1.1 Connector Pin Assignments................................................178
C.2 Jumpers...........................................................................................179
Page 52
9
MODEM 32144
Appendix D: DC Voltage Models ...............................................................181
D.1 Introduction...................................................................................181
D.2 Installation .....................................................................................182
D.3 Jumper Settings .............................................................................183
D.4 Jumper Locations ..........................................................................184
Appendix E: LCD Flow Chart ....................................................................185
Page 53
139
CHAPTER 7: Diagnostics
7.3 Physical Inspection
The next step in isolating a defective component is to inspect the system. If you have been able to trace the problem to a specific site, examine that site. Check the installation of the modem and DTE. Are all cables in good condition and fully connected? Are all components in the system receiving power? Inspect the system as thoroughly as possible.
7.4 Overview of Modem Diagnostics
Once you have identified the symptoms and conducted a physical inspection of the sites in question, you can use diagnostic monitoring and testing to further isolate the problem. The modem is equipped with diagnostic capabilities that will often enable the user to locate faults quickly and easily. The diagnostic features of the modem fall into two categories—local and remote— as listed below.
There are six types of local
modem diagnostics:
• Analog loopback (ALB)
• Analog loopback self test (ALBST)
• Analog loopback self test with errors (ST/E)
• External analog loopback (ALBX)
• External analog loopback self test (ALXST)
• Digital loopback (DLB)
There are two types of remote
diagnostics:
• Remote digital loopback (RDL)
• Remote digital loopback self test (RDLST)
The sequence in which diagnostic tests should be conducted depends upon the symptoms that have been identified as well as the availability of personnel at the remote site and external test equipment. The self test pattern generator and pattern detector built into the modem alleviates the requirement for external test equipment. With the non-self tests, either a standard DTE or an external bit error rate test (BERT) is used to generate test data and compare it with received data.
Because more transmission errors occur at higher speeds on marginal transmission facilities, begin testing at 14.4 Kbps. If errors occur, reduce the speed and try again. If you cannot correct the problem, contact Technical Support for assistance.
Page 54
140
MODEM 32144
7.5 How to Select and Activate Tests
7.5.1 F
RONT-PANELCONTROL
Tests are accessed and activated in the same way options are selected: by using the LCD and front-panel pushbuttons (as explained in Chapter 3). To find the LCD screen for a specific test, refer to the LCD flow chart (DIAGNOSTIC AND CONTROL FUNCTIONS) included with this manual. Once you have accessed the screen for a specific test, press pushbutton 1 to begin the test (select ON). A test status screen will then be automatically displayed. To deactivate a test, press the ENT pushbutton and then pushbutton
3. (The ENT button cannot be used to exit the text screen until the test has been deactivated.)
NOTE
For valid test results, error correction must be disabled before diagnostic tests are run. To disable error correction, set the V.42 Mode option to OFF.
7.5.2 R
UNNINGTESTS INHAYESMODE
In Hayes emulation mode only, most of the diagnostic tests available on the modem can be activated via the DTE keyboard by using the &T commands listed in Section 5.4. The duration of a test can be set by assigning a value to register S18. For example, AT S18=30 sets the test time to 30 seconds. The command &TO terminates a test. For further information, see Section 5.4.
7.5.3 R
EMOTETESTCONTROL
You can configure the modem to ignore or accept requests from remote modems to initiate tests on your modem. To access the remote test control option, select TEST from SETUP screen 4. Then select RMT from the TEST OPTIONS screen. From the REMOTE TEST screen, select ENABLE to allow remote test initiation or DISABLE to refuse remote test requests.
7.6 Diagnostic Monitoring: Status Screens
To obtain additional information about the status of the communications system, observe the status screen described in the following sections. To view these screens, push the ENT button until the EIA status screen appears. Use the right arrow pushbutton to advance to other status screens.
7.6.1 EIA S
TATUSSCREEN
The EIA status screen indicates the operational status of the modem as well as the condition of certain EIA RS-232 leads. The abbreviations that may appear are identified below; however, typically, only a few of these abbreviations will be displayed during actual operation.
Page 55
141
CHAPTER 7: Diagnostics
DTRMRRSCSTD 9600 TM ER CD RD
Handshake Display
When two modems establish a connection, they engage in an exchange known as a handshake. While a handshake is taking place, the modem displays several codes ranging from H-01 to H-28 in the lower left corner of the EIA status screen. A handshake typically lasts for up to 12 seconds and is accompanied by various audible tones.
Checksum Screens
By pressing pushbutton 1 while the EIA status screen is displayed, you can access two checksum screens, one for the main checksum and one for the data pump transmitter and receiver checksums. These checksums provide data intended for use by servicing personnel. The checksum screens also show the software revision levels (which are also shown on the power-on screen).
7.6.2 O
THER
S
TATUSSCREENS
QUALITY SCREEN. The quality screen displays the quality of the received signal carrier as a numeric value and as a horizontal bar graph. A low numeric value indicates good signal quality. The best possible signal quality is indicated when the bar graph extends all the way to the right edge of the LCD.
D=Dial line occupied
R=Ringing (R appears in same position as D.)
S=Connection secured by security handshake (S appears in same position as D. S and D may flash alternately.)
TR=Data Terminal Ready
MR=Data Set Ready
RS=Request to Send
CS=Clear to Send
TD=Transmit Data
9600, 4800, etc. = Data speed (“idle”—meaning the modem is off-line—or H-01, H-14, etc., may also be displayed in the data speed position; see following text.)
TM=Test mode
ER=Error (poor signal quality)
CD=Carrier Detect
RD=Receive Data
Page 56
142
MODEM 32144
LINE LEVELS SCREEN. This screen shows the preset level of the transmit signal (TX) and the measured level of the receive signal (RX).
The RX value is the approximate local receive level of the incoming signal. The range of measurement for RX is from 0 to –43 dBm in 1.5­dBm increments. If the signal level is less than the carrier detect threshold, <CD will be displayed.
ECHO CHARACTERISTICS SCREEN. This screen displays the characteristics of the echo portion of the receive signal. Specifically, it shows milliseconds of delay and the offset frequency in Hertz.
CHANNEL FREQUENCY OFFSET. This screen displays the frequency offset of the receive signal in Hertz.
THROUGHPUT SCREEN. This screen functions only if error correction has been enabled. It shows the rate (in bits per second) at which characters are being accepted by the modem from the DTE.
PACKET SCREEN. The packet screen functions only when error correction is enabled. It has three components, as explained next.
• SIZE. Shows size of data packets (MNP) or blocks (V.42/V.42 bis) currently being transmitted. MNP uses “shorter” packets to transmit through noisy lines and “longer” packets (which allow greater throughput) when line conditions are good. The maximum MNP packet size is 256 characters (MNP classes 4 and 5) or 64 (MNP classes 1-3). The block size for V.42/V.42 bis is fixed at 128 characters.
• TRANSMITTED (TX). Number of packets or blocks transmitted since the connection was established (or since counter reset).
• ERRORS (ER). Number of retransmissions (due to data errors) since the connection was established (or since the counter was reset).
To reset the TX and ER counters, press pushbutton 2 while the packet screen is displayed.
MODE AND RATE SCREEN. This screen shows the following data:
• MODE. Below MODE, this screen indicates the error­correction status:
- NORMAL, Error correction and buffer mode are both inactive.
Page 57
143
CHAPTER 7: Diagnostics
- V42, V.42 error correction (LAPM) is active.
- V42 bis, V.42 bis error correction (LAPM with data compression) is active.
- MNP 01 – MNP 05, MNP error correction is active.
- BUFFER, Buffer mode is active.
- OFFLINE, Modem is off-line.
• RATE. This screen shows the data rate of the DTE.
7.7 Rate Change Screen
If V.32bis mode and the Rate Renegotiation Procedure (RRP) option are both enabled, the modem will automatically adjust during data transmission to a higher or lower data rate, depending on the receive signal quality. For diagnostic purposes, the RATE screen (accessed from screen 3 of the MAIN MENU) may be used to manually initiate speed renegotiation from the front panel, as explained below.
The RATE screen is displayed only if V.32 bis mode is enabled (via Summary Setup, V.32 Mode option).
