Did a structural engineer approve the mounting structure? See page 5 for Big Ass Fans-approved
mounting structures.
Are you familiar with the function and use of the safety cable? See page 12 for information on
properly securing the safety cable.
Will the fan be installed so that the airfoils are at least 10 ft (3.05 m) above the oor?
Will the fan be installed so that the airfoils have at least 2 ft (0.61 m) of clearance from
obstructions?
Will the fan be installed so that it is not subjected to high winds such as from a Heating,
Ventilating, and Air Conditioning (HVAC) system or near a large garage door? If the fan is
mounted at the same level or higher than a diffuser, the airfoil tips must be at a distance that is at least
1x the measure of the fan’s diameter. If the fan is mounted at the same height or below a diffuser, the
airfoil tips must be at a distance that is at least 2x the measure of the fan’s diameter.
Will the distance between multiple fans be at least 2.5x the fans’ diameter when measured from
the centers of the fans?
If you ordered multiple fans, did you keep the parts of each fan together?
Customer Service: 1-877-BIG-FANS
(International: +1 859 233 1271)
Page 3
Installation Guide
E7, E10, E12
i
Installation Guide:
October 2018
Rev. G
10/11/2018
Conforms to ANSI/UL STD 507–Electric Fans
Conforms to CSA C22.2 No.113–Fans & Ventilators
Contact Information
Manufacturing
2251 Innovation Drive
Lexington, KY 40511
This product was manufactured in a plant whose Management System is certied as being in conformity with ISO 9001.
All trademarks used herein are the properties of their respective owners. No part of this document may be reproduced or translated into a different language without the prior written consent of Big Ass
Fans. The information contained in this document is subject to change without notice.
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
CAUTION: Installation work and electrical wiring must be done by qualied person(s) in accordance with all applicable codes and
standards.
CAUTION: When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
CAUTION: Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
WARNING: Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent
power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent
warning device, such as a tag, to the service panel.
CAUTION: The installation of a Big Ass Fan must be in accordance with the requirements specied in this installation manual
and with any additional requirements set forth by the National Electric Code (NEC), ANSI/NFPA 70-2011, and all local codes. Code
compliance is ultimately YOUR responsibility! Failure to comply with these codes could result in personal injury or property damage.
CAUTION: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or hazardous power
source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans if you have any questions
regarding the electrical installation of this fan.
WARNING: To reduce the risk of re, electric shock, and injury to persons, Big Ass Fans must be installed with Big Ass Fan supplied
controllers that are marked (on their cartons) to indicate the suitability with this model. Other parts cannot be substituted.
CAUTION: When service or replacement of a component in the fan requires the removal or disconnection of a safety device, the
safety device is to be reinstalled or remounted as previously installed.
WARNING: Risk of re, electric shock, or injury to persons during cleaning and user-maintenance! Disconnect the fan from the power
supply before servicing.
CAUTION: Do not bend the airfoils when installing, adjusting, or cleaning the fan. Do not insert foreign objects in between rotating
airfoils.
WARNING: Stay alert, watch what you are doing, and use common sense when installing fans. Do not install fans if tired or under the
inuence of drugs, alcohol, or medication. A moment of inattention while installing fans may result in serious personal injury.
CAUTION: The installation of this fan requires the use of some power tools. Follow the safety procedures found in the owner’s
manual for each of these tools and do not use them for purposes other than those intended by the manufacturer.
CAUTION: The Big Ass Fans product warranty will not cover equipment damage or failure caused by improper installation.
WARNING: This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of
the appliance by a responsible person. Children should be supervised to ensure that they do not play with the appliance.
Leave this installation guide with the owner of the fan after installation is complete.
CAUTION: Do not remove the main fan unit from its protective packaging or place it on a at surface prior to hanging it!
CAUTION: If you ordered multiple fans, be sure to keep the components of each fan together.
If you are missing any piece required for installation, contact Big Ass Fans Customer Service. Note: Drawings below are not to scale. All
boxes are labeled to identify the contents.
Hardware
1
Mounting Hardware
(5) M10 x 40 mm Hex Head
Cap Screw
(9) M10 Flat Washer
(5) M10 Nylock Nut
Airfoil Tip Hardware
(7) M5 x 12 mm Button Head
Screw
Lower Cover Hardware
(9) 6-32 x 3/8” Pan Head Screw
1. One extra of each piece of hardware is included except for the Safety Cable Hardware, Angle Iron Hardware, and Guy Wire Hardware.
2. Guy wires are designed to constrain the fan’s lateral movement. Big Ass Fans recommends using guy wires if the fan is exposed to high winds or similar conditions or if the
fan is close to any building xtures. Guy wires are packaged in the main box. The Guy Wire Hardware is packaged in the box with the extension tube.
Extension Tube Hardware
(3) M10 x 90 mm Socket Head
Cap Screw
(5) M10 Flat Washer
(3) M10 Nylock Nut
Airfoil Hardware
(13) M8 x 18 mm Socket Head
Cap Screw
(13) 8 mm Belleville Washer
(3) M8 x 75 mm Socket Head
Cap Screw
(5) M8 Flat Washer
(3) M8 Nylock Nut
Lower Cover Mounting
Bracket Hardware
(4) 8-32 x 3/8” Pan Head Screw
(4) 1/4-20 x 1” Eyebolt
(4) 1/4-20 Hex Nut
(4) Guy Wire
(4) Gripple
(16) Wire Rope Clip
Mounting
Main Fan Unit, Lower Cover, Lower
Upper Mount & Upper Mounting Brace
1. The upper mounting brace strengthens the upper mounting system and must be installed inside the top of the extension tube.
