The following are general safety precautions that are not necessarily
related to any specific part or procedure, and do not necessarily appear
elsewhere in this publication. These precautions must be thoroughly
understood and apply to all phases of operation and maintenance.
WARNING
Keep Away From Live Circuits
Operating Personnel must at all times observe general safety
precautions. Do not replace components or make adjustments to the
inside of the test equipment with the high voltage supply turned on.
To avoid casualties, always remove power.
WARNING
Shock Hazard
Do not attempt to remove the RF transmission line while RF power
is present.
WARNING
Do Not Service Or Adjust Alone
Under no circumstances should any person reach into an enclosure
for the purpose of service or adjustment of equipment except in the
presence of someone who is capable of rendering aid.
WARNING
Safety Earth Ground
An uniterruptible earth safety ground must be supplied from the
main power source to test instruments. Grounding one conductor of
a two conductor power cable is not sufficient protection. Serious
injury or death can occur if this grounding is not properly supplied.
WARNING
Resuscitation
Personnel working with or near high voltages should be familiar
with modern methods of resuscitation.
WARNING
Remove Power
Observe general safety precautions. Do not open the instrument
with the power on.
iii
Bird Technologies
Safety Symbols
WARNING
Warning notes call attention to a procedure, which if not correctly
performed, could result in personal injury.
CAUTION
Caution notes call attention to a procedure, which if not correctly
performed, could result in damage to the instrument.
Note: Calls attention to supplemental information.
Warning Statements
The following safety warnings appear in the text where there is danger to operating and maintenance personnel, and are repeated here
for emphasis.
WARNING
Leaking RF energy is a potential health hazard. Never attempt to
connect or disconnect equipment from the transmission line while RF
power is being applied. Severe burns, electrical shock, or death can occur.
See page 7.
WARNING
Do not touch the center conductor of the power monitor ports while
RF power is being applied.
See page 8.
WARNING
Disconnect the unit from the RF power source and the AC line
before any disassembly. The potential for electrical shock exists.
See page 11 and 21.
WARNING
Shock hazard. Remove AC power before attempting to service the
equipment.
See page 22.
iv
Caution Statements
The following equipment cautions appear in the text and are repeated
here for emphasis.
CAUTION
The input voltage must be clean and stable. Be sure that the input
voltage does not surge and does not contain spikes. Failure to
comply may result in permanent damage to the instrument.
See page 8.
CAUTION
The maximum input voltage differential is 72 V. Do not apply an
input voltage differential greater than 72 volts. Failure to comply
may result in permanent damage to the instrument.
See page 8.
CAUTION
The +15V supply should only be used to power the ACM Panel.
Do not connect anything else to the power supply.
See page 11.
CAUTION
Do not use harsh or abrasive detergents for cleaning.
See page 21.
CAUTION
The +15V supply should only be used to power the ACM Panel.
Do not connect anything else to the power supply.
See page 22.
v
Bird Technologies
Safety Statements
USAGE
ANY USE OF THIS INSTRUMENT IN A MANNER NOT
SPECIFIED BY THE MANUFACTURER MAY IMPAIR THE
INSTRUMENT’S SAFETY PROTECTION.
USO
EL USO DE ESTE INSTRUMENTO DE MANERA NO
ESPECIFICADA POR EL FABRICANTE, PUEDE ANULAR LA
PROTECCIÓN DE SEGURIDAD DEL INSTRUMENTO.
BENUTZUNG
WIRD DAS GERÄT AUF ANDERE WEISE VERWENDET ALS VOM
HERSTELLER BESCHRIEBEN, KANN DIE GERÄTESICHERHEIT
BEEINTRÄCHTIGT WERDEN.
UTILISATION
TOUTE UTILISATION DE CET INSTRUMENT QUI N’EST PAS
EXPLICITEMENT PRÉVUE PAR LE FABRICANT PEUT
ENDOMMAGER LE DISPOSITIF DE PROTECTION DE
L’INSTRUMENT.
IMPIEGO
QUALORA QUESTO STRUMENTO VENISSE UTILIZZATO IN
MODO DIVERSO DA COME SPECIFICATO DAL PRODUTTORE
LA PROZIONE DI SICUREZZA POTREBBE VENIRNE
COMPROMESSA.
vi
SERVICE
SERVICING INSTRUCTIONS ARE FOR USE BY SERVICE TRAINED PERSONNEL ONLY. TO AVOID DANGEROUS
ELECTRIC SHOCK, DO NOT PERFORM ANY SERVICING
UNLESS QUALIFIED TO DO SO.