If you select DOWN from the RATE screen, the modem will fall back to the next lower speed. If you select UP, the modem will fall forward to the next higher speed— if the signal quality is good enough. The range within which the modem can fall forward or fall back is limited by the minimum and maximum rates set via the Speed Limit option. After you select UP or DOWN, the LCD will automatically switch to the EIA status screen so you can see the result of the rate change request (i.e., the current data rate, which is displayed in the lower left corner of the EIA status screen). However, if the local modem has reached the minimum or maximum speed, it will not switch to the EIA status screen.
NOTE
A request to increase the data rate may result in no change in the data rate if the signal quality is poor.
If you manually initiate speed renegotiation with RRP enabled, the modem will automatically renegotiate the speed (again) after receiving good signal quality for 4 seconds. If the originate modem attempts to negotiate a rate that is lower than the minimum rate setting of the answer modem, the answer modem will disconnect (GSTN cleardown).
Page 58
144
MODEM 32144
7.8 Local Modem Diagnostics
Local modem diagnostics are for testing the modem and its adjoin­ing system. These tests are accessed from the main menu and are easily performed if the modem is attached to DTE or an external BERT.
7.8.1 A
NALOGLOOPBACK
(ALB) T
EST
Analog loopback testing allows the user to test the local modem and its associated terminal independently from the telephone interface and the remote modem. Fig. 7-1 shows the connections automatically made during the test.
LOCAL MODEM
DATA TERMINAL EQUIPMENT
(DTE) AT LOCAL SITE
TRANSMITTER
RECEIVER
Fig. 7-1. Analog Loopback Test.
Page 59
145
CHAPTER 7: Diagnostics
In Hayes emulation mode only, the ALB test can be initiated using the command &T1 (preceded by AT). In any mode, the ALB test can be initiated by using the modem’s front panel controls, as explained in the following paragraphs.
Make sure the modem is idle, that the data rate is the same as that of the DTE and that the DTR circuit is on. (If TR is present on the EIA status screen, the DTR circuit is on.)
From screen 2 of the LCD MAIN MENU, select TEST. This will take you to screen 1 of the LOCAL TEST menu, where ALB will be displayed as one of the test selections. Select ALB.
The ANALOG LOOPBACK screen will be displayed, with ON and OFF as the possible selections.
Select ON to activate the test. (In general, the DSR during ALB test option discussed in chapter should be left ON—the default selection— to avoid disrupting the DTE and DTE software operations.)
The EIA status screen will be displayed while the test is being conducted. Ensure that test data is being generated. Watch for data errors. By transmitting test data and comparing it with the received copy, the DTE and modem are checked for proper operation.
To end the test, press the ENT pushbutton to return to the ANALOG LOOPBACK screen, and then select OFF.
7.8.2 A
NALOGLOOPBACKSELF-TEST
(ALBST)
In the analog loopback self-test, the modem is placed in analog loopback and data is sent and received by an internal 511-bit pattern generator and receiver; therefore, no DTE or external BERT is necessary. Fig. 7-2 shows the data flow for this test.
Page 60
146
MODEM 32144
Fig. 7-2. Analog Loopback Self Test (ALBST).
The SELFTEST screen will be displayed, with ON and OFF as the possible selections. Select ON to activate the test. The EIA status screen will be displayed while the test is being conducted. If “ER” is present on the front panel, data errors have occurred. The ER indicator may flash on when the test is first turned on, but it should quickly go out and remain off until the end of the test.
In Hayes mode only, the ALBST can be initiated using the command &T8 (preceded by AT). In any mode, the ALBST can be initiated by using the modem’s front-panel controls, as follows:
From screen 2 of the LCD MAIN MENU, select TEST. This will take you to screen 1 of the LOCAL TEST menu, where ALBST will be visible as one of the selections. Select ALBST.
TRANSMITTER
PATTERN
GENERATOR
RECEIVER
PATTERN
DETECTOR
Page 61
147
CHAPTER 7: Diagnostics
To end the test, press the ENT pushbutton to return to the SELFTEST screen, and then select OFF.
7.8.3 A
NALOGLOOPBACKSELF-TEST
WITH
E
RRORS
(ST/E)
In the analog loopback self test with errors, data is sent and received by an internal 511-bit pattern generator and receiver; therefore, no DTE or external BERT is necessary. This test differs from the ALBST in that errors are injected into the data flow every few seconds. The data flow is the same as that shown in figure -2 (the ALBST).
To run this test, follow these steps:
From screen 2 of the LCD MAIN MENU, select TEST. This will take you to screen 1 of the LOCAL TEST menu, where ST/E will be visible as one of the selections. Select ST/E.
The SELFTEST W/ERROR screen will be displayed, with ON and OFF as the possible selections. Select ON to activate the test. The EIA status screen will be displayed. The ER indicator should flash every few seconds, indicating that the pattern generator and detector are working. Errors are injected every few seconds. To end the test, press the ENT pushbutton to return to the SELFTEST W/ERROR screen, and then select OFF.
7.8.4 E
XTERNALANALOGLOOPBACK
(ALBX) T
EST
The external analog loopback test is available for 4-wire leased line mode only.
The ALBX test allows the user to test the local modem and its associated terminal and to verify the availability of the leased line circuit. The test circuit does not include the remote modem. Fig. 7-3 shows the connections automatically made during the ALBX test.
NOTE
The ALBX test may result in errors or may fail altogether even where conditions are satisfactory for normal operation. This is because the test channel presented to the modem during the ALBX test.includes all impairments of both the inbound and outbound channels (amplitude distortion, delay distortion, noise, etc.). The main purpose of the ALBX test is to verify that the modem is connected to the leased line and that the leased line circuit is complete. The test is not meant to assess the suitability of the leased line.
Page 62
148
MODEM 32144
The ALBX test can be initiated by using the modem’s front panel controls, as explained in the following paragraphs.
Make sure the local modem is not in communication with the remote modem, that the data rate is the same as that of the DTE and that the DTR circuit is on. (If TR is present on the EIA status screen, the DTR circuit is on.)
From screen 2 of the LCD MAIN MENU, select TEST. Go to screen 2 of the LOCAL TEST menu and select ALBX.
Fig. 7-3. External Analog Loopback (ALBX) Test.
EXTERNAL LOOPBACK
(LEASED LINE)
RECEIVER
TRANSMITTER
LOCAL MODEM
DATA TERMINAL EQUIPMENT
(DTE) AT LOCAL SITE
Page 63
149
CHAPTER 7: Diagnostics
The ANALOG LOOP(EXT) screen will be displayed, with ON and OFF as the possible selections.
Select ON to activate the test. (In general, the DSR during ALB test option discussed in chapter should be left ON—the default selection— to avoid disrupting the DTE and DTE software operations.)
The EIA status screen will be displayed while the test is being conducted. If no external loopback is present, the status screen will display an “IDLE” message. If a loopback is present, handshake­sequence codes will appear (H-01, etc.), followed by the modem speed. Make sure that test data is being generated. Watch for data errors. By transmitting test data and comparing it with the received copy, the DTE and modem are checked for proper operation. During the ALBX test, RD (receive data) may appear on the status screen even though no data is being received—this is normal.
On a flat line, the MODEM modem in ALBX test mode will train and remain running across the following range of signal loss: in V.32 mode, 0–51 dBm (0–52 dBm at 12.0 Kbps); for V.33 operation, 0-47 dBm; and for Bell 208A/B operation, 0–37 dBm. If signal loss exceeds these limits, the test may not start or may be halted.
During the ALBX test, the modem will attempt to retrain upon loss of carrier. In switched carrier mode, the modem will attempt to retrain upon loss of RTS.
To end the test, press the ENT pushbutton to return to the ANALOG LOOP(EXT) screen, and then select OFF.
7.8.5 E
XTERNAL
A
NALOGLOOPBACK
S
ELF-TEST
(ALXST)
The external analog loopback self test is available for 4-wire leased line mode only.
The ALXST places the modem in analog loopback and causes data to be sent and received by an internal 511-bit pattern generator and receiver; therefore, no DTE or external BERT is necessary. As shown in Fig. 7-4, the test circuit includes the leased lines (the external loopback).
Page 64
150
MODEM 32144
NOTE
The ALXST may result in errors or may fail altogether even where conditions are satisfactory for normal operation. This is because the test channel presented to the modem during the ALXST includes all impairments of both the inbound and out-bound
channels (amplitude distor­tion, delay distortion, noise, etc.). The main purpose of the ALXST is to verify that the modem is connected to the leased line and that the leased line circuit is complete. The test is not meant to assess the suitability of the leased line.
