Division of Garner Industries
7201 North 98th Street
Lincoln, NE 68507-9741
(402) 434-9102
WR-90 Point to Multi-Point Wireless
Instruction Manual
• Point to Multi-Point Signal Wire Replacement
• Simple to Configure Using WR Manager
Programming Software and Onboard USB
• Range: 1 Mile Line-of-Sight, 500 Ft Indoor
• Analog, Digital, and RS-485 Inputs and Outputs
• Remote or Attached, Directional and Omnidirectional Antennas Available
• Field Units Feature Flanges for Wall or Pipe Mounting
• Base Station Housed in Plastic NEMA 4X Field Enclosure
• Field Units Housed in IP68, NEMA 4X Enclosure

WR-90 Point to Multi-Point Wireless Instruction Manual
Table of Contents
Table of Contents ................................................... 3!
Table of Figures ..................................................... 3!
Introduction ............................................................. 4!
Ordering Information .............................................. 5!
Specifications ......................................................... 6!
WR-90 Base Station Specifications .................... 6!
General ........................................................... 6!
Dual Analog Inputs Module ............................. 6!
Dual 4-20 mA Outputs Module ........................ 6!
Digital Input / Output Module ........................... 6!
Dual Relays Module ........................................ 6!
WR-90 Field Unit Specifications ......................... 7!
General ........................................................... 7!
Isolated 4-20 mA Transmitter Output .............. 7!
Digital Input / Output Terminal ........................ 7!
General Specifications ........................................ 8!
Wireless Radio ................................................ 8!
WR Manager Software .................................... 8!
RS-485 Modbus® RTU Serial Comms ............. 8!
Safety Information .................................................. 8!
Installation .............................................................. 8!
Unpacking ........................................................... 8!
Pre-Installed Conduit Plug .................................. 9!
Base Station Conduit Holes ................................ 9!
Mounting Instructions .......................................... 9!
Cover Jam Screw................................................ 9!
FCC Notice ......................................................... 9!
IMPORTANT ................................................... 9!
Canada (IC) Notice ......................................... 9!
Base Station Connections ................................ 10!
Power Connector .......................................... 11!
Analog Input Connector ................................ 11!
Analog Output Connector .............................. 11!
Digital I/O Connector ..................................... 11!
Relays Connector .......................................... 12!
Switching Inductive Loads ............................. 12!
Modbus RTU Serial Communications ........... 13!
Field Unit Connections ...................................... 14!
Power Connector .......................................... 15!
Signal Connector ........................................... 16!
4-20 mA Output Connector ........................... 16!
Digital I/O Connector ..................................... 16!
Modbus RTU Serial Communications ........... 17!
Setup and Programming ...................................... 18!
Overview ........................................................... 18!
Programming the Base Station ......................... 18!
Connecting Field Units to Base Station ......... 19!
Base Station Configuration ........................... 20!
Input / Output Module Configuration ............. 21!
Remote Unit Configuration ............................ 25!
Advanced Configuration ................................ 29!
Programming the Field Units ............................ 30!
Field Unit Setup Menu ................................... 31!
Programming the Field Units with WR Manager
...................................................................... 34!
Troubleshooting .................................................... 37!
Mounting Dimensions ........................................... 40!
PDA6963-BM Stainless Steel Pipe Mounting Kit for
Field Units ............................................................ 41!
Table of Figures
Figure 1. Fully Loaded Base Station Main Board . 10!
Figure 2. Base Station Power Connection ........... 11!
Figure 3. Base Station Analog Input Connection 11!
Figure 4. Base Station Digital I/O Connection ...... 11!
Figure 5. Base Station Analog Output Connection
.............................................................................. 11!
Figure 6. Base Station Relays Connection ........... 12!
Figure 7. AC and DC Loads Protection ................ 12!
Figure 8. Low Voltage DC Loads Protection ........ 12!
Figure 9. Base Station Three- and Five-Wire RS-
485 Modbus Connection ...................................... 13!
Figure 10. Base Station Multiple Device RS-485
Modbus Connection ............................................. 13!
Figure 11. Field Unit Device Assembly, Rear View
.............................................................................. 14!
Figure 12. Field Unit Power Connection .............. 15!
Figure 13. WR-90 Field Unit and 2-Wire Transmitter
Powered from Same Supply ................................. 15!
Figure 14. Field Unit Analog Input Connection ..... 16!
Figure 15. Field Unit 4-20 mA Output Connection
.............................................................................. 16!
Figure 16. Field Unit Digital I/O Connection ......... 16!
Figure 17. Field Unit Three- and Five-Wire RS-485
Modbus Connection ............................................. 17!
Figure 18. Field Unit Multiple Device RS-485
Modbus Connection ............................................. 17!
Figure 19. Base Station Dimensions – Front View
.............................................................................. 40!
Figure 20. Base Station Dimensions – Side View 40!
Figure 21. Field Unit Dimensions – Front View .... 40!
Figure 22. Field Unit Dimensions – Side Cross
Section View ......................................................... 40!
Figure 23. PDA6963-BM Stainless Steel Pipe
Mounting Kit for Field Units .................................. 41!
3

