BKI HG101 Service Manual

TECHNICAL
TRAINING
COURSE
REV. 01/2015
USA
IT | GB
2
TECHNICAL TRAINING COURSE
1.0 OVEN INSTALLATION 4
1.1 POSITIONING 4
1.2 Water connection 4
1.3 Drain connection 5
1.4.1 Electric connection 5
1.4.2 Electric connection 6
1.5 Gas connection (gas ovens only) 6
1.6 Fumes exhaust 7
1.7 Adjust trolley of 20 1/1 and 20 2/1 ovens 8
2.0 OVEN START-UP 8
3.0 ELECTRICAL COMPONENTS IDENTIFICATION 9
3.1 Water electrovalves and injector codication (EU,EV,EL,ES,EA,ESH) 9
3.2 Transformers 10
3.3 Door micro-switch - SP 10
3.4 Resistance Elements contactor - KR 10
3.5 Motor thermal protection 11
3.6 Motor Inverter - power supply relay 11
Page
3.7 Fuses 11
3.8 Automatic security thermostat of the boiler 11
3.9 Cavity security thermostat - F1 12
3.10 Water pressostat - PA (direct steam oven with washing system) 12
3.11 Meteo System probes 12
3.12 EMC lters - PFC, FLC 12
3.13 Air pressostat - P1 (gas ovens) 13
3.14 Gas blower - MB, control board PWM 13
3.15 Burner control - IGN 13
3.16 Gas valve - EVG 13
3.17 Motorized discarging valve - MS 14
3.18 Washing pump - PL 14
3.19 Detergent pump - PD 14
3.20 Flowmeter - HALL 14
3.21 Buttery valve - MV 15
4.0 GAS OVEN - SETUP 15
4.1 Combustion analysys 15
4.2 Gas reference table 18
4.3 Setting ignition probes and detecting ame probe 18
4.4 Gas change procedure 19
4.5.1 Fixing the burner to the exchanger : GASKET SEQUENCE 21
4.5.2 Fixing the burner to the exchanger : NOTES 22
5.0 ELECTRONIC BOARDS and congurations 23
5.1 Conguration of electronic boards serial connections 24
TECHNICAL TRAINING COURSE
3
5.2 I-O Check 26
5.2.1 I-O Check - Probes 26
5.2.2 I-O Check - Digital inputs 27
5.2.3 I-O Check - Digital outputs 28
5.3 HACCP recording (touch board) 29
5.3.1 Cooking log memorisation 29
5.3.2 Print-out example 29
5.3.3 HACCP parameters 29
5.3.4 Download HACCP log ---> USB pen drive 30
5.4 Wash log - download - erase 30
5.5 Upload-download recipes 31
5.5.1 Upload recipes 31
5.5.2 Download recipes 31
5.6 Wash log - download - erase 32
5.7 ALARMS DESCRIPTION 33
5.8 Alarm log - download - erase 34
5.9 System info menu 35
Page
5.10 Inverter alarm signal diagnostic 35
5.11 Technical parameters 36
5.12 Firmware upgrade 37
5.13.1 Upload new parameters 38
5.13.2 Download parameters le from the oven 38
5.13.3 Upload new parameters 39
5.13.4 Download parameters from the oven 40
6.0 MAINTENANCE 41
6.1 Boiler descaling 41
6.2 Cleaning oven cavity 43
6.3 Cleaning panel air lter 44
6.4 Adjustment of the hinges and the closing pivot of the door 44
6.5 Changing door lights and glass cleaning 45
6.6 Washing sprinkler cleaning 45
7.0 SPECIAL MAINTENANCE 46
7.1 Boiler opening and check 46
7.2 Fans replacement
7.3 Door gasket replacement
7.4 Complete door handle replacement
8.0 ELECTRICAL DRAWINGS
9.0 SPARE PARTS EXPLODED VIEW
47
51
52
54
62
4
TECHNICAL TRAINING COURSE
1 INSTALLATION
1.1 POSITIONING
The appliances have been designed for installation in
closed premises, they cannot be used in the open air
and cannot be exposed to rain.
The place of installation of the oven must have a solid, at and horizontal surface able to safely support both
the mass weight of the appliance/support and that of maximum load capacity.
The appliance must be placed in adequately ventilated premises.
