Bird Electronics 8135 Operations Guide

Page 1
INSTRUCTION BOOK
OPERATING INSTRUCTIONS
TERMALINE®COAXIAL
LOAD RESISTOR
MODEL 8135
Electronic Corporation
Cleveland(Solon)Ohio USA
©Copyright 1996 by Bird Electronic Corporation Instruction Book Part Number 920-8135 Rev. B
®
Termaline
is a Registered Trademark
of Bird Electronic Corporation
Page 2
Page 3
SAFETY PRECAUTIONS
The following are general safety precautions that are not necessarily related to any specific part or procedure and do not necessarily appear elsewhere in this publication. These precautions must be throughly understood and apply to all phases of operation and maintenance.
KEEP AWAY FROM LIVE CIRCUITS
Operating personnel must at all times observe normal safety regulations. Do replace components or make adjustments to the inside of the test equipment with a high voltage supply turned on. To avoid casualties, always disconnect power.
DO NOT SERVICE OR ADJUST ALONE
Operating personnel must at all times observe normal safety regulations. Do not attempt to replace parts or disconnect an RF transmission or any other high voltage line while power is applied. When working with high voltage al­ways have someone present who is capable of rendering aid if necessary. Per­sonnel working with or near high voltage should be familiar with modern medthods of resuscitation.
SAFETY EARTH GROUND
An uninterruptible earth safety ground must be supplied from the main power source to test instruments. Grounding one conductor of a two conduc tor power cable is not sufficient protection. Serious injury or death can occur if this grounding is not properly supplied.
SHOCK HAZARD
HIGH VOLTAGE is used in the operation of this equipment. DEATH ON CONTACT may result if personnel fail to observe safety precautions. Learn the areas containing high voltages in each part of the equipment. Be careful not to contact high voltage connections when installing or operating this equipment.
CHEMICAL HAZARD
Solvents used to clean parts are potentially dangerous. Avoid inhalation of fumes and also prolonged skin contact.
-
i
Page 4
RESUSCITATION
Personnel working with or near high voltages should be familiar with modern methods of resuscitation.
SAFETY SYMBOLS
WARNING
Warning: Warning notes call attention to a procedure, which if not
correctly performed could result in personal injury.
CAUTION
Caution: Caution notes call attention to a procedure, which if not
correctly performed could result in damage to the instrument.
8135 WARNING STATEMENTS
The following safety warnings appear in the test where there is danger to op­erating and maintenance personnel and are repeated here for emphasis.
WARNING
When power is in the upper range of the load’s capacity, the radiator
will become hot - care should be used in touching the equipment.
WARNING
Never attempt to disconnect the equipment from the transmission line
while RF power is being applied. Leaking RF energy is a potential
health hazard.
8135 CAUTION STATEMENTS
The following equipment cautions appear in the text whenever the equipment is in danger of damage and are repeated here for emphasis.
CAUTION
Do not operate this equipment continuously above the rated 150 W.
ii
Page 5
About This Manual
This instruction book covers the models 8135 and 8135A Termaline Coaxial Load Resistor.
This instruction book is arranged so that essential information on safety is contained in the front of the book. Reading the Safety Precautions Section be fore operating the equipment is strongly advised.
The remainder of this Instruction Book is divided into Chapters and Sections. At the beginning of each chapter a general overview will be given, describing the contents of that chapter.
OPERATION
First time operators should read Chapter 1 - Introduction and Chapter 3 - In­stallation, to get an overview of equipment capabilities and how to install it. An experienced operator can refer to Chapter 4 - Operating Instructions. All instructions necessary to operate the equipment, are contained in this sec­tion.
MAINTENANCE
All personnel should be familiar with preventative maintenance found in Chapter 5 - Maintenance. If a failure should occur, the troubleshooting sec tion will aid in isolating and repairing the failure.
-
-
PARTS
For location of major assemblies or parts refer to the parts lists and associ ated drawings in Chapter 5.
CHANGES TO THIS MANUAL
We have made every effort to ensure this manual is accurate at the time of publication. If you should discover any errors or if you have suggestions for improving this manual, please send your comment to our factory. This man ual may be periodically updated, when inquiring about updates to this man ual refer to the part number and revision level on the title page.