WR-90 Point to Multi-Point Wireless Instruction Manual
6
Specifications
Except where noted all specifications apply to operation at +25°C.
WR-90 Base Station Specifications
General
Maximum
Connected
Field Units
Via PC with WR Manager software
24 VDC ±10%, 36 W max, 2.4 W
min; Power consumption is
dependent on type and number of
modules installed
All programmed settings are stored
in non-volatile memory for a
minimum of ten years if power is
lost.
Operating temp. range: -40 to 65°C
Storage temp. range: -40 to 85°C
Relative humidity: 0 to 90% noncondensing
Removable screw terminal blocks
accept 12 to 22 AWG wire.
15.75" x 11.81" x 7.03" (40 cm x 30
cm x 17.9 cm) (W x H x D);
NEMA 4X; Thermoplastic Polyester;
Color: Gray
Screw terminal connectors: 5 lb-in
(0.56 Nm)
17" x 14" x 9" (43.2 cm x 35.6 cm x
22.9 cm) (W x H X D)
Dual Analog Inputs Module
Field selectable: 4-20 mA, 0-10 V,
0-5 V, 1-5 V
±0.03% of calibrated span ±1 count
All ranges are calibrated at the
factory. Recalibration is
recommended at least every
12 months.
0.005% of calibrated span/°C max
from 0 to 65°C ambient,
0.01% of calibrated span/°C max
from -40 to 0°C ambient
Inputs will remain off (open circuit)
until wireless units are reconnected.
Voltage ranges: greater than
110 kW
Current ranges: less than 220 W
Analog input will not interfere with
existing HART communications on
the wired 4-20 mA signal
Dual 4-20 mA Outputs Module
Analog input from connected
wireless unit
Factory calibrated:
4.000 to 20.000 = 4-20 mA output
± 0.1% of span ± 0.004 mA
0.4 µA/°C max from 0 to 65°C
ambient, 0.8 µA/°C max from -40 to
0°C ambient.
Internally powered; no external
supply needed
After approximately 25 seconds of
trying to reconnect, mA output will
become 3.2 mA
Digital Input / Output Module
Four (4) digital connections,
independently field selectable as
either inputs or outputs
Dry contact to ground can be used
to activate the input
10 mA maximum output current
1.5 mA minimum input current
Digital output goes to logic high
2 SPDT (Form C); rated 3 A @
30 VDC and 125/250 VAC resistive
load; 1/14 HP (≈ 50 W) @ 125/250
VAC for inductive loads
Noise suppression is recommended
for each relay contact switching
inductive loads; see page 12 for
details.
After power failure, relays will
initialize to default state before
reconnecting to wireless units.
If mapped to digital input channel,
the relay energizes.

