BIG ASS FANS E7, E12, E10 Installation Manual

Page 1
INSTALLATION
GUIDE
E7, E10, E12
For help, call 1-877-BIG-FANS
or visit www.bigassfans.com
Page 2
Installation Checklist
Did a structural engineer approve the mounting structure? See page 5 for Big Ass Fans-approved
mounting structures.
Will the fan be installed so that the airfoils are at least 10 ft (3.05 m) above the oor?
Will the fan be installed so that the airfoils have at least 2 ft (0.61 m) of clearance from obstructions?
Will the fan be installed so that it is not subjected to high winds such as from a Heating, Ventilating, and Air Conditioning (HVAC) system or near a large garage door? If the fan is
mounted at the same level or higher than a diffuser, the airfoil tips must be at a distance that is at least 1x the measure of the fan’s diameter. If the fan is mounted at the same height or below a diffuser, the airfoil tips must be at a distance that is at least 2x the measure of the fan’s diameter.
Will the distance between multiple fans be at least 2.5x the fans’ diameter when measured from the centers of the fans?
If you ordered multiple fans, did you keep the parts of each fan together?
Customer Service: 1-877-BIG-FANS
(International: +1 859 233 1271)
Page 3
Installation Guide
E7, E10, E12
i
Installation Guide: October 2018 Rev. G 10/11/2018
Conforms to ANSI/UL STD 507–Electric Fans
Conforms to CSA C22.2 No.113–Fans & Ventilators
Contact Information
Manufacturing
2251 Innovation Drive Lexington, KY 40511
This product was manufactured in a plant whose Management System is certied as being in conformity with ISO 9001.
All trademarks used herein are the properties of their respective owners. No part of this document may be reproduced or translated into a different language without the prior written consent of Big Ass Fans. The information contained in this document is subject to change without notice.
www.bigassfans.com/patents www.bigassfans.com/product-warranties
Customer Service
2348 Innovation Drive Lexington, KY 40511 1-877-BIG-FANS Intl.: +1 859 233 1271 www.bigassfans.com
Warranty Returns
2251 Innovation Drive Lexington, KY 40511
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 4
ii
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
CAUTION: Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes and
standards.
CAUTION: When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
CAUTION: Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
WARNING: Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION: The installation of a Big Ass Fan must be in accordance with the requirements specied in this installation manual and with any additional requirements set forth by the National Electric Code (NEC), ANSI/NFPA 70-2011, and all local codes. Code compliance is ultimately YOUR responsibility! Failure to comply with these codes could result in personal injury or property damage.
CAUTION: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans if you have any questions regarding the electrical installation of this fan.
WARNING: To reduce the risk of re, electric shock, and injury to persons, Big Ass Fans must be installed with Big Ass Fan supplied controllers that are marked (on their cartons) to indicate the suitability with this model. Other parts cannot be substituted.
CAUTION: When service or replacement of a component in the fan requires the removal or disconnection of a safety device, the safety device is to be reinstalled or remounted as previously installed.
WARNING: Risk of re, electric shock, or injury to persons during cleaning and user-maintenance! Disconnect the fan from the power
supply before servicing.
CAUTION: Do not bend the airfoils when installing, adjusting, or cleaning the fan. Do not insert foreign objects in between rotating airfoils.
WARNING: Stay alert, watch what you are doing, and use common sense when installing fans. Do not install fans if tired or under the
inuence of drugs, alcohol, or medication. A moment of inattention while installing fans may result in serious personal injury.
CAUTION: The installation of this fan requires the use of some power tools. Follow the safety procedures found in the owner’s manual for each of these tools and do not use them for purposes other than those intended by the manufacturer.
CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure caused by improper installation.
WARNING: This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. Children should be supervised to ensure that they do not play with the appliance.
Leave this installation guide with the owner of the fan after installation is complete.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 5
Contents
Introduction
Pre-Installation
Installing the Fan
Important Safety Information ii Thank You 1 About this Fan 1
Parts Included 2 Tools Needed 3 Fan Diagram 4 Preparing the Work Site 5
1. Select Proper Angle Irons 6
2. Pre-drill Angle Irons 7
3. Secure Angle Irons (if span is longer than 8 ft) 7 4a. Fasten Single Angle Irons to Roof Structure Mounting Points 8 4b. Fasten Double Angle Irons to Roof Structure Mounting Points 9
5. Route Wiring and Safety Cable into Extension Tube 10
6. Attach Upper Mount and Upper Mounting Brace (to Extension Tube) 10
7. Attach Upper Mount (to Angle Irons) 11
8. Secure Safety Cable (to Angle Irons) 12
9. Secure Safety Cable (to Main Fan Unit) 12
10. Attach Main Fan Unit (to Extension Tube) 13
11. Tighten Hardware 13
12. Connect Power and Wall Controller Wiring 14
13. Install Cover Plate Assembly 15
14. Install Lower Cover Mounting Bracket 15
15. Install Lower Cover 16
16. Install Trim Ring 16
Installing Guy Wires
Installing Airfoils
Wiring the Fan
Mounting the Wall Controller
Operating the Fan
Preventive Maintenance
1. Attach Guy Wire Clamps 17
2. Attach Locking Carabiners to Guy Wire Clamps 18
3. Attach Beam Clamp 18
4. Route Guy Wire through Gripple® 19
5. Install Three Remaining Guy Wires 19
1. Attach Airfoil Tips (to Airfoils) 20
2. Position Airfoils 20
3. Attach Airfoils (to Main Fan Unit) 21
Electrical Safety Information 22 Power Requirements 22 Wiring Diagram 22 Wiring: Fire Signal Relay 23
Dimensions 24 Mounting to a Wall 24 Mounting to a Junction Box 24
Operating the Wall Controller 25 Changing the Fan Direction 25 Heating Season 26 Cooling Season 26
Annual Preventive Maintenance 27 General Preventive Maintenance 27
Annual Maintenance Checklist
Troubleshooting
Annual Maintenance Checklist 29
General Troubleshooting 31 Electrical Troubleshooting 32 Replacing Fuses 33
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 6
Contents
Warranty
Warranty Policy 35
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 7
Introduction
About this fan
Technical specications
Model Diameter Input power Minimum circuit size Rated current
E7 7 ft (2.13 m)
E10 10 ft (3.05 m)
E12 12 ft (3.66 m)
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
Φ 10 A 5.5 A
Φ 10 A 3.4 A
Φ 10 A 6.0 A
Φ 10 A 4.0 A
Φ 10 A 4.1 A
Φ 10 A 3.0 A
1
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 8
2
Pre-Installation
Parts included
CAUTION: Do not remove the main fan unit from its protective packaging or place it on a at surface prior to hanging it!
CAUTION: If you ordered multiple fans, be sure to keep the components of each fan together.
If you are missing any piece required for installation, contact Big Ass Fans Customer Service. Note: Drawings below are not to scale. All
boxes are labeled to identify the contents.
Hardware
1
Mounting Hardware
(5) M10 x 40 mm Hex Head Cap Screw (9) M10 Flat Washer (5) M10 Nylock Nut
Airfoil Tip Hardware
(7) M5 x 12 mm Button Head Screw
Lower Cover Hardware
(9) 6-32 x 3/8” Pan Head Screw
1. One extra of each piece of hardware is included except for the Safety Cable Hardware, Angle Iron Hardware, and Guy Wire Hardware.