2. Two (2) safety clips and two (2) carabiners are provided for safety cable installation in locations where the top of the mounting structure is inaccessible. Contact
Customer Service if you need assistance installing the safety cable.
1. The cover plate assembly includes a fan status LED and a switch used to change the direction of fan rotation. The LED will ash an error code if
there is a problem with the fan. See page 32 for information on the fan status LED. See page 25 for information on changing the fan direction.
2. The re relay is provided for fans that will be installed in buildings that have a re sprinkler system. See page 23 for re relay wiring details.
3. The CAT5 cable connects the wall controller to the fan. One end plugs into the wall controller, and the other end plugs into the controller input cable.
See pages 22–23 for wiring details. A longer CAT5 cable can be used if needed (customer-supplied).
Cover Plate
Assembly
20-ft Controller
Input Cable
1
Fire Relay
100-ft CAT5
Cable
2
(6) Airfoil Tip(6) Airfoil Retainer
3
Airfoils
(6) Airfoil
Tools needed
Big Ass Fans recommends gathering the following tools prior to beginning installation.
Refer to the diagram below to identify the fan components. Note: The safety cable is not pictured below; however, it is an important part
of the installation.
A. Upper mount. Secures the fan to the mounting structure.
B. Extension tube. Extends the fan from the ceiling and provides a path for wiring.
C. Upper mounting brace. Strengthens the upper mounting system.
D. Cover plate assembly. Provides access to wiring and includes a fan status LED and a switch used to change the direction of fan
rotation. The LED will ash an error code if there is a problem with the fan. See page 32 for LED error codes. See page 25 for
information on changing the fan direction.
E. Main fan unit. Includes the motor, hub, and power wiring.
F. Airfoil. Provides air movement. The unique, patented design provides efcient and effective air movement.
G. Airfoil tip. Ensures quiet fan operation.
H. Electronics cover. Provides access to the fan electronics and fuses. See page 33 for information on replacing fuses.
The fan should only be installed according to the instructions described in this manual. Consult a structural engineer
for installation methods not covered in this manual.
When surveying the work site, keep the following mechanical and electrical guidelines in mind.
Mechanical
• The main fan unit is heavy. A suitable means for lifting the weight of the fan, such as a scissor lift, and at least two installation
personnel will be required.
• If hanging the fan from angle irons, the minimum dimensions of the angle iron must be 2-1/2’’ × 2-1/2’’ × 1/4’’
(6.4 cm × 6.4 cm × 0.6 cm) and it cannot be longer than 12 ft (3.7 m). It must be secured to the structure. Do not mount the fan to a
single purlin, truss, or bar joist. Consult a structural engineer for installation methods not covered in this manual.
• To reduce the risk of injury to persons, install the fan so that the airfoils are at least 10 ft (3.05 m) above the oor.
• If mounting the fan in the vicinity of an infrared/radiant heater, it is recommended that the fan be mounted outside of the clearances
recommended by the manufacturer of the heater and at a height equal to or above the shielding on the heating element with the
controller on the opposite side of the heater. If mounting the fan below the heater shielding, all fan elements must be outside of the
clearances recommended by the heater manufacturer. The installation manual for the specic model of heater will typically provide
the minimum clearance to combustibles (MCC).
• Adhere to the safety requirements in the table below when selecting where to mount the fan.
Safety requirementMinimum distances
Clearance
Blade height≥10 ft above the floor
HVAC equipment≥1x fan diameter if above diffuser. ≥2x fan diameter if below diffuser. Refer to the illustration below.
Fan spacing2.5x fan diameter, center-to-center
Radiant/IR heatersSee the manufacturer’s requirements for the minimum clearance to combustibles.
≥2 ft from all fan parts and ≥3 ft below sprinklers. The fan installation area must also be free of
obstructions such as lights, cables, or other building structure.
5
HVAC
Diffuser
≥1x fan’s diameter (12 ft)
HVAC
Diffuser
(3.7 m)
12-ft diameter
the HVAC discharge or intake.
The fan is located below the
HVAC discharge or intake.
The fan is located at or above
≥2x fan’s diameter (24 ft) (7.3 m)
12-ft diameter
Electrical
• Ensure power wiring is routed to a junction box at the fan location prior to installation.
• To reduce the risk of electric shock, wiring should be performed by a qualied electrician! Incorrect assembly can cause electric
shock or damage the motor and the controller!
• Installation of a Big Ass Fan must be in accordance with the National Electrical Code (NEC), ANSI/NFPA 70-2011, and local codes.
WARNING: The fan should not be installed unless the structure on which the fan is to be mounted is of sound
construction, undamaged, and capable of supporting the loads of the fan and its method of attachment. A structural
engineer should verify that the mounting structure is adequate prior to fan installation. Verifying the stability of the
mounting structure is the sole responsibility of the customer and/or end user, and Big Ass Fans hereby expressly
disclaims any liability arising therefrom, or arising from the use of any materials or hardware other than those supplied by
Big Ass Fans or otherwise specied in these installation instructions.
CAUTION: Do not install the fan from a single purlin or truss or junction box.
CAUTION: Unsupported angle iron spans should not exceed 12 ft (3.7 m).
Installing the Fan
1. Select proper angle irons
Follow the table below when selecting angle irons for fan installation. Note: Angle irons and angle iron hardware are not included with
the fan.