-
-
-
iii
Page 6
Table Of Contents
Safety Precautions..................i
Warning Statements .....................ii
Caution Statements ......................ii
About This Manual ......................iii
Introduction ....................1
Purpose and Function .....................1
Performance Characteristics and Capabilities ...........1
Dimensions and Weight ....................1
Power and Utility Requirements ................1
Environmental Requirements ..................1
Items Furnished .......................1
Items Required ........................1
Tools and Test Equipment ...................1
Theory of Operation .................3
General ...........................3
Dielectric Coolant and Seal...................3
Installation .....................5
Location ...........................5
Mounting ..........................5
Operating Instructions ................7
Use and Function of Controls..................7
Initial Adjustment ......................7
iv
Page 7
Start Up...........................7
Normal Operation.......................7
Operation Under Abnormal Conditions ..............7
Shutdown Procedures .....................7
Emergency Shutdown .....................8
Maintenance ....................9
Troubleshooting ......................9
Cleaning ........................10
Radiator ..........................10
Inspection ........................10
Oil Leakage .........................10
Cleanliness .........................10
Completeness ........................10
Preventive Maintenance ..................10
RF Assembly Test ....................10
Disassembly .......................11
RF Input Connector Replacement ...............11
Diaphragm and Coolant Oil ..................11
RF Load Resistor Assembly ..................11
Assembly ........................12
RF Input Connector .....................12
Diaphragm and Coolant Oil ..................12
RF Load Resistor Assembly ..................12
Customer Service ......................12
Storage...........................13
Shipment ..........................13
v
Page 8
Bird Model 8135 Termaline Coaxial Load Resistor
Replacement Parts List ....................13
Difference Data Sheet ...............15
VSWR Difference ......................15
Operating position ......................15
vi
Page 9
Chapter 1
Introduction
Purpose and
Function
Performance
Characteristic
Requirements
Requirements
s and
Capabilities
Dimensions
and Weight
Power and
Utility
Enviromental
The Bird Model 8135 TERMALINE Load Resistor is a por table, general purpose 50 ohm coaxial transmission line ter mination. It is a self-contained unit requiring no outside power source or additional equipment. This coaxial load re sistor provides an accurate, dependable, and practically non-reflective termination for adjustment, standby, and testing of transmitters under nonradiating conditions.
The Model 8135 can absorb up to 150 watts continuously and dissipate it harmlessly as heat over a frequency range of dc to 4000 MHz. It is designed to show low reflectivity throughout this range. The VSWR will be 1.1 to 1.0 maxi mum from dc to 1000 MHz, 1.2 to 1.0 maximum from 1000 to 2500 MHz and 1.3 to 1.0 maximum from 2000 to 4000 MHz.
The Model 8135 is 8-13/16 inches long, 4 inches wide, and 6-7/16 inches high (224 x 102 x 164 mm). It has a weight of 6 lb (2.7 kg) net and a shipping weight of 8 lb (3.6 kg).
Being a passive electronic device, the Model 8135 needs no outside source or utility service.
The Model 8135 should be used in a dust and vibration-free environment. The ambient temperature range should be kept between -40C and +45C (-40F and +113F) for proper operation. Allow at least 6 inches of clearance around the load to permit an unimpeded access of convection air cur rents to the load.
-
-
-
-
-
Items
Furnished
Items
Required
Tools and
Test
Equipment
The RF input connector, located on the front face of the unit, is a Female N. It is a special “Quick-Change” design permit ting rapid and easy interchange with other Bird AN type “QC” connectors. This instruction book is the only other item provided.
The only other item required is a matching connector on the coaxial transmission line.
Only simple tools like screwdrivers are needed to disassem ble the Model 8135. A resistance bridge or ohmmeter with an accuracy of one percent or better at 50 ohms is useful for checking the resistance value of the RF section assembly.
-
-
1
Page 10
Bird Model 8135 Termaline Coaxial Load Resistor
SPECIFICATIONS
Impedance 50 ohms nominal VSWR 1.1:1.0 maximum dc-1000 MHz
1.2:1.0 maximum 1000-2500 MHz
1.3:1.0 maximum 2500-4000 MHz
Connectors Female N “QC” type
(normally supplied) Power Range 150 W continuous Frequency Range DC-4000 MHz Dimensions 8-13/16"L x 4"W x 6-7/16"H
(224 x 102 x 164 mm) Ambient Temperature -40C to +45C (-40F to +113F) Cooling Method Dielectric liquid & air convection Weight, Nominal 6 lb (2.7 kg) Operating Position Horizontal only Finish Grey Powder Coat Paint
NOTE - See Difference Data Sheet, Chapter 6, for additional 8135A
specifications.