The oven must only be installed on a stable support. The appliance must be removed from its
packaging, its integrity checked and arranged in the place of use, being careful not to position it above or against walls, sides, partition walls, kitchen cabinets or covers in ammable material.
We recommend scrupulously complying with the reproof Standard in force.
There must be a minimum distance of 2” on all sides between the oven and the walls or other equipment. We recommend leaving 20” of space between the left
side of the oven and the corresponding room wall, for
easy oven installation and its subsequent maintenance.
All materials used for packaging are compatible with the environment; they must be safely kept and dispo­sed of according to the Standard in force.
The oven must be levelled: to regulate the height of
the adjustable feet act, using as reference a spirit le-
vel. Signicant unevenness or inclinations can negati­vely inuence the functioning of the oven. Slowly remove all protective lm from the appliance external panels, being careful not to leave traces of adhesive. Check that the heat disposal or
inlet slots and openings are not obstructed.
1.2
WATER CONNECTION
The water pressure must be max. 6 bar. Should the wa-
ter pressure from the mains be higher than such value,
install a pressure reducer upstream of the oven. The
minimum water temperature for the correct functioning
of the oven must be higher than 0.5 bar. The oven has a
softened water inlet. Always install a water softener to
bring the hardness of the water at appliance inlet within
the values of between 5 TH and 10 TH. If the oven is
equipped with automatic washing system and the water
hardness is greater then 10 TH it racommanded to use
softened water for the second water inlet. Connect the
TECHNICAL TRAINING COURSE
"Water" duct to the specic cold water mains, and interpose a shut-off cock and lter. Before connecting, let sufcient amount of water ow to clean the duct from any iron residues.
Ensure the shut-off cock is located in a place and in a manner to be easily activated at any momentby the operator.
Attention: in case of water drain pipe fault, it must be replaced with a new one and the old and
faultyone must never be re-used.
5
1.3
1.4.1
The electric system, as prescribed and specied by the Standard in force, must be equipped
Have professionally qualied staff check that the plug cables section is adequate to the power
absorbed by the appliance.
Loosen the screws xing the left side of the oven and extract it. Place the power supply cable inside the cable gland hole in the lower part, on the left of the
oven.Connect the cable to the terminal board following the indications on tab 1.
Lock the cable with the cable gland.
ELECTRIC OVENS GAS OVENS
L1 L2 L3 N L N X
tab 1
DRAIN CONNECTION
The oven is equipped with a water draining device;such device is located at the bottom in the rear part of the appliance and has a tube with a 2” diameter. Connect the tube that protrudes from the draining de­vice .The draining device is a siphon; we recommend connecting the tube on an open funnel.
Check that the internal siphon is full of water and, if not, ll it by introducing water through the drain in the
cooking compartment.
ELECTRIC CONNECTION
with an efcient ground. It is possible to guarantee the
electric safety of the appliance only in the presence of Standard electric system. For direct connection to the mains it is necessary to in­terpose a device between the equipment and the same
mains, dimensioned depending on the load, that ensures
its disconnection and which contacts have an opening
distance enabling the full disconnection, in compliance
with the installation regulations; this device also must be located in a place and in a manner to be easily accessible at any moment by the operator.
Bring the main switch, to which the power supply cable plug will be collected, in position 0 (zero).
The power supply voltage with machine
funcioning,must not be different from the nominal
voltage value of ±10%.
6
TECHNICAL TRAINING COURSE
1.4.2
When a high current ows through a conductor, differences in potential appear between the conductor and nearby metallic surfaces near the appliance. As a result, sparks may be produ-
ced between the appliance and surrounding metal surfaces. These sparks could cause serious
injury, damage, or re.
BKI provides an Equipotential ground terminal for the connection of a bonding conductor after the installation of the appliance per lEC60417-1. This terminal is located on the inside of the Power Entry Supply box near the Earth connection and is marked with this symbol:
For gas ovens, complete gas connection to the appliance before assembling
the oven side again; for electric ovens assemble the oven side.
1.5
The oven is originally calibrated for functioning with the gas type specied during ordering.
The type of gas for which the oven is adjusted is reported on the technical place on the appliance
During testing, ascertain the factory calibrations carried out on the burners are appropriate for the specic installation type, by means of analysis of the gases produced by combustion (CO2
and CO) and check of the thermal capacity.