Angle iron span
(between mounting points)
6 ft (1.8 m) or less2.5” (6.4 cm) x 2.5” (6.4 cm) x 0.25” (0.6 cm)2
over 6 ft (1.8 m) to 8 ft (2.4 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm)2
over 8 ft (2.4 m) to 12 ft (3.7 m) 3” (7.6 cm) x 3” (7.6 cm) x 0.25” (0.6 cm)4*
*Two pairs of angle irons. Pairs should be placed back to back and fastened in center (see step 3).
Drill two Ø 7/16” (1.1 cm) holes exactly 5-1/2” (14 cm) apart in the centers of two angle irons.
Measure the distance between the mounting points of the roof structure that the angle irons will span. Measure the same distance on
the angle irons, and drill Ø 9/16” (1.4 cm) holes through each end of the angle irons. Drill holes in two angle irons if span is 8 ft (2.4 m)
or less. Drill holes in four angle irons if span is greater than 8 ft (2.4 m).
7
Ø 9/16’’ (1.4 cm)Ø 7/16’’ (1.1 cm)
5-1/2’’ (14 cm)
Distance between roof structure mounting points
3. Secure angle irons (if span is longer than 8 ft)
If the angle iron span is 8 ft (2.4 m) or less, proceed to
step 4a on the following page.
If the angle iron span is longer than 8 ft (2.4 m), it is necessary to
use double angle irons.
Locate the center of the angle iron length. Drill Ø 9/16” (1.4 cm) hole
through the center of the vertical wall of the angle iron. Drill a total of
four angle irons.
A
1/2 A
c
b
Place two drilled angle irons back to back. Fasten the angle irons
together with customer-supplied Grade 8 hardware.
Align the angle irons to each other and tighten the bolts to 25 ft·lb (33.9 N·m) using a torque wrench with a 3/4” or 19 mm socket.
Repeat step for remaining two angle irons.
Proceed to step 4b.
Angle Iron Hardware (Customer-Supplied):
a. (2) 1/2-13 or M12 Bolt
b. (4) 1/2” or M12 Washer
c. (2) 1/2” or M12 Nut
4a. Fasten single angle irons to roof structure mounting points
If installation requires double angle irons, i.e., span is greater than 8 ft (2.4 m), proceed to step 4b.
CAUTION: The angle irons must be fastened to the roof structure at each end.
Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown. Tighten
the hardware so that it is snug, but do not torque until the fan has been mounted to the angle irons. Note: Big Ass Fans
recommends orienting the angle irons so that the horizontal legs are facing each other. Refer to the illustration below.
Proceed to step 5.
Angle Iron Hardware (Customer-Supplied):
a. (4) 1/2-13 or M12 Bolt
b. (8) 1/2” or M12 Washer
c. (4) 1/2” or M12 Nut
4b. Fasten double angle irons to roof structure mounting points
CAUTION: The angle irons must be fastened to the roof structure at each end.
Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 8 hardware as shown. Tighten
the hardware so that it is snug, but do not torque until the fan has been mounted to the angle irons.
Proceed to step 5.
9
Angle Iron Hardware (Customer-Supplied):
a. (8) 1/2-13 or M12 Bolt
b. (16) 1/2” or M12 Washer
c. (8) 1/2” or M12 Nut
5. Route wiring and safety cable into extension tube
Note: To facilitate installation, Big Ass Fans recommends that the extension
tube is horizontal with the rectangular access hole facing up during this step.
To route the wiring and safety cable into the extension tube:
1. Route the end of the controller input cable with the wiring harness on it (the
end without the three loose wires) down into the top of the extension tube
and out the rectangular access hole as shown.
2. Route the end of the power supply cable with the wiring harness on it down
into the top of the extension tube and out the rectangular access hole as
shown.
3. Route the end of the safety cable with the lug on it down into the top of the
extension tube and out the bottom of the tube as shown.
Controller Input
Cable
Access Hole
6. Attach upper mount and upper mounting brace (to extension tube)
Note: To facilitate installation, Big Ass Fans recommends that the extension tube is horizontal with
the rectangular access hole facing up during this step. Wiring and the and safety cable are not
shown in the illustrations.
Insert the upper mounting brace into the top of the extension tube and align the four (4) mounting
holes in the brace with the four (4) mounting holes at the top of the tube as shown on the right.
Position the power supply cable, controller input cable, and safety cable in any of the four (4)
spaces between the upper mounting brace and the extension tube as shown below. Note: The
cables can go in any of the four spaces. They do not all need to be in the same space.
Power Supply
Cable
Safety Cable
Upper
Mounting
Brace
Attach the upper mounting brace (inside the extension tube) and the upper mount to the extension
tube using the Extension Tube Hardware as shown below. Tighten the hardware so that it is
snug, but do not torque.
Extension Tube Hardware:
a. (2) M10 x 90 mm Socket Head Cap Screw
b. (4) M10 Flat Washer
c. (2) M10 Nylock Nut
Secure the upper mount (with extension tube and upper mounting brace already attached) directly to the angle irons using the Mounting
Hardware as shown. Consult the diagrams below for distances between the angle irons. Tighten the hardware so that it is snug, but
do not torque.
Mounting Hardware:
a. (4) M10 x 40 mm Hex Head Cap Screw
b. (8) M10 Flat Washer
c. (4) M10 Nylock Nut
WARNING: The safety cable is a crucial part of the
fan and must be installed correctly. If you have
any questions, call Customer Service.
To secure the safety cable to the angle irons:
1. Route the free end of the safety cable into one of the
two (2) holes in the Gripple
through the Gripple until the Gripple rests at the top of
the extension tube.
