Bioscrypt 4GFVSTHW, 4GFVSTPW, 4GFVSTGW User Manual

Installation Guide –April 2010
CHAPTER 4 - INSTALL HARDWARE
CHAPTER OVERVIEW
This chapter explains how to install a V-Station 4G or V-Flex 4G device, how to mount a wall plate, how to attach a device to a wall plate, and how to make the required electrical connections to the device.
4.1 INSTALL HARDWARE
4.1.1 WALL-MOUNTING SCHEMES
The V-Station 4G and V-Flex 4G devices are mounted, by use of a mounting plate, either directly to a wall or to an electrical box recessed in the wall. The V-Station 4G device can be flush mounted only. The V-Flex 4G device can be either flush or recess­mounted on a wall.
2010
The V-Station 4G Extreme devices are mounted, by use of a stainless steel mounting plate, directly to a wall.
4.1.2 INSTALLING A MOUNTING PLATE
The procedure for mounting a wall plate directly to a wall is as follows:
Hold the mounting plate onto the wall in the desired location, trace the square hole that
will be cut out, and mark the mounting screw locations. Note that for the V-Flex 4G, the large square hole is at the bottom and for the V-Station 4G the hole is to the right.
Cut out the square hole with a jigsaw or drywall saw. If the V-Flex 4G device is to be
recess-mounted, cut out a hole in the drywall to accommodate the rear extension on the device housing.
Drill holes for the nylon wall anchors and install them.
Fish wires through the wall to the square hole.
Align the hole in the wall plate with the hole in the wall.
Fasten the mounting plate to the nylon wall anchors in the wall with the provided
screws.
If the V-Flex 4G device is to be recess-mounted on an electrical box, a double gang box is required to accept the rear extension of the housing.
If mounting the V-Station 4G device to an electrical box, attach the mounting plate to a single
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 46
Installation Guide –April 2010
gang box and use wall anchors on the remaining four holes for additional security.
To install the mounting plate on to an electrical box, screw the mounting plate to the box with the provided 6-32 screws.
When installing a recess-mounted V-Flex 4G device, be careful not to damage the tamper switch, as careless handling can shear it off.
Figure 4-1 V-Flex 4G Flush-mount Mounting Plate
CAUTION
2010
Figure 4-2 V-Flex 4G Recessed-mount Mounting Plate
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 47
Installation Guide –April 2010
Figure 4-3 V-Station 4G Mounting Plate
2010
NOTICE
The V-Station 4G device can only be flush mounted.
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 48
Installation Guide –April 2010
Figure 4-4 FingerVein Station 4G Mounting Plate
2010
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 49
Installation Guide –April 2010
Figure 4-5 V-Station 4G Extreme Mounting Plate
2010
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 50
Installation Guide –April 2010
Figure 4-5 4G Extreme PIV/TWIC Mounting Plate
2010
4.1.3 INSTALLATION HARDWARE
4.1.3.1 4G V-Station and V-Flex Indoor devices
Quantity
1 Wall mounting plate/mullion mounting plate
6 #6-32 3/4" Philips pan-head screw
6 #6 1" Philips pan-head self-tapping screws
6 #4-8 1" nylon wall anchors
The hardware shown above is provided to mount the mounting plate to the wall and the V- Station 4G or V-Flex 4G device to the mounting plate.
4.1.3.2 4G Extreme Devices
1 Stainless Steel, Wall Mount Plate
8 wall mount anchor, conical, for #8 screws
6 6-32 Security Screw 1/8" pin-in-hex 3/8" length
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 51
Installation Guide –April 2010
8 #8x1" thread forming screw, pan head, Philips
8 wall mount anchor, conical, for #8 screws
4.1.4 ATTACH DEVICE TO MOUNTING PLATE
4.1.4.1 4G V-STATION AND V-FLEX INDOOR DEVICES
Once all the electrical connections have been made to the device, it can be attached to the mounting plate as follows:
For the V-Flex 4G, insert the four hooked protrusions on the rear of the device into the corresponding slots on the mounting plate. Hold the device against the plate and gently press it in a downward direction to engage the hooks. Insert the star-shaped screw at the bottom center of the mounting plate and tighten with the wrench provided. Do not over-tighten.