WR-90 Point to Multi-Point Wireless Instruction Manual
7
WR-90 Field Unit Specifications
General
32-character dual-line alphanumeric
dot matrix LCD display with backlight
(4.68mm x 2.21mm characters)
Display may be mounted at 180°
from default orientation
Four programming buttons (behind
glass) or PC with WR Manager
software.
All inputs and outputs are calibrated
at the factory. Recalibration is
recommended at least every
12 months.
Process/
Digital I/O
Display
Press the display button once to
display the present analog input and
output. Press the display button
again to display digital I/O states.
A programmable password restricts
modification of programmed settings.
All programmed settings are stored
in non-volatile memory for a
minimum of ten years if power is lost.
Operating temp. range: -40 to 65°C
(display inoperable < -20 °C)
Storage temp. range: -40 to 85°C
Relative humidity: 0 to 90% noncondensing
Removable screw terminal blocks
accept 16 to 30 AWG wire.
Cast aluminum with glass window,
0.3% max copper content, corrosion
resistant powder coating, color: blue.
IP68. Two ½" NPT threaded conduit
openings. One ½" NPT stainless
steel conduit plug with 10 mm hex
key fitting installed.
May be mounted directly to conduit.
Two mounting holes for 1.5" pipe or
wall mounting. See Mounting
Dimensions on page 40 for mounting
space requirements.
Signal
Connector
Tightening
Torque
17" x 14" x 9" (43.2 cm x 35.6 cm x
22.9 cm) (L x W X H)
Field selectable: 4-20 mA, 0-10 V,
0-5 V, 1-5 V
±0.03% of calibrated span ±1 count
0.005% of calibrated span/°C max
from 0 to 65°C ambient,
0.01% of calibrated span/°C max
from -40 to 0°C ambient
Voltage ranges: greater than
110 kW
Current ranges: less than 220 W
Inputs will remain off (open circuit)
until wireless units are reconnected.
Analog input will not interfere with
existing HART communications on
the wired 4-20 mA signal
Isolated 4-20 mA Transmitter Output
Analog input from connected
wireless unit
Factory calibrated:
4.000 to 20.000 = 4-20 mA output
± 0.1% of span ± 0.004 mA
Internally powered; no external
supply needed
0.4 µA/°C max from 0 to 65°C
ambient, 0.8 µA/°C max from -40 to
0°C ambient
After approximately 25 seconds of
trying to reconnect, mA output will
become 3.2 mA
Digital Input / Output Terminal
Four (4) digital connections,
independently field selectable as
either inputs or outputs
Dry contact to ground can be used
to activate the input
10 mA maximum output current
1.5 mA minimum input current
Digital output goes to logic high

WR-90 Point to Multi-Point Wireless Instruction Manual
8
General Specifications
Wireless Radio
500 ft (152.4 m) indoor, 1 mi
(1.61 km) outdoor (line-of-sight)
AES 128-bit encryption available
using WR Manager software
Frequency Hopping Spread
Spectrum (FHSS)
Microsoft® Windows® XP/Vista/7/8/10
USB 2.0 (Standard USB A to Micro
USB B)
Configure devices one at a time
RS-485 Modbus® RTU Serial Comms
Removable screw terminal connector
8 bit (1 start bit, 1 or 2 stop bits)
Even, Odd, or None with 2 stop bits
0.5, 1, 2, 3, 4, 5 seconds;
user selectable
Caution: Read complete instructions
prior to installation and operation of the
device.
Warning: Read all product labels
completely and follow all instructions
and requirements listed on the labels
for installation or service.
Installation and service should be performed only by trained
service personnel. Service requiring replacement of internal
components must be performed at the factory.
Installation
Base Station: All wiring connectors are accessed by opening the enclosure. To access electrical
connectors, unclasp enclosure and open.
Field Units: All pushbuttons and wiring connectors are accessed by opening the enclosure. To
access electrical connectors, remove the 2 captive screws and remove the display assembly.
Unpacking
Remove both units from box. Inspect the packaging and contents for damage. Report damages, if
any, to the carrier. If any part is missing or the units malfunction, please contact your supplier or
the factory for assistance.