SERVICIO
LAS INSTRUCCIONES DE SERVICIO SON PARA USO
EXCLUSIVO DEL PERSONAL DE SERVICIO CAPACITADO. PARA
EVITAR EL PELIGRO DE DESCARGAS ELÉCTRICAS, NO
REALICE NINGÚN SERVICIO A MENOS QUE ESTÉ
CAPACITADO PARA HACERIO.
WARTUNG
ANWEISUNGEN FÜR DIE WARTUNG DES GERÄTES GELTEN
NUR FÜR GESCHULTES FACHPERSONAL.
ZUR VERMEIDUNG GEFÄHRLICHE, ELEKTRISCHE SCHOCKS,
SIND WARTUNGSARBEITEN AUSSCHLIEßLICH VON
QUALIFIZIERTEM SERVICEPERSONAL DURCHZUFÜHREN.
ENTRENTIEN
L’EMPLOI DES INSTRUCTIONS D’ENTRETIEN DOIT ÊTRE
RÉSERVÉ AU PERSONNEL FORMÉ AUX OPÉRATIONS
D’ENTRETIEN. POUR PRÉVENIR UN CHOC ÉLECTRIQUE
DANGEREUX, NE PAS EFFECTUER D’ENTRETIEN SI L’ON N’A
PAS ÉTÉ QUALIFIÉ POUR CE FAIRE.
ASSISTENZA TECNICA
LE ISTRUZIONI RELATIVE ALL’ASSISTENZA SONO PREVISTE
ESCLUSIVAMENTE PER IL PERSONALE OPPORTUNAMENTE
ADDESTRATO. PER EVITARE PERICOLOSE SCOSSE
ELETTRICHE NON EFFETTUARRE ALCUNA RIPARAZIONE A
MENO CHE QUALIFICATI A FARLA.
vii
Bird Technologies
ACM
– M – DM NF T L
Frequency
Range
Base
Model
Input Conn.
and Gender
Output Conn.
and Gender
Monitor
Port
Conn.
Power
Supply
Voltage
470 – 960 MHz ACM with male 7/16 input, female N output,
female TNC monitor ports, requiring a low voltage power supply
About This Manual
Sample Model ACM–M–DMNFTL
Base
Model
ACML0108 – 138NM Male NN Female NL+11 to +26 Vdc
ACM
500
Frequency Range
(MHz)
L1136 – 225NFFemale N T Female TNC H ± (36 to 72) Vdc
L2225 – 520DM Male 7/16
M470 – 960DFFemale
H960 – 2400
RF
Connectors
DIN
7/16 DIN
Monitor Port
Connectors
B Female BNC
Power Supply
Vol tag e
Note: Exception: Model ACM-L2-DFDFTL-12SP and
ACM-L2-DFDFTH-48SP has no other variations.
Note: Exception: Models in ACM500 series do not support
frequency range L0 and H and any of its variations.
Changes to this Manual
We have made every effort to ensure this manual is accurate. If you
discover any errors, or if you have suggestions for improving this man
ual, please send your comments to our Solon, Ohio factory. This manual may be periodically updated. When inquiring about updates to
this manual refer to the part number and revision on the title page.
-
viii
Chapter Layout
Introduction —
Theory of Operation — Describes the ACM’s alarm options.
Installation — Provides instructions for installing the ACM at a site,
as well as detailed information on the cable connections.
Operating Instructions — Explains computer commands for control-
ling the ACM and describes operation of the optional PCTool software.
Maintenance — Lists routine maintenance tasks for the ACM, as well
as troubleshooting information for common problems. Specifications
and parts lists are also included.
Designed for 50 ohm coaxial transmission lines, the Bird Antenna &
Cable Monitor is the solution for monitoring transmission antenna
systems. Service providers and end users can rely on it to keep their
critical sites up and running. Designed to detect antenna and cable
faults that transmitter-internal VSWR monitors may not detect, it
also provides accurate in-line power measurement functionality.