Fig. 7-4. External Analog Loopback Self Test (ALXST).
TRANSMITTER
PATTERN
GENERATOR
EXTERNAL LOOPBACK
(LEASED LINE)
RECEIVER
PATTERN
DETECTOR
Page 65
151
CHAPTER 7: Diagnostics
The ALXST can be initiated from the modem’s front panel, as follows:
From screen 2 of the LCD MAIN MENU, select TEST. Go to screen 2 of the LOCAL TEST menu and select ALXST.
The ANALOG ST (EXT) screen will be displayed, with ON and OFF as the possible selections. Select ON to activate the test.
The EIA status screen will be displayed while the test is being conducted. If no external loopback is present, the status screen will display an “IDLE” message. If a loopback is present, handshake sequence codes will appear, followed by the modem speed. If “ER” is present on the front panel, data errors have occurred. The ER indicator may flash on when the test is first turned on, but it should quickly go out and remain off until the end of the test.
The information at the end of the previous section (for the ALBX test) concerning signal loss, loss of carrier and loss of RTS also apply to the ALXST.
To end the test, press the ENT pushbutton to return to the ANALOG ST (EXT) screen, and then select OFF.
7.8.6 D
IGITALLOOPBACKTEST
(DLB)
Digital loopback testing determines the operational performance of the local modem, the remote modem, and the telephone line as a composite system. For this test, data must be sent and received at the remote modem. This test regenerates the data and loops it back to the remote modem. As with the ALB test, a comparison of the results of the DLB test can indicate whether or not the DTE is performing satisfactorily. A comparison of the results of the ALB and DLB tests can help determine whether the modem or the telephone line is defective.
In the DLB test, the data to be sent and received is originated and checked by the DTE or external BERT. Fig. 7-5 shows the data flow for this test.
Page 66
152
MODEM 32144
Fig. 7-5. Digital Loopback (DLB) Test.
In Hayes mode only, the DLB test can be initiated using the command &T3 (preceded by AT). In any mode, the DLB test can be initiated using the modem’s front­panel controls, as follows:
From screen 2 of the LCD MAIN MENU, select TEST. Go to screen 2 of the LOCAL TEST menu and select DLB.
The DIGITAL LOOPBACK screen will be displayed, with ON and OFF as the possible selections. Select ON to activate the test. The EIA status screen will be displayed while the test is being conducted. Make sure that test data is being generated. Watch for data errors. By transmitting test data and comparing it with the received copy, the DTE is checked for proper operation. To end the test, press the ENT pushbutton to return to the DIGITAL LOOPBACK screen, and then select OFF.
TRANSMITTER
RECEIVER
LOCAL MODEM
RECEIVER
TRANSMITTER
REMOTE
MODEM
DATA TERMINAL EQUIPMENT
(DTE) AT LOCAL SITE
Page 67
153
CHAPTER 7: Diagnostics
7.9 Remote Modem Diagnostics
The modem is capable of performing two tests on compatible remote modems: remote digital loopback (RDL) and remote digital loopback self-test (RDLST). If a problem is encountered and the local modem passes all diagnostic tests, the local modem can test the remote modem.
There are two (noncontiguous) REMOTE TEST screens on the modem LCD: (1) The remote tests are initiated from the REMOTE TEST menu. (Select RMT from MAIN MENU screen 2, and then select TEST. Then select the test type.) (2) A remote test cannot be initiated unless the Remote Test option is enabled on the remote modem. This option (also REMOTE TEST on the LCD) is accessed via SETUP screen 4.
7.9.1 R
EMOTEDIGITALLOOPBACK
(RDL) T
EST
The RDL test (Fig. 7-6) allows testing of the local modem, remote modem and telephone line from the local site.
In Hayes mode only, the RDL test can be initiated using the command &T6 (preceded by AT). In any mode, the RDL test can be initiated from the modem’s front panel, as follows:
Both modems should be on-line and should be tested at the data rate used by the DTE. Ensure that the DTR circuit is on. (If TR is present on the EIA status screen, the DTR circuit is on.)
From screen 2 of the MAIN MENU, select RMT, and then select TEST. From the REMOTE TEST menu, select RDL.
Page 68
154
MODEM 32144
Fig. 7-6. Remote Digital Loopback (RDL) Test.
7.9.2 R
EMOTEDIGITAL
L
OOPBACK
S
ELF-TEST
(RDLST)
The RDLST allows testing of the local modem, remote modem and telephone line from the local site as did the previous test, except that the test data is generated by internal modem circuitry as opposed to a DTE or external BERT. Fig. 7-7 shows the connections automatically made during the test.
From the REMOTE DIGIT LOOP screen, select ON to activate the test. The status screen will be displayed as the test is being conducted. Make sure that test data is being generated. Watch for data errors. By transmitting test data and comparing it with the received copy, the modems as well as the telephone line can be checked for proper operation.
To end the test, press the ENT pushbutton to return to the REMOTE DIGIT LOOP screen, and then select OFF.
DATA TERMINAL EQUIPMENT
(DTE) AT LOCAL SITE
RECEIVER
TRANSMITTER
LOCAL
MODEM
TRANSMITTER
RECEIVER
REMOTE MODEM
Page 69
155
CHAPTER 7: Diagnostics
In Hayes mode only, the RDLST can be initiated using the command &T7 (AT &T7). In any mode, the RDLST test can be initiated from the front panel as follows: Both modems must be on-line. From screen 2 of the MAIN MENU, select RMT, and then select TEST. From the REMOTE TEST menu, select RDLST.
From the RDL SELFTEST screen, select ON to activate the test. The status screen will be displayed as the test is being conducted. If “ER” is present on the status screen, the modem is detecting errors. If numerous errors are detected, steps should be taken to try to identify their source.
Fig. 7-7. Remote Digital Loopback Self Test.
PATTERN
GENERATOR
PATTERN
DETECTOR
TRANSMITTER
RECEIVER
TRANSMITTER
RECEIVER
REMOTE MODEM
LOCAL MODEM
Page 70
128
MODEM 32144
6.1.2 2 = D
IALERMODE
(DIAL V.25
BISSCREEN
)
If you enable the V.25 bis autodialer using the Dialer Mode option, no other options will be changed. To enable the autodialer this way, select DIALER from SETUP screen 2. Then press the right arrow pushbutton to go to the DIAL V25 bis screen (screen 2). Select the V.25 bis data protocol that is appropriate for the DTE to be used: asynchronous (Asyn); synchronous, character-oriented (Syn_c); or synchronous, bit­oriented (Syn_b).
6.1.3 DTR D
IALING IN
V.25
BISMODE
An alternative to using the V.25bis CRS command to dial a stored number is to use the DTR dialing option. With DTR dialing enabled, the autodialer will dial the number stored in phone cell 0 when DTR goes high for at least 50 ms.
To enable V.25 bis DTR dialing, use the Summary Setup feature (as described in appendix ) to change the parameter for Penril/V25 bis DTR dialing to 0. Do not select DTR dialing via the front-panel DIALER screen; this will not enable DTR dialing for V.25 bis mode. The Summary Setup Penril/V25 bis DTR dialing option applies to either V.25 bis mode or Penril mode—whichever is enabled; therefore, for V.25 bis DTR dialing, the V.25 bis autodialer must be enabled.
6.2 V.25 bis Autodialer Commands
In asynchronous applications, V.25 bis commands are issued directly from the DTE keyboard or through communications software. In synchronous applications, the V.25 bis commands can be used to facilitate computer-controlled communications.
Punctuation and spaces may be used with V.25 bis commands for clarity, but they are not required. If used, they will be ignored by the modem. One exception is the colon (:), which instructs the autodialer to wait for a dial tone.
The V.25 bis commands are described below and are summarized in Table 6-1. See Table 6-3 for explanation of the codes that may be displayed in response to commands.
CIC - CONNECT NEXT INCOMING CALL. The CIC command instructs the autodialer to answer the next incoming call. After the modem goes off hook, the modem will answer the next call only if auto-answer is enabled from the front panel.