WR-90 Point to Multi-Point Wireless Instruction Manual
9
Pre-Installed Conduit Plug
The WR-90 field units are supplied with one pre-installed optional conduit plug for installations that do not
require the use of both conduit entries. The conduit plug includes an internal hexagonal socket recess for
removal.
Base Station Conduit Holes
No predrilled conduit holes are provided in the base station enclosure from the factory. Drilling of conduit
holes is left to the end user so that they may be placed wherever appropriate for the application. Be sure
to use suitable hardware (cable glands, plugs, etc.) in order to maintain NEMA 4X/IP66 rating on the
enclosure.
Mounting Instructions
The base station can be wall mounted using the included mounting hardware. Securely screw the four
brackets into the threaded holes provided at the rear of the enclosure with the bend facing toward the wall
in order to provide the necessary clearance. Then, secure exposed mounting holes to wall.
The field units have two mounting holes that may be used for a 1.5” pipe mounting or wall mounting.
Alternatively, the unit may be supported by the conduit using the conduit holes provided. The antenna is
threaded into one of the three conduit holes and may be moved as appropriate for the installation.
It can also be mounted by using the PDA6963-BM mounting bracket in order to orient the device antenna
away from the pipe. Refer to Mounting Dimensions on page 40 for details on space requirements.
Cover Jam Screw
The cover jam screw should be properly installed once the field units have been wired and tested in a
safe environment. The cover jam screw is intended to prevent the removal of the units’ cover while in
operation without the use of tools. Using a M2 hex wrench, turn the screw clockwise until the screw
contacts the unit. Turn the screw an additional 1/4 to 1/2 turn to secure the cover.
Caution: Excess torque may damage the threads and/or wrench.
FCC Notice!
Contains FCC ID: MCQ-XB900HP
The enclosed device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (i.) this device may not cause harmful interference and (ii.) this device must accept any
interference received, including interference that may cause undesired operation.
IMPORTANT
The RF module has been certified for remote and base radio applications. If the module will be used for
portable applications, the device must undergo SAR testing. This equipment has been tested and found
to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference
by one or more of the following measures: Re-orient or relocate the receiving antenna, Increase the
separation between the equipment and receiver. Connect equipment and receiver to outlets on different
circuits, or consult the dealer or an experienced radio/TV technician for help.
Canada (IC) Notice
Contains Model: XB900HP, IC: 1846A-XB900HP
Integrator is responsible for its product to comply with IC ICES-003 & FCC Part 15, Sub. B - Unintentional
Radiators. ICES-003 is the same as FCC Part 15 Sub. B and Industry Canada accepts FCC test report or
CISPR 22 test report for compliance with ICES-003.

WR-90 Point to Multi-Point Wireless Instruction Manual
12
Relays Connector
The relays module includes two mechanical relays. Relay connections
are made to the six-terminal connector shown to the right.
Each relay’s C terminal is common only to the normally open (NO) and
normally closed (NC) contacts of the corresponding relay.
If a field unit’s digital input channel is mapped to a relay module
channel on the base station, the effect may be opposite of what is
expected. An open connection at the digital input will result in the relay
going into an active state. This is because the digital input channels
are active low. This can be changed by swapping the NO and NC
connections to the relay channel.
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent
disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts.
Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased
as complete assemblies. Refer to the following circuits for RC network assembly and installation:
Figure 7. AC and DC Loads Protection
Choose R and C as follows:
R: 0.5 to 1 Ω for each volt across the contacts
C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the device's relay screw terminals. An RC network may also be installed
across the load. Experiment for best results.
Figure 8. Low Voltage DC Loads Protection
RC Networks
RC networks should be applied to each relay contact switching an inductive load.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
Figure 6. Base Station
Relays Connection
NO NC C
1 2
RELAY
NO NC C
Use a diode with a reverse
breakdown voltage two to
three times the circuit voltage
and forward current at least as
large as the load current.