Specically, with oven functioning at full capacity, the values of the undiluted CO present during draining, must be within 300 ppm (normally a well calibrated pre-mix system does not produce
CO which mean the value should be 0).
If the presence of undiluted CO over such limit is detected, the adjustment of the burners must be checked by a technician authorised by the manufacturer, who will make all due amendments
ELECTRIC CONNECTION
GAS CONNECTION (GAS OVENS ONLY)
to the devices governing combustion and to the relative parameters. The detected data must be recorded and become integrating part of the technical documentation of that appliance.
Installation prescriptions
The oven installation and commissioning operations must be
carried out only by qualied staff according to regulations and
standards in force.
The gas systems, the electric connections and the installation
premises of the appliances must be compliant with regulations and Standards in force. Bear in mind that the air necessary for combustion of the burners is of 2 m3/h per kW of installed power.
In activities open to the public, the Standards for the safety prevention of accidents and re and panic must be complied with.
The connection to the gas supply tting can be carried out using exible metal piping, interposing an approved shut-off cock in an
easily accessible point.
Ensure that the exible metal connection tube to the gas inlet tting does not touch overheated parts of the oven and that it is
not submitted to torsion or extension stresses.
Use securing clips compliant with installation Standards.
TECHNICAL TRAINING COURSE
Checks to be carried out before installation
On the technical plate located on the left side of the oven check that the appliance has been tested for the type of gas available with the user.
Check the data on the technical plate that the pressure reducer capacity is sufcient for powering
the equipment. Avoid interposing section reductions between the reducer and the appliance.
We recommend mounting a gas lter upstream of the pressure regulator to guarantee optimal
oven functioning.
Connect the oven to the gas supply system by means of special 1/2” NPG tube.
After gas connection, check there are no leaks on the joints and ttings. For this purpose, use soapy water or a specic foamy product to detect leaks. It is opportune for the routine maintenance of the gas ovens to be carried out yearly, in compliance with specic Standards, by an authorised technician; during which the fuel gas will
be analysed and the thermal power checked.
7
1.6
a) the extracted volume must be above that of the generated fuel gas (see Standard in force);
b) the material with which the hood lter is made must resist the fuel gas temperature that, at conveyor outlet, can reach 572°F;
FUMES EXHAUST
In compliance with installation Standards, the ovens
must be started in premises suitable for evacuation of the combustion products.
It is possible to connect the ue passage by means of a forced evacuation system, like a hood equipped
with mechanical extractor fan. In this case, the gas
supply to the appliance must be directly controlled by such system and must interrupt should capacity drop below the prescribed values. When the appliance is
installed underneath the extractor hood, check that
the following indications are complied with:
c) the end of the evacuation duct of the appliance must be positioned inside the projection of the hood base perimeter;
d) the re-admission of the gas to the appliance must only be possible manually.
8
TECHNICAL TRAINING COURSE
1.7
A correct adjustment of the coupling between trolley and oven allows to prevent steam or water
leakage, when the trolley is inserted inside the oven with the door closed.
1. The oven must be levelled to allow the edge of the sheet metal seal of the trolley to remain about 3 mm under the glass limit of the oven door.
2. Then screw spacers must be adjusted between the front and the stop of the trolley, at
13 - 15 mm height.
ADJUST TROLLEY OF 20 1/1 AND 20 2/1 OVENS
NO
In this picture the gasket placed under the glass is too compressed and so the front gasket crushes until drawing.
2.0
Before commissioning the oven, scrupulously carry out the necessary checks to ensure the
compliance of the systems and installation of the appliance with the legal Standards and technical and safety indications in the user manual.
The following points must also be satised:
The ambient temperature of the place of installation of the oven must be higher than 4°F.
The cooking compartment must be empty.
All packaging must be fully removed, including the protective lm applied on the oven walls.
The air vents and louvers must be open and not obstructed.
The eventually dismantled oven pieces must be, for installation purposes, re-mounted.
The main electric switch must be closed and the water and gas shut-off cocks upstream of
the appliance must be open.
OVEN START-UP
In this picture the distance between the trolley
and the door glass has been reduced, the gasket
is less compressed and it does not overhang. In this way the front gasket does not deform itself.