2
Page 11
Chapter 2
Theory of Operation
General The Model 8135 TERMALINE Load consists essentially of a
cylindrical film type resistor immersed in dielectric coolant. The resistor, individually selected for its accuracy, is en closed in a special tapered housing which provides a linear reduction in surge impedance directly proportional to the distance along the load resistor. This produces the uniform, practically reflectionless line termination over the stated frequencies of the load.
-
Dielectric
Coolant and
Seal
The coolant oil is chosen for its desirable dielectric proper ties and thermal characteristics. Cooling of the load is ac complished by natural fluid and air convection. The dielectric coolant, 0.1 gallon, carries the electrically gener ated heat from the resistor to the walls of the cylindrical cooling tank.
The tank is encased in a set of heavy gauge metal radiating fins, which are firmly pressed on the cylinder. The heat from the oil is transferred to the surrounding air by the ra­diating fins.
A synthetic rubber diaphragm located in the rear dome of the load allows the coolant to expand as the temperature rises.
-
-
-
3
Page 12
Bird Model 8135 Termaline Coaxial Load Resistor
4
Page 13
Chapter 3
Installation
Location Free air circulation around the Model 8135 TERMALINE
Load is essential. Keep the load in the clear, and do not place it near heated surfaces. The Model 8135 should have at least a 6 inch clearance on all sides. Keep the space above the unit unobstructed for good air circulation. This load is to be mounted only in a horizontal position to insure that the load resistor will always be immersed in the coolant.
Mounting The Model 8135 may be fastened to a work or test bench. To
do this, remove the four rubber bumpers from the bottom of the radiator. These bumpers are fastened to the corners of the bottom radiator brace by 8-32 studs which are set per manently into the rubber feet. The bumpers unscrew easily by hand. The holes are threaded for 8-32 screws. The fasten­ers must be placed up through the bench and into the load. These holes are ona3x7inch rectangle (76 x 178 mm).
-
5
Page 14
Bird Model 8135 Termaline Coaxial Load Resistor
6
Page 15
Chapter 4
Operating Instructions
Use and
Function of
Controls
Initial
Adjustment
Start Up Connect the Model 8135 TERMALINE Load to the trans
The Model 8135 is a passive electronic device and therefore has no controls to operate.
No adjustments or setting are required.
mitting equipment under test with 50 ohm coaxial cable such as RG213/U or equal, and a Male N type plug (UG-21E/U or equal) which mates with the RF Input con nector of the load. After the transmitter has been connected to the load, proceed according to the transmitter manufac turer’s instructions. When reconnecting the antenna, it may become necessary to readjust the transmitter due to possi­ble differences in VSWR.
Normal
Operation
Being a passive device, the Model 8135 will function without an operator in attendance provided its stated performance limits are not exceeded. WARNING
When power is in the upper range of the load’s capacity, the radiator will become hot - care should be used in touching the equipment.
CAUTION
Do not operate this equipment continuously
above the rated 150 W.
-
-
-
Operation
Under
Abnormal
Conditions
Sutdown
Procedures
The Model 8135 can be subjected to moderate overloads for short periods of time, providing a sufficient amount of time is allowed between intervals for adequate cooling. An exam ple would be 250 watts for a maximum of 5 minutes, allow ing at least a 20 minute interval for cooling between power applications.
There is no way to turn off the Model 8135; power must be shut off at the RF source instead.
-
-
7
Page 16
Bird Model 8135 Termaline Coaxial Load Resistor
Emergency
Shutdown
Power must be shut off from the RF source as in the above procedure.
WARNING
Never attempt to disconnect the equipment from the
transmission line while RF power is being applied.
Leaking RF energy is a potential health hazard.
8
Page 17
Chapter 5
Troubleshooting
Maintenance
Table 1
Troubleshootin
For corrections requiring repair or replacement of compo nents, refer to the appropriate section for your specific model.
g
Lakage of cool ant oil around clamping band or radiator housing
Overheating of the radiator
High and low dc resistance values per para RF As sembly Test
PROBLEM POSSIBLE
CAUSE
Clamping bands
­not tight
Faulty O-Ring (front)
Faulty dia­phragm (rear)
Transmitter power too high
Coolant oil level too low
Faulty RF sec tion assembly
Faulty RF input connector
-
Loose RF input connector
-
REMEDY
Tighten slightly with screwdriver
Replace per para Disassembly, RF Load Resistor Assembly
Replace per para Disassembly, Di­aphragm and Coolant Oil
Reduce transmit­ter power
Add more coolant oil to the radia­tor per para Dis assembly, Diaphragm and Coolant Oil
Replace per para Disassembly, RF Load Resistor Assembly
Replace per para Disassembly, RF Input Connector Replacement
Tighten with a screwdriver
-
-
9
Page 18
Bird Model 8135 Termaline Coaxial Load Resistor
Cleaning
Radiator The principle maintenance required by the operator will be
the cleaning of the radiator fins. Keep the radiator of the Model 8135 Termaline Load clean and free of dust. Wipe away the accumulated dust and grime with a soft clean cloth. If the insulator or metallic contact surfaces of the RF input connector should become dirty or grimy, clean care fully with a soft clean cloth. Use self-drying, spray or aero sol contact cleaner that leaves no residue on the inaccessible portions of the connector.