2. Guy wires are designed to constrain the fan’s lateral movement. Big Ass Fans recommends using guy wires if the fan is exposed to high winds or similar conditions or if the
fan is close to any building xtures. Guy wires are packaged in the main box. The Guy Wire Hardware is packaged in the box with the extension tube.
Extension Tube Hardware
(3) M10 x 90 mm Socket Head Cap Screw (5) M10 Flat Washer (3) M10 Nylock Nut
Airfoil Hardware
(13) M8 x 18 mm Socket Head Cap Screw (13) 8 mm Belleville Washer
Angle Iron Hardware
(8) 3” Square Washer
Safety Cable Hardware
5/16” Clevis Pin
Cotter Pin
®
Gripple
Cover Plate Assembly Hardware
(3) 8-32 x 1/2” Flat Head Screw
Guy Wire Hardware
2
(2) Guy Wire Clamp (2) 1/4-20 X 1” Carriage Bolt (2) 1/4-20 Nylock Flange Nut (8) Locking Carabiner (4) 1/4” Beam Clamp
Main Fan Unit Hardware
(3) M8 x 75 mm Socket Head Cap Screw (5) M8 Flat Washer (3) M8 Nylock Nut
Lower Cover Mounting Bracket Hardware
(4) 8-32 x 3/8” Pan Head Screw
(4) 1/4-20 x 1” Eyebolt (4) 1/4-20 Hex Nut (4) Guy Wire (4) Gripple (16) Wire Rope Clip
Mounting
Main Fan Unit, Lower Cover, Lower
Upper Mount & Upper Mounting Brace
1. The upper mounting brace strengthens the upper mounting system and must be installed inside the top of the extension tube.
2. Two (2) safety clips and two (2) carabiners are provided for safety cable installation in locations where the top of the mounting structure is inaccessible. Contact Customer Service if you need assistance installing the safety cable.
1
Cover Mounting Bracket, & Trim Ring
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Extension Tube & Safety Cable
2
Page 9
Parts included (cont.)
Note: Drawings below are not to scale.
Pre-Installation (cont.)
3
Electrical
Wall Controller
20-ft Power
Supply Cable
1. The cover plate assembly includes a fan status LED and a switch used to change the direction of fan rotation. The LED will ash an error code if there is a problem with the fan. See page 32 for information on the fan status LED. See page 25 for information on changing the fan direction.
2. The re relay is provided for fans that will be installed in buildings that have a re sprinkler system. See page 23 for re relay wiring details.
3. The CAT5 cable connects the wall controller to the fan. One end plugs into the wall controller, and the other end plugs into the controller input cable.
See pages 22–23 for wiring details. A longer CAT5 cable can be used if needed (customer-supplied).
Cover Plate
Assembly
20-ft Controller
Input Cable
1
Fire Relay
100-ft CAT5
Cable
2
(6) Airfoil Tip (6) Airfoil Retainer
3
Airfoils
(6) Airfoil
Tools needed
Big Ass Fans recommends gathering the following tools prior to beginning installation.
Mechanical installation
Standard and metric wrench sets
Standard and metric socket and ratchet sets
Torque wrench capable of 29 ft·lb (39.3 N·m)
Phillips and at head screwdrivers
Metric Allen wrench set
Metric Allen head sockets
Drill
Hacksaw
Level
Tape measure
Electrical installation
Phillips and at head screwdrivers
#10 to #14 AWG strippers
Medium size channel locks
Multimeter
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 10
4
Pre-Installation (cont.)
Fan diagram
Refer to the diagram below to identify the fan components. Note: The safety cable is not pictured below; however, it is an important part of the installation.
A. Upper mount. Secures the fan to the mounting structure.
B. Extension tube. Extends the fan from the ceiling and provides a path for wiring.
C. Upper mounting brace. Strengthens the upper mounting system.
D. Cover plate assembly. Provides access to wiring and includes a fan status LED and a switch used to change the direction of fan
rotation. The LED will ash an error code if there is a problem with the fan. See page 32 for LED error codes. See page 25 for
information on changing the fan direction.
E. Main fan unit. Includes the motor, hub, and power wiring.
F. Airfoil. Provides air movement. The unique, patented design provides efcient and effective air movement.
G. Airfoil tip. Ensures quiet fan operation.
H. Electronics cover. Provides access to the fan electronics and fuses. See page 33 for information on replacing fuses.
C
G
F
A
B
D
H
E
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 11
Pre-Installation (cont.)
Preparing the work site
The fan should only be installed according to the instructions described in this manual. Consult a structural engineer for installation methods not covered in this manual.
When surveying the work site, keep the following mechanical and electrical guidelines in mind.
Mechanical
• The main fan unit is heavy. A suitable means for lifting the weight of the fan, such as a scissor lift, and at least two installation
personnel will be required.
• If hanging the fan from angle irons, the minimum dimensions of the angle iron must be 2-1/2’’ × 2-1/2’’ × 1/4’’
(6.4 cm × 6.4 cm × 0.6 cm) and it cannot be longer than 12 ft (3.7 m). It must be secured to the structure. Do not mount the fan to a single purlin, truss, or bar joist. Consult a structural engineer for installation methods not covered in this manual.
To reduce the risk of injury to persons, install the fan so that the airfoils are at least 10 ft (3.05 m) above the oor.
• If mounting the fan in the vicinity of an infrared/radiant heater, it is recommended that the fan be mounted outside of the clearances
recommended by the manufacturer of the heater and at a height equal to or above the shielding on the heating element with the controller on the opposite side of the heater. If mounting the fan below the heater shielding, all fan elements must be outside of the
clearances recommended by the heater manufacturer. The installation manual for the specic model of heater will typically provide
the minimum clearance to combustibles (MCC).
• Adhere to the safety requirements in the table below when selecting where to mount the fan.
Safety requirement Minimum distances
Clearance
Blade height ≥10 ft above the floor
HVAC equipment ≥1x fan diameter if above diffuser. ≥2x fan diameter if below diffuser. Refer to the illustration below.
Fan spacing 2.5x fan diameter, center-to-center
Radiant/IR heaters See the manufacturer’s requirements for the minimum clearance to combustibles.
≥2 ft from all fan parts and ≥3 ft below sprinklers. The fan installation area must also be free of
obstructions such as lights, cables, or other building structure.
5
HVAC Diffuser
≥1x fan’s diameter (12 ft)
HVAC Diffuser
(3.7 m)
12-ft diameter
the HVAC discharge or intake.
The fan is located below the HVAC discharge or intake.
The fan is located at or above
≥2x fan’s diameter (24 ft) (7.3 m)
12-ft diameter
Electrical
• Ensure power wiring is routed to a junction box at the fan location prior to installation.
To reduce the risk of electric shock, wiring should be performed by a qualied electrician! Incorrect assembly can cause electric
shock or damage the motor and the controller!
• Installation of a Big Ass Fan must be in accordance with the National Electrical Code (NEC), ANSI/NFPA 70-2011, and local codes.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 12
6
WARNING: The fan should not be installed unless the structure on which the fan is to be mounted is of sound construction, undamaged, and capable of supporting the loads of the fan and its method of attachment. A structural engineer should verify that the mounting structure is adequate prior to fan installation. Verifying the stability of the mounting structure is the sole responsibility of the customer and/or end user, and Big Ass Fans hereby expressly disclaims any liability arising therefrom, or arising from the use of any materials or hardware other than those supplied by Big Ass Fans or otherwise specied in these installation instructions.