WR-90 Point to Multi-Point Wireless Instruction Manual
16
Signal Connector
The analog input may be either 4-20 mA, 0-10 V, 0-5 V, or 1-5 V.
The appropriate input type must be programmed for each unit.
Once the appropriate input type has been programmed, wire the
analog signal source to the device as shown in the diagram at
right.
The analog input will not interfere with any existing HART signal
on a 4-20 mA current loop. However, the HART signal will not be
transmitted wirelessly.
4-20 mA Output Connector
The 4-20 mA output corresponds with the analog input signal on
the paired wireless device. The analog output signal is always
4-20 mA, regardless of the input type on the other wireless
module.
For instance, if the analog input type on the first device was
0-10 V and the input value was 5 V, the second device would
output 12 mA.
Connect the mA OUT terminals to a device scaled to read a
4-20 mA signal.
The analog output is internally powered; no external power
supply is required.
Digital I/O Connector
All digital connections are referenced to ground. The base
station I/O settings determine the I/O settings of the field units
(e.g. if D1 of the base station is an input then it can only be
mapped to a digital output of a field unit).
Note: Each connection may be set independently in the
device settings as either an input or an output. In the
diagram to the right, D4 & D3 are digital inputs and D2
is a digital output.
Figure 14. Field Unit Analog
Input Connection
Figure 15. Field Unit
4-20 mA Output Connection
Figure 16. Field Unit Digital I/O
Connection
Voltage or
Current Signal
Source
4-20 mA Input
Display, Chart
Recorder, Etc.

WR-90 Point to Multi-Point Wireless Instruction Manual
30
Programming the Field Units
The field units can be programmed using the buttons
located behind the enclosure cover or using WR
Manager. Because of the limited number of options
available for the field units, it is easier in most cases
to use the programming buttons.
When programming the field units using the
programming buttons, use the menu button to enter
or exit programming mode, the next button to cycle
forward through menu options, the previous button to
cycle backward through menu options, and the enter
button to select the menu item or option you want.
During number entry, use the next button to select a
digit and the previous button to increment the
selected digit.
Press the display button while in run mode to show
the current analog and digital inputs and outputs.
Menu
Enter or exit the
device menu
Received Signal Strength Indicator
Indicates the wireless signal strength
between wireless devices on a scale of
1 to 10.
Enter
Select a menu item
of option
Receiving/Transmitting
Flashes while the devices are sending
and/or receiving data
Previous
Cycle backward
through menus or
increment digit
Modbus Address
Indicates the Modbus address of the
field unit. This is the unique identifier
that the base station uses to
communicate with the field unit.
Next
Cycle forward
through menus or
select next digit
Link Status
Displays whether or not the units are
currently connected
Display
Show current inputs
and outputs
Analog Input/Analog Output
Labels for the current analog input and
analog output
(Shown when the display button is pressed)
Digital Input/Digital Output
Labels for each of the current digital
inputs or outputs
(Shown when the display button is pressed twice)

WR-90 Point to Multi-Point Wireless Instruction Manual
31
Field Unit Setup Menu
The setup menu consists of analog, digital (discrete), and Modbus® input/output settings, network ID,
password, and factory defaults restoration.
Display Functions & Messages
Shown below is a list of all display messaged in each field unit’s setup menu. This list is in order of
appearance when pressing the next button. An indented line indicates a sub-menu or item.
Action/Setting Description
Displays the point-to-multipoint wireless network ID (press enter to change)
The network ID can be any number between 01 and 99
The unique ID used by the base station to differentiate between field units
The Modbus address can be any number between 001 and 247
Change the device password
Displays the current device password (press enter to change)
Password can be any number from 0001 to 9999 (0000 disables)
Restore the unit to factory default settings
Factory restoration confirmation prompt
No, do not restore the device to factory defaults (press enter)
Yes. restore the device to factory defaults (press enter)
LINK OK
016 RSSI 10 RT
NOW: 01
NETW ORK ID
NOW: 016
MODB US ADDRE SS
SETU P
PASS WORD
DEFA ULTS
REST ORE
Run Mode
SET: 01
NETW ORK ID
increments selected digit.
selects next digit to the right.
NOW: 0000
PASS WORD (0= OFF)
SETU P MENU
BACK TO
SET: 0123
PASS WORD (0= OFF)
increments selected digit.
selects next digit to the right.
0000 disables the pas sword.
NO
LOAD DEFAULT S?
YES
LOAD DEFAULT S?
Unit will load default
settings and reboots.
SET: 016
MODB US ADDRE SS
increments selected digit.
selects next digit to the right.