Inspection
-
-
Periodic Inspection - with the rugged and simple construc tion of the Model 8135 Termaline Load, periodic inspection will be necessary at only about six month intervals. Inspec tion should include the items listed below:
Oil Leakage Check for coolant oil seepage around the radiator tank, and
particularly at the front and back around the underside of the clamping bands. See paragraph 5.1, Troubleshooting, if leakage is observed. Check tightness of the clamping bands, both front and back.
Cleanliness Check for cleanliness of the radiator fins and the RF connec-
tor. Proceed as in paragraph Cleaning.
Completenes
Inspect the Model 8135 Termaline Load for completeness
s
and general condition of the equipment.
Preventive Maintenance
Most of the preventive maintenance procedures are covered in the previous paragraph 5.5, Inspection. If any portions of the radiator are corroded or rusted, clean the area carefully with a fine flint sandpaper, and touch up the grey enamel.
RF Assembly Test
DC Resistance - Check the condition of the load resistor by accurate measurement of the dc resistance between the in ner and outer conductors of the RF input connector. Use a resistance bridge or ohmmeter with an accuracy of one per cent or better at 50 ohms for this purpose. The measured re sistance should be nominal 50 ohms. For greater accuracy, the resistance of the load should be carefully checked prior to use at ambient room temperature. This resistance value should be recorded and used as a reference. Subsequent re sistance measurements should not deviate more than two percent from this value.
10
-
-
-
-
-
-
Page 19
Maintenance
Disassembly
There are no special techniques required for the repair or replacement of components in the Model 8135 TERMALINE Load. A screwdriver is the only tool needed. The paragraphs below outline component removal.
RF Input
Connector
Replacement
Diaphragm
and Coolant
Oil
The input connector is a patented “Quick-Change” design which permits easy interchange with the use of only a screwdriver. This process does not interfere with the essen tial coaxial continuity of the load resistor RF input or the coolant oil seal. For replacement, proceed as follows:
1. Remove the four 8-32 x 5/16 inch round head machine screws from the corners of the RF con
-
nector.
2. Pull the connector straight out of its socket.
Remove the diaphragm to replace or examine the coolant oil. Replacement of the diaphragm and coolant oil are out­lined in the following steps:
1. Stand the load vertically, with the back end up.
2. Loosen the clamp screw until clamping band is released.
3. Remove the diaphragm cover and lift diaphragm from back end of radiator tank. If the diaphragm is no longer pliable or shows signs of surface cracks, replace it.
4. The coolant oil level should be about one inch be low the top of the radiator cylinder. If the oil ap pears to be contaminated, replace it.
-
-
-
RF Load
Resistor
Assembly
To replace the load resistor assembly, proceed as follows:
1. Stand load vertically, connector end up.
2. Loosen clamp screw until clamping band is re
-
leased.
3. Lift load resistor assembly straight up out of the cylinder, allowing the coolant to drip back into cylinder.
4. Inspect the O-Ring seal which is located just in side the mounting flange of the resistor assembly.
-
11
Page 20
Bird Model 8135 Termaline Coaxial Load Resistor
RF Input
Connector
Diaphragm
and Coolant
Oil
RF Load
Resistor
Assembly
Customer
Service
DO NOT reuse the O-Ring if it is no longer pli
-
able or shows signs of surface cracks.
ASSEMBLY
Reverse the procedure in the RF Input Connector Replace ment paragraph to install a new connector. Be sure that the projecting center contact pin on the connector is carefully engaged and properly seated with the mating socket of the load resistor input.
To reassemble, reverse the procedure in the Diaphragm and Coolant oil paragraph.
To replace the load assembly, reverse the procedure in the RF Load Resistor Assembly paragraph.
Any maintenance or service procedure beyond the scope of those provided in this section should be referred to a quali­fied service center. Bird Electronic Corporation maintains complete repair and calibration facilities.