CAUTION: Do not install the fan from a single purlin or truss or junction box.
CAUTION: Unsupported angle iron spans should not exceed 12 ft (3.7 m).
Installing the Fan
1. Select proper angle irons
Follow the table below when selecting angle irons for fan installation. Note: Angle irons and angle iron hardware are not included with the fan.
Angle iron span
(between mounting points)
6 ft (1.8 m) or less 2.5” (6.4 cm) x 2.5” (6.4 cm) x 0.25” (0.6 cm) 2
over 6 ft (1.8 m) to 8 ft (2.4 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm) 2
over 8 ft (2.4 m) to 12 ft (3.7 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm) 4*
*Two pairs of angle irons. Pairs should be placed back to back and fastened in center (see step 3).
Minimum angle iron dimensions
(W x H x T)
6’ (1.8m) or less
Number of angle
irons needed
Angle Iron Side View
(see table for dimensions)
Thickness
Height
Width
over 6’ (1.8m) – 8’ (2.4 m)
over 8’ (2.4 m) – 12’ (3.7 m)
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 13
Installing the Fan (cont.)
2. Pre-drill angle irons
Drill two Ø 7/16” (1.1 cm) holes exactly 5-1/2” (14 cm) apart in the centers of two angle irons.
Measure the distance between the mounting points of the roof structure that the angle irons will span. Measure the same distance on the angle irons, and drill Ø 9/16” (1.4 cm) holes through each end of the angle irons. Drill holes in two angle irons if span is 8 ft (2.4 m) or less. Drill holes in four angle irons if span is greater than 8 ft (2.4 m).
7
Ø 9/16’’ (1.4 cm) Ø 7/16’’ (1.1 cm)
5-1/2’’ (14 cm)
Distance between roof structure mounting points
3. Secure angle irons (if span is longer than 8 ft)
If the angle iron span is 8 ft (2.4 m) or less, proceed to step 4a on the following page.
If the angle iron span is longer than 8 ft (2.4 m), it is necessary to use double angle irons.
Locate the center of the angle iron length. Drill Ø 9/16” (1.4 cm) hole through the center of the vertical wall of the angle iron. Drill a total of four angle irons.
A
1/2 A
c
b
Place two drilled angle irons back to back. Fasten the angle irons together with customer-supplied Grade 8 hardware.
Align the angle irons to each other and tighten the bolts to 25 ft·lb (33.9 N·m) using a torque wrench with a 3/4” or 19 mm socket.
Repeat step for remaining two angle irons.
Proceed to step 4b.
Angle Iron Hardware (Customer-Supplied):
a. (2) 1/2-13 or M12 Bolt b. (4) 1/2” or M12 Washer c. (2) 1/2” or M12 Nut
b
a
Side view
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 14
8
Installing the Fan (cont.)
4a. Fasten single angle irons to roof structure mounting points
If installation requires double angle irons, i.e., span is greater than 8 ft (2.4 m), proceed to step 4b.
CAUTION: The angle irons must be fastened to the roof structure at each end.
Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown. Tighten the hardware so that it is snug, but do not torque until the fan has been mounted to the angle irons. Note: Big Ass Fans
recommends orienting the angle irons so that the horizontal legs are facing each other. Refer to the illustration below.
Proceed to step 5.
Angle Iron Hardware (Customer-Supplied):
a. (4) 1/2-13 or M12 Bolt b. (8) 1/2” or M12 Washer c. (4) 1/2” or M12 Nut
a
b
Angle Iron Hardware:
d. (8) 3” Square Washer (see diagram)
Square Washer
3”
(7.6 cm)
Ø 9/16”
(1.4 cm)
Thickness:
1/4” (6 mm)
3”
(7.6 cm)
d
b
c
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 15
A
Installing the Fan (cont.)
4b. Fasten double angle irons to roof structure mounting points
CAUTION: The angle irons must be fastened to the roof structure at each end.
Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown. Tighten the hardware so that it is snug, but do not torque until the fan has been mounted to the angle irons.
Proceed to step 5.
9
Angle Iron Hardware (Customer-Supplied):
a. (8) 1/2-13 or M12 Bolt b. (16) 1/2” or M12 Washer c. (8) 1/2” or M12 Nut
a
b
Angle Iron Hardware:
d. (8) 3” Square Washer (see diagram)
Square Washer
(7.6 cm)
Ø 9/16”
(1.4 cm)
Thickness:
1/4” (6 mm)
3”
3”
(7.6 cm)
d
b c
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 16
10
Installing the Fan (cont.)
5. Route wiring and safety cable into extension tube
Note: To facilitate installation, Big Ass Fans recommends that the extension tube is horizontal with the rectangular access hole facing up during this step.
To route the wiring and safety cable into the extension tube:
1. Route the end of the controller input cable with the wiring harness on it (the
end without the three loose wires) down into the top of the extension tube and out the rectangular access hole as shown.
2. Route the end of the power supply cable with the wiring harness on it down
into the top of the extension tube and out the rectangular access hole as shown.
3. Route the end of the safety cable with the lug on it down into the top of the
extension tube and out the bottom of the tube as shown.
Controller Input
Cable
Access Hole
6. Attach upper mount and upper mounting brace (to extension tube)
Note: To facilitate installation, Big Ass Fans recommends that the extension tube is horizontal with the rectangular access hole facing up during this step. Wiring and the and safety cable are not shown in the illustrations.
Insert the upper mounting brace into the top of the extension tube and align the four (4) mounting holes in the brace with the four (4) mounting holes at the top of the tube as shown on the right. Position the power supply cable, controller input cable, and safety cable in any of the four (4) spaces between the upper mounting brace and the extension tube as shown below. Note: The
cables can go in any of the four spaces. They do not all need to be in the same space.
Power Supply
Cable
Safety Cable
Upper Mounting Brace
Attach the upper mounting brace (inside the extension tube) and the upper mount to the extension tube using the Extension Tube Hardware as shown below. Tighten the hardware so that it is
snug, but do not torque.
Extension Tube Hardware:
a. (2) M10 x 90 mm Socket Head Cap Screw b. (4) M10 Flat Washer c. (2) M10 Nylock Nut
Spaces for cables
(use any of the four)
a
Extension tube with upper
mounting brace inside
(view from above)
Upper Mounting Brace
b
c
b
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 17
Installing the Fan (cont.)
11
7. Attach upper mount (to angle irons)
Secure the upper mount (with extension tube and upper mounting brace already attached) directly to the angle irons using the Mounting Hardware as shown. Consult the diagrams below for distances between the angle irons. Tighten the hardware so that it is snug, but
do not torque.
Mounting Hardware:
a. (4) M10 x 40 mm Hex Head Cap Screw b. (8) M10 Flat Washer c. (4) M10 Nylock Nut
5 1/2” (13.97 cm)
5 1/2” (13.97 cm)
Note: Dashed lines represent angle irons.
Side View
a
b
b
c
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 18
12
Installing the Fan (cont.)