Features
z Measures forward and reflected power as well as VSWR and
Return Loss.
z Measures true average power of pulses with high peak-to-
average ratios - works with any modulation!
z Worldwide systems include Tetra, Cellular, and PCS with dig-
ital or analog modulation. Other applications include 3G,
AMPS, Broadcast, CDMA, CDMA 2000, DCS, EDGE, Government, GPRS, GSM, iDEN, Industrial, NPSPAC, Microwave,
Military, Paging, Public Safety, Rail, SMR, TDMA, Tetrapol,
Trunking, UHF, Utilities, VHF, W-CDMA, and WLL
z When monitoring transmitter output power, alarms available
for low or high power.
z Accurately monitors antenna and cable system VSWR. Alarm
triggered if antenna or cable fails.
z Integral coupler measures small changes in VSWR through
high feeder and interface losses. High directivity maximizes
measurement accuracy.
z Sampling ports allow signal measurements without requiring
system downtime.
z Excellent passive intermod allows the unit to be inserted into
multichannel systems with a single Tx/Rx antenna with no
desensing or degradation of receiver performance.
z Can be rack mounted at the output of transmitter combiner or
linear power amplifier.
z Local or remote setup and operation via RS-232 port and
PCTool software. (For other telemetry options, such as TCP/
IP, contact the factory)
Items Supplied
z ACM Unit
z Instruction Manual
1
Bird Technologies
Optional Accessories
Refer to "Replacement Parts" on page 26 for part numbers of accessories.
Digital Display - Displays the ACM status and provides a low voltage
(+15 Vdc) power supply. Includes a power cord and 50 foot, 9 pin and
15 pin cables.
PCTool Software - PC software for data display, alarm monitoring,
and setting alarm options
Rack Mount - Allows two units to be mounted in a standard (2U)
panel mount. Available with and without a low voltage (+15 Vdc)
power supply.
DB-15 Power/Alarm Cables - Connects the Antenna Monitor to a
power supply and to external controllers. 50 feet long with male/
female connectors. Refer to
for pin layout.
DB-15 Interface Connector - Allows easy custom data cable connections to the ACM.
9 pin RS-232 PC Interface Cables - Connects the Antenna Monitor to
a PC. Available in either 10 or 50 foot lengths, with male/female con
nectors. Refer to Figure 7 on page 11 for pin layout.
Panel Mount - The Panel Mount Kit allows up to two ACMs to be
installed in a standard (2U) panel mount. They are secured with locator
holes and a velcro strap. Power is provided through 15-pin parallel
cables, connected to a terminal strip at the factory. The ACM-RACKU
includes a +15V power supply, while the ACM-RACK requires a 48V
customer-provided power supply.
lights important components.
Figure 3 on page 9and Figure 5 on page 10
-
Figure 2 lists dimensions and high-
Note: Exception: Model ACM-L2-DFDFTL-12SP requires
a 12V customer-provided power supply in place of the 48V
power supply.
2
Component Description
1”
(27 mm)
67
8
910
4
321
5
0.8”
(20 mm)
4.2”
(107 mm)
7.0”
(178 mm)
4.75”
(121 mm)
Figure 1 Antenna & Cable Monitor Outline
Introduction
1RF InputConnect to the amplifier or combiner
2Forward Monitor PortSamples the forward travelling wave
3Reflected Monitor Port Samples the reflected wave
4RF OutputConnect to the antenna or feeder
5Mounting HolesFour holes, two top and two bottom, for positioning
the ACM on a rack. Supplied with 4-40 screws, will
fit M3 holes.
6Reset SwitchPress to reset the alarm. If an alarm trigger is still
present, the alarm will reactivate
7Operation/Test LEDGreen LED that lights when the unit is powered
8Alarm LEDRed LED that lights when an alarm is triggered
9RS-232 Serial Port9 pin female connector. Interface to a PC using a
10 Power/Alarm Parallel
Port
male 9 pin RS-232 cable
15 pin female connector (15 pin male connector on
models ACM-L2-DFDFTL-12SP and ACM-L2-
DFDFTH-48SP only). Connects to the power
supply using a male 15 pin cable. Also used for
remote operation.
3
Bird Technologies
3.00”
(77 mm)
19.0”(483 mm)
3.47”
(82 mm)
INPUT
OUTPUT
NO
NC
COMMON
ALARM
RESET
EARTH GND
EARTH GND
+15V
VELCRO
MOUNTING
STRAPS
LOCATOR
HOLES (4)
POWER/ALARM
WIRING
POWER/ALARM
CONNECTOR
15 VOLT DC
POWER SUPPLY
7.36”
(187 mm)
9.24”
(235 mm)
6.22”
(158 mm)
Figure 2 Panel Mount Outline
4
Chapter 2Theory of Operation
Alarm Response
When an alarm is triggered, the Bird Antenna & Cable Monitor turns
on the alarm LED and activates a Form C dry contact relay.