Service Group
U.S.A. Sales and Manufacturing
Bird Electronic Corporation 30303 Aurora Road Cleveland (Solon), Ohio 44139-2794 Phone: (440) 248-1200 Fax: (440) 248-5426
-
12
Sales Offices
For the location of the sales office nearest you, give us a call or visit our Web site at:
http://www.bird-electronic.com
Page 21
Maintenance
Storage No special preparations for storage are necessary other than
covering the load to keep it dust free. Store in a dry and dust-free environment. Keeping the ambient temperature within the -40C to +45C (-40F to +113F) working range is preferable.
Shipment Wrap the RF connector with padding and tape it securely.
Pack and brace the Model 8135 in a suitable shipping con tainer. A corrugated paper box should suffice. It is not nec essary to remove the dielectric coolant before shipping.
-
-
Replacement
Parts List
Model 8135
Item Qty. Description Part Number
1 1 RF load resistor assembly 2 1 Radiator
8130-015 2400-025
3 1 O-Ring seal 4 2 Clamping band assembly 5 1 Diaphragm 6 1 Diaphragm cap 7 1 Connector 8 0.1 gallon
Coolant Oil
(0.4 liters)
(1 pint container)
7500-254 2400-015 2400-050
*See Below
*Available QC Type Connectors N-Female N-Male HN-Female HN-Male LC-Female LC-Male
4240-062 4240-063 4240-268 4240-278 4240-031 4240-025
LT-Female LT-Male C-Female C-Male UHF-Female (SO-239) UHF-Male (PL-259)
4240-018 4240-012 4240-100 4240-110 4240-050 4240-179
7/8" EIA Air Line 4240-002
5-229
5-030-1
13
Page 22
Bird Model 8135 Termaline Coaxial Load Resistor
14
Page 23
Chapter 6
Difference Data Sheet
MODEL 8135A TERMALINE LOAD RESISTOR
The Model 8135A is identical to the Model 8135 electrically and physically. It has, however, a special RF section which provides special peak power handling capabilities. It will handle up to 35 kW peak power with a pulse width of one microsecond. For further information on peak power rat ings, contact the factory.
When ordering a new RF section for the Model 8135A, order part number 8130-022. All other part numbers remain the same.
-
VSWR
Difference
Operating
Position
Less than 1.1 to 1.0 maximum dc to 1000 MHz. Less than
1.2 to 1.0 maximum 1000 to 4000 MHz.
Horizontal or vertical with connector end down.
15
Page 24
Limited Warranty
All products manufactured by Seller are warranted to be free from defects in material and workmanship for a period of one (1) year, unless otherwise spec ified, from date of shipment and to conform to applicable specifications, draw ings, blueprints and/or samples. Seller’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or re pairs, or any other work, unless such charges are authorized in advance by Seller.
If Seller’s products are claimed to be defective in material or workmanship or not to conform to specifications, drawings, blueprints and/or samples, Seller shall, upon prompt notice thereof, either examine the products where they are located or issue shipping instructions for return to Seller (transporta tion-charges prepaid by Buyer). In the event any of our products are proved to be other than as warranted, transportation costs (cheapest way) to and from Seller’s plant, will be borne by Seller and reimbursement or credit will be made for amounts so expended by Buyer. Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writ­ing within ten (10) days from the date of discovery of the defect.
The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts thereof furnished by Buyer or acquired from others at Buyer’s request and/or to Buyer’s specifications. In addition, Seller’s warranties do not extend to the failure of tubes, transistors, fuses and batteries, or to other equipment and parts manufactured by others except to the extent of the original manufac turer’s warranty to Seller.
-
-
-
-
-
The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, IN CLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR SELLER ANY OBLIGA TION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
16
-
-
Page 25
DECLARATION OF CONFORMITY
Manufacturer: Bird Electronic Corporation
Product: TERMALINE RF COAXIAL LOAD RESISTOR
The undersigned hereby declares, on behalf of Bird Electronic Corporation of Cleveland, Ohio, that the above-referenced product, to which this declaration relates, is in conformity with the provisions of the following standards;
1. European Standard EN 61010-1:1993 - Safety, Group II.
This standard is in accordance with Council Directive 73/23/EEC and 93/68/EEC.
The technical documentation file required by this directive is maintained at the corporate headquarters of Bird Electronic Corporation, 30303 Aurora Road, Cleveland, Ohio.
30303 Aurora Road Cleveland, Ohio 44139-2794
Models: 8135 8135A 8135-075
Ken DeVore Metrology/QA Manager Bird Electronic Corporation
17
Loading...