8. Secure safety cable (to angle irons)
WARNING: The safety cable is a crucial part of the fan and must be installed correctly. If you have any questions, call Customer Service.
To secure the safety cable to the angle irons:
1. Route the free end of the safety cable into one of the
two (2) holes in the Gripple through the Gripple until the Gripple rests at the top of the extension tube.
2. Wrap the safety cable around the angle irons, leaving
6–10 in. (15.2–25.4 cm) of slack.
3. Route the loose end of the safety cable through the
remaining hole in the Gripple and pull to tighten
®
, and then pull the cable
.
6–10 in.
9. Secure safety cable (to main fan unit)
CAUTION: Do not remove the main fan unit from its protective packaging or place it on a at surface prior to hanging it!
CAUTION: To prevent damage, avoid contact with the stator wires located on the bottom of the main fan unit!
CAUTION: The main fan unit is heavy. Use caution when raising it.
(15.2–25.4 cm)
Raise the main fan unit directly from its packaging to the extension tube. Route the three (3) sets of wires from the main fan unit up into the bottom of the extension tube and out the rectangular access hole near the bottom of the tube. Ensure the wires are positioned inside the grooves on the motor shaft. Note: Wiring not shown in the illustrations below.
While supporting the main fan unit, secure the safety cable to the motor shaft using the Safety Cable Hardware as shown. Insert the clevis pin through the safety cable lug and motor shaft, and then insert the straight leg of the cotter pin into the small hole on the clevis pin.
Safety Cable Hardware:
a. 5/16” Clevis Pin b. Cotter Pin
6–10”
(15.2–25.4 cm)
a
Route wires from main fan unit out here
Safety Cable
b
Cotter Pin Inserted into Clevis Pin
Safety Cable
a
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
b
Page 19
Installing the Fan (cont.)
10. Attach main fan unit (to extension tube)
CAUTION: The main fan unit is heavy. Use caution when raising it.
CAUTION: Be careful not to pinch the fan wiring between the extension tube and main fan unit during installation.
CAUTION: Do not discard the main fan unit packaging and foam. It should be used if the fan is ever moved or relocated.
Attach the main fan unit to the extension tube using the Main Fan Unit Hardware as shown. Note: Wiring not shown in the illustration on the
right.
Tighten the hardware to 25 ft·lb (33.9 N·m) using a 6 mm Allen wrench and a torque wrench with a 13 mm socket.
Main Fan Unit Hardware:
a. (2) M8 x 75 mm Socket Head Cap Screw b. (4) M8 Flat Washer c. (2) M8 Nylock Nut
13
c
b
a
b
11. Tighten hardware
After attaching the main fan unit to the extension tube, tighten the following hardware to the specied torque.
Tighten the Mounting Hardware to 25 ft·lb (33.9 N·m) using a 17 mm wrench and a torque wrench with a 17 mm socket.
Mounting Hardware
Allow the extension tube to hang freely and balance itself, and then tighten the Extension Tube Hardware to 25 ft·lb (33.9 N·m) using an 8 mm Allen wrench and a torque wrench with a 17 mm socket.
Extension Tube Hardware
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 20
14
A
Tighten all hardware securing the angle irons to the roof structure (Angle Iron Hardware) to 40 ft·lb (54.2 N·m) using a 3/4” or 19 mm wrench and a torque wrench with a 3/4” or 19 mm socket.
Angle Iron Hardware (single angle irons) Angle Iron Hardware (double angle irons)
Installing the Fan (cont.)
12. Connect power and wall controller wiring
Plug the male wiring harnesses on the fan wiring into the female wiring harnesses on the power supply cable and the controller input cable as shown. Carefully tuck the wiring into the extension tube.
Power Supply
Cable
Controller Input
Cable
Power Wiring
Wall Controller Wiring from Fan
(8 wires)
from Fan
(3 wires)
Cover Plate Assembly Wiring from Fan
(4 wires, to be connected later)
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 21
Installing the Fan (cont.)
13. Install cover plate assembly
Plug the remaining male wiring harness from the fan into the female wiring harness on the cover plate assembly as shown.
15
Ensure all wiring is tucked inside the extension tube, and then attach the cover plate assembly to the extension tube using the Cover Plate Assembly Hardware as shown.
Cover Plate Assembly Hardware:
(2) 8-32 x 1/2" Flat Head Screw
14. Install lower cover mounting bracket
Remove the protective plastic cover from the bottom of the main fan unit before installing the mounting bracket.
Cover Plate Assembly
Ensure that the three (3) stator wires on the bottom of the main fan unit are tucked in securely before installing the mounting bracket. Be careful not to damage the stator wires while installing the mounting bracket and lower cover.
WARNING: Disconnect power to the fan before installing the lower cover mounting bracket and lower cover.
Attach the lower cover mounting bracket to the bracket on the bottom of the main fan unit using the Lower Cover Mounting Bracket Hardware as shown. Loosely attach all three (3) screws, and then tighten them.
Lower Cover Mounting Bracket Hardware:
(3) 8-32 x 3/8" Pan Head Screw
Lower Cover Mounting Bracket
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 22
16
Installing the Fan (cont.)
15. Install lower cover
WARNING: Disconnect power to the fan before installing the lower cover mounting bracket and lower cover.
Attach the lower cover to the lower cover mounting bracket using the Lower Cover Hardware as shown. Loosely attach all eight (8) screws, and then tighten them.
Lower Cover Hardware:
(8) 6-32 x 3/8" Pan Head Screw
Lower Cover
16. Install trim ring
Snap the trim ring onto the lower cover as shown.
Trim Ring
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 23
Installing Guy Wires
Guy wires are designed to constrain the fan’s lateral movement. Big Ass Fans recommends using guy wires if you are installing the 4-ft (1.2 m) extension tube, if the fan is exposed to high winds or similar conditions, or if the fan is close
to any building xtures.
WARNING: Disconnect power to the fan before installing the guy wires.
17
1. Attach guy wire clamps
Position the guy wire clamps between the two bolts at the bottom of the extension tube. Refer to the diagram below. Secure the clamps to the extension tube using the Guy Wire Hardware.
Guy Wire Hardware:
a. (2) 1/4-20 x 1” Carriage Bolt b. (2) 1/4-20 Nylock Flange Nut
Guy Wire Clamps
Position the guy wire clamps between the two bolts at the bottom of the extension tube.
b
a
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 24
18
Installing Guy Wires (cont.)
2. Attach locking carabiners to guy wire clamps
Secure the four (4) locking carabiners to the guy wire clamps as shown.
Securely tighten the carabiners.
3. Attach beam clamp
The guy wire should be at a 45° angle from the extension tube (see the illustrations on the following page). Attach the beam clamp to the mounting structure accordingly.
For best results, the guy wires should be installed at 45° in the X-Y, Y-Z, and X-Z planes as shown on the following page. If the angle deviates by more than 15°, contact Customer Service for assistance.
a
b
Fasten the small eyebolt and nut onto the beam clamp (the nut will be on the outside of the beam clamp).
Loop the crimped end of the guy wire into the locking carabiner and secure to the eyebolt as shown. Securely tighten the carabiner.
Guy Wire Hardware:
a. 1/4” Beam Clamp b. 1/4-20 x 1” Eyebolt c. 1/4-20 Hex Nut d. Locking Carabiner e. Guy Wire
d
c
e
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 25
Installing Guy Wires (cont.)