The alarm relay defaults to fail/safe. That is, the alarm activates when
the relay is not energized or power is lost. However, the PCTool soft
ware can configure the alarm to either energize or de-energize in
response to an alarm.
Alarm Reset
z Alarms can be reset locally with the reset switch.
z Alarms are reset when the reset pin on the Power/Alarm port
is activated by a TTL compatible logic low signal (0 to 0.8 Vdc).
z The PCTool can reset the unit through the RS-232 port by
sending a “Reset Alarm” command.
Alarm Latching
The alarm defaults to latching operation. In this mode, the alarm will
stay active until reset. In non-latching mode, the alarm will reset auto
matically about forty seconds after the trigger condition is corrected.
-
-
VSWR Alarm
The ACM continuously monitors forward and reflected power. From
the power measurements, the VSWR is calculated and compared to
the allowed maximum (default of 1.5 to 1). Based on the results of the
comparison, possible actions include:
z No alarm is activated if the VSWR is less than the maximum,
or if the VSWR alarm is disabled.
z If the VSWR is equal to or slightly greater than the maximum,
additional measurements are accumulated to determine a
trend. If reverse power is increasing, an alarm is triggered. If
the reverse power is stable, measurements continue until a
trend is established. An alarm will be triggered if the VSWR
exceeds the maximum for more than thirty seconds.
z If the VSWR is much greater than the maximum then an
alarm condition is triggered immediately.
5
Bird Technologies
Alarm on Zero Power
When the forward power is very small (< 2.5% of full scale), the measured VSWR becomes large due to the noise floor of the sensor. Under
these conditions, the VSWR level is meaningless. When the zero power
alarm is disabled, the VSWR will not be monitored at these low powers.
High Power Alarm
When the high power alarm is enabled, the forward power is continuously monitored. The alarm trigger is a percentage of the Monitor’s
full scale power, from 0 – 125%. If the forward power is greater than
the trigger level, an alarm is triggered.
Low Power Alarm
When the low power alarm is enabled, the forward power is continuously monitored. The alarm trigger is a percentage of the Monitor’s
full scale power, from 0 – 125%. If the forward power is less than the
trigger level, an alarm is triggered.
Push-to-Talk
The low power alarm and the VSWR alarm can falsely trigger when
the transmitter is not keyed. The Push-to-Talk feature uses a logic
input from the transmitter to control when alarm monitoring is active.
In order to prevent false alarms while monitoring for low power and
high VSWR, the Push-to-Talk feature must be enabled.
6
Chapter 3Installation
This chapter provides information for preparing the Bird Antenna &
Cable Monitor for use.
Unpacking and Inspection
1. Carefully inspect the shipping container for signs of damage.
Note: If damage is noticed, do not unpack the unit. Immedi-
ately notify the shipping carrier and Bird Electronic Corporation.
2. If the shipping container is not damaged, unpack the unit.
Note: Save the packing material in case the unit needs to
be shipped again.
3. Inspect all of the components for visible signs of damage.
Note: Immediately notify the shipping carrier and Bird
Electronic Corporation of equipment damage or missing parts.
The Bird ACM is shipped complete and ready for use upon receipt.
After unpacking and inspecting the unit, it is ready to be installed.
WARNING
Leaking RF energy is a potential health hazard. Never
attempt to connect or disconnect equipment from the
transmission line while RF power is being applied.
Severe burns, electrical shock, or death can occur.
Mounting
Mount the ACM in the feeder line between the combiner and the
antenna. Make sure that the alarm LED and reset button are
accessible, and that the connecting cables have proper clearance.
Cable Connections
When connecting the Bird ACM to RF power, use 50 ohm coaxial cable
suitable for the frequency and power level of operation. The cable
connector should mate with the connector on the unit.
7
Bird Technologies
Connect the amplifier or combiner to the Monitor’s input. Connect the
antenna or feeder to the output.
WARNING
Do not touch the center conductor of the power
monitor ports while RF power is being applied.
To monitor the RF waveform, connect the forward and reflected power
monitor ports to an appropriate power sensor or meter.
Note: If a power monitor port is not being used, terminate
it with a 50Ω load.
Power/Alarm Connector
Connect the external power supply here. Pin numbers and descriptions
are given in
Figure 3 and Figure 5.