For the V-Station 4G, hold the device with the top slightly tilted toward you, at about a 30-degree angle to the wall. Hold the bottom of the device against the mounting plate and lower it so that the two hooks on the bottom of the mounting plate engage the corresponding slots on the device. When the hooks are properly engaged, the top of the device can be pivoted up against the mounting plate. It will drop down slightly, locking itself in the closed position, and should be secured in this position with the star-shaped screws in the holes at the right and left ends on the bottom of the device. Do not over­tighten.
2010
With the securing screws removed, the V-Station 4G device can be pivoted down 90 degrees from the wall, to allow access for making connections, etc. The device can be removed from the mounting plate by tilting it at an angle approximately 30 degrees to the wall and gently lifting it up off the hooks on the mounting plate.
Figure 4-6 Device Open for Installation or Service
4.1.4.2 4G EXTREME DEVICES
TBD
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 52
Installation Guide –April 2010
4.1.5 CONNECT DEVICE TO POWER SOURCE
The V-Station 4G and V-Flex 4G, and 4G Extreme devices can be powered by 12V-24V DC power sources, or through a Power Over Ethernet (PoE) injector for V-Station 4G and V-Flex 4G.
The two options for providing 1 2V power to V-Station 4G and V-Flex 4G devices are by using an external wall plug-in adapter (Figure 4-7), or through external wiring and a mini plug (Figure 4-8).
12V power can be provided to 4G Extreme devices only through the 3-Wire back cable (Figure 4-9).
Figure 4-7 Connections for an External Wall Adapter (4G Indoor)
2010
Figure 4-8 Connections for an External Power Source (4G Indoor)
Figure 4-9 Connections for an External Power Source (4G Extreme)
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 53
Installation Guide –April 2010
The V-Station 4G, V-Flex 4G devices both support Power over Ethernet (PoE), using their RJ-45 Ethernet interface. When these devices are to be powered over Ethernet, an IEEE 802.3af compliant Active Midspan Injector must be used. Such an injector is not supplied with L-1 Identity Solutions products. An example of a suitable PoE injector is Model No. AT-61 01 G from Allied Telesis Inc. (http://www.alliedtelesis.com).
Any such device should carry at least one of the certifications shown below and should be FCC listed.
Figure 4-11 Power Over Ethernet Connection
Figure 4-10 Certification Marks
2010
Specifications for suitable PoE Injectors for 4G Indoor devices are as follows:
Input voltage: 90-264 VAC, 60 Hz
Input current: 0.4A @ 100 VAC
Output voltage: -48 VDC
Output current: 0.32A
Power: 15.36 W
For Power over Ethernet, RJ-45 pin numbers 4, 5 are considered VB1 (+) positive DC supply, and pin numbers 7, 8 are VB2(-) DC return.
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 54
Installation Guide –April 2010
Detailed RJ-45 pin assignments for PoE are given in Table PoE Pin Assignments, and the physical location of the pins in the RJ-45 connector.
4.1.6 CONNECT DEVICE TO NETWORK
The V-Station 4G and V-Flex 4G devices support both RS-232/RS-485 and Ethernet 1 0baseT and 1 00baseTX network protocols.
4.1.6.1 ETHERNET NETWORK CONNECTIONS
Figure 4-12 RJ45 Pin Location
2010
Ethernet connections to the device are made through a standard RJ-45 connector on the back of the device.
4.1.6.2 RS-232/RS-485 NETWORK CONNECTIONS
To connect a device to an RS-232 or RS-485 network, connect the appropriate wires to the provided pigtail in accordance with the pin-out diagram.
Table 4-1 Pin-out Diagram
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 55
Installation Guide –April 2010
When connecting the device to the network, the following procedures must be followed:
Use Category 5 cabling with a characteristic impedance of 120 ohms
for RS-485 networks. Category 5 cables with a characteristic impedance of 100 ohms can also be used, but with lower performance.
Cable manufacturers provide cables with multiple twisted pairs
designed for this type of communication (characteristic impedance is 120 ohm).
Unused pairs within the cable must be terminated with characteristic
impedance (100 or 120 ohm) on both ends.
AWG 24 should be considered as the minimum gauge.