45°
19
4. Route guy wire through Gripple
Route the guy wire through the Gripple® and the carabiner on the guy wire clamp, and then back through the Gripple as shown below. Do not tighten the Gripple until the remaining guy wires have been installed.
Note: To back the guy wire out of the Gripple, insert the small tool included with the Gripple set or a 0.050" Allen wrench into the small hole on the Gripple.
Note: Angle irons mounted to bar joists are shown in the illustration below. Your mounting structure may differ.
®
Gripple
45º 45º
Guy Wire
Guy Wire
5. Install three remaining guy wires
CAUTION: Over-tightening the guy wires could throw the fan off balance.
Repeat steps 3–4 to install the three remaining guy wires.
Evenly cinch all four guy wires into place using the Gripples. The guy wires should be taut, evenly spaced around the fan, and away from the path of the airfoils. Maintain a distance of 6”–8” between the Gripple and the carabiner.
Once all of the guy wires are taut, secure their loose ends with the wire rope clips and torque to 4.5 ft·lb (6.1 N·m). Ensure all electrical cords/cables are unobstructed by the
guy wire system.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Wire Rope Clip
Page 26
20
Big Ass Fans recommends wiring the fan (page 22) before installing the airfoils.
WARNING: Disconnect power to the fan before installing the airfoils.
Installing Airfoils
1. Attach airfoil tips (to airfoils)
Attach the airfoil tips to the airfoils using the Airfoil Tip Hardware as shown. Securely tighten the screws using a 3 mm Allen wrench. Attach airfoil tips to all six (6) airfoils before attaching the airfoils to the fan.
Airfoil Tip Hardware:
(6) M5 x 12 mm Button Head Screw
2. Position airfoils
Slide the airfoils onto the tabs as shown.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 27
Installing Airfoils (cont.)
21
3. Attach airfoils (to main fan unit)
WARNING: Disconnect power to the fan before installing airfoils.
Attach the six (6) airfoil retainers using the Airfoil Hardware. Moving clockwise around the fan hub, position the airfoil retainers as shown. Hole A of the retainer should be positioned over top of Hole B. Do not tighten the bolts until all airfoil retainers have been
attached!
Tighten the bolts along the outside perimeter to 29 ft·lb (39.3 N·m) using a torque wrench with a 6 mm Allen head socket. After the outer perimeter bolts are torqued, tighten the bolts along the inner perimeter to 29 ft·lb (39.3 N·m).
Airfoil Hardware:
a. (12) M8 x 18 mm Socket Head Cap Screw b. (12) 8 mm Belleville Washer
Belleville Washer
Airfoil Retainer
Hole A
Hole B
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
a
b
Page 28
22
Wiring the Fan
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualied electrician! Incorrect assembly
can cause electric shock or damage the motor and the controller! Hazard of electrical shock!
WARNING: The installation of a Big Ass Fan must be in accordance with the requirements specied in this installation manual and with any additional requirements set forth by the National Electric Code (NEC), ANSI/NFPA 70-2011, and all local codes. Code compliance is ultimately YOUR responsibility!
WARNING: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans if you have any questions regarding the electrical installation of this fan.
Power requirements
The fan is shipped with either a 110–125 VAC motor or a 200–240 VAC motor. The fan’s voltage is marked on the fan packaging and on the label on top of the main fan unit. The voltage cannot be changed during installation. Ensure your fan is the correct voltage prior to beginning installation.
Model Diameter Input power Minimum circuit size Rated current
E7 7 ft (2.13 m)
E10 10 ft (3.05 m)
E12 12 ft (3.66 m)
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
110–125 VAC, 50/60 Hz, 1
200–240 VAC, 50/60 Hz, 1
Φ 10 A 5.5 A
Φ 10 A 3.4 A
Φ 10 A 6.0 A
Φ 10 A 4.0 A
Φ 10 A 4.1 A
Φ 10 A 3.0 A
Wire color chart and wiring diagram
AC Line (L1) AC Line/Neutral (L2/N) Earth/PE
North America 100–120 V system
North America 208–240 V system
Australia Brown or Red Black or Light Blue
All other regions Brown Blue
Power Supply
Power
Supply
GREEN
Cable
WHITE
L1/AC LINE
PE/GROUND
L2/AC NEUTRAL
BLACK
Black White
Black, Red, or Blue Red, Blue, or Black
Controller Input Cable
BLUE YELLOW
Green or Bare Copper
Green with Yellow Tracer
CAT5 Cable
Controller Input Cable
White +0-10 VDC Speed Ref.
Brown Not Used
Orange Status LED (+)
Yellow
Blue
Green Status LED (-)
Red +10 VDC Supply
Black DC Common
Run Enable Closed: Enable, Open: Disable
To wall
controller
Wall Controller
See page 24 for
mounting instructions.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 29
Wiring the Fan (cont.)
23
Wiring: Fire signal relay
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualied electrician! Incorrect assembly
can cause electric shock or damage the motor and the controller! Hazard of electrical shock!
CAUTION: Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable
codes and standards.
ATTENTION: If installing the re relay, the fan must be installed per the following National Fire Protection Association (NFPA)
guidelines:
• The fan must be centered approximately between four adjacent sprinklers.
• The vertical distance from the fan to the sprinkler deector must be at least 3 ft (91.4 cm).
• The fan must be interlocked to shut down immediately upon receiving a waterow signal from the alarm system.
The re relay is provided for fans that will be installed in buildings that have a re sprinkler system. The re relay integrates the fan with
the sprinkler system and shuts down the fan upon receiving an alarm signal from the system.
Controller Input Cable
White +0-10 VDC Speed Ref.
Brown Not Used
Orange Status LED (+)
Yellow
Blue
Green Status LED (-)
Red +10 VDC Supply
Black DC Common
Note: In the conguration shown, power must be applied to the re relay to enable
fan operation.
Run Enable Closed: Enable, Open: Disable
RED
YELLOW
ORANGE
WHITE
From main FACP or NAC box, if applicable
RED
WHITE
Controller
Input Cable
Wall Controller
See page 24 for
mounting instructions.
YELLOW
BLUE
BLUE
Relay Coil/Contact Details
White (X2) (-) C Blue
NC Yellow
Red (X2) (+) NO Orange
Coil: 20–32 VDC @ 20 mA
CAT5 Cable
To wall
controller
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 30
24
Mount the wall controller so that the fan it controls is visible from the controller location. Install the controller on a at surface that is
readily accessible, free from vibration, and where there is adequate distance from foreign objects or moving equipment. The controller
can be surface-mounted to a wall or mounted to a customer-supplied junction box.
Mounting the Wall Controller
Dimensions
2.96” (7.52 cm)
4.71” (11.97 cm)
2.95” (7.49 cm)
Mounting to a wall
To mount the wall controller to a wall:
1. Attach the back plate of the wall controller to the wall
using suitable customer-supplied mounting screws. Use any of the available mounting holes on the back plate.
2. Route the CAT5 cable from the fan through any of the
available knockouts on the wall controller, and connect it to the CAT5 connector inside the controller. Note:
Knockouts and the CAT5 cable are not shown in the illustration on the right.
3. Snap the controller onto the back plate as shown.
Wall Controller
Back Plate
(mounted to wall
with customer-
supplied screws)
Mounting to a junction box
Note: A junction box is not supplied.