YES
TECHNICAL TRAINING COURSE
9
3.0
3.1
ELECTRICAL COMPONENT IDENTIFICATIONS
WATER ELECTRO-VALVES AND INJECTOR CODIFICATION (EU, EV, EL, ES, EA, ESH)
The solenoid valve is the device that supplies water in the pre-established times and methods.
At the electro-valve outlet a injector (nozzle) is normally applied.
STEAMBOX VALVE, NOZZLE:
HUMIDIFIER
BOILER
(VER. ‘H’ ONLY)
WASHING
SYSTEM
ABHE061 BROWN 0,07 ÷ 0,14 L/min RED 0,2 ÷ 0,3 L/min NO WASH. SYS. ABHE062-101 RED 0,2 ÷ 0,3 L/min RED 0,2 ÷ 0,3 L/min NO WASH. SYS.
ABTE061-062-101 RED 0,2 ÷ 0,3 L/min
ABTE102-ABHE102
YELLOW 0,32 ÷ 0,42 L/min
ABTE201-ABHE201 2 X RED 0,2 ÷ 0,3 L/min ABTE202-ABHE202
2 X YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min
ABHE061R BROWN 0,07 ÷ 0,14 L/min RED 0,2 ÷ 0,3 L/min ABHE062R-ABHE101R
ABTE061R-ABTE061R-062R-101R
ABHE102R
RED 0,2 ÷ 0,3 L/min RED 0,2 ÷ 0,3 L/min RED 0,2 ÷ 0,3 L/min
YELLOW 0,32 ÷ 0,42 L/min
ABTE201R-ABHE201R 2 X RED 0,2 ÷ 0,3 L/min
ABTE202R-ABHE202R
2 X YELLOW 0,32 ÷ 0,42 L/min
NO BOILER YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min
NO WASH. SYS. NO WASH. SYS. NO WASH. SYS. NO WASH. SYS.
BLU 4,5 ÷ 6 L/min BLU 4,5 ÷ 6 L/min
NO BOILER BLU 4,5 ÷ 6 L/min YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min
YELLOW 0,32 ÷ 0,42 L/min
BLU 4,5 ÷ 6 L/min BLU 4,5 ÷ 6 L/min + 2
NERO 1,9 ÷ 3,5 L/min
BLU 4,5 ÷ 6 L/min + 2
NERO 1,9 ÷ 3,5 L/min
ABHG061-062-101 RED 0,2 ÷ 0,3 L/min RED 0,2 ÷ 0,3 L/min NO WASH. SYS. ABHG102
YELLOW 0,32 ÷ 0,42 L/min
ABHG201 2 X RED 0,2 ÷ 0,3 L/min ABHG202
2 X YELLOW 0,32 ÷ 0,42 L/min
ABHG061R-062R-101R RED 0,2 ÷ 0,3 L/min RED 0,2 ÷ 0,3 L/min ABHG102R
YELLOW 0,32 ÷ 0,42 L/min
ABHG201R 2 X RED 0,2 ÷ 0,3 L/min
ABHG202R
2 X YELLOW 0,32 ÷ 0,42 L/min
YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min
YELLOW 0,32 ÷ 0,42 L/min YELLOW 0,32 ÷ 0,42 L/min
YELLOW 0,32 ÷ 0,42 L/min
NO WASH. SYS. NO WASH. SYS. NO WASH. SYS.
BLU 4,5 ÷ 6 L/min BLU 4,5 ÷ 6 L/min BLU 4,5 ÷ 6 L/min + 2
NERO 1,9 ÷ 3,5 L/min
BLU 4,5 ÷ 6 L/min + 2
NERO 1,9 ÷ 3,5 L/min
10
TECHNICAL TRAINING COURSE
3.2
TRANSFORMERS
TR1 – Electronic board transformer (for main card and power cards): power 17 VA, PRY 230 Volts - SEC 2 x 12Volt (12VA + 5VA)
TR2-TR3 – PWM card and fan blower transformer: power 60 VA, PRY 230 Volts - SEC 24Volt.
TRAL - Halogen light transformer: power 60 VA , PRY 230 Volts - SEC 12 Volt
TRAF (ELE ovens) -
TRAF (GAS ovens) -
TR2
Main power supply transformer: power 250 VA , PRY 208 Volts - SEC 230 Volt
Main power supply transformer: power 1500 VA , PRY 120 Volts - SEC 230 Volt
3.3
3.4
TRAF
DOOR MICRO-SWITCH - SP
The door micro-switch is a magnetic type. The magnet is applied
inside the door. The sensor is xed inside the main control panel.