2. Wrap the safety cable around the angle irons, leaving
6–10 in. (15.2–25.4 cm) of slack.
3. Route the loose end of the safety cable through the
remaining hole in the Gripple and pull to tighten
®
, and then pull the cable
.
6–10 in.
9. Secure safety cable (to main fan unit)
CAUTION: Do not remove the main fan unit from its protective packaging or place it on a at surface prior to hanging it!
CAUTION: To prevent damage, avoid contact with the stator wires located on the bottom of the main fan unit!
CAUTION: The main fan unit is heavy. Use caution when raising it.
(15.2–25.4 cm)
Raise the main fan unit directly from its packaging to the extension tube. Route the three (3) sets of wires from the main fan unit up
into the bottom of the extension tube and out the rectangular access hole near the bottom of the tube. Ensure the wires are positioned
inside the grooves on the motor shaft. Note: Wiring not shown in the illustrations below.
While supporting the main fan unit, secure the safety cable to the motor shaft using the Safety Cable Hardware as shown. Insert the
clevis pin through the safety cable lug and motor shaft, and then insert the straight leg of the cotter pin into the small hole on the clevis
pin.
CAUTION: The main fan unit is heavy. Use caution when
raising it.
CAUTION: Be careful not to pinch the fan wiring between the
extension tube and main fan unit during installation.
CAUTION: Do not discard the main fan unit packaging and
foam. It should be used if the fan is ever moved or relocated.
Attach the main fan unit to the extension tube using the Main Fan Unit
Hardware as shown. Note: Wiring not shown in the illustration on the
right.
Tighten the hardware to 25 ft·lb (33.9 N·m) using a 6 mm Allen wrench
and a torque wrench with a 13 mm socket.
Main Fan Unit Hardware:
a. (2) M8 x 75 mm Socket Head Cap Screw
b. (4) M8 Flat Washer
c. (2) M8 Nylock Nut
13
c
b
a
b
11. Tighten hardware
After attaching the main fan unit to the extension tube, tighten the following hardware to the specied torque.
Tighten the Mounting Hardware to 25 ft·lb (33.9 N·m) using a 17 mm wrench and a torque wrench with a 17 mm socket.
Mounting Hardware
Allow the extension tube to hang freely and balance itself, and then tighten the Extension Tube Hardware to 25 ft·lb (33.9 N·m) using
an 8 mm Allen wrench and a torque wrench with a 17 mm socket.
Tighten all hardware securing the angle irons to the roof structure (Angle Iron Hardware) to 40 ft·lb (54.2 N·m) using a 3/4” or 19 mm
wrench and a torque wrench with a 3/4” or 19 mm socket.
Angle Iron Hardware (single angle irons)Angle Iron Hardware (double angle irons)
Installing the Fan (cont.)
12. Connect power and wall controller wiring
Plug the male wiring harnesses on the fan wiring into the female wiring harnesses on the power supply cable and the controller input
cable as shown. Carefully tuck the wiring into the extension tube.
Plug the remaining male wiring harness from the fan into the female
wiring harness on the cover plate assembly as shown.
15
Ensure all wiring is tucked inside the extension tube, and then attach
the cover plate assembly to the extension tube using the Cover Plate
Assembly Hardware as shown.
Cover Plate Assembly Hardware:
(2) 8-32 x 1/2" Flat Head Screw
14. Install lower cover mounting bracket
Remove the protective plastic cover from the bottom of the main fan unit before installing the mounting bracket.
Cover Plate
Assembly
Ensure that the three (3) stator wires on the bottom of the main fan unit are tucked in securely before installing the
mounting bracket. Be careful not to damage the stator wires while installing the mounting bracket and lower cover.
WARNING: Disconnect power to the fan before installing the lower cover mounting bracket and lower cover.
Attach the lower cover mounting bracket to the bracket on the bottom of the main fan unit using the Lower Cover Mounting Bracket
Hardware as shown. Loosely attach all three (3) screws, and then tighten them.
WARNING: Disconnect power to the fan before installing the lower cover mounting bracket and lower cover.
Attach the lower cover to the lower cover mounting bracket using the Lower Cover Hardware as shown. Loosely attach all eight (8)
screws, and then tighten them.
Guy wires are designed to constrain the fan’s lateral movement. Big Ass Fans recommends using guy wires if you are
installing the 4-ft (1.2 m) extension tube, if the fan is exposed to high winds or similar conditions, or if the fan is close
to any building xtures.
WARNING: Disconnect power to the fan before installing the guy wires.
17
1. Attach guy wire clamps
Position the guy wire clamps between the two bolts at the bottom of the extension tube. Refer to the diagram below. Secure the clamps
to the extension tube using the Guy Wire Hardware.
Guy Wire Hardware:
a. (2) 1/4-20 x 1” Carriage Bolt
b. (2) 1/4-20 Nylock Flange Nut
Guy Wire Clamps
Position the guy wire clamps
between the two bolts at the
bottom of the extension tube.
Secure the four (4) locking carabiners to the guy wire clamps as shown.
Securely tighten the carabiners.
3. Attach beam clamp
The guy wire should be at a 45° angle from the extension tube (see the illustrations on
the following page). Attach the beam clamp to the mounting structure accordingly.
For best results, the guy wires should be installed at 45° in the X-Y, Y-Z, and X-Z
planes as shown on the following page. If the angle deviates by more than 15°, contact
Customer Service for assistance.
a
b
Fasten the small eyebolt and nut onto the beam clamp (the nut will be on the outside of
the beam clamp).