To mount the wall controller to a junction box:
1. Remove the wall controller’s front cover assembly by
unscrewing the two (2) screws on the front cover. Set the screws aside in a safe location.
2. Route the CAT5 cable from the fan into the junction box
and connect it to the CAT5 connector on the front cover assembly.
3. Mount the front cover assembly to the junction box using
the two (2) screws as shown.
Wall Controller Hardware:
(2) 6-32 x 1/2” Oval Head Screw
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
CAT5
Cable
Junction Box
(in wall,
customer-supplied)
Wall Controller
Front Cover Assembly
Page 31
Operating the Fan
Operating the wall controller
To start the fan, press the control knob on the wall controller. Note: The LED
indicator at the top of the controller is lit when power is applied. The LED indicator
will ash an error code if there is a problem with the fan. See page 32 for LED
error codes.
To stop the fan, press the control knob.
25
LED Indicator
To increase fan speed, turn the control knob clockwise toward
To decrease fan speed, turn the control knob counterclockwise toward
Note: The fan may take 30–60 seconds to start rotating after it is turned on. It is normal to see an initial slight jerking forward and
backward upon startup as the fan positions itself relative to the motor stator.
.
.
Changing the fan direction
Big Ass Fans recommends operating the fan in the forward (FWD) direction. The fan should be rotating counterclockwise when viewed from below.
To reverse the direction of the fan, remove power from the fan. Select the direction of the fan using the fan direction selector switch
located on the fan’s cover plate assembly. Reapply power to the fan. For fan status LED denitions, see page 32.
Fan Direction Selector Switch
Cover Plate Assembly
Fan Status LED
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 32
26
Moving at a low speed means less energy used for operation, translating into more energy savings year-round. Follow the procedures below to ensure the most efcient operation of your Big Ass Fan.
To ensure proper fan rotation:
1. Turn on the fan.
2. Verify that the fan is rotating in the counterclockwise direction (when viewed from below).
3. If the fan is not rotating counterclockwise, reverse the fan direction. See the previous page for instructions on changing the direction
of rotation.
Operating the Fan (cont.)
Heating season
In spaces with higher ceilings, E7, E10, and E12 fans return heat from the ceiling to oor level more efciently than smaller ceiling
fans. For maximum energy savings, the fan should be operated continuously during the heating season and should not be operated in reverse (clockwise). Big Ass Fans are designed to operate efciently at very low speeds, so turning the fan very slowly in the forward
direction (counterclockwise) will provide enough air movement to circulate the hot air at the ceiling down to the oor without causing a
draft.
Stand directly below the tips of the airfoils with hand outstretched. If you feel a draft, slightly decrease the fan speed. Repeat until the draft is no longer noticeable.
Cooling season
The cooling effect created by the breeze from E7, E10, and E12 fans keeps occupants comfortable with the thermostat at a higher setting. During the cooling season, every degree higher that the thermostat is reset reduces the energy consumed by the air conditioner by 1.5–2%. To minimize energy usage during the cooling season, operate the fan only when building occupants are present.
Increase the speed of the fan until desired air speed or maximum fan speed is reached. In air conditioned facilities, increase the thermostat setting by 2 to 7°F to reduce energy consumption and save energy.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 33
Preventive Maintenance
WARNING: Before servicing or cleaning unit, switch power off at the service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device (such as a tag) to the service panel.
WARNING: When service or replacement of a component in the fan requires the removal or disconnection of a safety device, the safety device is to be reinstalled or remounted as previously installed.
Please take a few moments each year to perform the following preventive maintenance inspection on your fan to ensure its safe and
efcient operation. Before contacting Customer Service, try resolving the issue using the troubleshooting procedures on page 31. If you
have any questions, contact Customer Service.
27
Annual preventive maintenance
Perform the following maintenance procedures each year using the Annual Maintenance Checklist on page 29.
1. Ensure all upper mounting bolts are present and torqued to 25 ft·lb (33.9 N·m).
2. Ensure airfoils are secured to one another by airfoil retainers.
3. Ensure all 12 bolts securing the airfoils to the fan are present and torqued to 29 ft·lb (39.3 N·m).
4. Ensure the two (2) bolts securing the extension tube to the main fan unit are present and torqued to 25 ft·lb (33.9 N·m).
5. Ensure all airfoil tip hardware is secure.
6. Check guy wires (if installed) for fraying or damage (not shown in the illustration below).
General preventive maintenance
Verify proper fan rotation. To be effective, the fan must be turning counterclockwise when viewed from the oor.
• Dust airfoils and motor. If desired, use a gentle cleaner or degreasing agent to polish the airfoils. Do not use Clorox® or other chlorine
based cleaners! This could result in the release of toxic/fatal fumes. Do not use cleansers on the electronics enclosure.
• Check that the safety cable and upper mounting system are secure.
• Observe the motion of the fan during operation. The fan should not wobble or precess. If any wobble is noticed, ensure the mounting
structure is rigid enough to support the fan and that the guy wires, if used, are sufciently taut. If guy wires were not used, Big Ass Fans suggests installing them. Contact Customer Service.
WARNING: Do not operate a fan with missing or damaged components. Please contact Customer Service.
1
5
4
View from Below
2
3
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 34
Notes
Page 35
Annual Maintenance Checklist
Fan Model: Fan Model: Fan Model:
Serial #: Serial #: Serial #:
Location: Location: Location:
Date Initials Date Initials Date Initials
Page 36
Page 37
Troubleshooting
WARNING: When servicing or replacement of a component in the fan requires the removal or disconnection of a safety device, the safety device is to be reinstalled or remounted as previously installed.
CAUTION: Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
WARNING: Before servicing or cleaning unit, switch power off at the service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
31
General troubleshooting
For questions about your product or customer service inquiries, please call our toll free number (1-877-BIG-FANS).
Some issues can be resolved before requesting service. Review the below troubleshooting tips before contacting Customer Service for support.
Symptom Possible solution(s)
A popping noise is coming from the fan.
Airfoil noise is a result of airfoils that are
not tightened to the specied torque.
The fan will not start. Verify the following:
Switch off power at the service panel and lock the service disconnecting means. (If it cannot be locked, fasten a prominent warning device.) Tighten the airfoil hardware to 29 ft·lb (39.3 N·m). If popping still occurs, verify that the airfoils are not contacting each other. If the airfoils are contacting each other, please contact Customer Service.
• All wires are securely connected.
• The blue wire and the yellow wire on the controller input cable are wired together. See pages 22–23 for wiring details.
• The wall controller has power.
• Supply power is adequate and functional.
• All fuses are functional. If a fuse is blown, see page 33 for instructions on replacing fuses.
If the fan still does not start, contact Customer Service.
The LED on the wall controller is ashing.
The LED on the wall controller will ash
an error code if there is a problem with the fan.
The fan jerks upon startup. This is normal and may happen occasionally upon startup as the fan positions itself
See the following page for fan error code descriptions and possible solutions.
relative to the motor stator. An initial slight jerking forward and backward does not affect fan operation.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 38
32
Troubleshooting (cont.)
Electrical troubleshooting
Fan status LED denitions
The fan direction selector switch and fan status LED are located on the cover plate assembly at the bottom of the fan’s extension tube.