Choose one twisted pair of conductors to use for RS-485 differential
connections, other conductors should be used for Signal Ground (RS­485 GND on Weidmuller connection).
2010
The RS-232 to RS-485 converter must support Sense Data to be able
to switch from Send to Receive mode.
Check each device's cabling for ground faults before connecting to an
RS-485 network.
Each device should have pin 3 of the mini-connector connected to
earth ground.
After all devices are configured and connected to the RS-485 network, the baud rate can be increased to the highest supported rate (some experimentation might be required).
4.1.6.3 WIRELESS NETWORK CONNECTIONS
After the physical installation, the device can be configured for wireless network connection. The wireless network can be set up either through SecureAdmin (see Chapter 7 in the Operator's Manual) or through the front panel of the V-Station 4G device.
To set up wireless operation through the front panel of a V-Station 4G device, perform the following steps:
2. Power up the device.
Ensure that the wireless network is functioning.
Use one of these supported modes:
WEP Open
WPA Personal
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 56
Installation Guide –April 2010
WPA2 Personal.
L-1 Identity Solutions does not recommend using the "No encryption" mode.
Enter the Admin menu on the device by pressing the Left arrow and Enter keys simultaneously.
Key in the Admin password (default is "0000") and press OK.
Select the Communications icon and press OK
Select "Network Interface" and press OK.
Select "WLAN" Configuration and press OK.
NOTICE
2010
Select Managed/Adhoc mode from WLAN Network type.
Select the intended wireless networks.
Enable WLAN mode from WLAN parameters.
Choose Encryption mode and encryption .
Enter the key.
Select "DHCP" or "Static" and press OK. If you selected "DHCP", the device reboots.
Afterwards, it will have a dynamic IP address. If you selected "Static IP", specify an IP, a Net Mask, a Gateway, and then press OK.
SecureAdmin can scan for and auto-detect wireless devices. If you want to use SecureAdmin to scan for wireless devices, ensure that the "multicasting" option is enabled in your router.
NOTICE
The maximum recommended distance from an access point is 25 feet.
4.1.7 SINGLE-DOOR CONTROLLER INSTALLATION
The V-Station 4G and V-Flex 4G devices incorporate an internal relay that enables them to operate a deadbolt/door strike directly.
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 57
Installation Guide –April 2010
The internal relay is limited to a maximum current of 170 mA. If the deadbolt/ doorstrike to be controlled draws more than 170 mA, damage to the device may occur. If the deadbolt/door strike load exceeds 170 mA, an external relay must be used, as described below. Do not use the same power supply to power a V-Series 4G device and a door strike.
Assuming the current drawn by the deadbolt/door strike is less than 170 mA, the connections between the V-Station 4G or V-Flex 4G device, deadbolt/door strike, and power supply for the deadbolt/door strike should be made. Note that a snubber diode (1 N4007 or equivalent) must be connected across the deadbolt/door strike to protect the DC power supply from inductive kickback.
WARNING
CAUTION
2010
The snubber diode and DC power supply for the deadbolt/door strike are not supplied with the V-Station 4G and V-Flex 4G devices. The power supply should be specified in accordance with the voltage and current requirements of the deadbolt/door strike, but it must be ensured that the current to operate the dead bolt/door strike does not exceed 170 mA.
If the current required to operate the deadbolt/door strike exceeds 170 mA, an external relay must be used in conjunction with the V-Station 4G or V-Flex 4G device. The external relay must be specified so that its contacts are rated to carry the current required by the deadbolt/door strike, and that the current required to operate its energizing coil is within the 170 mA capacity of the V-Station 4G or V-Flex 4G device's internal relay.
Figure 4-13 Connections for Internal Relay Operation
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 58
Installation Guide –April 2010
The power supply for the external relay must be chosen to match the operating voltage and current of the external relay coil, but its voltage must not exceed the V-Station 4G or V-Flex 4G device's internal relay maximum voltage rating of 250 volts.
The external relay should be connected. Note that snubber diodes (1 N2007 or equivalent) should be connected across the external relay coil and the deadbolt/door strike.
2010
Figure 4-14 Connections for External Relay Operation
October 15 2009 – Installation Guide Draft – Edit Purposes Only Page 59
Loading...
+ 30 hidden pages