Page 71
129
CHAPTER 6: V.25 bis Autodialer
CRN - CALL REQUEST, NUMBER PROVIDED. (Syntax: CRN
5557979) By using the CRN command, you can dial a number directly from the DTE keyboard. Numbers from 0 through 9 can be dialed, and if tone dialing is enabled, the characters A, B, C, D, # and * can also be dialed.
The dialing parameters listed in table -2 can be used with the CRN command to specify how or when a number should be dialed. For example, the command line CRN :T3331234 instructs the autodialer to wait for a dial tone (:) and then tone dial (T) the number 333-1234.
CRS - CALL REQUEST, ADDRESS PROVIDED. (Syntax: CRS 2) The CRS command allows you to dial a stored number simply by specifying its memory address (phone cell). In the example given above, the autodialer will dial the number stored in phone cell 2. The number must first be stored in the specified phone cell using the PRN command (Table 6-1).
DIC - DISREGARD INCOMING CALLS. The DIC command instructs the autodialer not to answer incoming calls. The DIC command is canceled when the CIC command is issued or the modem is reset. In the event of a reset, the modem will answer if auto-answer is enabled from the front panel.
PRN - PROGRAM NORMAL (STORE NUMBER). (Syntax: PRN 1;5551212) The PRN command is used to store a number or dial string in a phone cell so it can be dialed later by specifying only the phone cell number. As shown above, PRN is followed by the phone cell number, a semicolon and the phone number to be stored. After a number is stored, it can be dialed using the CRS command. Any of the characters listed in Table 6-2 may be stored.
Ten phone cells (0-9) are available for phone number storage. Each cell can hold a maximum of 25 characters, although cells 1 through 9 will automatically expand to the next empty phone cell if loaded with more than 25 digits. Even if a stored number is continued to another cell, the maximum number of characters that can be stored is 36. You cannot store a number in a phone cell unless it is empty. To clear a cell, enter PRN and the phone cell number, without a phone number. Only cell 0 can be accessed from the modem’s front panel (via the PHONE LCD screen).
Page 72
130
MODEM 32144
RLN - REQUEST STORED NUMBER(S). RLN can be used to request a list of all stored numbers or to show the number stored in a specific phone cell. RLN, used alone, requests a list of all stored numbers. The DTE display will show the stored numbers as follows: LSN 0; 301 555 1234 LSN 1; 301 123 4567 LSN 2; 301 555 5555
(and so on through phone cell 9)
If a phone cell number is specified after RLN, e.g., RLN 5, the DTE display will show only the number stored in the specified phone cell.
How to Disconnect a Call
To disconnect a call locally, use your communication software to force DTR to go low, or select HANGUP from the front-panel AUTO-DIAL screen.
Page 73
131
CHAPTER 6: V.25 bis Autodialer
Table 6-1. V.25bis Autodialer Commands
Command Function
CIC Connect next incoming call.
CRN n Call request—dial number (n) entered on DTE
keyboard.
CRS m Call request—dial number stored in specified
memory address (m).
DIC Disregard incoming calls.
PRN m; n Program normal—store number or dial string n in
memory address m.
RHA Switch to Hayes dialing mode (also resets modem
configuration).
RLN Request list of all stored numbers.
RLN m Request to see number stored at address m.
n represents a number to be dialed or stored (e.g., 5557979); m represents a memory address where a number is stored (0-9).
A comma (,) can be included in a dial string to effect a pause.
A colon (:) can be included to instruct the autodialer to wait for a dial tone before proceeding.
Page 74
132
MODEM 32144
6.3 Dialing Parameters
Table 6-2 lists dialing parameters that may be used with the CRN command to modify dialing operations.
Table 6-2. V.25 bis Dialing Parameters
(Table also applies to Dumb mode and Bell 208 operation)
Characters that can be pulse or tone dialed: 0-9 Can only be tone dialed: A, B, C, D, #, and *
L Links a phone number to
another number to be dialed as an alternate when the primary number is busy or does not answer. See L—Link in Section 5.4.
P Sets pulse dialing mode.
T Sets tone dialing mode.
W or : (colon) Wait 30 seconds for dial tone before
proceeding.
[CR] or . Required at end of dial command line. (carriage return [CR] is sent from DTE keyboard. or period) Dumb/208 mode only: period has same
function, but may be entered via the front panel (PHONE LCD screen).
, (comma) or < Pause before processing next character
in dial string.
Page 75
133
CHAPTER 6: V.25 bis Autodialer
Table 6-2. V.25 bis Dialing Parameters
(Table also applies to Dumb mode and Bell 208 operation)
Characters that can be pulse or tone dialed: 0-9 Can only be tone dialed: A,B, C, D, # and *
@ Wait for silence.
! (exclamation) Flash hook
L, P, T, and W may be entered as upper or lowercase letters. Spaces or hyphens (-) may be used as separators for clarity; they will have no effect.
6.4 V.25 bis Result Codes
Table 6-3 explains the result codes, or responses that may be displayed on the DTE monitor in response to V.25 bis commands.
Page 76
134
MODEM 32144
Table 6-3. V.25 bis Result Codes
Code Meaning Sent by—
1
CFI AB Call failure—call aborted because of ORG
loss of DTR or because HANGUP was selected from front-panel AUTO-DIAL screen.
CFI CB Call failure because DCE is busy. ORG
(Modem dialing or handshaking as a result of a front-panel dial request.)
CFI ET Call failure because of busy signal. ORG
(Engaged tone.)
CFI ND Call failure—no dial tone. Modem did ORG
not detect dial tone or line current during dialing or handshaking.
CFI NS Call failure—call request specified ORG
an address that does not contain a stored number. (No stored number.)
CFI NT Call failure—no answer tone. Remote ORG
unit answered but did not issue answer tone.
1
Column 3 indicates which modem sends the result code. (ANS/ORG indicates answer and/or originate modem.) A semicolon is used to separate parameters,. e.g., LSN 4;5559797.
Page 77
135
CHAPTER 6: V.25 bis Autodialer
Table 6-3. V.25bis Result Codes (continued)
Code Meaning Sent by—
1
CFI RT Call failure—ring tone. Ringback ORG
detected, but no answer.
CNX Call connecting. ANS/ORG
INC Incoming call. ANS
INV CU Invalid—command unknown. ANS/ORG
INV MS Invalid message (command) syntax. ANS/ORG
INV PS Invalid parameter value. Specified ANS/ORG
parameters are out of range for command used.
LSN List of stored numbers. LSN is ANS/ORG
followed by memory address, stored number, next memory address and stored number, etc.
VAL Valid—command accepted; waiting ANS/ORG
for next command.
Page 78
136
MODEM 32144
6.5 Message Format
The message format for V.25 bis DTE-to-DCE communications is summarized below:
6.5.1 A
SYNCHRONOUS
MARK|MESSAGE|CR|LF|MARK
This format uses one start bit, 8-bit data units, and a 1-unit stop bit. The 8-bit data units are formed by a 7-bit IA5 character and an even parity bit.
6.5.2 S
YNCHRONOUS
, C
HARACTER
-
O
RIENTED
|SYN\SYN\STX|MESSAGE|ETX|
This format uses consecutive 8-bit data units formed by a 7-bit IA5 character and an odd parity bit.
Page 79
137
CHAPTER 6: V.25 bis Autodialer
||FLAG|ADDR|CTRL|MESSAGE|FCS|FLAG|
Consecutive 8-bit data units are used within the message and submitted to the HDLC framing (zero insertion). The 8-bit data units are formed by a 7-bit IA5 character and an off parity bit.
6.5.3 S
YNCHRONOUS
, BIT-O
RIENTED
Page 80
98
MODEM 32144
• ESCAPE SEQUENCE (+++). The escape sequence causes the modem to escape from the data transfer mode so it can interpret commands. (Alternate characters for the escape sequence can be assigned via S register S2.)
• ATTENTION CODE. AT, the attention code, must begin all command lines. There are a few exceptions—but only a few.
• COMMAND SEQUENCE. For dialing, a command line begins with AT and is followed by D and the phone number. Other commands should be placed before the dial command—or after the dial command if it is terminated with a semicolon— for example:
AT M2 V1 D 555-1212; S2=1O
This instructs the modem to: Keep speaker on (M2), send word result codes (V1), dial (D) 555­1212, end dial command (;), set register 2 to 1 (S2=1), and go on­line and wait for carrier (O).