RESISTANCE ELEMENTS CONTACTOR - KR
KR 1/3 = 1 elements of the resistance KR 2/3 = 2 elements of the resistance
FULL POWER = KR 1/3 + KR 2/3
or
KR 1/2 = 1/2 elements of the resistance KR 2/2 = all elements of the resistance
FULL POWER = KR 1/2 + KR 2/2
TECHNICAL TRAINING COURSE
11
3.5
3.6
The Inverter CARD INV control the functionament of the oven motor/s. The Relay K0 switch on/off the main power supply of the Inverter.
MOTOR THERMAL PROTECTION
The white wires are connected to a temperature sensor inside the motor (clikson)
MOTOR INVERTER - POWER SUPPLY RELAY - FUSE
FU3/FU4): Inverter power supply
protection->T10A (slow blow)
3.7
FU0 : Power supply transformer protection
TRAF 208/230 250VA -> T2A (slow blow) TRAF 120/230 1500VA -> T15A (slow blow)
FU1 or FU2: gas burner control protection ->F2A (fast) FU5 : Main board transformer protection (TR1)->T200mA (slow blow) FU6 : Light transformer protection (TRAL)->T315mA (slow blow) FU7 : Pwm board transformer protection (TR2)->T315mA (slow blow)
3.8
FUSES
AUTOMATIC SECURITY THERMOSTAT OF THE BOILER
The automatic security thermostat prevent functioning of the boiler without water. It reset itself.
1
BOILER ELEMENTS PHASE CONNECTION
P(L)
ELECTRONIC BOARD RELAY
12
TECHNICAL TRAINING COURSE
3.9
3.10
CAVITY SECURITY THERMOSTAT - F1
If the temperature inside the cooking compartment
reaches 662°F, the safety thermostat interrupts supply
to the oven’s heating elements.
To reset it push the red (or brown) button.
WATER PRESSOSTAT - PA (DIRECT STEAM OVEN WITH WASHING SYSTEM)
CONTROL
LEVEL BOARD
Connect ‘C’ plug to the ground cable and ‘NO’ plug to main board control level.
3.11
3.12
GROUND
METEO SYSTEM PROBES
ALARM PROBE 4: UPPER PROBE
FOR METEO SYSTEM
ALARM PROBE 5: LOWER PROBE
FOR METEO SYSTEM
EMC FILTERS - PFC, FLC
PFC = Inductance
for Harmonic noise of
Inverter
FLC = Line lter
TECHNICAL TRAINING COURSE
13
3.13
The air pressostat control the correct chimney evacuation
AIR PRESSOSTAT - P1 (gas ovens)
AIR
3.14
GAS BLOWER - MB / CONTROL BOARD - PWM
NC/2 : disconnected
NO/2 : connected
C/1 : connected
The gas blower is controlled by PWM card. The power supply of PWM is 24Volt - AC.
3.15
3.16
BURNER CONTROL - IGN
This electronic card switch on the burner (make the
spark between two probes) and also detect the ame
with a special probe.
GAS VALVE - EVG
Coil functionality test:
To verify the coils
600Ω (3-4) 3,7kΩ (3-1)
functionality must be
measured resistance
values. Please see
reference values
(cold coil)
14
TECHNICAL TRAINING COURSE
3.17
3.18
MOTORIZED DISCARGING VALVE - MS
Automatic operations:
Cooking mode : valve open Automatic washing mode : valve close
WASHING PUMP - PL
The washing pump working when the water discarge is
closed and a ll of water is charged in the cavity. It’s
termically protected and the reset is automatic when the temperature of the pump cool down.
3.19
3.20
DETERGENT PUMP - PD
Detergent pump for the automatic washing system.
FLOWMETER WASHING SYSTEM
The owmeter control the quantity of water is load
during a washing cycle.
TECHNICAL TRAINING COURSE
Rigenerazione
Cottura manuale Rigenerazione
Service
15
3.21
BUTTERFLY VALVE - MV
The buttery valve open or
close the air inlet to regulate the humidity in the cavity. It’s normally closed when the oven is switch on in STOP mode.