Loop the crimped end of the guy wire into the locking carabiner and secure to the
eyebolt as shown. Securely tighten the carabiner.
Guy Wire Hardware:
a. 1/4” Beam Clamp
b. 1/4-20 x 1” Eyebolt
c. 1/4-20 Hex Nut
d. Locking Carabiner
e. Guy Wire
Route the guy wire through the Gripple® and the carabiner on the guy wire clamp, and then back through the Gripple as shown below.
Do not tighten the Gripple until the remaining guy wires have been installed.
Note: To back the guy wire out of the Gripple, insert the small tool included with the Gripple set or a 0.050" Allen wrench into the small
hole on the Gripple.
Note: Angle irons mounted to bar joists are shown in the illustration below. Your mounting structure may differ.
®
Gripple
45º45º
Guy Wire
Guy Wire
5. Install three remaining guy wires
CAUTION: Over-tightening the guy wires could throw the fan off balance.
Repeat steps 3–4 to install the three remaining guy wires.
Evenly cinch all four guy wires into place using the Gripples. The guy wires should be
taut, evenly spaced around the fan, and away from the path of the airfoils. Maintain a
distance of 6”–8” between the Gripple and the carabiner.
Once all of the guy wires are taut, secure their loose ends with the wire rope clips and
torque to 4.5 ft·lb (6.1 N·m). Ensure all electrical cords/cables are unobstructed by the
Big Ass Fans recommends wiring the fan (page 22) before installing the airfoils.
WARNING: Disconnect power to the fan before installing the airfoils.
Installing Airfoils
1. Attach airfoil tips (to airfoils)
Attach the airfoil tips to the airfoils using the Airfoil Tip Hardware as shown. Securely tighten the screws using a 3 mm Allen wrench.
Attach airfoil tips to all six (6) airfoils before attaching the airfoils to the fan.
WARNING: Disconnect power to the fan before installing airfoils.
Attach the six (6) airfoil retainers using the Airfoil Hardware. Moving clockwise around the fan hub, position the airfoil retainers as
shown. Hole A of the retainer should be positioned over top of Hole B. Do not tighten the bolts until all airfoil retainers have been
attached!
Tighten the bolts along the outside perimeter to 29 ft·lb (39.3 N·m) using a torque wrench with a 6 mm Allen head socket. After the
outer perimeter bolts are torqued, tighten the bolts along the inner perimeter to 29 ft·lb (39.3 N·m).
Airfoil Hardware:
a. (12) M8 x 18 mm Socket Head Cap Screw
b. (12) 8 mm Belleville Washer
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualied electrician! Incorrect assembly
can cause electric shock or damage the motor and the controller! Hazard of electrical shock!
WARNING: The installation of a Big Ass Fan must be in accordance with the requirements specied in this installation
manual and with any additional requirements set forth by the National Electric Code (NEC), ANSI/NFPA 70-2011, and all
local codes. Code compliance is ultimately YOUR responsibility!
WARNING: Exercise caution and common sense when powering the fan. Do not connect the fan to a damaged or
hazardous power source. Do not attempt to resolve electrical malfunctions or failures on your own. Contact Big Ass Fans
if you have any questions regarding the electrical installation of this fan.
Power requirements
The fan is shipped with either a 110–125 VAC motor or a 200–240 VAC motor. The fan’s voltage is marked on the fan packaging and on
the label on top of the main fan unit. The voltage cannot be changed during installation. Ensure your fan is the correct voltage prior
to beginning installation.
ModelDiameterInput powerMinimum circuit sizeRated current
Moving at a low speed means less energy used for operation, translating into more energy savings year-round. Follow the procedures
below to ensure the most efcient operation of your Big Ass Fan.
To ensure proper fan rotation:
1. Turn on the fan.
2. Verify that the fan is rotating in the counterclockwise direction (when viewed from below).
3. If the fan is not rotating counterclockwise, reverse the fan direction. See the previous page for instructions on changing the direction
of rotation.
Operating the Fan (cont.)
Heating season
In spaces with higher ceilings, E7, E10, and E12 fans return heat from the ceiling to oor level more efciently than smaller ceiling
fans. For maximum energy savings, the fan should be operated continuously during the heating season and should not be operated in
reverse (clockwise). Big Ass Fans are designed to operate efciently at very low speeds, so turning the fan very slowly in the forward
direction (counterclockwise) will provide enough air movement to circulate the hot air at the ceiling down to the oor without causing a
draft.
Stand directly below the tips of the airfoils with hand outstretched. If you feel a draft, slightly decrease the fan speed. Repeat until the
draft is no longer noticeable.
Cooling season
The cooling effect created by the breeze from E7, E10, and E12 fans keeps occupants comfortable with the thermostat at a higher
setting. During the cooling season, every degree higher that the thermostat is reset reduces the energy consumed by the air conditioner
by 1.5–2%. To minimize energy usage during the cooling season, operate the fan only when building occupants are present.
Increase the speed of the fan until desired air speed or maximum fan speed is reached. In air conditioned facilities, increase the
thermostat setting by 2 to 7°F to reduce energy consumption and save energy.
WARNING: Before servicing or cleaning unit, switch power off at the service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device (such as a tag) to the service panel.
WARNING: When service or replacement of a component in the fan requires the removal or disconnection of a safety
device, the safety device is to be reinstalled or remounted as previously installed.