Characters not in the command set are ignored during the dial command. For this reason, punctuation or spaces can be included in the telephone number to make it easier to read:
AT DT 9,(212)555-1234 or AT DT 9, 212 555 1234
• A/ COMMAND. Repeats the commands included in the previous command line. Because the AT is also repeated, no AT is needed to begin this command, nor is a carriage return needed. A/ is useful for redialing a telephone number.
• BACKSPACE KEY. The backspace key deletes the last character entered (provided there is no intervening carriage return) and can be used for simple editing.
• CARRIAGE RETURN [CR]. A carriage return is required at the end of a command line. The modem will not execute a command without it. A carriage return is sent from the DTE keyboards; a period, which may be entered via the modem’s front panel (PHONE LCD screen), has the same function. (On most keyboards, the carriage return [CR] key is labeled “Enter” or “Return.”)
• DIAL COMMAND MODIFIERS. Several modifiers can be used with the basic D (dial) command to alter dialing operations. These modifiers are listed and explained briefly below—they are explained in detail in Section 5.4
Page 81
99
CHAPTER 5: Hayes Emulation Mode
Dial command modifiers:
L—Links a phone number to another number to be dialed as an alternate.
P—Sets pulse-dialing mode.
S=m—Dial number stored at memory location m.
T—Sets tone-dialing mode.
W or : (colon)—Pause for 2 seconds.
, (comma)—Pause for 2 seconds.
; (semicolon)—Return to command state after dialing.
@—Wait for silence.
! (exclamation)—Flash hook
With few exceptions, dial command modifiers will function only if they are used in a command line with the D command or included in a stored number. A carriage return of period must be used at the end of a dial string. An example of a command line with two dial modifiers is:
AT DT 9,555-1212
The modifier T instructs the modem to tone dial, and the comma instructs it to pause after dialing 9 before dialing the remaining digits.
MISSING PARAMETER. A missing parameter is interpreted as a zero. For example, the E command (echo) can be sent as either E0 or E1, but if an E alone
is sent, the modem will interpret it
as if an E0 was sent.
COMMAND BUFFER. The command buffer can hold a maximum of 40 characters. If the command line exceeds 40 characters, the modem refuses to execute any portion of the command line and sends an error message. The AT at the beginning of the command line, control characters, and spaces do not take up space in the command buffer. Punctuation (except for spaces) does take up space in the command buffer.
5.2 Result Codes
Result codes (Table 5-2) are messages sent by the modem to the DTE monitor in response to your commands. Result code options are selected using the V and X commands, as explained below.
Result codes may be words (V1 command) or digits (V0). Word codes are preceded and followed by a carriage return, line feed sequence. Digit codes are only followed by a carriage return.
Page 82
100
MODEM 32144
Result codes 0-4 comprise the basic result code set: OK, CONNECT, RING, NO CARRIER, and ERROR. Codes 5-43 provide additional response information, as explained in Table 5-2. Various combinations of these codes can be enabled or disabled by using the X command and its four parameters, as explained later under X— SELECT RESULT CODE.
NOTE
With the default Hayes mode settings in effect, the modem transmits result codes to the DTE. In some installations, this may cause undesirable interaction with the attached DTE. If such interaction occurs, result codes for incoming calls should be suppressed (using the command AT Q2).
5.3 Transmission Speed
This section applies only to connections made without error correction or buffering (V.42/V.42 bis, MNP and Buffer Mode options).
Transmission speed is governed by the speed of the system with which you wish to communicate. You must set the transmission speed of your computer by setting a switch in the hardware or by issuing a software command. (Refer to your computer documentation.) When the modem originates a call, it automatically detects and adjusts
to the transmission speed set when the communication port was initialized.
When answering a call, the modem determines the transmission speed from the carrier signal of the originating modem. Change the speed (baud) setting of your equipment to match that of the remote system. Otherwise, unintelligible data will appear on your screen. (Depending on the parameter used with the X command, the speed will be indicated by the CONNECT response code.)
Autobaud
When a call is originated in Hayes mode, the AT attention code causes the modem to autobaud. The speed at which the modem autobauds defines the speed limit for subsequent connections and overrides any front panel Speed Limit or DTE Speed settings. If the unit is not autobauded, the default interface rate is 38,400 bps.
NOTE
If AT is entered at one speed and followed by a carriage return [CR] at another speed, the modem will not recognize any further commands until a [CR] is entered at the same speed of the AT.
Page 83
101
CHAPTER 5: Hayes Emulation Mode
5.4 Compatible Commands
All that can be used with the modem are listed in Table 5-1 (near the end of the chapter.) More detailed information is provided below for selected Hayes commands—particularly those used to answer and originate calls, and other commonly used commands. For Hayes commands that control modem options, additional information on options may be found in Chapter 5. Commands are listed in alphabetical order in this section and in Table 5-1.
For most commands there are parameters—numerical values used with the commands that specify the function of the command. For example, the command L controls the modem’s speaker volume. L2 sets the volume to medium. The default value is a predetermined value which is in effect the first time the modem is powered up or when a reset command is given. The possible parameters and default value for each command are shown in Table 5-1.
A—ANSWER. The A command immediately puts the modem into the answer mode. The modem will not execute any command entered in the command line after A.
The A command is used to manually answer an incoming call or to transfer a call between two individuals to a communication between their computers: One person enters AT A while the other enters AT D.
A/-REPEAT PREVIOUS COMMAND. A/ is most commonly used to redial a telephone number that results in a busy signal. The AT prefix is not used with A/, and no carriage return is required. Commands are available for repetition in the command buffer only until AT is entered or power to the unit is turned off. A/ will not work following an AT or power OFF-power ON.
D-ORIGINATE MODE FOR DIALING. The modem dials the number that follows and attempts to go on-line. The dial command D is followed by—
• A telephone number to be dialed, or
• A string consisting of a phone number and dial command modifiers (e.g., T, P, and ;).
An example of the D command
is AT D3331234.
Page 84
102
MODEM 32144
In response to this command, the modem dials the telephone number 333-1234, and then waits for a carrier tone from the distant modem (default wait time, 30 seconds). If the modem is able to establish a call, it gives a CONNECT result code, indicating that it is on-line. If it cannot connect, it will use a different result code , such as NO CARRIER, BUSY, or NO DIALTONE.
The characters that can be dialed are 0 through 9, A, B, C, D, #, and *.
The dial command modifiers are listed in the preceding Command Guidelines section.
AT D—the dial command without a telephone number
causes the modem to pick up the telephone line without dialing
a number.
DS—DIAL STORED NUMBER. The DS command instructs the modem to dial a phone number or dial string previously stored using the &Z command. The syntax is DS=m, where m specifies the memory location where the number to be dialed will be stored. Up to ten numbers may be stored in memory locations 0-9. S=m may be placed anywhere in the dial string for example, AT D2345S=2 will dial 2345 and the number
stored in memory location 2.
H—TELEPHONE SWITCH HOOK. The H command on-hook) is used to terminate a call. (On­hook corresponds to off-line.) H may also be used to alternate between voice and data transmission during the same call (if your communication software supports this capability).
The H1 command (off-hook) activates the telephone line relay, causing a dial tone to be sent (after a 2-second delay). For most purposes, this command is not necessary, since the switch hook is automatically activated when the modem originates or answers a call.
L—LINK. The L dial modifier is used to link one phone number to another so that one may be designated as an alternate number to be dialed if a connection cannot be made to a primary number. The L parameter must be used after a phone number, and prior to a carriage return or period. A number is used after L to specify ;the memory address (0-9) that contains the number to be linked to the first number:
AT D 555-1212 L5
Page 85
103
CHAPTER 5: Hayes Emulation Mode
NOTE
L may also be used in V.25 bis mode with the CRN command (instead of AT D), in Dumb mode and in 208 operation. In Dumb mode or 208 operation, L is stored via the PHONE screen. In all cases, L is used the same way and has the same function as described here (except that AT D is not used.)
Two or more addresses may be linked in a cyclic fashion to alternate dialing until a connection is established.