Fan Direction Selector Switch
Cover Plate Assembly
Fan Status LED
Note: For information on changing the fan direction, see page 25.
LED status: Denition:
One 1/2-Second Flash/4 Seconds Off Over Temperature
Two 1/2-Second Flashes/4 Seconds Off Motor Stall
Three 1/2-Second Flashes/4 Seconds Off Output Device Failure
Four 1/2-Second Flashes/4 Seconds Off Internal Communication Error
Five 1/2-Second Flashes/4 Seconds Off DC Buss Undervoltage
Six 1/2-Second Flashes/4 Seconds Off DC Buss Over Voltage
Seven 1/2-Second Flashes/4 Seconds Off Run Enable Jumper Open
Eight 1/2-Second Flashes/4 Seconds Off Motor Overload/Thermal Trip
Nine 1/2-Second Flashes/4 Seconds Off Current Limit/Short Circuit
Fan status LED troubleshooting
LED code Description/Possible cause(s) Possible solution(s)
Over Temperature
Output Device Failure
Internal Communication Error
DC Buss Undervoltage Buss voltage has fallen below 255 VDC.
DC Buss Over Voltage Buss voltage has exceeded 373 VDC.
Motor Overload/Thermal Trip Thermal motor overload protection has been activated.
Current Limit/Short Circuit
Motor Stall
Run Enable Jumper Open
The fan drive electronics have exceeded safe operating temperature limits.
The fan drive electronics have failed or output phase loss has occurred.
The main fan drive has failed to respond to the command source (daughterboard, etc.).
The hardware current limit has been reached. A severe overload or short circuit condition exists on the fan drive output.
The fan failed to accelerate to the target RPM within one (1) minute of startup.
The run enable circuit is open and motor operation is disabled.
The fan will shut down for ve (5) minutes
and then attempt to restart two (2) times. If the fan does not restart after two attempts, reset power to the fan. If the fan still does not restart, contact Customer Service.
The fan will shut down and will not attempt to restart. Contact Customer Service.
Make sure the blue wire and the yellow wire on the controller input cable are wired together. See pages 22–23 for wiring details.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 39
Troubleshooting (cont.)
33
Replacing fuses
WARNING: Ensure power is disconnected before replacing fuses.
CAUTION: Do not touch the fan’s electronics unless necessary!
To replace the fuses on the main fan unit, remove the electronics cover from the fan as shown. The electronics cover is attached to the fan with four (4) screws. Gently twist and pull out the appropriate fuse holder, and replace the fuse. Reinstall the fuse holder, and then reattach the fan’s electronics cover. See below for fuse recommendations.
Electronics Cover
Fuse Holders
Suitable Fuse Replacements
250 VAC 10 A (AC Mains Supply)
• Bussman S505 Series
• Littelfuse 215 Series
• Mersen Fuse GSF
• Bel Fuse 5HT
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 40
Page 41
Warranty Policy
35
Congratulations on your purchase of a Big Ass Fan! We are delighted that you have chosen our product to improve the quality of your environment, and hope you’ll have much pleasure using the fan for years to come.
Warranty period
Item Period of coverage
Hub and airfoils Lifetime (parts)
Motor and controller 1 year (parts)
All other fan components 1 year (parts)
What is covered?
This Warranty covers any defects in materials or workmanship under normal use and maintenance that adversely affect the ability of the fan to operate properly when the product is installed correctly according to Big Ass Fans’ written installation instructions by a state
qualied or licensed electrical contractor and operated pursuant to these instructions, and when such fans are purchased directly from
Big Ass Fans, Big Ass Fans Afliated Companies in Australia, or a Big Ass Fans Authorized Dealer. This Limited Warranty is subject to all provisions, conditions, limitations, and exclusions described within this document.
Who is covered?
This Warranty extends to the original purchaser and subsequent owners, but only while the fan remains at the site of the original
installation. This Warranty extends through the rst installation of the fan and terminates if the fan is moved or reinstalled at a new
location.
When does the Warranty Period begin?
The Warranty Period commences on the date the product is installed, or 15 days following shipment of the product, whichever date is earlier. To obtain warranty service, the customer will be required to provide documentation verifying the date the product was installed.
What will Big Ass Fans do?
1. During the Warranty Period, Big Ass Fans will, at its option: a. Repair or replace the affected components of any defective product; b. Repair or replace the defective product; or c. Refund the price you paid for the product upon return of the product to Big Ass Fans, shipping and insurance prepaid.
What are the steps required to obtain Warranty service?
1. If the fan is operating, immediately turn off the fan.
2. Contact Big Ass Fans’ Technical Support Department as soon after the issue is discovered as possible by:
a. Calling 1-877-BIG-FANS (244-3267); or b. Going online to www.bigassfans.com/technical-support and completing a Technical Service form; or c. Completing the Warranty Claim form and the Responsibility Agreement located in the back of the Installation Manual, and mailing
the forms to Big Ass Fans Technical Support Department, 2348 Innovation Drive, Lexington, KY 40511, or by faxing them to 859-967-1695.
Technical Support is open from 8:00 a.m. to 5:00 p.m. Eastern Time, Monday–Friday, excluding major holidays. Every effort will be made to respond to all Technical Support requests within 24 hours of receipt.
3. Once the Technical Support Representative has received your warranty claim, a case will be processed. In order to process this case, please have the following information available: a. Your name, address, phone number, and installation address; b. Product brand name, serial number, purchase price, and verication of product installation or premises possession date; c. Detailed description of the problem you have experienced.
4. If the Technical Support Representative determines that the warranty claim is valid and that a replacement part is required, the Representative will process the claim and the replacement part will be shipped to you. Included in the shipment of the replacement part will be any shipping labels and documents needed to return the original part, including a Return Materials Authorization (RMA) number.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 42
36
Warranty Policy (cont.)
Steps to obtain Warranty service (cont.)
Note: Your receipt of the replacement part constitutes your agreement to return the failed part to Big Ass Fans within 15 days of the receipt of the replacement part delivery. If Big Ass Fans does not receive the original part, you will be invoiced for the retail cost of the replacement part and shipping, and you will be responsible for payment for the replacement part upon receipt of the invoice. Big Ass Fans reserves all rights it retains under law to collect the retail cost of the replacement part and shipping if the original is not returned
as specied above.
5. Obtaining service may involve contacting a contractor to remove, repair, or replace the fan, or to remove the fan and return it to us.
The cost of labor incurred, for factory installed fans, to remove, repair, or reinstall the fans will be covered only during the rst 12 months after the warranty becomes effective, and only pursuant to the terms of the denition of “Labor” below.
6. If we ask you to ship the fan back to Big Ass Fans for repairs or replacement, we will prepay the shipping and insurance for factory
installed fans during the rst 12 months after the warranty becomes effective; however, you will have to repackage the fan in such a
way that there is no damage to the fan in transit. You will be sent any return shipment documentation necessary to help you return the fan to Big Ass Fans. If we determine that no warrantable failure occurred or defect exists, we may invoice you for these shipping costs.
Please be patient while we arrange for or undertake the necessary warranty service. We will provide you with regular status updates, as well as shipment dates, if appropriate, until your fan is back in service.