Please take a few moments each year to perform the following preventive maintenance inspection on your fan to ensure its safe and
efcient operation. Before contacting Customer Service, try resolving the issue using the troubleshooting procedures on page 31. If you
have any questions, contact Customer Service.
27
Annual preventive maintenance
Perform the following maintenance procedures each year using the Annual Maintenance Checklist on page 29.
1. Ensure all upper mounting bolts are present and torqued to 25 ft·lb (33.9 N·m).
2. Ensure airfoils are secured to one another by airfoil retainers.
3. Ensure all 12 bolts securing the airfoils to the fan are present and torqued to 29 ft·lb (39.3 N·m).
4. Ensure the two (2) bolts securing the extension tube to the main fan unit are present and torqued to 25 ft·lb (33.9 N·m).
5. Ensure all airfoil tip hardware is secure.
6. Check guy wires (if installed) for fraying or damage (not shown in the illustration below).
General preventive maintenance
• Verify proper fan rotation. To be effective, the fan must be turning counterclockwise when viewed from the oor.
• Dust airfoils and motor. If desired, use a gentle cleaner or degreasing agent to polish the airfoils. Do not use Clorox® or other chlorine
based cleaners! This could result in the release of toxic/fatal fumes. Do not use cleansers on the electronics enclosure.
• Check that the safety cable and upper mounting system are secure.
• Observe the motion of the fan during operation. The fan should not wobble or precess. If any wobble is noticed, ensure the mounting
structure is rigid enough to support the fan and that the guy wires, if used, are sufciently taut. If guy wires were not used, Big Ass
Fans suggests installing them. Contact Customer Service.
WARNING: Do not operate a fan with missing or damaged components. Please contact Customer Service.
WARNING: When servicing or replacement of a component in the fan requires the removal or disconnection of a safety
device, the safety device is to be reinstalled or remounted as previously installed.
CAUTION: Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
WARNING: Before servicing or cleaning unit, switch power off at the service panel and lock the service disconnecting
means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag, to the service panel.
31
General troubleshooting
For questions about your product or customer service inquiries, please call our toll free number (1-877-BIG-FANS).
Some issues can be resolved before requesting service. Review the below troubleshooting tips before contacting Customer Service for
support.
SymptomPossible solution(s)
A popping noise is coming from the fan.
Airfoil noise is a result of airfoils that are
not tightened to the specied torque.
The fan will not start.Verify the following:
Switch off power at the service panel and lock the service disconnecting means. (If it
cannot be locked, fasten a prominent warning device.) Tighten the airfoil hardware to
29 ft·lb (39.3 N·m). If popping still occurs, verify that the airfoils are not contacting each
other. If the airfoils are contacting each other, please contact Customer Service.
• All wires are securely connected.
• The blue wire and the yellow wire on the controller input cable are wired together.
See pages 22–23 for wiring details.
• The wall controller has power.
• Supply power is adequate and functional.
• All fuses are functional. If a fuse is blown, see page 33 for instructions on replacing
fuses.
If the fan still does not start, contact Customer Service.
The LED on the wall controller is ashing.
The LED on the wall controller will ash
an error code if there is a problem with the
fan.
The fan jerks upon startup.This is normal and may happen occasionally upon startup as the fan positions itself
See the following page for fan error code descriptions and possible solutions.
relative to the motor stator. An initial slight jerking forward and backward does not affect
fan operation.
Nine 1/2-Second Flashes/4 Seconds OffCurrent Limit/Short Circuit
Fan status LED troubleshooting
LED codeDescription/Possible cause(s)Possible solution(s)
Over Temperature
Output Device Failure
Internal Communication Error
DC Buss UndervoltageBuss voltage has fallen below 255 VDC.
DC Buss Over VoltageBuss voltage has exceeded 373 VDC.
Motor Overload/Thermal TripThermal motor overload protection has been activated.
Current Limit/Short Circuit
Motor Stall
Run Enable Jumper Open
The fan drive electronics have exceeded safe operating
temperature limits.
The fan drive electronics have failed or output phase
loss has occurred.
The main fan drive has failed to respond to the
command source (daughterboard, etc.).
The hardware current limit has been reached. A severe
overload or short circuit condition exists on the fan drive
output.
The fan failed to accelerate to the target RPM within one
(1) minute of startup.
The run enable circuit is open and motor operation is
disabled.
The fan will shut down for ve (5) minutes
and then attempt to restart two (2) times. If
the fan does not restart after two attempts,
reset power to the fan. If the fan still does
not restart, contact Customer Service.
The fan will shut down and will not attempt
to restart. Contact Customer Service.
Make sure the blue wire and the yellow
wire on the controller input cable are wired
together. See pages 22–23 for wiring details.
WARNING: Ensure power is disconnected before replacing fuses.
CAUTION: Do not touch the fan’s electronics unless necessary!
To replace the fuses on the main fan unit, remove the electronics cover from the fan as shown. The electronics cover is attached to the
fan with four (4) screws. Gently twist and pull out the appropriate fuse holder, and replace the fuse. Reinstall the fuse holder, and then
reattach the fan’s electronics cover. See below for fuse recommendations.
Congratulations on your purchase of a Big Ass Fan! We are delighted that you have chosen our product to improve the quality of your
environment, and hope you’ll have much pleasure using the fan for years to come.
Warranty period
ItemPeriod of coverage
Hub and airfoilsLifetime (parts)
Motor and controller1 year (parts)
All other fan components1 year (parts)
What is covered?