Contents of memory location 0: 555-1212 L1
Contents of memory location 1: 444-1234 L2
Contents of memory location 2: 888-5555 L0
With the memory locations loaded as shown above, if the command AT DS=0 is issued, the autodialer will go to location 0 and dial the number stored there. If unable to connect, the L1 command stored in location 0 will direct the autodialer to dial the number in location 1. In similar fashion, the L2 stored in memory location 1 directs the autodialer to location 2 (assuming a connection cannot be made); and the L0 command stored in location 2 directs the autodialer back to location 0. The numbers will be
dialed in a loop until a connection can be established or until 10 calls have been attempted.
O
—FORCED ON-LINE. This command applies to asynchronous operation only. When the modem is on-line, you can return to the command state by entering the escape code (+++). After the desired command has been executed, use the O command to force the modem from the command state to the on-line state.
P—PULSE DIAL. The P command instructs the modem to pulse dial. It can be entered anywhere in the dialing string: AT P5551212; or it can be entered alone, followed by a carriage return, AT P, in which case all subsequent telephone numbers will be pulse dialed. If the dial command does not specify which dialing mode to use, the modem defaults to the last mode specified.
S—MODIFY S REGISTER. This command is used to write information to a specified S register. The syntax is Sr=n, where r is the number of the register to be modified and n is the value to be written to it; for example:
AT S7=30
Page 86
104
MODEM 32144
This command would change the value of register S7 to 30. If you enter just =5, the autodialer will change the value of the last register used to 5. More information on S registers is included later in this chapter.
S?—READ S REGISTER. This command instructs the autodialer to read the contents of the specified S register. The syntax is Sr?, where r specifies the register to be read. For example, S7? reads the value of register S7. The value is displayed on the computer or terminal monitor. If you enter ? by itself, the autodialer will display the value of the last register used; if = is entered by itself, the autodialer will display the number of the last register used (e.g., S2). For information on how to interpret S register values, see Table 5-3.
T—TONE DIALING. This command causes a telephone number in the dial command string to be dialed using tone signals. (See the P command above for additional information.)
W—WAIT FOR DIAL TONE. The W command (or colon) is used in a dial string to instruct the modem to wait for a dial tone before proceeding. The wait time (30 seconds by default) can be adjusted by changing the value in register S7. If no dial tone is detected within the specified time, the modem will hang up and give a NO DIALTONE result code (if this
result code is enabled by the X command).
Z—RECALL STORED USER PROFILE. The Z command resets the modem and recalls a profile of the modem configuration settings previously saved using the &W command. The profile is designated as profile 0 or profile 1 when it is saved using the &W command.
,—PAUSE. A comma causes the modem to pause for 2 seconds (or time specified in register S8) before processing the next character in a dial string or command. This command is used to place an outside call through a PBX switchboard, where 9 has to be dialed to gain outside access— the pause allows time for the dial tone to occur before the modem dials the number.
AT D9,3331234
Similarly, a comma may be used to cause the modem to wait for a second dial tone before beginning to dial a telephone number. Multiple commas may be used to increase the pause time.
;—FORCED COMMAND STATE. A semicolon placed at the end of a dial command causes the modem to return to the command state after dialing without disconnecting.
The following examples illustrate how the ; command is used:
Page 87
105
CHAPTER 5: Hayes Emulation Mode
The first example is a banking transaction: The command AT D333-1234; dials the bank’s phone number and returns the modem to the command state. After the OK prompt is displayed on the DTE, the command AT D T 0901# is entered. This transmits the identification number 0901 to the bank, and again returns the modem to the command state. An account number and other data may be transmitted in the same way.
The second example illustrates one method of autodialing: Enter a dial string that ends with a semicolon, for example, AT DT9,
3331234. During the ring signal or when the call is answered, pick up the phone and enter AT H. You may then use a telephone connected to the modem for voice communication.
@—WSAIT FOR SILENCE BEFORE DIALING. The @ command is used to gain access to a system that does not provide a dial tone. It tells the modem to wait for 30 seconds or the time specified by a register S7 for one or more rings followed by 5 seconds of silence before processing the next symbol in the dial string.
!—INITIATE FLASH HOOK. The ! command causes the modem to go on-hook for 1/2 second. This has the same effect as holding the switch-hook button on your telephone down for 1/2 second.
You may be able to use this command for transferring calls.
&F—RECALL FACTORY CONFIGURATION. The &F command restores the modem to its original factory configuration, using data stored in ROM. However, this change is not permanent. If the modem is turned off or reset, the recalled configuration will be replaced with the default stored profile. (See the &Y command.)
&V—VIEW ACTIVE CONFIGURATION, ETC. This command displays the active modem configuration, user profiles stored using the &W command, and phone numbers stored using the &Z command. When &V is invoked, the DTE displays the configuration commands last issued, including parameters used, and the values currently stored in the S registers. The &V command should be issued as the last command on a line.
&W—WRITE PROFILE TO MEMORY. The &W command saves the storable parameters of the modem’s active configuration by writing the configuration profile to non-volatile memory. By selecting either &W0 or &W1, two different user profiles can be saved (profile 0 or 1). One of these profiles will be automatically restored whenever the modem is powered on or when the Z command is issued. (See the &Y and Z commands.)
Page 88
106
MODEM 32144
The &W command cannot be used to write changes to the user profiles if the modem front panel has been disabled by the Front Panel Control option.
The parameters listed below cannot be stored—they are all set by changing S register values (as indicated in Table 5-3):
S1—Ring count
S2—Escape-sequence character
(ASCII 43)
S3—Carriage-return character
(ASCII 13)
S4—Line-feed character (ASCII
10)
S5—Backspace character (ASCII
08)
S6—Wait time before blind
dialing
S7—Wait time for carrier/dial
tone
S8—Pause duration (effected by
comma)
S9—Carrier detect response time
S10—Delay: Lost carrier until
hangup time
S11—DTMF tone duration
S12—Escape-sequence guard
time
S25—DTR detection
When the &W command is used to save a configuration profile, stored phone numbers are not saved as part of the profile.
&Z—STORE TELEPHONE NUMBER. The &Z command is used to store a telephone number that can be subsequently dialed
using the DS (dial stored number) command. The syntax is &Zm=n, where m specifies the memory location where the phone number or dial string will be stored and n is the number or dial string to be stored. For example, AT &Z5=T1 (301) 555-1212 will store the specified number at memory location 5. Ten memory locations are available: 0-9.
(The &Z command is also used to store passwords, as explained in Section 4, Security Operation.)
For pulse dialing, digits 0 through 9 can be stored; for tone dialing, 0 through 9, A through D, # and * can be stored. The dial command modifiers listed in the Command Guidelines section can also be stored.
Each memory location can hold a maximum of 24 digits, although locations 1 through 9 will automatically expand to the next empty location if loaded with more than 24 digits. Even if a stored number is continued to another location, the maximum length is 36 characters. (Attempting to dial a dial string of more than 36 characters will result in an ERROR message.) A memory location cannot be used for storage unless it is empty. To delete an entry, enter AT&Zm=, where m is the memory location number. Only location 0 can be accessed from the modem’s front panel (via the PHONE LCD screen).
Page 89
107
CHAPTER 5: Hayes Emulation Mode
\S—VIEW STATUS OF V.42­RELATED CONFIGURATION. The \S command displays the active V.42 error correction configuration, stored V.42 profiles, and certain other data not displayed by the &V command.
5.5 Registers
The modem includes 28 registers (S0-S27) that can be used to control specific modem operations in Hayes mode only. Each register holds a value that serves as a specific operating instruction for the modem. Several of the S registers affect how the previously described commands will be executed.
The functions of the registers intended for user access are explained below and summarized in Table 5-3.
5.5.1 R
EADING ANDSETTINGREGISTERS
Use the S command to read the value of a register or to change its value.
To read the current value of a register, use the command S?, where the number of the register is specified between the S and the ?, as follows: S9?. The decimal value of the register contents will then be displayed. Multiple registers may be read. For example, if you wish to read the current value in registers S0 and S7, enter
AT S0? S7?
A typical response might be 001,030, OK, meaning that the values stored in registers S0 and S7 are 1 and 30, respectively.
To set or change a parameter, use the command S=, where the number of the register follows S and a value between 0 and 255 (the range of values that can be assigned to the registers) follows the equal sign:
AT S0=5
This command will change the value stored in S0 to 5.