To correct CLOSE position is
showed in the picture.
4.0
GAS OVEN SETUP
The oven is originally calibrated for functioning with the gas type specied during ordering.
The type of gas for which the oven is adjusted is reported on the technical place on the appliance.
During testing, ascertain the factory calibrations carried out on the burners are appropriate for the specic installation type, by means of analysis of the gases produced by combustion (CO2
and CO) and check of the thermal capacity.
The detected data must be recorded and become integrating part of the technical documentation of that appliance.
4.1
STEP 1 : SELECT
Service
Service functions
Cottura manuale
Manual
Cooking
Rigenerazione
Regeneration
COMBUSTION ANALISYS
STEP 2 : SELECT
” TO OPEN:
Recipe
Ricette
Service
Advanced functions
INSERT PASSWORD ‘156’
Service functions

Wash Program
Descaling
Password
Date and Time
156
Parameters
System info
Language
Advanced functions
” AND
STEP 3 :
PRESS KNOB
TO CONFIRM
STEP 4 :
SELECT
Gas test
Service functions

Wash Program
Descaling
Test service
Date and Time
Gas test
Parameters
I/O Check
System info
Log & USB
Language
Advanced functions
16
1. The gas test must be carried out with the door open.
TECHNICAL TRAINING COURSE
Gas test
Testing stage: Please open the door
Burner 1
ON
TESTING PHASE
ON/OFF: ENABLE OR
DISABLE BURNER 1
OVENS 20 GN 1/1 e 2/1 ONLY
20 RACK CAP. OVENS
ONLY
PRESS TO RETURN TO THE PREVIOUS “STATE”
2. Starting gas test procedure:
After opening the oven door the testing procedure can be started by pressing the “NEXT”key.
Gas test
Burner 2
OFF
Back Next
ON/OFF: ENABLE OR DISABLE BURNER 2
OVENS 20 GN 1/1 e 2/1 ONLY
FORWARD/START:
START THE TEST OR GOES TO THE NEXT PHASE
Testing stage: Ready to start
Burner 1
Burner 2
ON
OFF
Back Next
GAS TEST START KEY
TECHNICAL TRAINING COURSE
3. Adjustment of burners to minimum and maximum power:
17
Gas test
Testing stage: Firing
Burner 1
Burner 2
ON
OFF
Back Next
Gas test
Testing stage: Maximum speed
Burner 1
ON
Gas test
STATE: BURNER IGNITION
STATE: BURNER/S AT MAXIMUM POWER
Testing stage: Minimum speed
Burner 1
Burner 2
ON
OFF
Back Next
STATE: BURNER/S AT MINIMUM POWER
Burner 2
OFF
PRESS ON/OFF TO SWITCH ON OR OFF THE CORRE­SPONDING BURNER (1 OR 2)
Back Next
PRESS BACK NEXT TO MOVE
FROM MINIMUM TO MAXIMUM
POWER AND VICE-VERSA
To end the GAS test procedure press NEXT until exiting the main menu screen
18
TECHNICAL TRAINING COURSE
4.2
GAS REFERENCE TABLE
ADJUSTEMENT COMBUSTION VALUES #
OVEN
MODEL
6 GN
1/1
6 GN
2/1
10 GN
1/1
10 GN
2/1
TYPE OF GAS
TYPE OF
GAS
NATURAL G20 43 44 8 12 9,5 % 9,2 %
LPG
NATURAL G20 43 44
LPG
NATURAL G20 44 45 13 19 9,8% 9,4%
LPG
NATURAL G20 44
LPG
TO MAKE
REFERENCE
FOR THERMAL
CAPACIT
G30 G31
G30 G31
G30 G31
G30 G31
NOZZLE
1/10 mm
35 34 - 36 8,5 12
35 34 - 36
35 34 - 36 13,5 19
35
ALTERNA-
TIVE
NOZZLES
45 22 27
34 - 36 22 27
POWER
MAX
16,5 20 9,6 % 9,6 %
16,5 20
POWER
MAX
REFERENCE
11%-11,8%
G31 - G30
11,2%-11,5%
G31 - G30
11,5%-11,8%
G31 - G30
11,4%-11,7%
G31 - G30
CO2
MIN
9,8 10,2
CO2
REFERENCE
MAX
10,7 %-11,3%
G31 - G30
11,2%-11,5%
G31 - G30
10,9%-11,5%
G31 - G30
11,6%-11,9%
G30 - G31
B U R N E R S
1
1
1
1
4.3
DETECTING
FLAME PROBE
SETTING IGNITION PROBES AND DETECTING FLAME PROBE
IGNITION
PROBES
5mm
5mm
3,5mm
TECHNICAL TRAINING COURSE
Rigenerazione
Cottura manuale Rigenerazione
Service
19
4.4
GAS CHANGE PROCEDURE
1. Replace nozzle (injector) on gas valve
2. Insert the USB drive in the oven USB port (the PARAMETERS
FILE loaded is specic for each oven model and gas
setting: FILE “PARXXX.CSV).