This Warranty covers any defects in materials or workmanship under normal use and maintenance that adversely affect the ability of
the fan to operate properly when the product is installed correctly according to Big Ass Fans’ written installation instructions by a state
qualied or licensed electrical contractor and operated pursuant to these instructions, and when such fans are purchased directly from
Big Ass Fans, Big Ass Fans Afliated Companies in Australia, or a Big Ass Fans Authorized Dealer. This Limited Warranty is subject to
all provisions, conditions, limitations, and exclusions described within this document.
Who is covered?
This Warranty extends to the original purchaser and subsequent owners, but only while the fan remains at the site of the original
installation. This Warranty extends through the rst installation of the fan and terminates if the fan is moved or reinstalled at a new
location.
When does the Warranty Period begin?
The Warranty Period commences on the date the product is installed, or 15 days following shipment of the product, whichever date is
earlier. To obtain warranty service, the customer will be required to provide documentation verifying the date the product was installed.
What will Big Ass Fans do?
1. During the Warranty Period, Big Ass Fans will, at its option:
a. Repair or replace the affected components of any defective product;
b. Repair or replace the defective product; or
c. Refund the price you paid for the product upon return of the product to Big Ass Fans, shipping and insurance prepaid.
What are the steps required to obtain Warranty service?
1. If the fan is operating, immediately turn off the fan.
2. Contact Big Ass Fans’ Technical Support Department as soon after the issue is discovered as possible by:
a. Calling 1-877-BIG-FANS (244-3267); or
b. Going online to www.bigassfans.com/technical-support and completing a Technical Service form; or
c. Completing the Warranty Claim form and the Responsibility Agreement located in the back of the Installation Manual, and mailing
the forms to Big Ass Fans Technical Support Department, 2348 Innovation Drive, Lexington, KY 40511, or by faxing them to
859-967-1695.
Technical Support is open from 8:00 a.m. to 5:00 p.m. Eastern Time, Monday–Friday, excluding major holidays. Every effort will be
made to respond to all Technical Support requests within 24 hours of receipt.
3. Once the Technical Support Representative has received your warranty claim, a case will be processed. In order to process this
case, please have the following information available:
a. Your name, address, phone number, and installation address;
b. Product brand name, serial number, purchase price, and verication of product installation or premises possession date;
c. Detailed description of the problem you have experienced.
4. If the Technical Support Representative determines that the warranty claim is valid and that a replacement part is required, the
Representative will process the claim and the replacement part will be shipped to you. Included in the shipment of the replacement
part will be any shipping labels and documents needed to return the original part, including a Return Materials Authorization (RMA)
number.
Note: Your receipt of the replacement part constitutes your agreement to return the failed part to Big Ass Fans within 15 days of the
receipt of the replacement part delivery. If Big Ass Fans does not receive the original part, you will be invoiced for the retail cost of the
replacement part and shipping, and you will be responsible for payment for the replacement part upon receipt of the invoice. Big Ass
Fans reserves all rights it retains under law to collect the retail cost of the replacement part and shipping if the original is not returned
as specied above.
5. Obtaining service may involve contacting a contractor to remove, repair, or replace the fan, or to remove the fan and return it to us.
The cost of labor incurred, for factory installed fans, to remove, repair, or reinstall the fans will be covered only during the rst 12
months after the warranty becomes effective, and only pursuant to the terms of the denition of “Labor” below.
6. If we ask you to ship the fan back to Big Ass Fans for repairs or replacement, we will prepay the shipping and insurance for factory
installed fans during the rst 12 months after the warranty becomes effective; however, you will have to repackage the fan in such a
way that there is no damage to the fan in transit. You will be sent any return shipment documentation necessary to help you return
the fan to Big Ass Fans. If we determine that no warrantable failure occurred or defect exists, we may invoice you for these shipping
costs.
Please be patient while we arrange for or undertake the necessary warranty service. We will provide you with regular status updates,
as well as shipment dates, if appropriate, until your fan is back in service.
Conditions
1. Big Ass Fans reserves the right to make the nal determination, based on its own evaluation of the fan and all components, as to
whether:
a. The problem in question is the result of a defect in design, workmanship, or materials, and not a result of error, misuse, or abuse
on the part of the customer as set forth under the exclusions detailed below;
b. Noise heard during operation is within normal operating levels, in which case this Warranty would be inapplicable. Note:
Certain electrical, motor, or other operating noise may be impossible to eliminate due to the fan design and/or site conditions.
Dissatisfaction with normal operating noise levels is not covered by this Warranty, and return of any fans for this reason will be
subject to Big Ass Fans’ Return Policy (see below).
c. Adverse site conditions, (including, but not limited to, excessive dust, heat, humidity, unstable electric service, or any other
unknown or unforeseen condition that affects the proper operation of the products) improper application, or improper installation
is determined to be the basis for the failure.
d. The problem or defect is material and requires action under this warranty; and
e. The remedy of repair, replacement, or refund is appropriate.
2. If Big Ass Fans determines, in its sole discretion, that the appropriate remedy under the Warranty is a refund, the refund amount
will be limited to the price paid by the customer for the product alone, and under no circumstances will it include the cost of labor,
shipping, handling, packaging, or any other incidental or consequential costs incurred or anticipated by the customer.
3. With respect to replacement or repair rendered, Big Ass Fans reserves the right to use replacement parts that are refurbished. Big
Ass Fans warrants that the parts replaced or repaired, whether or not they have been refurbished or are original equipment, will
operate properly and be free from defects in materials and workmanship for a period of 90 days from the date of shipment to the
customer, or for the remainder of the original warranty period, whichever is longer.