CAUTION
The input voltage must be clean and stable. Be sure
that the input voltage does not surge and does not
contain spikes. Failure to comply may result in
permanent damage to the instrument.
Low voltage models (ACM-x-xxxxxL and ACM500-x-xxxxxL) require
+11 to +26 Vdc power @ 0.1 A (nominal +15 Vdc).
Note: Exception: Model ACM-L2-DFDFTL-12SP is a low
voltage model but it requires a +9 to +18 Vdc (12 V nominal) @
0.13 mA. Either terminal (10 or 11) may be connected to DC
input ground, as dictated by the power supply requirements.
CAUTION
The maximum input voltage differential is 72 V. Do
not apply an input voltage differential greater than
72 volts. Failure to comply may result in
permanent damage to the instrument.
High voltage models (ACM-x-xxxxxH and ACM500-x-xxxxxH) require
36 to 72 Vdc (48 V nominal) @ 0.1 A. Either terminal (10 or 11) may be
connected to DC input ground, as dictated by the power supply
requirements.
8
Figure 3 DB-15 Power/Alarm Connector, Female
1
15
FEMALE
8
9
- 48 V Connection
+ 48 V Connection- 11 V to + 26 V Connection
11
1115
13
Gnd
Gnd
Gnd
- 48 V
+ 48 V
+ 11 V to + 26 V
10
10
14
12
1
15
8
9
1
15
8
9
189
PinDescription
1Relay, normally closed contact
(closed when relay is not energized)
(open when there is no alarm)
2Relay, common contact
3TTL compatible alarm, 0 to ≥ 4.0 Vdc with a 10k load
when the alarm is active
4PTT input, +5V to +24V to activate,
0V or open to deactivate
5TTL compatible reset, 0 to +0.8 Vdc resets alarm
6-8Internal connection
9Relay, normally open contact
(open when relay is not energized)
(closed when there is no alarm)
Installation
10DC input, 36 to 72 Vdc, + terminal
(ACM-x-xxxxxH models only). See Fig. 4.
11DC input, 36 to 72 Vdc, – terminal
(ACM-x-xxxxxH models only). See Fig. 4.
12-13DC input, +11 to +26 Vdc (ACM-x-xxxxxL models only).
Pins 12 and 13 are internally connected (see Fig. 4).
14-15DC input and signal ground. Pins 14 and 15 are internally
connected (see Fig. 4).
Figure 4 Power/Alarm Connector Wiring, Female
9
Bird Technologies
1
15
8
9
MALE (model ACM-L2-DFDFTL-12SP only)
- 12 V Connection
+ 12 V Connection
+ 12 V
- 12 V
Gnd
Gnd
13
13
14
14
1
15
8
9
1
15
8
9
DETAIL “A”
DETAIL “B”
Figure 5 DB-15 Power/Alarm Connector, Male
PinDescription
1-3Internal connection
4TTL compatible reset, 0 to +0.8 Vdc resets alarm
5PTT input, +5V to +24V to activate,
0V or open to deactivate
6TTL compatible alarm, 0 to ≥ 4.0 Vdc with a 10k load
when the alarm is active
7Relay, common contact
8Relay, normally closed contact (closed when relay is
not energized)
(open when there is no alarm)
9-10DC input and signal ground
11-12No connection (model ACM-L2-DFDFTL-12SP only)
13DC input, 9 to 18 Vdc, - terminal
(model ACM-L2-DFDFTL-12SP only).
See DETAIL “A” in Fig. 6.
DC input, 36 to 72 Vdc, - terminal
(model ACM-L2-DFDFTL-48SP only).
See DETAIL “B” in Fig. 6.
14DC input, 9 to 18 Vdc, + terminal
(model ACM-L2-DFDFTL-12SP only).
See DETAIL “A” in Fig. 6.
DC input, 36 to 72 Vdc, + terminal
(model ACM-L2-DFDFTL-48SP only).
See DETAIL “B” in Fig. 6.
15Relay, normally open contact (open when relay is not
energized)
(closed when there is no alarm)
Figure 6 Power/Alarm Connector Wiring, Male
10
Installation
RS-232 Connector
The RS-232 connector carries ASCII data between the Antenna Monitor and a display panel or PC. If a PC is connected to the display front
panel, it is also routed to this connector. Pin numbers and connection
descriptions are given in
Figure 7 DB-9 RS-232 Connector
PinDescription
1Carrier Detect, always > +5 Vdc
2Transmit Output, RS-232 data signal
3Receive Input, RS-232 data signal
4Data Set Ready Input, connected but not used
5Data Signal Ground
Figure 7.