The S command can also be used without ? or = to point to a register that will be subsequently read from or written to without being specified. To illustrate this, if you enter
AT S7
a pointer is set to the address of register S7. As long as no other S command is entered, the register value can be requested at any time without specifying the number. If you enter AT? the modem displays the current value in the S7 register. Similarly, if you enter AT=8 the modem will change the value in the S7 register to 8.
Page 90
108
MODEM 32144
5.5.2 S R
EGISTERFUNCTIONS
This section describes the function of individual S registers. Table 5-3 lists the range of possible parameters and the default value for each S register. Only S registers that are intended for user access are listed.
S0—RING TO ANSWER ON. The value in this register determines on what ring (first, second, third, etc.) the modem will answer on. Setting S0 to 0 disables auto-answer.
S1—RING COUNT. Register S1 counts the number of ring signals for each incoming call. If more than 8 seconds have passed since the last ring, S1 is cleared to zero.
S2—ESCAPE CODE CHARACTER. The escape code is effective for asynchronous operation only. Values greater than 127 will completely disable escape code detection and prevent you from issuing a hangup command.
S3—CARRIAGE RETURN. Register S3 is effective for asynchronous operation only. Normally, the ASCII carriage return value, 13, is used.
S4—LINE FEED. This register is effective for asynchronous operation only. The line-feed character follows the carriage
return only when word result codes have been selected (command V1). Line feed can be changed to a null but cannot be totally disabled.
S5—BACKSPACE. This register is effective for asynchronous operation only. The value in S5 defines the backspace character. Do not use values between 33 and
126.
S6—BLIND DIALING WAIT TIME. The value in S6 determines how long the modem will wait after picking up the telephone line (going off-hook) before it begins to dial. If S6 is set for less than 2 seconds, the modem still waits 2 seconds before dialing. If the X2 to X4 command is in effect, dial tone detection will be enabled and blind dialing will be disabled, meaning that the value in S6 will have no effect.
S7—CARRIER/DIAL TONE WAIT TIME. This register controls two wait times—wait time for carrier and, if W is included in the dial string, wait time for dial tone (or wait time for silence if @ is used).
S8—PAUSE TIME. The pause time effected by a comma in a dial string or other command line is controlled by register S8.
S9—CARRIER DETECT RESPONSE TIME. Register S9 determines how long a carrier tone must be present for the modem to
Page 91
109
CHAPTER 5: Hayes Emulation Mode
recognize the tone and indicate a carrier detect. (The time required for the absence of a carrier tone to be recognized is fixed at 0.5 second.)
S10—LOSS OF CARRIER DELAY. The value in register S10 determines how long the delay will be from the occurrence of a loss of carrier until the modem hangs up the telephone line. A value of 255 disables the modem’s carrier disconnect option (and line current option), meaning that the modem will not hang up in the absence of carrier or line current.
S11—TONES. This register sets the spacing of tones used for dialing. The rate can be slowed by increasing the value of S11 to the maximum value, 255. This register has no effect on pulse dialing, which is fixed at 10 pulses per second.
S12—GUARD TIME. This register is effective for asynchronous operation only. The escape guard time delay is required immediately before and after entering the escape code; therefore, the three escape-code characters must be entered within the guard time delay of each other. The unit for this register is 1/50 second (or 20 ms), meaning that the default value of 50 equals 1 second.
If the guard time is zero, timing will not be a factor at all. The three escape characters can occur with
any timing relationship, but they must be consecutive. Be cautious when assigning small guard times, however. You may not be able to enter three characters fast enough, especially if the guard time is less than the time required to transmit one character at the current transmission rate.
S18—DIAGNOSTIC TIMER. The value in register S18 determines how long a diagnostic test will run. For example, if S18 is set to 120, the test (activated by one of the &T commands) will run for 120 seconds. If S18 is set to zero, the default, the test timer will be disabled and the test will run indefinitely. To terminate a test when the test timer is disabled, use the command &T0 or reset the modem. Register S18 is set to zero on powerup or by the command AT Z or AT S18=0.
S25—DELAY TO DTR. The effect of the value stored in register S25 is dependent on the operating mode, as explained below.
Synchronous mode 1: A delay occurs after a call is established before the modem examines the state of DTR. The duration of this delay is the value specified in S25 (in seconds). This allows the operator time to disconnect the modem from an asynchronous data terminal and attach it to a synchronous terminal without forcing the modem back into the command state.
Page 92
110
MODEM 32144
Synchronous modes 1, 2, and 3:
A change in DTR (ON or OFF) which lasts for less than the value in register S25 (in 1/100ths of a second) is ignored by the modem.
S26—RTS TO CTS DELAY INTERVAL. This register affects synchronous operation only. With the command &R0 in effect, CTS is turned on in response to an OFF­to-ON transition of RTS from the local DTE—after the delay specified by the value in register S26 (but only if the modem is on­line and ready to receive synchronous data).
5.6 Saving Option Selections
Changes made to option settings will cease to be effective if power is removed from the modem or if a factory reset has occurred—unless the modem configuration (all option settings) is saved to nonvolatile memory. The storable parameters of the modem’s configuration can be saved to user profile 0 or 1 using the &W command (&W0 or &W1). Upon powerup, the modem will recall either profile 0 or profile 1, depending on which has been designated as the default profile. (The modem is shipped from the factory with profile 0 as the default profile.)
As explained in the following sections, the modem is programmed to treat profile 0 and
profile 1 differently. Use profile 0 for your standard configuration and make it the default profile (&Y0). Profile 1 (optional) is intended to be used to store an alternate configuration (e.g., for
an alternate application).
To view the contents of the user profiles, use the &V and \S commands.
User Profile 0
User profile 0 is linked to the modem’s front panel (i.e., selections made using the front­panel LCD).
• If you make option changes using the front panel, the changes for options for which there are associated Hayes commands will be saved to profile 0 when you exit the SETUP menu.
• If profile 0 is recalled as the active configuration, the LCD screens will reflect the profile 0 configuration.
• If profile 0 is changed by means of Hayes commands or via the Summary Setup feature and then saved, the changes made will be reflected on the LCD and will be effective for all modes.
If you make option changes from the front panel but have not exited the SETUP menu, and then make option changes using Hayes
Page 93
111
CHAPTER 5: Hayes Emulation Mode
commands and save them to profile 0 using the &W command, the changes made using Hayes commands and saved to profile 0 will override the front-panel selections.
A Quick Setup will overwrite most modem option settings. However, certain option settings stored in user profile 0 are not altered by Quick Setup—unless you change the configuration from one Quick Setup type to another. The following parameters in user profile 0 are not affected by a Quick Setup of the same type: Option settings set by the Hayes compatible commands E, F, Q, V, X, &J, &L, &P, &M, &Q, &Z, and \V; and S register values in registers S18, S25, and S26. A factory reset will reset these parameters—and all others—to the factory-default settings.
User Profile 1
User profile 1 is not linked to the front panel.
• Option changes made from the front panel are not saved to profile 1. Profile 1 can be changed only by using Hayes commands or the Summary Setup feature.
• If profile 1 is recalled as the active configuration, the LCD screens will not be affected. (This means that when profile 1 is active, it is possible for the
LCD to display an option setting that does not reflect the setting currently in effect.)
• If profile 1 is changed by means of Hayes commands or via the Summary Setup feature, the changes will not be reflected on the LCD and will only affect Hayes mode operation.
If profile 1 is being used as the active configuration, the options marked with an asterisk (*) in Table 5-1 should be controlled by using the AT commands listed in
Table 5-1 or by using the Summary Setup
feature described in Appendix B. When profile 1 is active, these options can be changed via the front panel LCD, but the changes will not be effective for Hayes mode operation. (However, if profile 0 is subsequently recalled as the active configuration, the changes will be effective at that time.)
5.7 Facsimile (Fax) Transmission
Fax operation is available in Hayes mode only. The modem supports fax classes 1 and 2. You can use your modem with a fax program to transmit and receive facsimile data.
5.8 Hayes Mode Reference Tables
Table 5-1 lists the Hayes compatible commands that can be used with the modem.