4. A service fee, parts replacement fee, and shipping charges may be imposed if any fan is returned for warranty service that is missing
components or that has been modied in any way or when we determine that no warrantable failure occurred or defect exists. Such
fees and charges will vary based upon the actual material and labor costs necessary to replace missing or modied parts and to
return the fan to its original factory condition.
Return policy
Returns must be received within 90 days of shipment. The customer will be responsible for return freight charges. A restocking fee of
25% for unopened boxes and 50% for opened boxes applies to all returns.
What is not covered (exclusions)?
1. Units purchased and used outside the USA and its territories, Canada, or Australia.
2. Units purchased from any entity other than Big Ass Fans, Big Ass Fans Afliated Companies in Australia, or a Big Ass Fans
Authorized Dealer.
3. Units or components where the serial number or part number sticker has been removed or defaced.
4. Defects, malfunctions, failure or physical damage caused by unauthorized service/parts and improper installation, adverse
site conditions (including, but not limited to, excessive heat, dust or humidity, unstable electric service, or any other unknown
or unforeseen condition that affects the proper operation of the products), mishandling, modications, or damage while in your
possession including failure to provide reasonable and necessary maintenance, which shall include, but not be limited to:
a. Failure to follow the required installation procedures specied in the Big Ass Fans-supplied Installation Manual and in all other
documentation supplied with the fans and related equipment;
b. Failure to follow all relevant codes and ordinances including, but not limited to, the National Electric Code and state and local
building codes;
c. Failure to follow electrical engineering industry standards regarding the approved method of installing solid-state electrical
equipment having the characteristics of the fan, the fan control, and their related components, even if such standards are not
specically referenced in any instructions or literature supplied by Big Ass Fans; and
d. Failure to use properly all installation and mounting hardware supplied by Big Ass Fans.
ATTENTION: Under no circumstances will Big Ass Fans be responsible for remedial work necessary to correct installation
procedures by others that do not conform to those established by the instructions, codes, and standards described under
items 4.a through 4.d above.
e. Any modication or alteration of, or adjustment to the fans, fan control, and/or mounting and installation hardware and/or any
disassembly of the major components of the fans and fan controls for any purpose whatsoever, including any attempt to diagnose
and/or repair any problem, without prior written authorization from Big Ass Fans’ Technical Support Department;
f. Misuse, abuse, accidents, unreasonable use, or Acts of God;
g. Incorrect electric current, voltage, or supply;
h. Failure to use fan controls supplied by Big Ass Fans unless:
i. Big Ass Fans’ Technical Support Department has provided written permission prior to installation; and
ii. The fan controls are built, operated, and maintained according to specications provided to and approved by Big Ass Fans’
Technical Support Department.
i. Failure to perform periodic maintenance as detailed in the Big Ass Fans-supplied Installation Manual.
5. Consequential or incidental damages sustained by any person, entity, or structure as a result of any breach of these warranties,
except where such damages may not be excluded by law.
6. Claims made for products that have not been paid for in full.
7. Damage caused by premises structural defects, structural movement or settlement, exposure to chemicals, salt water, acid rain or
other corrosive elements, excessive humidity, and/or wind.
8. Normal changes to the nish caused by ordinary use or damage to non-factory applied nishes.
9. Damage or failure caused by subjection of the product to conditions outside its design limitations.
10. Defects reported more than 90 days from when they were discovered or should have been discovered.
11. With regard to electrical and electronic components provided by Big Ass Fans that comprise part of the products, including motors,
motor drives, and variable frequency drives, Big Ass Fans relies on the determination by the original manufacturer as to whether
the failure of such component was the result of a defect. If the manufacturer of such component determines that there was no
defect and therefore refuses to cover it under warranty, Big Ass Fans likewise will not warranty such item unless Big Ass Fans
determines that the failure of such electrical or electronic component was the result of a defect of design, workmanship, or material
within some other part of the products.
Denitions
“Operate properly” applies to mechanical, electrical, and structural functions only. No guarantee, unless and except by separate written
agreement, is made regarding the dimensions or air movement generated or the appropriateness of the effectiveness of any product for
its intended purpose or for the customer’s particular application.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE, AND OF ALL OTHER OBLIGATIONS AND
LIABILITIES ON BIG ASS FANS’ PART, AND BIG ASS FANS NEITHER ASSUMES NOR AUTHORIZES ANY PERSON TO ASSUME
FOR IT ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THE PRODUCTS. NO OTHER WARRANTY, EXPRESSED
OR IMPLIED, WHETHER OF FITNESS FOR A PARTICULAR PURPOSE OR OF MERCHANTABILITY OR OF ANY OTHER
KIND, WHETHER OR NOT SIMILAR IN NATURE TO ANY PREVIOUSLY SPECIFIED, SHALL EXIST WITH RESPECT TO SUCH
PRODUCTS, ALL SUCH WARRANTIES BEING HEREBY DISCLAIMED BY BIG ASS FANS AND WAIVED BY CUSTOMER. UNDER
NO CIRCUMSTANCES SHALL BIG ASS FANS BE LIABLE FOR ANY LOSS, DAMAGE, COST OF REPAIR, OR INCIDENTAL
OR CONSEQUENTIAL DAMAGES OF ANY KIND IN CONNECTION WITH THE USE, SALE, OR REPAIR OF ANY PRODUCTS
PURCHASED FROM BIG ASS FANS, UNLESS SUCH DAMAGES CANNOT BE EXCLUDED BY LAW.
Big Ass Fans reserves the right to change this warranty at any time without advance notice.