6Data Terminal Ready Output, connected but not used
7Clear-To-Send, shorted internally to Ready-To-Send
8Ready-To-Send, shorted internally to Clear-To-Send
9Ring Indicator, no connection
Panel Mount
Disconnect the unit from the RF power source and the
AC line before any disassembly. The potential for
The +15V supply should only be used to power the ACM
Panel. Do not connect anything else to the power supply.
WARNING
electrical shock exists.
CAUTION
11
Bird Technologies
Installation
To install a Bird Antenna Monitor in the panel mount, follow these
instructions (Refer to
1. Unbuckle the velcro strap and move the power/alarm connector
out of the way.
2. Place the ACM on the panel so that the screws on the bottom of
the Monitor fit into the locator holes on the panel.
Figure 2 on page 4):
Note: The ACM should lock into place.
3. Use the strap to secure the ACM.
4. Plug the power/alarm connector into the power/alarm parallel port
on the ACM.
5. Make RF and RS-232 connections as described in this chapter.
Power Supply
The ACM–RACKU includes a +15 Vdc supply already connected to the
terminal strip.
The ACM–RACK requires a customer-provided power supply. Connect
the supply according to the manufacturer’s instructions (
Mount Wiring” on page 22 for details on the panel wiring configuration).
See “Panel
RS-232 Port Setup
The RS-232 port is configured for 9600 baud, 8 data bits, 1 stop bit and
no parity. This configuration is fixed in the firmware and cannot be
modified. Operate the serial interface as follows:
z Connect the Bird Antenna Monitor to the computer’s serial
port with a DB-9 cable. Do not use a null modem adapter. The
port is configurable from within the PCTool software.
z To use the Bird PCTool software, install it on the computer
and start the application. Refer to "PCTool Software" on
page 15 for information about using the program.
z To use a terminal program, configure it for 9600 baud, 8 data
bits, 1 stop bit, no parity, and no handshake. Set the preferences so that echo is off and line feeds are not appended to output transmission. The commands available are detailed in
"Terminal Commands" on page 20.
12
Installation
PCTool Software
Computer Requirements
The Bird PCTool software will run on any computer running Windows
NT or Windows 95/98/2000. To install and run the program, your com
puter system must meet or exceed the requirements listed below:
486 or better CPU (66 MHz or better recommended)
1 MB of free memory
Hard Disk Drive
CD-ROM Drive
Follow the instructions on the CD provided to install the software.
-
13
Bird Technologies
14
Chapter 4Operating Instructions
PCTool Software
Main Screen
The PCTool communicates with and configures the Bird Antenna &
Cable Monitor. It displays forward and reverse power along with
VSWR, return loss, match efficiency and transmitted power.
shows a sample of the display screen. Refer to the software “Help” file
for specific instructions.
Figure 8 Sample Display
Figure 8
The main screen has two buttons at the bottom, “Trigger” and “Continuous”. Clicking on these will trigger readings. “Trigger” will display a single reading, while “Continuous” will take a new reading every second.
15
Bird Technologies
Com Settings
The PCTool software must be set to use the correct Com Port to communicate with the Antenna Monitor. The default is Com Port 1. To
change the Com Port, select the correct one from the “View>Comm
Port” menu, shown in
Figure 9 Com Menu
Alarm Options
Three alarms can be configured from the software. All alarms are configured from the “View>Options” menu, shown in Figure 10 below.
z High VSWR: Calculated VSWR exceeds a setpoint.
z High Forward Power: Measured power exceeds a setpoint.
z Low Forward Power: Measured power is less than a setpoint.
Figure 9 below.
Note: Some models are not equipped with all alarm variations.
Master Alarm Enable -
box is unchecked, all alarms will be disabled. When it is checked, the
VSWR alarm will automatically be enabled while “Alarm on Zero
Power”, “High Power Alarm”, and “Low Power Alarm” will be on or off
depending on their checkboxes.
Relay Energized on Alarm - The energized state of the relay can be
set. When this checkbox is unchecked, the relay will be de-energized
when an alarm is detected and energized when there is no alarm.
With this setting, the alarm is fail-safe. When it is checked, the relay
will be energized when an alarm is detected and de-energized when
there is no alarm.