WR-90 Point to Multi-Point Wireless Instruction Manual
37
Troubleshooting
If you are experiencing difficulties with your wireless installation, consult the troubleshooting steps listed
below. For best results, identify the symptoms of the problem you are having and attempt all of the
corrective actions listed for the particular symptom.
Devices will not connect.
Devices have
mismatched
network IDs.
• Devices will not connect if they do not have
the same network ID. Verify that both devices
share the same network ID.
Devices are out of
range or there are
obstacles
blocking the
wireless path.
• Bring devices closer together to see if it
alleviates the issue. Units will display LINK
OK if they are connected. If devices connect,
consider placing closer together
permanently, removing any obstacles, or
mounting higher.
• Ensure antennas are on parallel plane.
Devices that are vertically separated will not
have as strong of a connection.
• If communicating over distance of miles,
consider installing WR-30-RP repeaters or a
high gain directional antenna.
Multiple wireless
devices in the
area with the
same ID.
• If there are multiple WR-90 wireless systems
or WR-30 wireless signal bridges, verify that
each system has its own unique network ID.
All units intended to communicate with each
other should share a unique network ID.
Encryption keys
do not match
• If using encryption, ensure that the
encryption keys on both devices match
exactly.
Intermittent signal issues.
• Check RSSI. If signal is too low, consider
moving devices closer together, clearing
obstacles in wireless path, or mounting
devices higher.
• Ensure devices are on parallel plane.
• If communicating over distance of miles,
consider installing high gain directional
antenna.
Temporary
obstacles are
blocking the
wireless path.
• Temporary obstacles, such as large trucks or
heavy equipment, can interfere with wireless
path. Consider moving wireless units higher
or to an area with less traffic.

WR-90 Point to Multi-Point Wireless Instruction Manual
38
Destination device reads out
of range, zero, or incorrect.
Wireless device
has mismatched
input type.
• Make sure that input type on the device is
correct for the analog input being used.
Options are 4-20 mA, 0-10 V, 0-5 V, or 1-5 V.
Destination
device is not
scaled properly.
• Destination device must accept 4-20 mA
signal and be scaled to properly display the
signal. Check the manufacturer’s instruction
manual for how to do this.
Signal
connections are
improperly wired.
• Double check to make sure all of the signal
connections are properly wired to all devices.
Check wiring diagrams starting on page 10.
While trying to connect field
units using WR Manager,
none appear in the
Unassociated Remote Units
list.
Devices have
mismatched
network IDs.
• Devices will not connect if they do not have
the same network ID. Verify that all devices
share the same network ID.
Multiple field units
have same
Modbus address.
• If multiple field units share the same Modbus
address it will cause a conflict. Verify that all
field units have unique Modbus addresses.
Devices have
differing
encryption
settings.
• Encryption settings must be the same on all
devices. Use WR Manager to verify the
encryption settings on all devices.
Device will not power on.
Not enough
voltage is coming
from the power
supply.
• Devices require at least 12 VDC each in
order to power on. Check that the power
supply is providing enough voltage to the
device and that there are not too many
devices drawing from the supply.
Devices are
improperly wired.
• Check to make sure all power connections
are properly wired to all devices. Check
wiring diagrams starting on page 10.