Conditions
1. Big Ass Fans reserves the right to make the nal determination, based on its own evaluation of the fan and all components, as to whether:
a. The problem in question is the result of a defect in design, workmanship, or materials, and not a result of error, misuse, or abuse
on the part of the customer as set forth under the exclusions detailed below;
b. Noise heard during operation is within normal operating levels, in which case this Warranty would be inapplicable. Note:
Certain electrical, motor, or other operating noise may be impossible to eliminate due to the fan design and/or site conditions. Dissatisfaction with normal operating noise levels is not covered by this Warranty, and return of any fans for this reason will be subject to Big Ass Fans’ Return Policy (see below).
c. Adverse site conditions, (including, but not limited to, excessive dust, heat, humidity, unstable electric service, or any other
unknown or unforeseen condition that affects the proper operation of the products) improper application, or improper installation
is determined to be the basis for the failure. d. The problem or defect is material and requires action under this warranty; and e. The remedy of repair, replacement, or refund is appropriate.
2. If Big Ass Fans determines, in its sole discretion, that the appropriate remedy under the Warranty is a refund, the refund amount will be limited to the price paid by the customer for the product alone, and under no circumstances will it include the cost of labor, shipping, handling, packaging, or any other incidental or consequential costs incurred or anticipated by the customer.
3. With respect to replacement or repair rendered, Big Ass Fans reserves the right to use replacement parts that are refurbished. Big Ass Fans warrants that the parts replaced or repaired, whether or not they have been refurbished or are original equipment, will operate properly and be free from defects in materials and workmanship for a period of 90 days from the date of shipment to the customer, or for the remainder of the original warranty period, whichever is longer.
4. A service fee, parts replacement fee, and shipping charges may be imposed if any fan is returned for warranty service that is missing
components or that has been modied in any way or when we determine that no warrantable failure occurred or defect exists. Such fees and charges will vary based upon the actual material and labor costs necessary to replace missing or modied parts and to
return the fan to its original factory condition.
Return policy
Returns must be received within 90 days of shipment. The customer will be responsible for return freight charges. A restocking fee of 25% for unopened boxes and 50% for opened boxes applies to all returns.
What is not covered (exclusions)?
1. Units purchased and used outside the USA and its territories, Canada, or Australia.
2. Units purchased from any entity other than Big Ass Fans, Big Ass Fans Afliated Companies in Australia, or a Big Ass Fans Authorized Dealer.
3. Units or components where the serial number or part number sticker has been removed or defaced.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 43
Warranty Policy (cont.)
37
Exclusions (cont.)
4. Defects, malfunctions, failure or physical damage caused by unauthorized service/parts and improper installation, adverse site conditions (including, but not limited to, excessive heat, dust or humidity, unstable electric service, or any other unknown
or unforeseen condition that affects the proper operation of the products), mishandling, modications, or damage while in your
possession including failure to provide reasonable and necessary maintenance, which shall include, but not be limited to:
a. Failure to follow the required installation procedures specied in the Big Ass Fans-supplied Installation Manual and in all other
documentation supplied with the fans and related equipment;
b. Failure to follow all relevant codes and ordinances including, but not limited to, the National Electric Code and state and local
building codes;
c. Failure to follow electrical engineering industry standards regarding the approved method of installing solid-state electrical
equipment having the characteristics of the fan, the fan control, and their related components, even if such standards are not specically referenced in any instructions or literature supplied by Big Ass Fans; and
d. Failure to use properly all installation and mounting hardware supplied by Big Ass Fans.
ATTENTION: Under no circumstances will Big Ass Fans be responsible for remedial work necessary to correct installation procedures by others that do not conform to those established by the instructions, codes, and standards described under items 4.a through 4.d above.
e. Any modication or alteration of, or adjustment to the fans, fan control, and/or mounting and installation hardware and/or any
disassembly of the major components of the fans and fan controls for any purpose whatsoever, including any attempt to diagnose
and/or repair any problem, without prior written authorization from Big Ass Fans’ Technical Support Department; f. Misuse, abuse, accidents, unreasonable use, or Acts of God; g. Incorrect electric current, voltage, or supply; h. Failure to use fan controls supplied by Big Ass Fans unless:
i. Big Ass Fans’ Technical Support Department has provided written permission prior to installation; and
ii. The fan controls are built, operated, and maintained according to specications provided to and approved by Big Ass Fans’
Technical Support Department.
i. Failure to perform periodic maintenance as detailed in the Big Ass Fans-supplied Installation Manual.
5. Consequential or incidental damages sustained by any person, entity, or structure as a result of any breach of these warranties, except where such damages may not be excluded by law.
6. Claims made for products that have not been paid for in full.
7. Damage caused by premises structural defects, structural movement or settlement, exposure to chemicals, salt water, acid rain or other corrosive elements, excessive humidity, and/or wind.
8. Normal changes to the nish caused by ordinary use or damage to non-factory applied nishes.
9. Damage or failure caused by subjection of the product to conditions outside its design limitations.
10. Defects reported more than 90 days from when they were discovered or should have been discovered.
11. With regard to electrical and electronic components provided by Big Ass Fans that comprise part of the products, including motors,
motor drives, and variable frequency drives, Big Ass Fans relies on the determination by the original manufacturer as to whether the failure of such component was the result of a defect. If the manufacturer of such component determines that there was no defect and therefore refuses to cover it under warranty, Big Ass Fans likewise will not warranty such item unless Big Ass Fans determines that the failure of such electrical or electronic component was the result of a defect of design, workmanship, or material within some other part of the products.
Denitions
“Operate properly” applies to mechanical, electrical, and structural functions only. No guarantee, unless and except by separate written
agreement, is made regarding the dimensions or air movement generated or the appropriateness of the effectiveness of any product for its intended purpose or for the customer’s particular application.
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 44
38
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE, AND OF ALL OTHER OBLIGATIONS AND LIABILITIES ON BIG ASS FANS’ PART, AND BIG ASS FANS NEITHER ASSUMES NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THE PRODUCTS. NO OTHER WARRANTY, EXPRESSED OR IMPLIED, WHETHER OF FITNESS FOR A PARTICULAR PURPOSE OR OF MERCHANTABILITY OR OF ANY OTHER KIND, WHETHER OR NOT SIMILAR IN NATURE TO ANY PREVIOUSLY SPECIFIED, SHALL EXIST WITH RESPECT TO SUCH PRODUCTS, ALL SUCH WARRANTIES BEING HEREBY DISCLAIMED BY BIG ASS FANS AND WAIVED BY CUSTOMER. UNDER NO CIRCUMSTANCES SHALL BIG ASS FANS BE LIABLE FOR ANY LOSS, DAMAGE, COST OF REPAIR, OR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND IN CONNECTION WITH THE USE, SALE, OR REPAIR OF ANY PRODUCTS PURCHASED FROM BIG ASS FANS, UNLESS SUCH DAMAGES CANNOT BE EXCLUDED BY LAW.
Big Ass Fans reserves the right to change this warranty at any time without advance notice.
Warranty Policy (cont.)
WWW.BIGASSFANS.COM ©2015 DELTA T LLC ALL RIGHTS RESERVED
Page 45
Page 46
Page 47
Page 48
ESS-INST-41-MUL-01
REV. G
10/11/2018
2251 Innovation Drive, Lexington, KY 40511
1 (877) BIG-FANS | WWW.BIGASSFANS.COM
Loading...