Allows the alarms to work. When this check-
16
Figure 10 Options Menu
Operating Instructions
Latch Alarms -
absence of an alarm condition.When this checkbox is unchecked, if an
alarm trigger is corrected the alarm will reset after a forty second
delay. When it is checked, the alarm must be manually reset.
Alarm at Power (Pwr) Up - At power up, before the instrument is
ready to take measurements, the microcontroller resets the circuitry
to the default condition and then performs internal initialization tasks
(such as memory test, hardware setup, and reading EEPROM param
eters). Check the Alarm at Pwr Up box to have the alarm relay set
(enabled) during the microcontroller initialization time. This is the
default setting. Uncheck the Alarm at Pwr Up box to disable the alarm
during the microcontroller initialization time.
Sets whether the alarm will reset automatically in the
Note: When the Alarm at Pwr Up feature is disabled, the
alarm relay may set for a few milliseconds during initialization.
17
-
Bird Technologies
VSWR Alarm -
allow the VSWR alarm to trigger even at low forward power (<
Adjustable from 1.3 to 2.5 by increments of 0.1. To
2.5% of
full scale power), check the “Alarm on Zero Power” checkbox.
While the VSWR trip point can now be set out to 2.5, the instrument
cannot always measure VSWR above 1.9. This is due to the large
amount of reflected power caused at higher VSWRs. The maximum
VSWR that can be physically measured is determined by the full scale
ratio of the forward and reflected detectors. This ratio is 10:1. The
maximum measurable VSWR occurs when the reflected channel is
near its limit. The following table shows the maximum possible VSWR
measurement as a function of percentage of full scale forward input
power. Use this table as a guide to determine the VSWR trip point.
High Power Alarm - Adjustable from 0 to 125% of the ACM’s full scale
power. The alarm setpoint is entered as the % of full scale.
Example - A 100W full scale unit and an alarm is needed
when the forward power exceeds 75 W, the alarm setpoint
would be 75 /100 x 100 or 75%. Enter “75” into the data field
and check the “Enable High Power Alarm” checkbox.
Low Power Alarm -
Set in the same way as the High Power Alarm,
however this alarm will trigger when the forward power is less than
the alarm setpoint.
18
Operating Instructions
Push-to-Talk
Setting Push-to-Talk
1. Open the Power Monitor Options dialog.
2. Do one of the following:
z Check the Enable checkbox to turn the Push-to-Talk feature on.
z Uncheck the Enable checkbox to turn the Push-to-Talk feature off.
3. Enter any value for the time up to 14 sec.
Note: The time actually programmed on the ACM will be a
multiple of 156.25 ms. For this reason, the time displayed will be
slightly different from the time set. The actual delay from the
PTT signal is uncertain because the PTT signal is asynchronous
to the internal measurement samples. The uncertainty is +/-
156.25 ms.
Figure 11 Push-to-Talk
19
Bird Technologies
Terminal Commands
There are three commands which can be sent when the Bird Antenna
Monitor is connected to a terminal.
“T”
The “T” command will cause the unit to echo a single measurement.
The format is:
nnn.n,nn.nnXX<CR><LF>
That is, three digits of forward power, a decimal point, a fourth digit of
forward power, a comma, followed by two digits of reverse power, a
decimal point, and two digits of reverse power.
The first character following will be “A” if an alarm has been triggered
until the alarm is reset, and will be blank if there is no alarm. The sec
ond character will be “0” if “Alarm on Zero Power” is disabled, and “1”
if “Alarm on Zero Power” is enabled.
“C”
-
The “C” command will cause the unit to echo measurements repeatedly. The format is identical to the “T” command. The “C” command
can be interrupted at any time by sending the “T” command.
“A”
The “A” command will reset the alarm. If an alarm condition is still
present, the alarm will turn back on after being reset.
20
Chapter 5Maintenance
This chapter contains troubleshooting instructions, part information,
and specifications for the Bird Antenna & Cable Monitor.
Inspection and Cleaning
This unit requires only simple and routine maintenance.
CAUTION
Do not use harsh or abrasive detergents for cleaning.
WARNING
Disconnect the unit from the RF power source and
the AC line before any disassembly. The potential
for electrical shock exists.
1. Wipe off dust and dirt regularly.
Note: Use a soft, clean cloth dampened with mild detergent.
2. Check connectors, connector pins, and cables for damage.
Note: If needed, clean the connectors using a self-drying
contact cleaner that leaves no residue.
Troubleshooting
The Bird Antenna Monitor has no operator serviceable parts. Any
required service must be performed at an authorized service facility.