Page 94
112
MODEM 32144
Table 5-1. Hayes Compatible Commands
Command Function/Explanation
A ANSWER No parameters. A/ REPEAT PREVIOUS COMMAND. No
parameters. B BELL/CCITT COMPATIBILITY MODE* B0 Selects CCITT V.22 mode (2100 Hz). B1 Selects Bell 212A mode (2225 Hz). C1 Modem displays OK; command has no other
effect. (This response—instead of ERROR—
maintains a degree of compatibility with older
modems that support this command.) D ORIGINATE MODE FOR DIALING. No
parameters. DS DIAL STORED NUMBER. Parameters are
0-9 (available memory locations). E ECHO E0 No echo. E1 Echoes all characters back to terminal screen
when using a full duplex terminal and in local
command mode. F1 Modem displays OK. Command has no other
effect—unless V.22bis/V.22/V.21/V.23 fallback
operation has been enabled. (For details, see
Automatic Fallback in Chapter 4.) H TELEPHONE SWITCH HOOK H0 On-hook (hang up). H1 or H2 Off-hook. Default settings (where applicable) are in bold face. *If user profile is active, option can be controlled (for Hayes mode operation) only by given command or by using Summary Setup. Do not change via front panel (except via Summary Setup).
Page 95
113
CHAPTER 5: Hayes Emulation Mode
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
I PRODUCT CODE OR CHECKSUM I0 Requests product code. I1 Requests checksum for the modem’s software.
(Only a portion of the checksum displayed via
the front panel will be displayed, in decimal
format.) I2 Requests verification of software checksum. I3 Requests the following for each EPROM
(programmable memory unit): chip, part and
revision number; checksum. I4 Reserved. L SPEAKER VOLUME* L0 or L1 Low speaker volume. L2 Medium volume. L3 High volume. M SPEAKER CONTROL* M0 Speaker always OFF. M1 Speaker ON until carrier is detected. M2 Speaker always ON. M3 Speaker OFF during dialing; otherwise ON
until carrier is detected. O FORCED ON-LINE. Forces modem to on-line
state. P PULSE DIAL. No parameters, but the default
is T (for tone dial). Q SEND RESULT CODE Q0 Send result codes. Q1 Withhold result codes (quiet). Q2 Withhold result codes for incoming calls only
(quiet answer).
Page 96
114
MODEM 32144
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
Sn=v MODIFY S REGISTER. n is the register to be
modified; v is the value to be written. Sn? READ S REGISTER. n is the register to be
read. T TONE DIAL. No parameters. V WORD/DIGIT RESULT CODE V0 Result codes are transmitted as digits. V1 Result codes are transmitted as words. W WAIT FOR DIAL TONE No parameters, but
default wait time (register S7) is 30 seconds. X SELECT RESULT CODE X0 Selects basic result codes, 0-4.
Modem will blind dial (without dial tone). X1 No speed indication; no busy or dial tone detect. X2 Selects result codes 0-6, 10, 11, 13, 14, 15, and
18.
X3 Same as X1 except busy signal detect is
enabled. Selects result codes 0-5, 7, 10, 11,
13, 14, 15, and 18. X4 Same as X1 except busy signal detect is
enabled. Selects all result codes. Connection
speed (up to 14,400 bps) indicated; busy
signal and dial tone detect enabled.
Note: Result code 8 is independent of the X
command; it is displayed only when the @ dial
modifier is used. Y LONG SPACE DISCONNECT* Y0 Disables long space disconnect. Y1 Enables long space disconnect. Z RECALL STORED USER PROFILE
Page 97
115
CHAPTER 5: Hayes Emulation Mode
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
Z0 Resets modem and recalls stored user profile 0. Z1 Resets modem and recalls stored user profile 1. , (comma) PAUSE. No parameters, but default pause time
(in register S8) is 2 seconds. ; (semicolon) FORCEDCOMMAND STATE. No parameters. @ WAIT FOR SILENCE BEFORE DIALING. No
parameters, but default wait time (register S7) is
30 seconds. ! (exclamation) INITIATE FLASH HOOK. No parameters. &C DATA CARRIER DETECT CONTROL* &C0 DCD always ON when DTR is present. &C1 DCD ON only in the presence of suitable data. &C2 DCD ON when DTR is present; then toggles off
for 500 ms upon disconnect. &D DATA TERMINAL READY CONTROL* &D0 Ignore DTR. &D1 Go on-hook, assume command state and
disable auto-answer upon DTR loss. &D2 Disconnect upon DTR loss. &D3 Reinitialize upon DTR loss. &F RECALL FACTORY CONFIGURATION
No parameters. &G GUARD TONE CONTROL* &G0 Guard tone disabled. &G1 Enables 550-Hz guard tone. &G2 Enables 1800-Hz guard tone. &J Modem displays OK result code; command has
no other effect. (The modem is configured for
A/A1 control or MI/MIC control via jumpers JP2
and JP3, as detailed in Appendix C.)
Page 98
116
MODEM 32144
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
&L Modem displays OK result code; command has
no other effect. (The modem is configured for
leased line or dialup line operation via the
front-panel QUICK SETUP and/or LINE TYPE
screens.) &M Can be substituted for &Q. &P Modem displays OK result code; command has
no other effect. (The pulse dialing ratio is
factory-set, depending on whether the modem
is a US or international model.) &Q ASYNCHRONOUS/SYNCHRONOUS MODE &Q0 Asynchronous mode. &Q1 Synchronous mode 1—
Synchronous/asynchronous mode. &Q2 Synchronous mode 2—OFF-to-ON DTR
causes the modem to automatically dial a
stored number. &Q3 Synchronous mode 3—Synchronous mode with
manual dial. (A manually dialed call will switch
immediately to synchronous mode.) &R RTS AND CTS OPTIONS* &R0 CTS follows RTS. &R1 CTS follows DTR from the DTE. &R2 CTS is on while the modem is on-line. &S DATA SET READY CONTROL* &S0 DSR always on. &S1 DSR operates on according to RS-232
specification. &S2 Options DSR operation for a crossover
connection.
Page 99
117
CHAPTER 5: Hayes Emulation Mode
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
&T TEST COMMANDS &T0 Terminates a test in progress.
&T0 must be the last command in a command
line. &T1 Initiates a local analog loopback test. &T3 Initiates a local digital loopback test. &T4 Allows the local modem to accept a request
from the remote modem for a remote digital
loopback test. &T5 Prevents the modem from accepting a request
from the remote modem for a remote digital
loopback test self-test. &T6 Initiates a remote digital loopback test. &T7 Initiates a remote digital loopback test self-test. &T8 Initiates a local analog loopback self-test. &V VIEW ACTIVE CONFIGURATION, ETC. &V0 Displays modem configuration, user profiles,
and phone numbers stored in memory
locations 0-5. &V1 Displays all stored phone numbers (contents
of memory locations 0-9). &W WRITE PROFILE TO MEMORY &W0 Saves storable configuration parameters as
user profile 0. &W1 Saves storable configuration parameters as
user profile 1. &X TRANSMITTER CLOCKING* &X0 Selects internal clocking. &X1 Selects external clocking. &X2 Selects receive-mode (slaved) clocking.
Page 100
118
MODEM 32144
Table 5-1. Hayes Compatible Commands (continued)
Command Function/Explanation
&Y DEFAULT USER PROFILE &Y0 Stored user profile 1 will be recalled on powerup. &Y1 Stored user profile 1 will be recalled on powerup. &Z STORE TELEPHONE NUMBER. Parameters
0-9 (available memory locations). \A KEYBOARD ABORT (answer unit only) \A0 Enables keyboard abort. When keyboard
abort is enabled, pressing any key on the
answer unit will abort handshaking (and
thereby prevent a connection from being
made). \A1 Disables keyboard abort. \B BUFFER MODE/SPEED CONVERSION*
1
\B0 Disables speed conversion. \B1 Enables speed conversion \C MNP CLASS (LIMIT)*
1
\C1 Limits operation to MNP class 1. \C2 Limits operation to MNP classes 1 and 2. \C3 Limits operation to MNP classes 1 through 3. \C4 Limits operation to MNP classes 1 through 4. \C5 Limits operation to MNP classes 1 through 5. \D DIALING MESSAGE \D0 Disables ”DIALING” message. \D1 Enables “DIALING” message. \F MNP FLYBACK BUFFER*
1
\F0 Enables flyback buffer. \F1 Disables flyback buffer. \K V.42 BREAK HANDLING*
1
\K0 Selects normal break handling. \K1 Selects destructive/expedited break handling.
Loading...