3.1.a UPLOAD GAS PARAMETERS
STEP 1 : SELECT
Service
” TO OPEN:
Service functions
STEP 2 : SELECT
Advanced functions
INSERT PASSWORD ‘114
Service functions
Manual

ttura manuale
Ricette
Cooking
Recipe
Service
Wash Program
Descaling
Date and Time
Password
Parameters
114
System info
Language
Advanced functions
Ver 250 : OLD BOARD
STEP 3 :
” AND
PRESS KNOB
TO CONFIRM
A pop-up stating that
the transfer is complete
appears
Log & USB
Upload recipes
Download recipes
USB UPDATE
Download HACCP log
Download parameters
Upload parameters
OK
Firmware upgrade
OK!
20
Rigenerazione
Cottura manuale Rigenerazione
Service
Rigenerazione
Cottura manuale Rigenerazione
Service
TECHNICAL TRAINING COURSE
3.1.b UPLOAD GAS PARAMETERS
STEP 1 : SELECT
Service
” TO OPEN:
STEP 4 :
SELECT
Log & USB
Service functions
Cottura manuale
Manual
Cooking
Rigenerazione
Regeneration
Recipe
Service
Ricette
STEP 5 :
SELECT
Upload parameters
Ver 344 : NEW BOARD
STEP 2 : SELECT
Advanced functions
INSERT PASSWORD ‘156’
” AND
Service functions

Wash Program
Descaling
Password
Date and Time
156
Parameters
System info
Language
Advanced functions
A pop-up stating that
the transfer is complete
appears
STEP 3 :
PRESS KNOB
TO CONFIRM
ERROR
pop-up appears
if no le or wrong le
Service functions

Wash Program
Descaling
Test service
Date and Time
Gas test
Parameters
I/O Check
System info
Log & USB
Language
Advanced functions
Log & USB
Upload recipes
Download recipes
Download HACCP log
Download parameters
Upload parameters
Firmware upgrade
4.1 ACTIVATE GAS TEST PROCEDURE
STEP 1 : SELECT
Service
” TO OPEN:
Service functions
STEP 2 : SELECT
Advanced functions
INSERT PASSWORD ‘156’
Service functions
Log & USB
Upload recipes
Download recipes
USB UPDATE
Download HACCP log
Download parameters
Upload parameters
OK
Firmware upgrade
” AND
OK!
STEP 3 :
PRESS KNOB
TO CONFIRM
Log & USB
Upload recipes
Download recipes
ERROR!
Download HACCP log
Download parameters
Upload parameters
OK
Firmware upgrade
STEP 4 :
SELECT
Gas test
Service functions
Cottura manuale
Manual
Cooking
Rigenerazione
Regeneration
Recipe
Service
Ricette

Wash Program
Descaling
Password
Date and Time
156
Parameters
System info
Language
Advanced functions

Wash Program
Descaling
Test service
Date and Time
Gas test
Parameters
I/O Check
System info
Log & USB
Language
Advanced functions
TECHNICAL TRAINING COURSE
5. Check the combustion and, if necessary, change the nozzle.
21
4.5.1
FIXING THE BURNER TO THE EXCHANGER: GASKET SEQUENCE
EXCHANGER
GRAPHITE GASKET
OVEN CHAMBER
GRAPHITE GASKET
22
TECHNICAL TRAINING COURSE
4.5.2
FIXING THE BURNER TO THE EXCHANGER: NOTES
SPECIAL GREASE
SELF BLOCKING NUT M6
WASHER
Loading...
+ 50 hidden pages