The table below contains troubleshooting information for problems
which can occur during normal operation. This manual cannot list all
malfunctions that may occur, or their corrective actions. If a problem
is not listed or is not corrected by the listed actions, notify a qualified
service center.
ProblemPossible CauseCorrection
Operation/Test LED
does not illuminate
Alarm LED does not
illuminate
High VSWRDirty connectorsClean connectors.
No DC powerCheck power source.
Defective LEDReturn the unit to an
authorized service center.
Defective LEDReturn the unit to an
authorized service center.
Defective connectorsReplace connectors.
Shorted or open
transmission line
Have the line serviced.
21
Bird Technologies
NO
NC
COMMON
ALARM
RESET
EARTH GND
EARTH GND
+15V
+
12V
–
NO
NC
COMMON
ALARM
RESET
EARTH GND
Panel Mount Wiring
The power/alarm connectors for the Bird ACM Panel Mount are provided wired to the terminal strips. Figure 12, Figure 13, and Figure 14
show the wiring schematics for 15V, 12V, and 48V respectively.
WARNING
Shock hazard. Remove AC power before attempting
to service the equipment.
CAUTION
The +15V supply should only be used to power the
ACM Panel.
Do not connect anything else to the power supply.
Note the following, which apply to both panel styles:
z The top two terminals are not used.
z For either model, the power/alarm connector is wired identi-
cally on both terminal strips.
z The 15V, 12V, and 48V connectors have different connection
callouts. Be sure to use the correct wiring schematic for each
specific model.
Figure 12 15V Wiring Schematic
Figure 13 12V Wiring Schematic
22
Figure 14 48V Wiring Schematic
+
48V
–
NO
NC
COMMON
ALARM
RESET
EARTH GND
Maintenance
23
Bird Technologies
Customer Service
Any maintenance or service procedure beyond the scope of those provided in this chapter should be referred to a qualified service center.
If you need to return the unit for any reason, contact the Bird Service
Center for a return authorization. All instruments returned must be
shipped prepaid and to the attention of Bird Service Center.
Instruction Manual920-ACM
PCTool Software7005A970
Rack Mount Kit
With 15Vdc power supply
Without power supply
9 pin RS-232 Interface Cable
50 ft.
10 ft.
DB-15 Interface Cable,
50 ft., male/female
DB-15 Interface ConnectorSUBCON-15/M-SH
26
ACM-RACKU
ACM-RACK
5A2264-09-MF-50
5A2264-09-MF-10
5A2264-15-MF-50
Limited Warranty
All products manufactured by Seller are warranted to be free from
defects in material and workmanship for a period of one (1) year,
unless otherwise specified, from date of shipment and to conform to
applicable specifications, drawings, blueprints and/or samples. Seller’s
sole obligation under these warranties shall be to issue credit, repair
or replace any item or part thereof which is proved to be other than as
warranted; no allowance shall be made for any labor charges of Buyer
for replacement of parts, adjustment or repairs, or any other work,
unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/
or samples, Seller shall, upon prompt notice thereof, either examine
the products where they are located or issue shipping instructions for
return to Seller (transportation-charges prepaid by Buyer). In the
event any of our products are proved to be other than as warranted,
transportation costs (cheapest way) to and from Seller’s plant, will be
borne by Seller and reimbursement or credit will be made for amounts
so expended by Buyer. Every such claim for breach of these warranties
shall be deemed to be waived by Buyer unless made in writing within
ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof
which have been subjected to any misuse or neglect, damaged by acci
dent, rendered defective by reason of improper installation or by the
performance of repairs or alterations outside of our plant, and shall
not apply to any goods or parts thereof furnished by Buyer or acquired
from others at Buyer’s request and/or to Buyer’s specifications. Rou
tine (regularly required) calibration is not covered under this limited
warranty. In addition, Seller’s warranties do not extend to the failure
of tubes, transistors, fuses and batteries, or to other equipment and
parts manufactured by others except to the extent of the original man
ufacturer’s warranty to Seller.
The obligations under the foregoing warranties are limited to the precise
terms thereof. These warranties provide exclusive remedies, expressly in
lieu of all other remedies including claims for special or consequential
damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER
WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY,
OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY
AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME
FOR SELLER ANY OBLIGATION OR LIABILITY NOT STRICTLY IN
ACCORDANCE WITH THE FOREGOING.
-
-
-
27
Bird Technologies
28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.